Model PS51080-SNMP NFPA Public Safety Signal Booster

2
WESTELL.COM Page 1 of 2 Model PS51080-SNMP NFPA Public Safety Signal Booster General Informaon The PS51080-SNMP is an in-building repeater that will meet both the exisng public safety communicaons regulaons and future mandates for emergency and disaster preparedness communicaons. Model PS51080-SNMP is NFPA-code compliant with NEMA Type 4 enclosure, independent control of the 700 and 800 MHz bands. Frequency Range Uplink 788-805/806-809 or 806-816 MHz Downlink 758-775/851-854 or 851-861 MHz Product Features NFPA 72/1221 compliant Class B Amplifier Compact red NEMA Type 4 enclosure VSWR Antenna Detecon UL Listed FirstNet Ready Energy efficient (less load for baery backup) 700 and 800 MHz bands independently controlled Passband opons 17 MHz: 788-805 / 758-775 MHz 3 MHz: 806-809 / 851-854 MHz 10 MHz: 806-816 / 851-861 MHz Independent power and gain control per band Sharp SAW filtering reduces interference from compeng signals Easy to install and maintain Dry Contacts for Fire panel connecon 80 dB gain 27 dBm (½ Wa) Supports SNMP Supports digital and analog modulaon including P25 phase 1 & 2 Oscillaon Detecon and Automac Gain Control (AGC) Built-in oscillaon control and self-healing Shutdown in the event of non-correctable severe condions Alarms System (PLL) Isolaon PA Shutdown (UL/DL) Power Failure Antenna DL VSWR (Can be disabled) Antenna UL VSWR (Can be disabled) Manual Amp off All alarms trigger Summary Dry contact Supported LED Status Power Isolaon Oscillaon (OSC) Alarm Ordering Informaon CS14-710-810 PS51080 .5W BDA (Direct Replacement for CS14-700-800) PS51080-SNMP NFPA Public Safety Signal Booster

Transcript of Model PS51080-SNMP NFPA Public Safety Signal Booster

Page 1: Model PS51080-SNMP NFPA Public Safety Signal Booster

WESTELL .COM

Page 1 of 2

Model PS51080-SNMP NFPA Public Safety Signal Booster

General InformationThe PS51080-SNMP is an in-building repeater that will meet both the existing public safety communications regulations and future mandates for emergency and disaster preparedness communications.

Model PS51080-SNMP is NFPA-code compliant with NEMA Type 4 enclosure, independent control of the 700 and 800 MHz bands.

Frequency Range• Uplink 788-805/806-809 or 806-816 MHz

• Downlink 758-775/851-854 or 851-861 MHz

Product Features• NFPA 72/1221 compliant Class B Amplifier

• Compact red NEMA Type 4 enclosure

• VSWR Antenna Detection

• UL Listed

• FirstNet Ready

• Energy efficient (less load for battery backup)

• 700 and 800 MHz bands independently controlled

• Passband options

• 17 MHz: 788-805 / 758-775 MHz

• 3 MHz: 806-809 / 851-854 MHz

• 10 MHz: 806-816 / 851-861 MHz

• Independent power and gain control per band

• Sharp SAW filtering reduces interference from competing signals

• Easy to install and maintain

• Dry Contacts for Fire panel connection

• 80 dB gain

• 27 dBm (½ Watt)

• Supports SNMP

• Supports digital and analog modulation including P25 phase 1 & 2

Oscillation Detection and Automatic Gain Control (AGC)• Built-in oscillation control and self-healing

• Shutdown in the event of non-correctable severe conditions

Alarms• System (PLL)

• Isolation

• PA Shutdown (UL/DL)

• Power Failure

• Antenna DL VSWR (Can be disabled)

• Antenna UL VSWR (Can be disabled)

• Manual Amp off

• All alarms trigger Summary Dry contact

Supported LED Status• Power

• Isolation

• Oscillation (OSC)

• Alarm

Ordering Information

CS14-710-810 PS51080 .5W BDA (Direct Replacement for CS14-700-800)

PS51080-SNMP NFPA Public Safety Signal Booster

Page 2: Model PS51080-SNMP NFPA Public Safety Signal Booster

Copyright © 2019 by Westell, Inc. All Rights Reserved. Westell, ClearLink, Kentrox, and Optima Management System are registered trademarks of Westell, Inc. All other names are trademarks of their respective owners. Information is correct at time of printing and is subject to change without notice. Westell, Inc. is an Equal Opportunity/Affirmative Action employer.

WESTELL .COM

IBW-CS14-710-810_PS51080BDA-DS-121219

Page 2 of 2

PS51080-SNMP NFPA Public Safety Signal Booster

Electrical Specifications

Power Requirements 0.5 Amps @ 110 VAC – 60 Hz

Linear Output Power 27 dBm

Noise Figure @ Max Gain <5 dB, Typical

AGC Dynamic Range 25 dB

Propagation Delay <4 µsec

Gain Adjustment Range 30 dB, 1 dB Steps

VSWR < 2:1

Mechanical Specifications

Dimensions (L x H x D) 11.46 x 16.76 x 3.23 in

Weight 14.5 lbs.

Weatherproofing IP65, NEMA Type 4

Connectors

Antenna Ports N-Female

User Interface (GUI) RJ-45

Alarm Relay 9P D-SUB, Female

Operating Temperature -30° to 50° C

DRY Contact Alarms

Alarm One AC Power/System

Alarm Two Active RF Emitting Device Malfunction