Modeling and Predictive Control Strategies in Buildings with Mixed-Mode Cooling Jianjun Hu,...
-
Upload
jaquez-woodruff -
Category
Documents
-
view
217 -
download
1
Transcript of Modeling and Predictive Control Strategies in Buildings with Mixed-Mode Cooling Jianjun Hu,...
Modeling and Predictive Control Strategies in Buildings with Mixed-Mode Cooling
Jianjun Hu, Panagiota KaravaSchool of Civil Engineering (Architectural Engineering Group)
Purdue University
2
Background - Mixed-Mode Cooling
Hybrid approach for space conditioning;
Combination of natural ventilation, driven by wind or thermal buoyancy forces, and mechanical systems;
โIntelligentโ controls to optimize mode switching minimize building energy use and maintain occupant
thermal comfort.
3
Background - Mixed-Mode Strategies
Air exchange with corridor inlet grilles
3-storey atria
Atria connecting floor grilles
ExhaustWhen outdoor conditions are appropriate: Corridor inlet grilles and atria connecting grilles
open;
Atrium mechanical air supply flow rate reduced to minimum value, corridor air supply units close;
Atrium exhaust vent open;
(Karava et al., 2012)
- When should we open the windows ? - For how long?- Can we use MPC?
Institutional building located in Montreal
Mixed-mode cooling concept
4
Background โ MPC for Mixed-Mode Buildings Modeling Complexity
Pump and fan speed, opening position (inverse model identified from measurement data) - Spindler, 2004
Window opening schedule (rule extraction for real time application) - May-Ostendorp, 2011
Shading percentage, air change rate (look-up table for a single zone) โ Coffey, 2011
Blind and window opening schedule (bi-linear state space model for a single zone) โ Lehmann et al., 2012
5
Objectives Develop model-predictive control strategies for
multi-zone buildings with mixed-mode cooling, high solar gains, and exposed thermal mass.
Switching modes of operation for space cooling (window schedule, fan assist, night cooling, HVAC)
Coordinated shading control
6
MPC: Problem Formulation
Thermal Dynamic Model:Nonlinear
Discrete Control Variables:Open/Close (1/0)
Offline MPC (deterministic);
baseline simulation study for a mixed-mode
building
Linearized prediction models
(state-space)
Algorithms for discrete optimization
On-line MPC (implementation, identification, uncertainty)
Operable vents
MPC: Dynamic Model (Thermal & Airflow Network)
Building section (9 thermal zones)
7
Glass facade
AtriumSection 1 Section 2 Section 3 Section 4
8
Heat balance for atrium air node
is the air exchange flow rate between zones (obtained from the airflow network model) :
pressure difference ฮP:
Solved by FDM method and Newton-Raphson
๐ถ๐๐ก๐๐๐๐๐ก๐๐๐ก
=โ ๐๐ค๐๐๐๐ โ๐ ๐๐ก๐๐ ๐ค๐๐๐๐๐ก๐๐ +๐๐๐ข๐ฅ+๏ฟฝฬ๏ฟฝ๐๐ (๐๐๐๐๐โ๐ ๐๐ก๐ )
๏ฟฝฬ๏ฟฝ
๏ฟฝฬ๏ฟฝ=๐ถ๐ท๐ดโ2๐ โ๐
MPC: Dynamic Model (Thermal & Airflow Network)
โ ๐= ๐ (๐ ,๐ ๐๐ก๐ ,๐ ๐๐๐ )
Thermal model
๏ฟฝฬ๏ฟฝ=๐ถ๐ท๐ดโ2๐ โ๐
โ๐= ๐ (๐ ,๐ ๐๐ก๐ ,๐ ๐๐๐ )
9
MPC: Dynamic Model (State-Space) State-space representation:
๏ฟฝฬ๏ฟฝ=๐จ๐ฟ+๐ฉ๐ผ+ ๐ ( ๐ฟ ,๐ผ ,๏ฟฝฬ๏ฟฝ )๐=๐ช๐ฟ +๐ซ๐ผ
obtained from the airflow network model๏ฟฝฬ๏ฟฝ=๐ ( ๐ฟ ,๐ผ )
Linear time varying (LTV-SS)
A, B, C, D: coefficient matricesX: state vectorU: input vectorY: Output vector
๏ฟฝฬ๏ฟฝ=๐จ (๐ ) ๐ฟ+๐ฉ (๐ )๐ผ๐=๐ช๐ฟ +๐ซ๐ผ
is a nonlinear term, i.e.: heat transfer due to the air exchange.๐ (๐ฟ ,๐ผ ,๏ฟฝฬ๏ฟฝ )
10
States (X): X = [Ti , Tij , Tij,k]T
i โ zone index j โ wall index k โ mass node index
Inputs (U): U = [Tout, Sij, Load]T
Tout โ outside air temperature;
Sij โ solar radiation on surfaces ij; Load โ heating/cooling load;
Outputs (Y): Y= [Ti , Tij , Tij,k]T
Zone air temperature; Wall temperature; โฆโฆโฆโฆ
MPC: Dynamic Model (State-Space)
11
[ ๏ฟฝฬ๏ฟฝ ๐๏ฟฝฬ๏ฟฝ ๐๐๏ฟฝฬ๏ฟฝ ๐๐ ,๐]280ร 1
=[ ๐ด1,1 โฏ ๐ด1,280โฎ โฑ โฎ๐ด280,1 โฏ ๐ด280,280] โ[
๐ ๐๐ ๐๐๐ ๐๐ ,๐]
280ร1
+[ ๐ต1,1 โฏ ๐ต1,52โฎ โฑ โฎ๐ต280,1 โฏ ๐ต280,52] โ[
๐ ๐๐ข๐ก๐๐๐๐ฟ๐๐๐ ๐]
52ร1
๏ฟฝฬ๏ฟฝ=๐จ (๐ ) ๐ฟ+๐ฉ (๐ )๐ผ
Find the matrices from the heat balance equations
e.g. atrium zone air node: ๐ด235,1=๏ฟฝฬ๏ฟฝ๐๐ธ 1๐๐ก๐๐๐๐ถ๐๐ก๐๐
๐ด235,118=๏ฟฝฬ๏ฟฝ๐๐ 1๐๐ก๐
๐๐๐ถ๐๐ก๐ ๐
๐ด235,118=1
๐ถ๐๐ก๐ ๐๐ 11๐ค๐๐๐๐ด235,240=
1๐ถ๐๐ก๐๐๐ 11๐๐๐๐
๐ด235,241=1
๐ถ๐๐ก๐๐๐ 31๐๐๐
๐ด235,243=1
๐ถ๐๐ก๐๐๐ 41๐๐๐๐ด235,245=
1๐ถ๐๐ก๐๐๐ 51๐๐๐
๐ด235,247=๏ฟฝฬ๏ฟฝ๐๐ก๐ 2๐๐ก๐ 1๐๐๐ถ๐๐ก๐ ๐
๐ด235,235=(โ1 )โ ๐ด๐ต235,50=1
MPC: Dynamic Model (LTV-SS)
12
MPC: Control Variable, Cost Function, and Constraints Control variable: operation schedule
Cost function:Min: where: E is the energy consumption; IOt is vector of binary (open/close) decisions for the motorized envelope openings
๐ฝ ( ๏ฟฝโ๏ฟฝ๐๐ก )=๐ธ
๏ฟฝโ๏ฟฝ๐๐ก= {0 ,1 }
Constraints: Operative temperature within comfort range (23-27.6 ยฐC, which corresponds to PPD
of 10%) during occupancy hours; Use minimal amount of energy: cooling/heating (set point during occupancy hours
8:00-18:00 is 21-23 หC, during unoccupied hours is 13-30 ยฐC); Dew point temperature should be lower than 13.5 ยฐC (ASHRAE 90.1); Wind speed should be lower than 7.5 m/s.
13
MPC: Optimization (PSO) โOfflineโ deterministic MPC: Assume future predictions are exact Planning horizon: 20:00 -- 19:00, decide operation status during each hour.
19:0020:00 21:00 22:00 โฆโฆโฆโฆ.
Find optimal operation scheduleuuu u
find optimal sequence from 224 options;
Wetter (2011)
14
MPC: Optimization (Progressive Refinement)
Time frames Rules Temperature Transmitted Solr Decision
Early morning (6:00 โ 8:00)
Case 1 โฅ 21 ยฐC -- open
Case 2 โค 21 ยฐC -- close
Afternoon(15:00 โ 16:00)
Case 1 โค 23 ยฐC โค 400 W/m2 open
Case 2 > 23 ยฐC โค 400 W/m2 close
Case 3 โค 21 ยฐC > 400 W/m2 open
Case 4 > 21 ยฐC > 400 W/m2 close
Multi-level optimization Decide operation status for each two hours at night (20:00-5:00); Use simple rules (based on off-line MPC)
15
Simulation Study
0
200
400
600
800
1000
0
6
12
18
24
30
20:00 20:00 20:00 20:00 20:00 20:00 20:00 Dir
ect
norm
al ir
radi
ance
, w
/m2
Air
tem
pera
ture
, ยฐC
Time (20:00 of 8/17 -- 19:00 of 8/23), hour
T_dry T_dew DNI
Assumptions: Local controllers were ideal such that all feedback controllers follow set-points
exactly; Internal heat gains (occupancy, lighting) were not considered; An idealized mechanical cooling system with a COP value of 3.5 was modeled. TMW3 data (Montreal)
Cases: Baseline: mechanical cooling with night set back Heuristic: Tamb [15 , 25 ], Tโ โ โ dew โค 13.5 , Wโ speed < 7.5 m/s MPC
16
Results: Operation Schedule (Heuristic & MPC)
Hours during which vents are open are illustrated by cells with grey background Heuristic strategy leads to higher risk of over-cooling during early morning (Day 1,
Day 4, and Day 5);
17
Results: Energy Consumption & Operative Temperature (FDM & LTV-SS)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
8/18 8/19 8/20 8/21 8/22 8/23
Ope
rativ
e te
mpe
ratu
re d
evia
tion,
๏ฟฝC
Date
Baseline Heuristic MPC
0.0
1.0
2.0
3.0
20:00 20:00 20:00 20:00 20:00 20:00 20:00
Pow
er, k
W
Time (from 20:00 of 08/17 -- 19:00 of 08/23), hour
Baseline: FDM Heuristic: FDM MPC: FDMBaseline: LTV-SS Heuristic: LTV-SS MPC: LTV-SS
0
50
100
150
200
250
300
June July August
Cool
ing
ener
gy c
onsu
mpti
on, k
Wh
Baseline Heuristic MPC
18.0
22.0
26.0
30.0
20:00 20:00 20:00 20:00 20:00 20:00 20:00Ope
rativ
e te
mpe
ratu
re, ยฐ
C
Time (from 20:00 of 08/17 -- 19:00 of 08/23), hour
Baseline: FDM Heuristic: FDM MPC: FDMBaseline: LTV-SS Heuristic: LTV-SS MPC: LTV-SS
Comfort Acceptability reduced from 80% to 60%
18.0
22.0
26.0
30.0
20:00 20:00 20:00 20:00 20:00 20:00 20:00Operative
tempera
ture,
ยฐC
Time (from 20:00 of 08/17 -- 19:00 of 08/23), hour
Baseline: FDM Heuristic: FDM MPC: FDMBaseline: LTV-SS Heuristic: LTV-SS MPC: LTV-SS
18.0
22.0
26.0
30.0
20:00 20:00 20:00 20:00 20:00 20:00 20:00Operative tem
perature,
ยฐC
Time (from 20:00 of 08/17 -- 19:00 of 08/23), hour
Baseline: FDM Heuristic: FDM MPC: FDMBaseline: LTV-SS Heuristic: LTV-SS MPC: LTV-SS
-3.0 ยฐC1.3 ยฐC
18
Results: MPC with PSO and Progressive Refinement (ProRe)
Similar energy consumption and operative temperature;
Much faster calculation with ProRe;
3 Days
3 Hours
0.0
1.0
2.0
3.0
20:00 20:00 20:00 20:00 20:00 20:00 20:00
Pow
er, k
W
Time (from 20:00 of 8/17 to 19:00 of 8/23), hour
LTV-SS: Baseline LTV-SS: MPC (PSO) LTV-SS: MPC (ProRe)
18.0
22.0
26.0
30.0
20:00 20:00 20:00 20:00 20:00 20:00 20:00
Ope
rati
ve T
empe
ratu
re,
ยฐC
Time (from 20:00 of 8/17 to 19:00 of 8/23), hour
LTV-SS: Baseline LTV-SS: MPC (PSO) LTV-SS: MPC (ProRe)
19
Results: MPC with PSO and Progressive Refinement (ProRe)
Fine-tune rules in Progressive Refinement method for different climate (LA)
20
Conclusions For the simulation period considered in the present study, mixed-mode
cooling strategies (MPC and heuristic) effectively reduced building energy consumption.
The heuristic strategy can lead to a mean operative temperature deviation up to 0.7 ยฐC, which may decrease the comfort acceptability from 80% to 60%. The predictive control strategy maintained the operative temperature in desired range.
The linear time-variant state-space model can predict the thermal dynamics of the mixed-mode building with good accuracy.
The progressive refinement optimization method can find similar optimal decisions with the PSO algorithm but with significantly lower computational effort.
21
Acknowledgement This work is funded by the Purdue Research Foundation and
the Energy Efficient Buildings Hub, an energy innovation HUB sponsored by the Department of Energy under Award Number DEEE0004261.
In kind support is provided from Kawneer/Alcoa, FFI Inc., and Automated Logic Corporation