MAKING MODERN LIVING POSSIBLE Operating Instructions MCA 122 Modbus TCP

Transcript of Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the...

Page 1: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

MAKING MODERN LIVING POSSIBLE

Operating InstructionsMCA 122 Modbus TCP

Page 2: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction
Page 3: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Safety

Safety

Copyright, Limitation of Liability andRevision Rights

This publication contains information proprietary toDanfoss. By accepting and using this manual the useragrees that the information contained herein is used solelyfor operating equipment from Danfoss or equipment fromother vendors if such equipment is intended for communi-cation with Danfoss equipment over an Ethernet serialcommunication link. This publication is protected underthe Copyright laws of Denmark and most other countries.

Danfoss does not guarantee that a software programproduced according to the guidelines provided in thismanual functions properly in every physical, hardware, orsoftware environment.

Although Danfoss has tested and reviewed the documen-tation within this manual, Danfoss makes no warranty orrepresentation, either express or implied, with respect tothis documentation, including its quality, performance, orfitness for a particular purpose.

In no event shall Danfoss be liable for direct, indirect,special, incidental, or consequential damages arising out ofthe use, or the inability to use information contained inthis manual, even if advised of the possibility of suchdamages. In particular, Danfoss is not responsible for anycosts including but not limited to the damages incurred asa result of lost profits or revenue, loss or damage ofequipment, loss of computer programs, loss of data, thecosts to substitute these, or any claims by third parties.

Danfoss reserves the right to revise this publication at anytime and change its contents without prior notice or anyobligation to notify previous users of such revisions orchanges.

Safety Note

WARNINGHIGH VOLTAGEThe voltage of the frequency converter is dangerouswhenever connected to mains. Incorrect installation of themotor, frequency converter, or fieldbus may damage theequipment, cause serious personal injury, or death.Consequently, the instructions in this manual, as well asnational and local rules and safety regulations, must becomplied with.

Safety Regulations

1. The frequency converter must be disconnectedfrom mains before carrying out repair work.Check that the mains supply has been discon-nected and that the necessary time has passedbefore removing motor and mains plugs.

2. The off-command on the serial bus does notdisconnect the equipment from mains and shouldnot be used as a safety switch.

3. Correct protective earthing or grounding of theequipment must be established. The user mustbe protected against supply voltage, and themotor must be protected against overload inaccordance with applicable national and localregulations.

4. The earth leakage currents are higher than 3.5mA.

5. Do not remove the plugs for the motor andmains supply while the frequency converter isconnected to mains. Check that the mains supplyhas been disconnected and that the necessarytime has passed before removing motor andmains plugs.

Safety MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark

Page 4: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Warning against Uninteded Start

1. The motor can be brought to a stop with buscommands while the frequency converter isconnected to mains. These stop functions do NOTprovide protection against unintended starts.

2. While parameters are being changed, there is arisk that motor starts.

3. Electronic faults in the frequency converter andcease of

• temporary overload

• faults in supply mains, or

• fault in the motor connection

can cause an unintended start.

WARNINGELECTRICAL HAZARDTouching the electrical parts may be fatal - even after theequipment has been disconnected from mains.

Safety MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark

Page 5: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Contents

1 Introduction 3

1.1 Introduction 3

1.1.1 About this Manual 3

1.1.2 Assumptions 3

1.1.3 Background Knowledge 3

1.1.4 Available Literature 3

1.1.5 Modbus Conformance 3

1.1.6 Abbreviations 4

2 How to Install 5

2.1 The Modbus TCP Option 5

2.1.1 How to Install Option in Frequency Converter 5

2.1.2 LED Behaviour 6

2.1.3 Topology 7

2.1.4 Network 8

2.1.5 Recommended Design Rules 8

2.1.6 EMC Precautions 10

3 How to Configure 11

3.1 IP Settings 11

3.2 Ethernet Link Parameters 11

3.3 Configuring the Scanner 12

3.4 IP Traffic 15

4 How to Control 17

4.1 How to Control the Frequency Converter 17

4.1.1 Function Codes Supported by Modbus TCP 17

4.2 Modbus TCP Message Framing Structure 17

4.2.1 Function Code 17

4.2.2 Data Field 17

4.2.3 Parameter Handling 17

4.2.4 Storage of Data 17

4.2.5 IND 18

4.2.6 Text Blocks 18

4.2.7 Conversion Factor 18

4.2.8 Parameter Values 18

4.2.9 Modbus Exception Codes 18

4.3 PROFIdrive Control Profile 19

4.3.1 Control Word according to PROFIdrive Profile (CTW) 19

4.3.2 Status Word according to PROFIdrive Profile (STW) 20

Contents MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 1

Page 6: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

4.3.3 PROFIdrive State - Transition Diagram 21

4.4 Danfoss FC Control Profile 23

4.4.1 Status Word according to Frequency Converter Profile (STW) 24

4.5 Reference Handling 25

4.5.1 Bus Speed Reference Value 25

5 Parameters 27

5.1 Parameter Group 8-** 27

5.2 Parameter Group 12-** 30

5.2.1 12-0* IP Settings 30

5.2.2 12-1* Ethernet Link Parameters 31

5.2.3 12-2* Process Data 32

5.2.4 Modbus TCP 32

5.2.5 12-8* Other Ethernet Services 33

5.2.6 12-9* Advanced Ethernet Settings 33

5.3 Parameter List 34

5.4 Data Types 36

5.4.1 Data Types Supported by FC 102/FC 202/FC 302 36

6 Troubleshooting 37

6.1 Step-by-step Troubleshooting 37

6.2 Alarm Word and Warning Word 37

Index 41

Contents MCA 122 Modbus TCP

2 MG90P202 - VLT® is a protected Danfoss trademark

Page 7: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

1 Introduction

1.1 Introduction

1.1.1 About this Manual

First time users can find the most essential information forquick installation and set-up in these chapters:

1 Introduction

2 How to Install

3 How to Configure

For more detailed information including the full range ofset-up options and diagnosis tools, refer to the chapters:

3 How to Configure

4 How to Control

5 Parameters

6 Troubleshooting

TerminologyEthernet is a common term used to describe the physicallayer of the network and does not relate to the applicationprotocol.

1.1.2 Assumptions

These operating instructions are under the conditions thatthe MCA 122 Modbus TCP option is used with a DanfossFC 100/FC 202/FC 300 frequency converter, and that theinstalled option supports the interfaces described in thisdocument and that all the requirements stipulated in theoption, as well as the frequency converter, are strictlyobserved along with all limitations herein.

1.1.3 Background Knowledge

The Danfoss Modbus Option Card is designed tocommunicate with any system complying with the ModbusMessaging on TCP/IP Implementation Guide V1.0b andModbus Application Protocol Specification V1.1b standard.Familiarity with this technology is assumed. Issuesregarding hardware or software produced by othermanufacturers, including commissioning tools, are beyondthe scope of this manual, and are not the responsibility ofDanfoss.

For information regarding commissioning tools, orcommunication to a non-Danfoss node, consult theappropriate manuals.

1.1.4 Available Literature

Available Literature for FC 102/FC 202/FC 300- The Operating Instructions for VLT® HVAC Drive FC

102, VLT® AQUA Drive FC 202 and VLT®

AutomationDrive FC 302 provide the necessaryinformation for getting the frequency converterup and running.

- The Design Guides for VLT® HVAC Drive FC 102,VLT® AQUA Drive FC 202 and VLT®

AutomationDrive FC 302 entail all technicalinformation about the frequency converter designand applications including encoder, resolver, andrelay options.

- The VLT® AutomationDriveFC 302 ProfibusOperating Instructions, provide the informationrequired for controlling, monitoring, andprogramming the frequency converter via aProfibus Fieldbus.

- The VLT® AutomationDriveFC 302 OperatingInstructions, provide the information required forcontrolling, monitoring, and programming thefrequency converter via a DeviceNet Fieldbus.

- The MCT 10 Set-up Software Operating Instructions,provide information for installation and use of thesoftware on a PC.

- The VLT® AutomationDriveFC 302 IP21/Type 1Instruction, provides information for installing theIP21/Type 1 option.

- The VLT® AutomationDriveFC 302 24 V DC BackupInstruction, provides information for installing the24 V DC Backup option.

Danfoss technical literature is also available online atwww.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/Technical+Documentation.htm.

1.1.5 Modbus Conformance

The Modbus option is tested to conform to the Modbusstandards and is certified towards conformance test levelversion 3.

Introduction MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 3

1 1

Page 8: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

1.1.6 Abbreviations

Abbreviation Definition

API Actual Packet Interval

CC Control Card

CIP Common Industrial Protocol

CTW Control Word

DHCP Dynamic Host Configuration Protocol

EMC Electromagnetic Compatibility

I/O Input/Output

IP Internet Protocol

LCP Local Control Panel

LED Light Emitting Diode

LSB Least Significant Bit

MAR Major Recoverable fail

MAU Major Unrecoverable fail

MAV Main Actual Value (actual output)

MSB Most Significant Bit

MRV Main Reference Value

N/A Not applicable

ODVA Open DeviceNet Vendor Association

PC Personal Computer

PLC Programmable Logic Controller

PNU Parameter Number

REF Reference (=MRV)

RTC Real Time Clock

s Second

STP Spanning tree Protocol

STW Status Word

Table 1.1 Abbreviations

Introduction MCA 122 Modbus TCP

4 MG90P202 - VLT® is a protected Danfoss trademark

11

Page 9: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

2 How to Install

2.1 The Modbus TCP Option

Ethernet Port 1 Ethernet Port 2

MS LED

NS LEDs

MCA122MODBUS TCP

SW. ver. TM. ver.

MS

NS1

NS2

Ethernet Port 1 Ethernet Port2

Option A130B1196

MAC 00-1B-08-00-00-00Address

8 7 6 5 4 3 2 1ONOFF

130B

D19

0.10

Illustration 2.1 Overview of the Option

2.1.1 How to Install Option in FrequencyConverter

Items required for installing a fieldbus option in thefrequency converter

• The fieldbus option

• Fieldbus option adapter frame for the FC 102/FC202/FC 300. This frame is deeper than thestandard frame, to allow space for the fieldbusoption beneath

• Strain relief (only for A1 and A2 enclosures)

Illustration 2.2 Option Installed in Frequency Converter

Illustration 2.3 Strain Relief for Enclosure Types A1 and A2

How to Install MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 5

2 2

Page 10: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Instructions1. Remove LCP panel from the frequency converter.

2. Remove the frame located beneath and discard it.

3. Push the option into place. The Ethernetconnectors must be facing upwards.

4. Remove both knock-outs on the fieldbus optionadapter frame.

5. Push the fieldbus option adapter frame for thefrequency converter into place.

6. Replace the LCP and attach cable.

NOTICEDo not strip the Ethernet cable and ground it via the strainrelief-plate! The grounding of screened Ethernet cable isdone through the RJ-45 connector on the option.

NOTICEAfter installing the MCA 122 option, be aware of thefollowing parameter settings:8-01 Control Site: [2] control word only or [0] Digital and ctrl.word8-02 Control Word Source: [3] Option A

2.1.2 LED Behaviour

The option has three bi-coloured LEDs

LED label Description

MS Module Status

NS1 Network Status Ethernet Port 1

NS2 Network Status Ethernet Port 2

Table 2.1 Description of LEDs

State LED Description

No power Off The device is un-powered

Device operational Green: Solid green The device is operational

Standby Green: Flashing green The device needs commissioning

Minor fault Red: Flashing red The device has detected a recoverable fault

Major fault Red: Solid red The device has detected an un-recoverablefault

Self testRed: Flashing red/

greenThe Modbus TCP option is in self-test mode

Green:

No IP address Yellow Steady yellow No IP address configured or obtained

Wink Yellow Flashing yellow Flash for 20 s

Table 2.2 MS: Module Status

State LED Description

No IP-address (nopower)

Off No link present (or is un-powered)

Connected Green: Solid green Link present; but nor winked and no ACD

Duplicate IP Red: Solid redThe IP-address assigned to the device isalready in use

Self testRed: Flashing red/

greenThe Modbus TCP is in self-test mode

Green

Device has been winked Yellow Flashing yellow Flash for 20 s

Link present at 10 Mbps Yellow Steady yellow Link present; but nor winked and no ACD

Table 2.3 NS1+NS2: Network Status (One per Port)

How to Install MCA 122 Modbus TCP

6 MG90P202 - VLT® is a protected Danfoss trademark

22

Page 11: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

2.1.3 Topology

The MCA 122 features a built-in Ethernet-switch, thus having two Ethernet RJ-45 connectors. This enables the possibility forconnecting several Modbus TCP options in a line topology as an alternative to the typical star-topology.

The two ports are equal, in the sense that they are transparent for the option. If only one connector is used, either port canbe used.

AutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLT

130BA903.10

Illustration 2.4 Star Topology

AutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLT

130BA904.10

Illustration 2.5 Line Topology

NOTICEFor line topology, refer to 2.1.5 Recommended Design Rules. In a line topology all frequency converters must be powered,either by mains or by their 24 V DC option cards, for the built-in switch to work.

NOTICEObserve that mounting frequency converters of different power-sizes in a line topology may result in unwanted power-offbehaviour.Smaller frequency converters discharge faster than bigger frequency converters. This can result in loss of link in the linetopology, which may lead to control word timeout.To avoid this, mount the frequency converters with the longest discharge time first in the line topology.

How to Install MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 7

2 2

Page 12: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

AutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLTAutomationDrive

VLT

½

AutomationDrive

VLTAutomationDrive

VLT

130BA905.10

Illustration 2.6 Ring/Redundant Line Topology

2.1.4 Network

It is of high importance that the media chosen for Ethernetdata transmission are suitable. Usually CAT 5e and sixcables are recommended for industrial applications. Bothtypes of cable are available as Unshielded Twisted Pair andShielded Twisted Pair. Shielded cables are recommendedfor use in industrial environments and with frequencyconverters.A maximum cable-length of 100 m is allowed betweenswitches.

Optical fibres can be used for gapping longer distancesand providing galvanic isolation.

For connecting Modbus TCP devices both hubs andswitches can be used. It is, however, always recommendedto use suitable industrial graded Ethernet switches. For

more information regarding IP-switching, refer to 3.4.1 IPTraffic.

2.1.5 Recommended Design Rules

While designing Ethernet networks special attention andcaution must be taken regarding active networkcomponents.While designing a network for line topology it is importantto notice that a small delay is added with each everyswitch in the line.

It is not recommended to connect more than 32 frequencyconverters in a line at any API. Exceeding therecommended design rules, may result in failing communi-cation.

How to Install MCA 122 Modbus TCP

8 MG90P202 - VLT® is a protected Danfoss trademark

22

Page 13: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Illustration 2.7

How to Install MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 9

2 2

Page 14: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

2.1.6 EMC Precautions

NOTICERelevant national and local regulations, for exampleregarding protective earth connection, must be observed.

For interference-free operation of the Ethernet network,take the following EMC precautions.

• Keep the Ethernet communication cable awayfrom motor and brake resistor cables to avoid

coupling of high frequency noise from one cableto another

• Maintain the greatest possible distance (min. 200mm (8 inches)) between cables. Especially, wherecables run in parallel over long distances.

• If crossing is unavoidable, the Ethernet cablemust cross motor and brake resistor cables at anangle of 90°

Additional EMC information is available in the frequencyconverter Design Guide.

130B

C50

9.10

Illustration 2.8 EMC-correct Installation

How to Install MCA 122 Modbus TCP

10 MG90P202 - VLT® is a protected Danfoss trademark

22

Page 15: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

3 How to Configure

3.1 IP Settings

All IP-related parameters are located in parameter group12-0* IP Settings:

• 12-00 IP Address Assignment

• 12-01 IP Address

• 12-02 Subnet Mask

• 12-03 Default Gateway

• 12-04 DHCP Server

• 12-05 Lease Expires

• 12-06 Name Servers

• 12-07 Domain Name

• 12-08 Host Name

• 12-09 Physical Address

The MCA 122 option offers several ways of IP addressassignment.

Setting up the frequency converter with manually assignedIP address

Parameter Value

12-00 IP Address Assignment [0] MANUAL

12-01 IP Address 192.168.0.xxx*

12-02 Subnet Mask 255.255.255.0*

12-03 Default Gateway optional

Table 3.1 Assigning IP Adresses Manually

*= Class C IP address example. Any valid IP address can be entered.

NOTICEA power-cycle is necessary after setting the IP parametersmanually.

Setting up the frequency converter with automatically(BOOTP/DHCP) assigned IP address

Parameter Value

12-00 IP AddressAssignment

[1] DHCP/[2] BOOTP

12-01 IP Address Read only

12-02 Subnet Mask Read only

12-03 Default Gateway Read only

Table 3.2 Assigning IP Adresses Automatically

By IP address assigned by DHCP/BOOTP server, theassigned IP Address and Subnet Mask can be read out in12-01 IP Address and 12-02 Subnet Mask. In 12-04 DHCP

Server DHCP Server, the IP address of the found DHCP orBOOTP server is displayed.

For DHCP only: The remaining lease-time can be read-outin 12-05 Lease Expires Lease Expires.

12-09 Physical Address, Physical Address reads out the MACaddress of option, which is also printed on the label of theoption. If using fixed leases together with DHCP or BOOTP,the physical MAC address is linked with a fixed IP address.

NOTICEIf no DHCP or BOOTP reply has been received after fourattempts (for example, if the DHCP/BOOTP server has beenpowered off), the option will fallback to the last goodknown IP address.

12-03 Default Gateway, Default Gateway is optional andonly used in routed networks.

12-06 Name Servers, Name Servers12-07 Domain Name, Domain Name12-08 Host Name, Host Nameare used with Domain Name Server systems and are alloptional. If DHCP or BOOTP is selected as IP addressassignment, these parameters are read only.

NOTICEIt is only possible to assign valid class A, B, and C IPaddress to the option. The valid ranges are shown inTable 3.3.

Class A 1.0.0.1 - 126.255.255.254

Class B 128.1.0.1 - 191.255.255.254

Class C 192.0.1.1 - 223.255.254.254

Table 3.3 Valid Ranges of IP Addresses

3.2 Ethernet Link Parameters

Parameter group 12-1* Ethernet Link Parameters holdsinformation Ethernet Link information:

• 12-10 Link Status

• 12-11 Link Duration

• 12-12 Auto Negotiation

• 12-13 Link Speed

• 12-14 Link Duplex

How to Configure MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 11

3 3

Page 16: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

NOTICEThe Ethernet Link Parameters are unique per port.

12-10 Link Status and 12-11 Link Duration displaysinformation on the link status, per port.12-10 Link Status displays Link or No Link according to thestatus of the present port.12-11 Link Duration displays the duration of the link on thepresent port. If the link is broken the counter resets.

12-12 Auto Negotiation – is a feature that enables twoconnected Ethernet devices to choose commontransmission parameters, such as speed and duplex mode.In this process, the connected devices first share theircapabilities as for these parameters and then choose thefastest transmission mode they both support.By default this function is enabled.Incapability between the connected devices, may lead todecreased communication performance.To prevent this, Auto Negotiation can be disabled.If 12-12 Auto Negotiation is set to OFF, link speed andduplex mode can be configured manually in 12-13 LinkSpeed and 12-14 Link Duplex.

12-13 Link Speed – displays/sets the link speed per port.“None” is displayed if no link is present.

12-14 Link Duplex – displays/sets the duplex mode perport.Half-duplex provides communication in both directions,but only in one direction at a time (not simultaneously).Full-duplex allows communication in both directions, andunlike half-duplex, allows for communication in bothdirections, to happen simultaneously.

3.3 Configuring the Scanner

For configuring the scanner to communicate to thefrequency converter, no system (for example, EDS, GSD file)file is needed. The frequency converter is handled as ageneric device and as such, configured directly in thescanner. The following example sets up the scanner to IPaddresses 192.168.1.20 and the FC 302 to address192.168.1.20.

Configuring a Modicon scannerThe following example uses the Unity Pro tool from GroupSchneider to configure the PLC. The example only showsthe setting up of the Protocol and assigning I/O mappingto internal memory of the PLC.

Under network, add a network by right clicking theNetwork menu and select “New Network”

Illustration 3.1 Adding a Network

How to Configure MCA 122 Modbus TCP

12 MG90P202 - VLT® is a protected Danfoss trademark

33

Page 17: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

By selecting this menu, assign a name to the new network.In this example “Danfoss” has been chosen.

Illustration 3.2 Assigning a Network Name

After clicking [OK], the network “Danfoss” should show upunder Networks and by selecting the Network, the mainconfiguration page is shown.

Illustration 3.3 Main Configuration Page

Menu Menu point Setting

Model Family Model Family NOE 0100, NOE 110

Model Utilities IO Scanning YES

Global Data NO

Address Server NO

IP address configu-ration

Configured/From aserver

Configured

IP address 192.168.001.020

Subnetwork mask 255.255.255.0

Gateway address 0.0.0.0

Ethernet Configu-ration

Ethernet Configu-ration

Ethernet II

Table 3.4 Menu Settings

In the IP Configuration tab, press the [Configured] key, and the IPaddress and fill out [Subnetwork mask]. In this example the address192.168.1.20 is used as the address for the master.

The step assigns the protocol to the scanner, which is doneby selecting the scanner and selecting the “Function” menuand enables the Ethernet by selecting “ETH TCP IP” This bringsup the Net Link menu, where “Danfoss” has to be selected. Atthis time, the “Danfoss” Protocol is assigned to the Scannerand the last step is to configure the scanner to read and writeholding registers of the FC 302.

How to Configure MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 13

3 3

Page 18: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Illustration 3.4 Net Link Menu

Menu Menu point Setting

Function Function ETH TCP IP

Net Link Net Link Danfoss

Table 3.5 Menu Settings

How to Configure MCA 122 Modbus TCP

14 MG90P202 - VLT® is a protected Danfoss trademark

33

Page 19: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

At this time the “Danfoss” Protocol is assigned to the Scanner and the last step is to configure the scanner to read andwrite holding registers of the FC 302.

By first selecting the Danfoss network and second, selecting the IO Scanning tab, the scanning list appears. Fill out the listas shown in Illustration 3.5.

130B

B261

.11

Illustration 3.5 Scanning List

Menu Menu point Setting

IO Scanning IP address 192.168.001.030

Unit ID 255

Health Timeout 1500

Repetitive rate 60

RD Master Object %MW100

RD Slave Index 2910

RD Length 10

Last Value Hold Last

VR Master Object %MW200

VR Slave Index 2810

VR Lenght 10

Description -

Table 3.6 Menu Settings

This configuration copies the information stored from%MW200 to %M209 in the PLC to the Holding register2810 to 2819 of the FC 302. It reads the holding registers2910 to 2919 of the FC 302 to the PLCs memory %MW100to %M109.

3.4 IP Traffic

The use of Ethernet-based network for industrialautomation purposes, calls for careful and thoroughnetwork design. Especially the use of active networkcomponents like switches and routers requires detailedknow-how about the behaviour of IP traffic.

Some important issuesIGMPIGMP (Internet Group Management Protocol) is anintegrated part of IP. It allows hosts to join or leave amulticast host group. Group membership information isexchanged between a specific host and the nearestmulticast router.

Spanning Tree Protocol (STP)For an Ethernet network to function properly, only oneactive path can exist between two nodes. Spanning-TreeProtocol is a link management protocol that provides pathredundancy while preventing undesirable loops in thenetwork.

How to Configure MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 15

3 3

Page 20: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

When loops occur, some switches see stations appearingon both sides of them. This condition confuses theforwarding algorithm and allows for duplicate frames to beforwarded.

To provide path redundancy, Spanning-Tree Protocoldefines a tree that spans all switches in an extendednetwork. Spanning-Tree Protocol forces certain redundantdata paths into a standby (blocked) state. If one networksegment in the Spanning-Tree Protocol becomesunreachable, or if Spanning-Tree Protocol costs change,the spanning-tree algorithm reconfigures the spanning-treetopology and reestablishes the link by activating thestandby path.

Spanning-Tree Protocol operation is necessary if thefrequency converters are running in a ring/redundant linetopology.

How to Configure MCA 122 Modbus TCP

16 MG90P202 - VLT® is a protected Danfoss trademark

33

Page 21: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

4 How to Control

4.1 How to Control the FrequencyConverter

This section describes codes which can be used in thefunction and data fields of a Modbus TCP message. For acomplete description of all the message fields, refer to4.2 Modbus TCP Message Framing Structure.

4.1.1 Function Codes Supported byModbus TCP

Modbus TCP supports use of the following function codesin the function field of a message

Function Function code

Read holding registers 3 hex

Write single register 6 hex

Write multiple registers 10 hex

Get comm. event counter B hex

Report slave ID 11 hex

Read/Write multiple registers 17 hex

Table 4.1 Function Codes

Function Functioncode

Sub-functioncode

Sub-function

Diagnostics 8

1 Restart communication

2 Return diagnosticregister

10 Clear counters anddiagnostic register

11 Return bus messagecount

12 Return bus communi-cation error count

13 Return bus exceptionerror count

14 Return slave messagecount

Table 4.2 Subfunction Codes

4.2 Modbus TCP Message FramingStructure

4.2.1 Function Code

The function code of a message frame contains 8 bits.Valid codes are in the range of 1-FF. Use function codes tosend messages between master and slave. When amessage is sent from a master to a slave device, the

function code tells the slave what action to perform. Whenthe slave responds to the master, it uses the function codeto indicate either a normal (error-free) response, or thatsome error occurred (called an exception response). For anormal response, the slave echoes the original functioncode. For an exception response, the slave returns a codethat is equivalent to the original function code with itsmost significant bit set to logic 1. In addition, the slaveplaces a unique code into the data field of the responsemessage. This tells the master what error occurred, or thereason for the exception. Refer also to sections4.1.1 Function Codes Supported by Modbus TCP and4.2.9 Modbus Exception Codes.

4.2.2 Data Field

The data field is constructed using sets of two hexadecimaldigits, in the range of 00 to FF hexadecimal. These digitsare made up of one TCP character. The data field ofmessages sent from a master to slave device containsadditional information which the slave must use to takethe action defined by the function code. This can includeitems such as coil or register addresses, the quantity ofitems to be handled, and the count of actual data bytes inthe field.

4.2.3 Parameter Handling

The PNU (Parameter Number) is translated from theregister address contained in the Modbus read or writemessage. The parameter number is translated to Modbusas (10 x parameter number) DECIMAL. Example: Reading3-12 Catch up/slow Down Value (16bit): The holding register3120 holds the parameters value. A value of 1352(Decimal), means that the parameter is set to 12.52%

Reading 3-14 Preset Relative Reference (32bit): The holdingregisters 3410 & 3411 holds the parameters value. A valueof 11300 (Decimal), means that the parameter is set to1113.00 S.

For information on the parameters, size and convertingindex, consult the product relevant programming guide.

4.2.4 Storage of Data

The Coil 65 decimal determines whether data written tothe frequency converter are stored in EEPROM and RAM(coil 65=1) or only in RAM (coil 65= 0).

How to Control MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 17

4 4

Page 22: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

4.2.5 IND

Some parameters in the frequency converter are arrayparameters e.g. 3-10 Preset Reference. Since the Modbusdoes not support arrays in the Holding registers, thefrequency converter has reserved the Holding register 9 aspointer to the array. Before reading or writing an arrayparameter, set the holding register 9. Setting holdingregister to the value of 2, will cause all following read/write to array parameters to be to the index 2.

4.2.6 Text Blocks

Parameters stored as text strings are accessed in the sameway as the other parameters. The maximum text block sizeis 20 characters. If a read request for a parameter is formore characters than the parameter stores, the response istruncated. If the read request for a parameter is for fewercharacters than the parameter stores, the response is spacefilled.

4.2.7 Conversion Factor

The different attributes for each parameter can be seen inthe section on factory settings. Since a parameter valuecan only be transferred as a whole number, a conversionfactor must be used to transfer decimals.

4.2.8 Parameter Values

Standard data typesStandard data types are int16, int32, uint8, uint16 anduint32. They are stored as 4x registers (40001–4FFFF). Theparameters are read using function 03HEX "Read HoldingRegisters." Parameters are written using the function 6HEX"Preset Single Register" for 1 register (16 bits), and thefunction 10 HEX "Preset Multiple Registers" for 2 registers(32 bits). Readable sizes range from 1 register (16 bits) upto 10 registers (20 characters).

Non standard data typesNon standard data types are text strings and are stored as4x registers (40001–4FFFF). The parameters are read usingfunction 03HEX "Read Holding Registers" and written usingfunction 10HEX "Preset Multiple Registers." Readable sizesrange from 1 register (2 characters) up to 10 registers (20characters).

4.2.9 Modbus Exception Codes

For a full explanation of the structure of an exception coderesponse, refer to 4.2 Modbus TCP Message FramingStructure.

Code Name Meaning1 Illegal

functionThe function code received in the query isnot an allowable action for the server (orslave). This may be because the functioncode is only applicable to newer devices,and was not implemented in the unitselected. It could also indicate that theserver (or slave) is in the wrong state toprocess a request of this type, forexample because it is not configured andis being asked to return register values.

2 Illegal dataaddress

The data address received in the query isnot an allowable address for the server(or slave). More specifically, thecombination of reference number andtransfer length is invalid. For a controllerwith 100 registers, a request with offset96 and length 4 would succeed, a requestwith offset 96 and length 5 generatesexception 02.

3 Illegal datavalue

A value contained in the query data fieldis not an allowable value for server (orslave). This indicates a fault in thestructure of the remainder of a complexrequest, such as that the implied length isincorrect. It specifically does NOT meanthat a data item submitted for storage ina register has a value outside theexpectation of the application program,since the Modbus protocol is unaware ofthe significance of any particular value ofany particular register.

4 Slave devicefailure

An unrecoverable error occurred while theserver (or slave) was attempting toperform the requested action.

Table 4.3 Modbus Exception Codes

How to Control MCA 122 Modbus TCP

18 MG90P202 - VLT® is a protected Danfoss trademark

44

Page 23: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

4.3 PROFIdrive Control Profile

This section describes the functionality of the control wordand status word in the PROFIdrive profile. Select thisprofile by setting 8-10 Control Word Profile.

4.3.1 Control Word according to PROFIdriveProfile (CTW)

The Control word is used to send commands from amaster (for example, a PC) to a slave.

Bit Bit=0 Bit=1

00 OFF 1 ON 1

01 OFF 2 ON 2

02 OFF 3 ON 3

03 Coasting No coasting

04 Quick stop Ramp

05 Hold frequency output Use ramp

06 Ramp stop Start

07 No function Reset

08 Jog 1 OFF Jog 1 ON

09 Jog 2 OFF Jog 2 ON

10 Data invalid Data valid

11 No function Slow down

12 No function Catch up

13 Parameter set-up Selection lsb

14 Parameter set-up Selection msb

15 No function Reverse

Table 4.4 Control Word Bits

Explanation of the control bits

Bit 00, OFF 1/ON 1Normal ramp stops using the ramp times of the actualselected ramp.Bit 00="0" leads to the stop and activation of the outputrelay 1 or 2 if the output frequency is 0 Hz and if [Relay123] has been selected in 5-40 Function Relay.When bit 0="1", the frequency converter is in State 1:“Switching on inhibited”.Refer to Illustration 4.1.

Bit 01, OFF 2/ON 2Coasting stopWhen bit 01="0", a coasting stop and activation of theoutput relay 1 or 2 occurs if the output frequency is 0 Hzand if [Relay 123] has been selected in 5-40 Function Relay.When bit 01="1", the frequency converter is in State 1:“Switching on inhibited”. Refer to Illustration 4.1.

Bit 02, OFF 3/ON 3Quick stop using the ramp time of 3-81 Quick Stop RampTime. When bit 02="0", a quick stop and activation of theoutput relay 1 or 2 occurs if the output frequency is 0 Hzand if [Relay 123] has been selected in 5-40 Function Relay.

When bit 02="1", the frequency converter is in State 1:“Switching on inhibited”.Refer to Illustration 4.1.

Bit 03, Coasting/No coastingCoasting stop Bit 03="0" leads to a stop. When bit 03="1",the frequency converter can start if the other startconditions are satisfied.

NOTICEThe selection in 8-50 Coasting Select determines how bit 03is linked with the corresponding function of the digitalinputs.

Bit 04, Quick stop/RampQuick stop using the ramp time of 3-81 Quick Stop RampTime.When bit 04="0", a quick stop occurs.When bit 04="1", the frequency converter can start if theother start conditions are satisfied.

NOTICEThe selection in 8-51 Quick Stop Select determines how bit04 is linked with the corresponding function of the digitalinputs.

Bit 05, Hold frequency output/Use rampWhen bit 05="0", the current output frequency is beingmaintained even if the reference value is modified.When bit 05="1", the frequency converter can perform itsregulating function again; operation occurs according tothe respective reference value.

Bit 06, Ramp stop/StartNormal ramp stop using the ramp times of the actualramp as selected. In addition, activation of the output relay01 or 04 if the output frequency is 0 Hz if Relay 123 hasbeen selected in 5-40 Function Relay. Bit 06="0" leads to astop. When bit 06="1", the frequency converter can start ifthe other start conditions are satisfied.

NOTICEThe selection in 8-53 Start Select determines how bit 06 islinked with the corresponding function of the digitalinputs.

Bit 07, No function/ResetReset after switching off.Acknowledges event in fault buffer.When bit 07="0", no reset occurs.When there is a slope change of bit 07 to "1", a resetoccurs after switching off.

Bit 08, Jog 1 OFF/ONActivation of the pre-programmed speed in 8-90 Bus Jog 1Speed. JOG 1 is only possible if bit 04="0" and bit00-03="1".

How to Control MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 19

4 4

Page 24: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Bit 09, Jog 2 OFF/ONActivation of the pre-programmed speed in 8-91 Bus Jog 2Speed. JOG 2 is only possible if bit 04="0" and bit00-03="1".

Bit 10, Data invalid/validIs used to tell the frequency converter whether the controlword is to be used or ignored. Bit 10=“0” causes thecontrol word to be ignored, giving the opportunity to turnoff the control word when updating/reading parameters.Bit 10=“1” causes the control word to be used. Thisfunction is relevant, because the control word is alwayscontained in the telegram, regardless of which type oftelegram is used.

Bit 11, No function/Slow downIs used to reduce the speed reference value by the amountgiven in 3-12 Catch up/slow Down Value value. When bit11="0", no modification of the reference value occurs.When bit 11="1", the reference value is reduced.

Bit 12, No function/Catch upIs used to increase the speed reference value by theamount given in 3-12 Catch up/slow Down Value.When bit 12="0", no modification of the reference valueoccurs.When bit 12="1", the reference value is increased.If both slowing down and accelerating are activated (bit 11and 12="1"), slowing down has priority, that is, the speedreference value is reduced.

Bits 13/14, Set-up selectionBits 13 and 14 are used to choose between the fourparameter set-ups according to Table 4.5.

The function is only possible if Multi Set-up has beenchosen in 0-10 Active Set-up. The selection in 8-55 Set-upSelect determines how bits 13 and 14 are linked with thecorresponding function of the digital inputs. Changing set-up while running is only possible if the set-ups have beenlinked in 0-12 This Set-up Linked to.

Set-up Bit 13 Bit 14

1 0 0

2 1 0

3 0 1

4 1 1

Table 4.5 Parameter Set-ups

Bit 15, No function/ReverseBit 15=“0” causes no reversing.Bit 15=“1” causes reversing.

NOTICEIn the factory setting reversing is set to digital in 8-54 Reversing Select.

NOTICEBit 15 causes reversing only when Ser. communication,Logic or or Logic and is selected.

4.3.2 Status Word according to PROFIdriveProfile (STW)

The Status word is used to notify a master (for example, aPC) about the status of a slave.

Bit Bit=0 Bit=1

00 Control not ready Control ready

01 Drive not ready Drive ready

02 Coasting Enable

03 No error Trip

04 OFF 2 ON 2

05 OFF 3 ON 3

06 Start possible Start not possible

07 No warning Warning

08 Speed ≠ reference Speed=reference

09 Local operation Bus control

10 Out of frequency limit Frequency limit ok

11 No operation In operation

12 Drive OK Stopped, autostart

13 Voltage OK Voltage exceeded

14 Torque OK Torque exceeded

15 Timer OK Timer exceeded

Table 4.6 Status Word Bits

Explanation of the status bits

Bit 00, Control not ready/readyWhen bit 00="0", bit 00, 01 or 02 of the Control word is "0"(OFF 1, OFF 2 or OFF 3) - or the frequency converter isswitched off (trip).When bit 00="1", the frequency converter control is ready,but there is not necessarily power supply to the unitpresent (in the event of external 24 V supply of the controlsystem).

Bit 01, VLT not ready/readySame significance as bit 00, however, there is a supply ofthe power unit. The frequency converter is ready when itreceives the necessary start signals.

Bit 02, Coasting/EnableWhen bit 02="0", bit 00, 01 or 02 of the Control word is "0"(OFF 1, OFF 2 or OFF 3 or coasting) - or the frequencyconverter is switched off (trip).When bit 02="1", bit 00, 01 or 02 of the Control word is"1"; the frequency converter has not tripped.

Bit 03, No error/TripWhen bit 03="0", no error condition of the frequencyconverter exists.

How to Control MCA 122 Modbus TCP

20 MG90P202 - VLT® is a protected Danfoss trademark

44

Page 25: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

When bit 03="1", the frequency converter has tripped andrequires a reset signal before it can start.

Bit 04, ON 2/OFF 2When bit 01 of the Control word is "0", then bit 04="0".When bit 01 of the Control word is "1", then bit 04="1".

Bit 05, ON 3/OFF 3When bit 02 of the Control word is "0", then bit 05="0".When bit 02 of the Control word is "1", then bit 05="1".

Bit 06, Start possible/Start not possibleIf PROFIdrive has been selected in 8-10 Control Word Profile,bit 06 will be "1" after a switch-off acknowledgment, afteractivation of OFF2 or OFF3, and after switching on themains voltage. Start not possible is reset, with bit 00 of theControl word being set to "0" and bit 01, 02 and 10 beingset to "1".

Bit 07, No warning/WarningBit 07=“0” means that there are no warnings.Bit 07=“1” means that a warning has occurred.

Bit 08, Speed≠reference/Speed=referenceWhen bit 08="0", the current speed of the motor deviatesfrom the set speed reference value. This may occur, forexample, when the speed is being changed during start/stop through ramp up/down.When bit 08="1", the current speed of the motorcorresponds to the set speed reference value.

Bit 09, Local operation/Bus controlBit 09="0" indicates that the frequency converter has beenstopped with the stop button on the LCP, or that [Linkedto hand] or [Local] has been selected in 3-13 Reference Site.When bit 09="1", the frequency converter can becontrolled through the serial interface.

Bit 10, Out of frequency limit/Frequency limit OKWhen bit 10="0", the output frequency is outside the limitsset in 4-52 Warning Speed Low and 4-53 Warning SpeedHigh. When bit 10="1", the output frequency is within theindicated limits.

Bit 11, No operation/OperationWhen bit 11="0", the motor does not turn.When bit 11="1", the frequency converter has a startsignal, or the output frequency is higher than 0 Hz.

Bit 12, Drive OK/Stopped, autostartWhen bit 12="0", there is no temporary overloading of theinverter.When bit 12="1", the inverter has stopped due tooverloading. However, the frequency converter has notswitched off (trip) and will start again after the overloadinghas ended.

Bit 13, Voltage OK/Voltage exceededWhen bit 13="0", the voltage limits of the frequencyconverter are not exceeded.When bit 13="1", the direct voltage in the intermediatecircuit of the frequency converter is too low or too high.

Bit 14, Torque OK/Torque exceededWhen bit 14="0", the motor torque is below the limitselected in 4-16 Torque Limit Motor Mode and 4-17 TorqueLimit Generator Mode. When bit 14="1", the limit selectedin 4-16 Torque Limit Motor Mode or 4-17 Torque LimitGenerator Mode is exceeded.

Bit 15, Timer OK/Timer exceededWhen bit 15="0", the timers for the thermal motorprotection and thermal frequency converter protectionhave not exceeded 100%.When bit 15="1", one of the timers has exceeded 100%.

4.3.3 PROFIdrive State - Transition Diagram

In the PROFIdrive Control profile, the control bits 0 to 3perform the basic start-up/power down functions, whereasthe control bits 4-15 perform application-oriented control.

Illustration 4.1 shows the basic state-transition diagram,where control bits 0 to 3 control the transitions, and thecorresponding status bit indicates the actual state. Theblack bullets indicate the priority of the control signals,where fewer bullets indicate lower priority, and morebullets indicate higher priority.

How to Control MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 21

4 4

Page 26: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Illustration 4.1 PROFIdrive State Transition Diagram

How to Control MCA 122 Modbus TCP

22 MG90P202 - VLT® is a protected Danfoss trademark

44

Page 27: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

4.4 Danfoss FC Control Profile

Illustration 4.2 8-10 Control Word Profile=Frequency Converterprofile

Bit Bit value=0 Bit value=1

00 Reference value External selection LSB

01 Reference value External selection MSB

02 DC brake Ramp

03 Coasting No coasting

04 Quick stop Ramp

05 Hold output frequency Use ramp

06 Ramp stop Start

07 No function Reset

08 No function Jog

09 Ramp 1 Ramp 2

10 Data invalid Data valid

11 No function Relay 01 active

12 No function Relay 04 active

13 Parameter set-up Selection LSB

14 Parameter set-up Selection MSB

15 No function Reverse

Table 4.7 Control Word Bits

Explanation of control bitsBits 00/01Bits 00 and 01 are used to choose between the fourreference values, which are pre-programmed in 3-10 PresetReference according to Table 4.8.

Programmedref. value

Parameter Bit 01 Bit 00

1 3-10 [0] 0 0

2 3-10 [1] 0 1

3 3-10 [2] 1 0

4 3-10 [3] 1 1

Table 4.8 Reference Values

NOTICEIn 8-56 Preset Reference Select select a selection is made todefine how Bit 00/01 gates with the correspondingfunction on the digital inputs.

Bit 02, DC brakeBit 02=‘0’ leads to DC braking and stop. Braking currentand duration are set in 2-01 DC Brake Current and 2-02 DCBraking Time. Bit 02=‘1’ leads to ramping, 3-41 Ramp 1Ramp Up Time

Bit 03, CoastingBit 03=‘0’ causes the frequency converter to immediatelyrelease the motor (the output transistors are "shut off"), sothat it coasts to a standstill.Bit 03=‘1’ enables the frequency converter to start themotor if the other starting conditions have been fulfilled.

NOTICEIn 8-50 Coasting Select a selection is made to define howBit 03 gates with the corresponding function on a digitalinput.

Bit 04, Quick stopBit 04=‘0’ causes a stop, in which the motor speed isramped down to stop via 3-81 Quick Stop Ramp Time.

Bit 05, Hold output frequencyBit 05=‘0’ causes the present output frequency (in Hz) tofreeze. The frozen output frequency can then be changedonly with the digital inputs (5-10 Terminal 18 Digital Inputto 5-15 Terminal 33 Digital Input) programmed to Speed upand Speed down.

NOTICEIf Freeze output is active, the frequency converter can onlybe stopped by the following:

• Bit 03 Coasting stop

• Bit 02 DC braking

• Digital input (5-10 Terminal 18 Digital Input to5-15 Terminal 33 Digital Input) programmed to DCbraking, Coasting stop or Reset and coasting stop

Bit 06, Ramp stop/startBit 06=‘0’ causes a stop, in which the motor speed isramped down to stop via the selected ramp downparameter.Bit 06=‘1’ permits the frequency converter to start themotor, if the other starting conditions have been fulfilled.

NOTICEIn 8-53 Start Select Start select a selection is made to definehow Bit 06 Ramp stop/start gates with the correspondingfunction on a digital input.

Bit 07, ResetBit 07=‘0’ no reset.Bit 07=‘1’ resets a trip. Reset is activated on the leadingedge of the signal, that is, when changing from logic ‘0’ tologic ‘1’.

Bit 08, JogBit 08=‘1’ causes the output frequency to be determinedby 3-19 Jog Speed [RPM].

How to Control MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 23

4 4

Page 28: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Bit 09, Selection of ramp 1/2Bit 09=‘0’ means that ramp 1 is active (3-40 Ramp 1 Type to3-47 Ramp 1 S-ramp Ratio at Decel. Start). Bit 09=‘1’ meansthat ramp 2 (3-50 Ramp 2 Type to 3-57 Ramp 2 S-ramp Ratioat Decel. Start) is active.

Bit 10, Data not valid/Data validIs used to tell the frequency converter whether the controlword is to be used or ignored. Bit 10=“0” causes thecontrol word to be ignored, giving the opportunity to turnoff the control word when updating/reading parameters.Bit 10=“1” causes the control word to be used. Thisfunction is relevant, because the control word is alwayscontained in the telegram, regardless of which type oftelegram is used.

Bit 11, Relay 01Bit 11=‘0’ Relay not activated. Bit 11 = ‘1’ Relay 01activated, provided Control word bit 11 has been chosen in5-40 Function Relay.

Bit 12, Relay 02Bit 12=‘0’ Relay 02 has not been activated.Bit 12=‘1’ Relay 02 has been activated, provided Controlword bit 12 has been chosen in 5-40 Function Relay.

Bit 13/14, Selection of set-upBits 13 and 14 are used to select one of 4 menu set-upsaccording to Table 4.9:

Set-up Bit 14 Bit 13

1 0 0

2 0 1

3 1 0

4 1 1

Table 4.9 Menu Set-ups

The function is only possible when Multi-Set-ups is selectedin 0-10 Active Set-up.

NOTICEIn 8-55 Set-up Select a selection is made to define how Bit13/14 gates with the corresponding function on the digitalinputs.

Bit 15 ReverseBit 15=‘0’ causes no reversing.Bit 15=‘1’ causes reversing.

NOTICEIn the factory setting reversing is set to digital in 8-54 Reversing Select. Bit 15 causes reversing only when Ser.communication, Logic AND or Logic OR is selected.

4.4.1 Status Word according to FrequencyConverter Profile (STW)

Illustration 4.3 8-10 Control Word Profile

Bit Bit value=0 Bit value=1

00 Control not ready Control ready

01 Drive not ready Drive ready

02 Coasting Enable

03 No error Trip

04 No error Error (no trip)

05 Reserved -

06 No error Trip lock

07 No warning Warning

08 Speed ≠ reference Speed = reference

09 Local operation Bus control

10 Out of frequency limit Frequency limit ok

11 No operation In operation

12 Drive ok Stopped, auto start

13 Voltage ok Voltage exceeded

14 Torque ok Torque exceeded

15 Thermal ok Thermal exceeded

Table 4.10 Staus Word Bits

Explanation of the status bitsBit 00, Control readyBit 00=‘0’ means that the frequency converter has tripped.Bit 00=‘1’ means that the frequency converter controls areready, but that the power component is not necessarilyreceiving any power supply (in the event of external 24 Vsupply to controls).

Bit 01, Drive readyBit 01=‘1’. The frequency converter is ready for operation.

Bit 02, Coasting stopBit 02=‘0’. The frequency converter has released the motor.Bit 02=‘1’. The frequency converter can start the motorwhen a start command is given.

Bit 03, No error/TripBit 03=‘0’ means that the frequency converter is not infault mode.Bit 03=‘1’ means that the frequency converter is tripped,and that a reset signal is required to re-establish operation.

Bit 04, No error/Error (no trip)Bit 04=‘0’ means that the frequency converter is not infault mode.

How to Control MCA 122 Modbus TCP

24 MG90P202 - VLT® is a protected Danfoss trademark

44

Page 29: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Bit 04=‘1’ means that there is a frequency converter errorbut no trip.

Bit 05, ReservedBit 05 is not used in the status word.

Bit 06, No error/Trip lockBit 06=‘0’ means that the frequency converter is not infault mode.Bit 06 = ‘1’ means that the frequency converter is tripped,and locked.

Bit 07, No warning/WarningBit 07=‘0’ means that there are no warnings.Bit 07=‘1’ means that a warning has occurred.

Bit 08, Speed≠ reference/Speed=referenceBit 08=‘0’ means that the motor is running, but that thepresent speed is different from the preset speed reference.For example, this might occur while the speed is beingramped up/down during start/stop.Bit 08=‘1’ means that the present motor speed matchesthe preset speed reference.

Bit 09, Local operation/Bus controlBit 09=‘0’ means that [Stop/Reset] is activated on thecontrol unit, or that Local control in 3-13 Reference Site isselected. It is not possible to control the frequencyconverter via serial communication.Bit 09=‘1’ means that it is possible to control the frequencyconverter via the fieldbus/serial communication.

Bit 10, Out of frequency limitBit 10=‘0’, if the output frequency has reached the value in4-11 Motor Speed Low Limit [RPM] or 4-13 Motor Speed HighLimit [RPM].Bit 10=‘1’ means that the output frequency is within thedefined limits.

Bit 11, No operation/In operationBit 11=‘0’ means that the motor is not running.Bit 11=‘1’ means that the frequency converter has a startsignal or that the output frequency is greater than 0 Hz.

Bit 12, Drive OK/Stopped, auto startBit 12=‘0’ means that there is no temporary overtemperature on the inverter.Bit 12=‘1’ means that the inverter has stopped because ofover temperature, but that the unit has not tripped andresumes operation once the over temperature stops.

Bit 13, Voltage OK/Voltage exceededBit 13=‘0’ means that there are no voltage warnings.Bit 13=‘1’ means that the DC voltage in the frequencyconverter’s intermediate circuit is too low or too high.

Bit 14, Torque OK/Torque limit exceededBit 14=‘0’ means that the motor current is lower than thetorque limit selected in 4-16 Torque Limit Motor Mode and4-17 Torque Limit Generator Mode Torque limit.Bit 14=‘1’ means that the torque limit in 4-16 Torque LimitMotor Mode and 4-17 Torque Limit Generator Mode Torquelimit has been exceeded. The nominal torque can be readin 16-16 Torque [Nm].

Bit 15, Thermal OK/limit exceededBit 15=‘0’ means that the timers for both motor thermalprotection and frequency converter thermal protection,have not exceeded 100%.Bit 15=‘1’ means that one of the limits has exceeded 100%.

4.5 Reference Handling

4.5.1 Bus Speed Reference Value

0%=0 hex

100%=4000 hex

-100%=C000 hex

Depending of the setting of 3-00 Reference Range, thereference is scaled from – Max. to + Max. or from Min. toMax.

Reverse ForwardPar.3-00 set to

(1) -max- +max

Max reference Max reference

Par.3-00 set to

(0) min-max

Max reference

Forward

Min reference

100%

(4000hex)

-100%

(C000hex)

0%

(0hex)

Par.3-03 0 Par.3-03

Par.3-03

(4000hex)(0hex)

0% 100%

Par.3-02

130B

A27

7.10

Illustration 4.4 Scaling of Reference Values

The actual reference [Ref. %] in the frequency converterdepends on the settings in the following parameters:

1-23 Motor Frequency

1-25 Motor Nominal Speed

3-02 Minimum Reference

3-03 Maximum Reference

All references provided to the frequency converter areadded to the total reference value. If a reference is to becontrolled by the fieldbus only, ensure that all otherreference inputs are zero.

This means that digital and analogue input terminalsshould not be used for reference signals. The defaultsetting (0%) should be maintained for preset references in3-10 Preset Reference.

How to Control MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 25

4 4

Page 30: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

CAUTIONIf the bus speed reference is negative, and the controlword contains a run reverse signal, the frequencyconverter will run clockwise (- to - is +).

MAV is scaled in the same way as the reference.

How to Control MCA 122 Modbus TCP

26 MG90P202 - VLT® is a protected Danfoss trademark

44

Page 31: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

5 Parameters

5.1 Parameter Group 8-**

8-01 Control Site

Option: Function:

The setting in this parameter overridesthe settings in 8-50 Coasting Select to 8-56 Preset Reference Select.

[0] Digital andctrl.word

Control by using both digital input andcontrol word.

[1] Digital only Control by using digital inputs only.

[2] Controlword only Control by using control word only.

8-02 Control Word Source

Option: Function:

NOTICEThis parameter cannot be adjusted whilethe motor is running.

Select the source of the control word: one oftwo serial interfaces or four installed options.During initial power-up, the frequencyconverter automatically sets this parameter to[3] Option A if it detects a valid fieldbus optioninstalled in slot A. If the option is removed,the frequency converter detects a change inthe configuration, sets 8-02 Control WordSource back to default setting RS-485, and thefrequency converter trips. If an option isinstalled after initial power-up, the setting of 8-02 Control Word Source does not change, butthe frequency converter trips and displays:Alarm 67 Option Changed.When retrofitting a bus option into afrequency converter, that did not have a busoption installed to begin with, take an ACTIVEdecision to move the control to Bus based.This is done for safety reasons to avoid anaccidental change.

[0] None

[1] FC RS485

[2] FC USB

[3] Option A

[4] Option B

[5] Option C0

[6] Option C1

[30] ExternalCan

8-03 Control Word Timeout Time

Range: Function:

1 s* [ 0.1 -18000 s]

Enter the maximum time expected to passbetween the reception of two consecutivetelegrams. If this time is exceeded, it indicatesthat the serial communication has stopped.The function selected in 8-04 Control WordTimeout Functionis then carried out. A validcontrol word triggers the time-out counter.

8-04 Control Word Timeout Function

Select the time-out function. The time-out function activateswhen the control word fails to be updated within the timeperiod specified in 8-03 Control Word Timeout Time.

Option: Function:

[0] Off Resumes control via serial bus (fieldbus orstandard) using the most recent controlword.

[1] Freeze output Freezes output frequency until communi-cation resumes.

[2] Stop Stops with auto restart when communi-cation resumes.

[3] Jogging Runs the motor at JOG frequency untilcommunication resumes.

[4] Max. speed Runs the motor at maximum frequency untilcommunication resumes.

[5] Stop and trip Stops the motor, then resets the frequencyconverter to restart: via the fieldbus, via[Reset], or via a digital input.

[7] Select setup 1 Changes the set-up upon reestablishment ofcommunication following a control wordtime-out. If communication resumes after atime-out, 8-05 End-of-Timeout Functiondefines whether to resume the set-up usedbefore the time-out, or to retain the set-upendorsed by the time-out function.

[8] Select setup 2 See [7] Select setup 1

[9] Select setup 3 See [7] Select setup 1

[10] Select setup 4 See [7] Select setup 1

[26] Trip

NOTICETo change the set-up after a time-out, the followingconfiguration is required:Set 0-10 Active Set-up to [9] Multi set-up and select therelevant link in 0-12 This Set-up Linked to.

Parameters MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 27

5 5

Page 32: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

8-05 End-of-Timeout Function

Option: Function:

Select the action after receiving a valid controlword following a time-out. This parameter isactive only when 8-04 Control Timeout Functionis set to [7] Set-up 1, [8] Set-up 2, [9]Set-up 3 or[10] Set-up 4.

[0] Hold set-up Retains the set-up selected in 8-04 ControlTimeout Function and displays a warning, until8-06 Reset Control Timeout toggles. Then thefrequency converter resumes its original set-up.

[1] Resume set-up

Resumes the set-up active before the time-out.

8-06 Reset Control Word Timeout

This parameter is active only when [0] Hold set-up has beenselected in 8-05 End-of-Timeout Function.

Option: Function:

[0] Do not reset Retains the set-up specified in 8-04 ControlWord Timeout Function, following a controlword time-out.

[1] Do reset Returns the frequency converter to the originalset-up following a control word time-out. Thefrequency converter performs the reset andthen immediately reverts to the [0] Do not resetsetting

8-10 Control Word Profile

Select the interpretation of the control and status wordscorresponding to the installed fieldbus. Only the selections validfor the fieldbus installed in slot A will be visible in the display.For guidelines in selection of [0] FC profile and [1] PROFIdriveprofile refer to the Serial communication via RS-485 Interfacesection.For additional guidelines in the selection of [1] PROFIdrive profile,[5] ODVA and [7] CANopen DSP 402, refer to the OperatingInstructions for the installed fieldbus.

Option: Function:

[0] FC profile

[1] PROFIdrive profile

[5] ODVA

[7] CANopen DSP 402

[8] MCO

8-13 Configurable Status Word STW

Option: Function:

This parameter enables configuration ofbits 12–15 in the status word.

[0] No function

[1] * Profile Default Function corresponds to the profiledefault selected in 8-10 Control Profile.

[2] Alarm 68 Only Only set in case of an Alarm 68.

[3] Trip excl. Alarm68

Set in case of a trip, except if Alarm 68executes the trip.

8-13 Configurable Status Word STW

Option: Function:

[10] T18 DI status. The bit indicates the status of terminal 18.“0” indicates that the terminal is low“1” indicates that the terminal is high

[11] T19 DI status. The bit indicates the status of terminal 19.“0” indicates that the terminal is low“1” indicates that the terminal is high

[12] T27 DI status. The bit indicates the status of terminal 27.“0” indicates that the terminal is low“1” indicates that the terminal is high

[13] T29 DI status. The bit indicates the status of terminal 29.“0” indicates that the terminal is low“1” indicates that the terminal is high

[14] T32 DI status. The bit indicates the status of terminal 32.“0” indicates that the terminal is low“1” indicates that the terminal is high

[15] T33 DI status. The bit indicates the status of terminal 33.“0” indicates that the terminal is low“1” indicates that the terminal is high

[16] T37 DI status The bit indicates the status of terminal 37.”0” indicates T37 is low (safe stop)“1” indicates T37 is high (normal)

[21] Thermalwarning

The thermal warning turns on when thetemperature exceeds the limit in themotor, the frequency converter, the brakeresistor, or the thermistor.

[30] Brake fault(IGBT)

Output is Logic ‘1’ when the brake IGBT isshort-circuited. Use this function toprotect the frequency converter if there isa fault on the brake modules. Use theoutput/relay to cut out the main voltagefrom the frequency converter.

[40] Out of ref.range

[60] Comparator 0 See parameter group 13-1* Comparators. IfComparator 0 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[61] Comparator 1 See parameter group 13-1* Comparators. IfComparator 1 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[62] Comparator 2 See parameter group 13-1* Comparators. IfComparator 2 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[63] Comparator 3 See parameter group 13-1* Comparators. IfComparator 3 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[64] Comparator 4 See parameter group 13-1* Comparators. IfComparator 4 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[65] Comparator 5 See parameter group 13-1* Comparators. IfComparator 5 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[70] Logic Rule 0 See parameter group 13-4* Logic Rules. IfLogic Rule 0 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

Parameters MCA 122 Modbus TCP

28 MG90P202 - VLT® is a protected Danfoss trademark

55

Page 33: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

8-13 Configurable Status Word STW

Option: Function:

[71] Logic Rule 1 See parameter group 13-4* Logic Rules. IfLogic Rule 1 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[72] Logic Rule 2 See parameter group 13-4* Logic Rules. IfLogic Rule 2 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[73] Logic Rule 3 See parameter group 13-4* Logic Rules. IfLogic Rule 3 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[74] Logic Rule 4 See parameter group 13-4* Logic Rules. IfLogic Rule 4 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[75] Logic Rule 5 See parameter group 13-4* Logic Rules. IfLogic Rule 5 is evaluated as TRUE, theoutput goes high. Otherwise, it is low.

[80] SL DigitalOutput A

See 13-52 SL Controller Action. The outputgoes high whenever the Smart LogicAction [38] Set digital out A high isexecuted. The output goes low wheneverthe Smart Logic Action [32] Set digital outA low is executed.

[81] SL DigitalOutput B

See 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [39] Set digital out B high isexecuted. The input goes low wheneverthe Smart Logic Action [33] Set digital outB low is executed.

[82] SL DigitalOutput C

See 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [40] Set digital out C high isexecuted. The input goes low wheneverthe Smart Logic Action [34] Set digital outC low is executed.

[83] SL DigitalOutput D

See 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [41] Set digital out D high isexecuted. The input goes low wheneverthe Smart Logic Action [35] Set digital outD low is executed.

[84] SL DigitalOutput E

See 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [42] Set digital out E high isexecuted. The input goes low wheneverthe Smart Logic Action [36] Set digital outE low is executed.

[85] SL DigitalOutput F

See 13-52 SL Controller Action. The inputgoes high whenever the Smart LogicAction [43] Set digital out F high isexecuted. The input goes low wheneverthe Smart Logic Action [37] Set digital outF low is executed.

8-14 Configurable Control Word CTW

Option: Function:

Selection of control word bit 10, if it is activelow or active high.

[0] None

[1] Profile default

[2] CTW Valid,active low

[3] Safe OptionReset

[4] PID errorinverse

When enabled, it inverts the resulting errorfrom the process PID controller. Availableonly if "Configuration Mode" is set to "SurfaceWinder", "Extended PID Speed OL" or"Extended PID Speed CL".

[5] PID reset Ipart

When enabled, resets the I-part of the ProcessPID controller. Equivalent to 7-40 Process PIDI-part Reset. Available only if "ConfigurationMode" is set to "Surface Winder", "ExtendedPID Speed OL" or "Extended PID Speed CL".

[6] PID enable When enabled, enables the extended processPID controller. Equivalent to 7-50 Process PIDExtended PID. Available only if "ConfigurationMode" is set "Extended PID Speed OL" or"Extended PID Speed CL".

8-50 Coasting Select

Option: Function:

Select control of the coasting function via theterminals (digital input) and/or via the bus.

[0] Digitalinput

Activates Start command via a digital input.

[1] Bus Activates Start command via the serialcommunication port or fieldbus option.

[2] Logic AND Activates Start command via the fieldbus/serialcommunication port, AND additionally via oneof the digital inputs.

[3] Logic OR Activates Start command via the fieldbus/serialcommunication port OR via one of the digitalinputs.

8-51 Quick Stop Select

Select control of the Quick Stop function via the terminals(digital input) and/or via the bus.

Option: Function:

[0] Digital input

[1] Bus

[2] Logic AND

[3] Logic OR

Parameters MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 29

5 5

Page 34: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

8-52 DC Brake Select

Option: Function:

Select control of the DC brake via the terminals(digital input) and/or via the fieldbus.

NOTICEOnly selection [0] Digital input is availablewhen 1-10 Motor Construction is set to [1]PM non-salient SPM.

[0] Digitalinput

Activates Start command via a digital input.

[1] Bus Activates Start command via the serial communi-cation port or fieldbus option.

[2] Logic AND Activates Start command via the fieldbus/serialcommunication port, AND additionally via one ofthe digital inputs.

[3] Logic OR Activates Start command via the fieldbus/serialcommunication port OR via one of the digitalinputs.

8-53 Start Select

Option: Function:

Select control of the frequency converter startfunction via the terminals (digital input) and/orvia the fieldbus.

[0] Digitalinput

Activates Start command via a digital input.

[1] Bus Activates Start command via the serialcommunication port or fieldbus option.

[2] Logic AND Activates Start command via the fieldbus/serialcommunication port, AND additionally via oneof the digital inputs.

[3] Logic OR Activates Start command via the fieldbus/serialcommunication port OR via one of the digitalinputs.

8-54 Reversing Select

Option: Function:

[0] Digitalinput

Select control of the frequency converterreverse function via the terminals (digital input)and/or via the fieldbus.

[1] Bus Activates the Reverse command via the serialcommunication port or fieldbus option.

[2] Logic AND Activates the Reverse command via thefieldbus/serial communication port, ANDadditionally via one of the digital inputs.

[3] Logic OR Activates the Reverse command via thefieldbus/serial communication port OR via oneof the digital inputs.

8-55 Set-up Select

Option: Function:

Select control of the frequency converter set-upselection via the terminals (digital input) and/orvia the fieldbus.

[0] Digitalinput

Activates the set-up selection via a digital input.

[1] Bus Activates the set-up selection via the serialcommunication port or fieldbus option.

[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port, AND additionally viaone of the digital inputs.

[3] Logic OR Activate the set-up selection via the fieldbus/serial communication port OR via one of thedigital inputs.

8-56 Preset Reference Select

Option: Function:

Select control of the frequency converter PresetReference selection via the terminals (digitalinput) and/or via the fieldbus.

[0] Digitalinput

Activates Preset Reference selection via a digitalinput.

[1] Bus Activates Preset Reference selection via theserial communication port or fieldbus option.

[2] Logic AND Activates Preset Reference selection via thefieldbus/serial communication port, ANDadditionally via one of the digital inputs.

[3] Logic OR Activates the Preset Reference selection via thefieldbus/serial communication port OR via oneof the digital inputs.

5.2 Parameter Group 12-**

5.2.1 12-0* IP Settings

12-00 IP Address Assignment

Option: Function:

Selects the IP Address assignment method.

[0] * Manual IP-address can be set in 12-01 IP Address IPAddress.

[1] DHCP IP-address is assigned via DHCP server.

[2] BOOTP IP-address is assigned via BOOTP server.

12-01 IP Address

Range: Function:

[000.000.000.000 -255.255.255.255]

Configure the IP address of theoption. Read-only if 12-00 IP AddressAssignment set to DHCP or BOOTP.

Parameters MCA 122 Modbus TCP

30 MG90P202 - VLT® is a protected Danfoss trademark

55

Page 35: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

12-02 Subnet Mask

Range: Function:

[000.000.000.000 -255.255.255.255]

Configure the IP subnet mask of theoption. Read-only if 12-00 IP AddressAssignment set to DHCP or BOOTP.

12-03 Default Gateway

Range: Function:

[000.000.000.000 –255.255.255.255]

Configure the IP default gateway ofthe option. Read-only if 12-00 IPAddress Assignment set to DHCP orBOOTP.

12-04 DHCP Server

Range: Function:

[000.000.000.000 –255.255.255.255]

Read only. Displays the IP addressof the found DHCP or BOOTPserver.

NOTICEA power-cycle is necessary after setting the IP parametersmanually.

12-05 Lease Expires

Range: Function:

Size related* [ 0 - 0 ] Read only. Displays the lease-time left forthe current DHCP-assigned IP address.

12-06 Name Servers

Range: Function:

0 * [0 - 2147483647 ] IP addresses of Domain Name Servers.Can be automatically assigned whenusing DHCP.

12-07 Domain Name

Range: Function:

0 [0 - 2147483647 ] Domain name of the attached network.Can be automatically assigned whenusing DHCP network.

12-08 Host Name

Range: Function:

Blank [0-19 characters] Logical (given) name of option.

12-09 Physical Address

Range: Function:

0 * [0 - 0 ] Read only. Displays the Physical (MAC) address ofthe option.

5.2.2 12-1* Ethernet Link Parameters

Applies for whole parameter group.

Index [0] is used for Port 1 and Index [1] is used for Port 2.For EtherCAT, Index [0] is for In Port and Index [1] is forOut port.

12-10 Link Status

Option: Function:

Read only. Displays the link status of the Ethernetports.

[0] No Link

[1] Link

12-11 Link Duration

Range: Function:

Size related* [ 0 - 0 ] Read only. Displays the duration of thepresent link on each port in dd:hh:mm:ss.

12-12 Auto Negotiation

Option: Function:

Configures Auto Negotiation of Ethernet linkparameters, for each port: ON or OFF.

[0] Off Link Speed and Link Duplex can be configured in12-13 Link Speed and 12-14 Link Duplex.

[1] On

12-13 Link Speed

Option: Function:

Forces the link speed for each port in 10 or 100Mbps. If 12-12 Auto Negotiation is set to: [ON],this parameter is read only and displays theactual link speed. “None” is displayed if no linkis present.

[0] * None

[1] 10 Mbps

[2] 100 Mbps

12-14 Link Duplex

Option: Function:

Forces the duplex for each port to Full or Halfduplex. If 12-12 Auto Negotiation is set to: [ON],this parameter is read only.

[0] Half Duplex

[1] Full Duplex

NOTICEIn POWERLINK this parameter is locked to half duplex.

Parameters MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 31

5 5

Page 36: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

5.2.3 12-2* Process Data

12-21 Process Data Config Write

Range: Function:

[[0 - 9] PCD read 0 - 9] Configuration of readable processdata.

In POWERLINK this parameter is read only. Same appliesfor 12-22 Process Data Config Read, 12-23 Process DataConfig Write Size and 12-24 Process Data Config Read Size.

12-22 Process Data Config Read

Range: Function:

[[0 - 9] PCD read 0 - 9] Configuration of readable processdata.

12-27 Primary Master

Option: Function:

This parameter control allows fast swapping of masters.If this parameter is set 0.0.0.0, the first masters thataccess the frequency converter locks the interface forother masters.If the communication is lost, the frequency converterwill hold the connection for 30 s before a secondmaster can take control.By setting [0] IP address of first Master and setting [1] IPaddress of second Master, only these two masters cancontrol the frequency converter and the second masterdoes not have to wait 30 s to take control.Only one master may control the frequency converterat any time, otherwise the frequency converter mightmalfunction.

[0] * IP address of first Master.

[1] IP address of second Master.

12-28 Store Data Values

Option: Function:

This parameter activates a function that storesall parameter values in the non-volatilememory (EEPROM) thus retaining parametervalues at power-down.The parameter returns to “Off”.

[0] * Off The store function is inactive.

[1] Store Allset-ups

All parameter values are stored in the non-volatile memory, in all 5 set-ups.

12-29 Store Always

Option: Function:

Activates function that always stores receivedparameter data in non-volatile memory (EEPROM).

[0] * Off

[1] On

5.2.4 Modbus TCP

12-40 Status Parameter

Range: Function:

Read only. Displays the Modbus TCP- specific 16-bitStatus word.

0 * [0 - 0 ]

Bit Description Bit=[0] Bit=[1]

0 Link Statusport 1

Disconnected Connected

1 Link Statusport 2

Disconnected Connected

2 Link speed 0/10 Mbps 100 Mbps

3 Link Duplex Half Full

4 Port 502communi-cation

No Yes

5 UNUSED - -

6 Valid IPaddress

No Yes

7 Modbustimeout (30 s)

No Yes

8 Duplicate IP No Yes

9 Register 7error

No Yes

10 FTP server Disabled Enabled

11 HTTP server Disabled Enabled

12 SMTP service Disabled Enabled

13 Cablediagnosis

Disabled Enabled

14 Autocrossover

Disabled Enabled

15 IGMPsnooping

Disabled Enabled

Table 5.1 Bit Descriptions

12-41 Slave Message Count

Range: Function:

Read only.Displays the number of Modbus messages receivedand processed by the slave.

0 * [0 - 0 ]

12-42 Slave Exception Message Count

Range: Function:

Read only.Displays the number of Modbus messages forwhich the slave has sent an exception response.

0 * [0 - 0 ]

Parameters MCA 122 Modbus TCP

32 MG90P202 - VLT® is a protected Danfoss trademark

55

Page 37: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

5.2.5 12-8* Other Ethernet Services

12-80 FTP Server

Option: Function:

[0] Disabled Disables the built-in FTP server.

[1] Enabled Enables the built-in FTP server.

12-81 HTTP Server

Option: Function:

[0] Disabled

[1] Enabled Enables the built-in HTTP (web) server.

12-82 SMTP Service

Option: Function:

[0] Disabled

[1] Enabled Enables the SMTP (e-mail) service on the option.

12-89 Transent Socket Channel Port

Range: Function:

0* [0–9999] Configures the TCP port-number for the transentsocket channel. This enables Frequency converter-telegrams to be sent transently on Ethernet viaTCP. Default value is 4000, 0 means disabled.

5.2.6 12-9* Advanced Ethernet Settings

12-90 Cable Diagnostic

Option: Function:

Enables/disables advanced Cable diagnosisfunction. If enabled, the distance to cable errorscan be read out in 12-93 Cable Error Length. Theparameter resumes to the default setting of Disableafter the diagnostics have finished.

[0] Disabled

[1] Enabled

NOTICEThe cable diagnostics function is only issued on portswhere there is no link (see 12-10 Link Status, Link Status)

12-91 Auto Cross-Over

Option: Function:

[0] Disable Disables the auto cross-over function.

[1] * Enable Enables the auto cross-over function.

NOTICEDisabling of the auto cross-over function requires crossedEthernet cables for daisy-chaining the options.

12-92 IGMP Snooping

Option: Function:

This prevents flooding of the Ethernet protocolstack by only forwarding multicast packets to portsthat are a member of the multicast group.

[0] Disable Disables the IGMP snooping function.

[1] * Enable Enables the IGMP snooping function.

12-93 Cable Error Length

Range: Function:

0 * [0 -65535 ]

If Cable Diagnostics is enabled in 12-90 CableDiagnostic, the built-in switch is possible viaTime Domain Reflectometry (TDR). Thismeasurement technique detects commoncabling problems such as open circuits, shortcircuits, and impedance mismatches or breaks intransmission cables. The distance from theoption to the error is displayed in meters with

an accuracy of ±2 m. The value 0 means that noerrors detected.

12-94 Broadcast Storm Protection

Range: Function:

-1 %* [-1 -20 %]

The built-in switch is capable of protecting theswitch system from receiving too manybroadcast packages, which can use up networkresources. The value indicates a percentage ofthe total bandwidth that is allowed for broadcastmessages.

Example:The “OFF” means that the filter is disabled - allbroadcast messages passes through. The value“0%” means that no broadcast messages passesthrough. A value of “10%” means that 10% ofthe total bandwidth is allowed for broadcastmessages, if the amount of broadcast messagesincreases above the 10% threshold, they will beblocked.

-1 %* [-1 -20 %]

12-95 Broadcast Storm Filter

Option: Function:

Applies to 12-94 Broadcast StormProtection; if the Broadcast StormProtection should also includeMulticast telegrams.

[0] Broadcast only

[1] Broadcast &Multicast

Parameters MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 33

5 5

Page 38: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

12-98 Interface Counters

Range: Function:

4000 * [0 - 4294967295 ] Read only. Advanced Interfacecounters, from built-in switch, can beused for low-level troubleshooting,The parameter shows a sum of port1+port 2.

12-99 Media Counters

Range: Function:

0 * [0 - 4294967295 ] Read only. Advanced Interface counters,from built-in switch, can be used forlow-level troubleshooting, Theparameter shows a sum of port 1+port2.

5.3 Parameter List

Parameter Default value 4-set-up Change duringoperation

Conver-sion index

Type

8-0* General Settings

8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE - Uint8

8-02 Control Word Source null All set-ups TRUE - Uint8

8-03 Control Word Timeout Time 1.0 s 1 set-up TRUE -1 Uint32

8-04 Control Word Timeout Function null 1 set-up TRUE - Uint8

8-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint8

8-06 Reset Control Word Timeout [0] Do not reset All set-ups TRUE - Uint8

8-1* Ctrl. Word Settings

8-10 Control Word Profile [0] FC profile All set-ups TRUE - Uint8

8-13 Configurable Status Word STW [1] Profile default All set-ups TRUE - Uint8

8-14 Configurable Control Word CTW [1] Profile default All set-ups TRUE - Uint8

8-5* Digital/Bus

8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint8

8-51 Quick Stop Select [3] Logic OR All set-ups TRUE - Uint8

8-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint8

8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8

8-54 Reversing Select [3] Logic OR All set-ups TRUE - Uint8

8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8

8-56 Preset Reference Select [3] Logic OR All set-ups TRUE - Uint8

Table 5.2 Parameter Group 8-**

Parameters MCA 122 Modbus TCP

34 MG90P202 - VLT® is a protected Danfoss trademark

55

Page 39: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Parameter Default Value Range Conversion Index Data Type Array

12-0* IP Settings

12-00 IP Address Assignment 0.0.0.0 0-255 - Unsigned 8 -

12-01 IP Address 0.0.0.0 0-255 - Oct. string 4 -

12-02 Subnet Mask 0.0.0.0 0-255 - Oct. string 4 -

12-03 Default Gateway 0.0.0.0 0-255 - Oct. string 4 -

12-04 DHCP Server 0.0.0.0 0-255 - Oct. string 4 -

12-05 Lease Expires 00:00:00:00 - - Time diff. w/date -

12-06 Name Servers 0.0.0.0 0-255 - Oct. string 4 -

12-07 Domain Name - max. 19 ch. - Visible string 48 -

12-08 Host Name - max. 19 ch. - Visible string 48 -

12-09 Physical Address 00:1B:08:00:00:00 - - Visible string 17 -

12-1* Ethernet Link Parameters

12-10 Link Status [0] No Link [0 - 1] - Unsigned 8 [0-1]

12-11 Link Duration 00:00:00:00 - - Time diff. w/date [0-1]

12-12 Auto Negotiation [1] On [0-1] - Unsigned 8 [0-1]

12-13 Link Speed [0] None [0-2] - Unsigned 8 [0-1]

12-14 Link Duplex [1] Full Duplex [0-1] - Unsigned 8 [0-1]

12-2* Process Data

12-21 Process Data Config Write - - - Unsigned 16 [0-9]

12-22 Process Data Config Read - - - Unsigned 16 [0-9]

12-27 Master Address 0.0.0.0. 0-255 - Oct. string

[4]

12-28 Store Data Values [0] Off [0-1] - Unsigned 8 -

12-29 Store Always [0] Off [0-1] - Unsigned 8 -

12-4* Modbus TCP

12-40 Status Parameter [0-1]

12-41 Slave Message Count 0

12-42 Slave Exception MessageCount 0

12-8* Other Ethernet Services

12-80 FTP Server [0] Disable [0-1] - Unsigned 8 -

12-81 HTTP Server [0] Disable [0-1] - Unsigned 8 -

12-82 SMTP Service [0] Disable [0-1] - Unsigned 8 -

12-89 Transparent Socket ChannelPort [0] Disable [0-1] - Unsigned 8 -

12-9* Advanced Ethernet Settings

12-90 Cable Diagnostic [0] Disable [0-1] - Unsigned 8 -

12-91 Auto Cross Over [0] Enable [0-1] - Unsigned 8 -

12-92 IGMP Snooping [0] Enable [0-1] - Unsigned 8 -

12-93 Cable Error Length 0 0-200 0 Unsigned 16 [0-1]

12-94 Broadcast Storm Protection 0 Off-20% - Unsigned 16 [0-1]

12-95 Broadcast Storm Filter [1] Enable [0-1] - Unsigned 8 [0-1]

12-98 Interface Counters 0 0-65535 - Unsigned 16 [0-10]

12-99 Media Counters 0 0 - 65535 - Unsigned 16 [0-11]

Table 5.3 Parameter Group 12-**

Parameters MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 35

5 5

Page 40: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

5.4 Data Types

5.4.1 Data Types Supported by FC 102/FC202/FC 302

The number to the left refers to a conversion figure, theone on the right to be used when writing or readingparameters.

Conversion index Conversion factor

67 1/60

6 1000000

5 100000

4 10000

3 1000

2 100

1 10

0 1

-1 0.1

-2 0.01

-3 0.001

-4 0.0001

-5 0.00001

-6 0.000001

Table 5.4 Conversion Index

Parameters MCA 122 Modbus TCP

36 MG90P202 - VLT® is a protected Danfoss trademark

55

Page 41: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

6 Troubleshooting

6.1 Step-by-step Troubleshooting

Check: LEDsThe option contains two LEDs to indicate the state of the device and the network. During normal operation the MS and atleast one NS LED shows a constant green light.

State LED Description

No power Off The device is un-powered

Device operational Green: Solid green The device is operational

Standby Green: Flashing green The device needs commissioning

Minor fault Red: Flashing red The device has detected a recoverable fault

Major fault Red: Solid red The device has detected an un-recoverablefault

Self testRed: Flashing red/

greenThe Modbus TCP option is in self-test mode

Green:

No IP address Yellow Steady yellow No IP address configured or obtained

Wink Yellow Flashing yellow Flash for 20 s

Table 6.1 MS: Module Status

State LED Description

No IP-address (no power) Off No link present (or is un-powered)

Connected Green: Solid green Link present; but nor winked and no ACD

Duplicate IP Red: Solid redThe IP-address assigned to the device isalready in use

Self testRed: Flashing red/

greenThe Modbus TCP option is in self-test mode

Green

Device has been winked Yellow Flashing yellow Flash for 20 s

Link present at 10 Mbps Yellow Steady yellow Link present; but nor winked and no ACD

Table 6.2 NS1+NS2: Network Status (one per port)

Check: Link StatusThe status of the Ethernet link cannot be directly identifiedwith the LEDs.Use 12-10 Link Status, to verify presents of the link.Use 12-11 Link Duration, to verify that the link is steadypresent.The parameter shows the duration of the present link, andpreset to 00:00:00:00 if the link is broken.

Check: CablingIn rare cases of cabling mis-configuration, the option mightshow the presents of a link, but no communication isrunning. Exchange the cable in doubt.

Check: IP AddressVerify that the option has a valid IP address (refer to3.1.1 IP Settings) in 12-01 IP Address. If the option hasidentified a duplicate IP Address NS LEDs lights steady red.If the option is set up for BOOTP or DHCP, verify that aBOOTP or DHCP server is connected in 12-04 DHCP Server.

If no server is connected, the parameter shows:000.000.000.000.

6.2 Alarm Word and Warning Word

Alarm word and warning word are shown in the display inHex format. If there is more than one warning or alarm, asum of all warnings or alarms is shown. Warning word andalarm word are displayed in 16-90 Alarm Word to 16-95.For more information on the individual alarms andwarnings, refer to the product relevant Design Guides.

Troubleshooting MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 37

6 6

Page 42: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

NOTICEThe availability of the individual alarms and warnings aredependent on the frequency converter type.

Warning and Alarm Messages There is a clear distinction between alarms and warnings. Ifthere is an alarm, the frequency converter enters a faultcondition. After the cause for the alarm has been cleared,the master must acknowledge the alarm message in orderto start operation of the frequency converter again. Awarning, on the other hand, may appear when a warningcondition arises, then disappear when conditions return tonormal without interfering with the process.

WarningsAll warnings within the frequency converter arerepresented by a single bit within a warning word. Awarning word is always an action parameter. Bit status [0]FALSE means no warning, while bit status [1] TRUE meanswarning. Each bit status has a corresponding text stringmessage. In addition to the warning word message, themaster also notifies via a change in the status word.

Bit (Hex) Alarm word 2(16-91 Alarm Word 2)

00000001 Service Trip, Read/Write

00000002 Reserved

00000004 Service Trip, Typecode/Sparepart

00000008 Reserved

00000010 Reserved

00000020 No Flow

00000040 Dry Pump

00000080 End of Curve

00000100 Broken Belt

00000200 Discharge high

00000400 Start failed

00000800 Speed limit

00001000 Reserved

00002000 Reserved

00004000 Reserved

00008000 Reserved

00010000 Reserved

00020000 KTY error

00040000 Fans error

00080000 ECB error

00100000 Reserved

00200000 Reserved

00400000 Reserved

00800000 Reserved

01000000 Reserved

02000000 Reserved

04000000 Reserved

08000000 Reserved

10000000 Reserved

20000000 Reserved

40000000 PTC thermistor

80000000 Dangerous failure

Table 6.3 Alarm Word 2

Troubleshooting MCA 122 Modbus TCP

38 MG90P202 - VLT® is a protected Danfoss trademark

66

Page 43: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Bit (Hex) Warning word(16-92 Warning Word)

00000001 Brake check

00000002 Power card over temperature

00000004 Earth fault

00000008 Control card over temperature

00000010 Control word timeout

00000020 Over current

00000040 Torque limit

00000080 Motor thermistor over temp.

00000100 Motor ETR over temperature

00000200 Inverter overloaded

00000400 DC link under voltage

00000800 DC link over voltage

00001000 DC link voltage low

00002000 DC link voltage high

00004000 Mains phase loss

00008000 No motor

00010000 Live zero error

00020000 10 V low

00040000 Brake resistor power limit

00080000 Brake resistor short circuit

00100000 Brake chopper fault

00200000 Speed limit

00400000 Fieldbus comm. fault

00800000 24 V supply fault

01000000 Mains failure

02000000 Current limit

04000000 Low temperature

08000000 Voltage limit

10000000 Encoder loss

20000000 Output frequency limit

40000000 Safe stop

80000000 Extended status word

Table 6.4 Warning Word

Bit (Hex) Warning word 2(16-93 Warning Word 2)

00000001 Start Delayed

00000002 Stop Delayed

00000004 Clock Failure

00000008 Firemode was active

00000010 Reserved

00000020 No Flow

00000040 Dry Pump

00000080 End of Curve

00000100 Broken Belt

00000200 Discharge high

00000400 Reserved

00000800 Reserved

00001000 Reserved

00002000 Reserved

00004000 Reserved

00008000 Reserved

00010000 Reserved

00020000 KTY warning

00040000 Fans warning

00080000 ECB warning

00100000 Reserved

00200000 Reserved

00400000 Reserved

00800000 Reserved

01000000 Reserved

02000000 Reserved

04000000 Reserved

08000000 Reserved

10000000 Reserved

20000000 Reserved

40000000 PTC thermistor

80000000 Reserved

Table 6.5 Warning Word 2

Troubleshooting MCA 122 Modbus TCP

MG90P202 - VLT® is a protected Danfoss trademark 39

6 6

Page 44: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Bit (Hex) Extended status word(16-94 Ext. Status Word) FC 202

only !!

00000001 Ramping

00000002 AMA Running

00000004 Start CW/CCW

00000008 Slow Down

00000010 Catch Up

00000020 Feedback high

00000040 Feedback low

00000080 Output current high

00000100 Output current low

00000200 Output frequency high

00000400 Output frequency low

00000800 Brake check OK

00001000 Braking max

00002000 Braking

00004000 Out of speed range

00008000 OVC active

00010000 AC brake

00020000 Password Timelock

00040000 Password Protection

00080000 Reference high

00100000 Reference low

00200000 Local Ref./Remote Ref.

00400000 Reserved

00800000 Reserved

01000000 Reserved

02000000 Reserved

04000000 Reserved

08000000 Reserved

10000000 Reserved

20000000 Reserved

40000000 Reserved

80000000 Reserved

Table 6.6 Extended Status Word

Bit (Hex) FC 200 Extended status word 2(16-95)

FC 202 only !!

00000001 Off

00000002 Hand/Auto

00000004 PROFIbus OFF1 active

00000008 PROFIbus OFF2 active

00000010 PROFIbus OFF3 active

00000020 Relay 123 active

00000040 Start Prevented

00000080 Control ready

00000100 Drive ready

00000200 Quick Stop

00000400 DC Brake

00000800 Stop

00001000 Stand By

00002000 Freeze Output Request

00004000 Freeze Output

00008000 Jog Request

00010000 Jog

00020000 Start Request

00040000 Start

00080000 Start Applied

00100000 Start Delay

00200000 Sleep

00400000 Sleep Boost

00800000 Running

01000000 Bypass

02000000 Fire Mode

04000000 Reserved

08000000 Reserved

10000000 Reserved

20000000 Reserved

40000000 Reserved

80000000 Reserved

Table 6.7 Extended Status Word 2

Troubleshooting MCA 122 Modbus TCP

40 MG90P202 - VLT® is a protected Danfoss trademark

66

Page 45: Modbus TCP MCA 122 - ALBO · 1.1.5 Modbus Conformance The Modbus option is tested to conform to the Modbus standards and is certified towards conformance test level version 3. Introduction

Index

AAbbreviations........................................................................................... 4

Alarm Word............................................................................................. 37

Assumptions............................................................................................. 3

BBackground Knowledge....................................................................... 3

CCabling.............................................................................................. 33, 37

Configuration...................................................................... 27, 28, 32, 4

Control WordPROFIdrive Profile (CTW)........................................ 19

Conversion Index........................................................................... 35, 36

DData Type................................................................................................ 35

DC Backup................................................................................................. 3

DeviceNet.................................................................................................. 3

EEMC Precautions................................................................................... 10

Ethernet.......................................................... 10, 11, 15, 31, 33, 35, 37

FFrequency Converter Profile..................................................... 25, 24

HHardware.............................................................................................. iii, 3

II/O................................................................................................................. 4

IGMP................................................................................................... 15, 33

Installation........................................................................................... iii, 3

IPSettings......................................................................................... 11, 35Traffic.................................................................................................... 15

IP21/Type 1................................................................................................ 3

LLED........................................................................................................... 4, 6

LEDs........................................................................................................... 37

Literature.................................................................................................... 3

MMaster....................................................................................................... 38

ModbusConformance....................................................................................... 3Exception Codes............................................................................... 18

NNetwork.......................................................... 3, 10, 15, 31, 33, 37, 6, 8

OOverview.................................................................................................... 5

PParameter Values.................................................................................. 18

Parameters......................................................................................... iv, 11

Profibus....................................................................................................... 3

PROFIdrive State - Transition Diagram......................................... 21

RReference................................................................ 23, 24, 25, 4, 23, 40

SSafety.......................................................................................................... iii

Spanning Tree................................................................................... 4, 15

Status WordPROFIdrive Profile (STW)........................................... 20

TTopology.................................................................................... 7, 8, 15, 7

WWarning Word................................................................................. 39, 37