 Manuale per l’installazione l’uso e la manutenzione Operating and Service Manual Il manuale include informazioni di sicurezza ATEX per applicazioni in aree con pericolo di esplosione classificate come zona 21 / zona 22 The manual includes ATEX safety information for applications in potentially explosive atmospheres classified as Zone 21 / Zone 22 SONDA DI MISURA MOD. 6029A – MOD. 6029A-ATEX21 SPEED SWITCH MOD. 6029A – MOD. 6029A-ATEX21

Transcript of MOD.60-29A [A4]

  • Manuale per linstallazione luso e la manutenzione Operating and Service Manual

    Il manuale include informazioni di sicurezza ATEX per applicazioni in aree con pericolo di esplosione classificate come zona 21 / zona 22

    The manual includes ATEX safety information for applications in potentially explosive atmospheres classified as Zone 21 / Zone 22

    SONDA DI MISURA MOD. 6029A MOD. 6029A-ATEX21

    SPEED SWITCH

    MOD. 6029A MOD. 6029A-ATEX21

  • 2

    DIRETTIVE - DIRECTIVES NORMATIVE - STANDARDS CE 73/23 (Low Voltage Directive) EN 60204-1, EN60947-5-1 CE 98/37 (Machinery Directive) EN50014, EN 50281-1-1 94/9/CE ATEX IEC 61241-0, IEC 61241-1

    03-01-2007 A D.Cattaneo DMO EMISSIONE DATA DATE

    REV. REV.

    PREPARATO DRAWN-UP

    APPROVATO APPROVED

    DESCRIZIONE DESCRIPTION

    Document / File MOD.60-29A

  • 3

    INDICE GENERALE 1. Introduzione 1.1 Generalit 1.2 Particolarit costruttive 2. Descrizione apparecchiatura 2.1 Funzionamento 2.2 Dati tecnici 2.2.1 Sonda di misura Mod. 6029A 2.2.2 Sonda di misura Mod. 6029A-ATEX21 3. Uso dellapparecchiatura 3.1 Installazione 3.2 Manutenzione 4. ATEX: Istruzioni per un uso sicuro in

    ATMOSFERE POTENZIALMENTE ESPLOSIVE

    4.1 Introduzione 4.2 Marcatura 4.3 Collegamento Elettrico Allegati

    Indicazioni per installazione Dis .60-29A/05 Dimensioni ingombro Schema Morsettiere Certificato di conformit

    GENERAL INDEX 1. Introduction 1.1 General 1.2 Construction details 2. Description 2.1 Operation 2.2 Technical informations 2.2.1 Speed Switch Mod.6029A 2.2.2 Speed Switch Mod.6029A-ATEX21 3. Equipment use 3.1 Installation 3.2 Maintenance 4. ATEX: Instructions for a safety use in

    POTENTIALLY EXPLOSIVE ATMOSPHERES

    4.1 Introduction 4.2 Marking 4.3 Electrical wiring Attachments Installation indications Dwg.60-29A/04 Overall Dimensions Terminal wiring Conformity declaration

  • 4

    1. Introduzione 1.1 Generalit Il presente manuale contiene la descrizione, nonch le informazioni necessarie per linstallazione, luso e la manutenzione della sonda di misura velocit Mod. 6029A. 1.2 Particolarit costruttive Sonda di misura a prossimit non richiede accoppiamento meccanico. - Dispositivo idoneo per luoghi con

    pericolo di esplosioni classificati come Zona 21 / Zona 22 secondo la direttiva 94/9 CE ATEX (vedere sezione ATEX paragrafo 4)

    1. Introduction 1.1 General This manual provides a description of the Speed Switch Mod. 6029A and the information required for installation, use and maintenance. 1.2 Construction details Proximity measurement device no mechanical connections required. - Electrical apparatus available to work

    in potentially explosive atmospheres classified as Zone 21 / Zone 22 according to 94/9 CE ATEX (see section ATEX paragraph 4)

  • 5

    2. Descrizione 2.1 Funzionamento Il Mod. 6029A una sonda di misura che rileva il passaggio di un pezzo metallico installato su un oggetto rotante ed emette una segnale con frequenza proporzionale alla velocit. 2.2 Dati tecnici 2.2.1 Sonda di misura Mod. 6029A Alimentazione 48VDC; 10mA Uscita a collettore aperto: Max 50 mA Sensibilit al ferro: 10mm Grado di protezione: IP67 Temperatura Esercizio: -20 + 50C 2.2.2 Sonda di misura

    Mod. 6029A-ATEX21 Alimentazione 10-48VDC Uscita a collettore aperto PNP: 200 mA Max Portata Nominale Sn = 15mm Campo di funzionamento da 0-12mm Frequenza commutazione MAX 500Hz Grado di protezione: IP68 Temperatura Esercizio: -20 + 60C

    2. Description 2.1 Operation The Mod. 6029A is measuring element senses the passage of a piece of metal applied to the rotating object and emits a signal with a frequency which is proportional to the speed. 2.2 Technical information 2.2.1 Speed Switch mod.6029A Power Supply 48VDC; 10mA Output open collector: max 50 mA Sensitivity to iron: 10mm Construction: IP67 waterproof Operating Temperature: -20 + 50C 2.2.2 Speed Switch

    Mod.6029-ATEX21 Power Supply 10-58VDC Open Collector Output PNP 200mA Max. Nominal Range Sn = 15mm Operating Range 0-12mm Switching Frequency MAX 500Hz Construction: IP68 waterproof Operating Temperature: -20 + 60C

  • 6

    3. Uso dell apparecchiatura 3.1 Installazione (Vedi allegato) Per installazioni in luoghi con

    pericolo di esplosioni vedere sezione ATEX paragrafo 4

    Le dimensioni di ingombro e i collegamenti sono indicate nel dis.60-29A /05. Effettuare lattacco dei collegamenti elettrici alla sonda con guaina flessibile in modo da rendere stagna linstallazione e permettere di regolare la posizione della sonda mediante le apposite asole. Sullalbero rotante di cui si vuole misurare la velocit devono essere installati uno o pi pezzi di ferro il cui passaggio viene rilevato dalla sonda. Prevedere un numero di pezzi tale che la frequenza emessa dalla sonda alla velocit di allarme (frequenza minima di lavoro), sia allinterno del campo di misura. Per la versione ATEX prevedere un numero di pezzi tale che la frequenza emessa non superi il valore di 500Hz. Regolare la posizione della sonda in modo che, tenuto conto dei possibili spostamenti meccanici, la massima distanza possibile tra la sonda e il pezzo metallico non superi 8mm. Lunita di controllo collegata alla sonda Mod. 6029A dovr essere installata ad una distanza Max: 1500m utilizzando un cavo da 2,5mmq 2000m utilizzando un cavo da 4mmq

    3. Equipment use 3.1 Installation (See sketch attached) For Installation in potentially

    explosive atmospheres zone see section ATEX paragraph 4

    Overall dimensions and wirings are indicated in dwg.60-29A/05. Wirings to the speed detector have to be done by flexible sheath in order to assure watertight installation and to allow probes position to be adjusted by means of the slots provided for this purpose. One or more steel pieces have to be mounted on the rotating shaft whose speed is to be measured; their passage will be detected by the probe. The number of pieces has to be calculated in such a way that the frequency emitted by the probe, at alarm speed (minimum working frequency), will be within the measuring range. For ATEX version the number of pieces has to be calculated in such that the frequency do not exceed the d 500Hz. The probe has to be positioned so that, even allowing mechanical movements, the maximum distance between the metal piece and the probe is not greater than 8mm (normally is set to 5mm). The control unit can be installed at a distance from the speed measuring element (probe) Mod.6029A not higher than: 1500m for 2,5mmq cable 2000m for 4mmq cable.

  • 7

    3.2 Manutenzione

    Non aprire sotto tensione

    Lapparecchiatura completamente elettronica, pertanto non richiede alcuna manutenzione. In caso di cattivo funzionamento, effettuare le seguenti verifiche:

    - Integrit dei collegamenti elettrici - Corretto posizionamento della

    sonda - Tensione di alimentazione della

    sonda (Vedi dati tecnici) - Verificare che luscita elettrica

    della sonda cambi stato avvicinando un pezzo metallico alla testa della sonda.

    3.2 Maintenance

    Do not open under voltage

    The equipment is completely electronic and therefore does not require any maintenance. In case of defective operation, check the following: - Terminal wiring - Placement of the probe - Probe voltage supply (See technical data) - Check that the probe output changes status when an iron piece is brought close to yhe tip of the probe.

  • 8

    4. ATEX: Istruzioni per un uso sicuro in ATMOSFERE POTENZIALMENTE ESPLOSIVE

    4.1 Introduzione Per installazione in luoghi con pericolo di esplosione classificati come zona 21 / 22 attenersi scrupolosamente a quanto indicato nei paragrafi successivi

    4.2 Marcatura Contrassegno :

    CE II 2D EEx tD A21 IP68 T90C Temperatura Ambiente : -20C + 60C

    4.3 Collegamento elettrico NON APRIRE SOTTO TENSIONE

    I collegamenti elettrici devono essere eseguiti in tubo conduit o flessibile, attraverso pressacavi, installati nelle sedi predisposte sulla custodia. Per mantenere il grado di protezione originale, i pressatavi devono avere le seguenti caratteristiche: - grado di protezione IP68 - guarnizione di tenuta -filettatura come da caratteristiche i Assicurarsi che, ad installazione avvenuta i pressacavi siano fermamente bloccati sulla custodia. E obbligatorio collegare la messa a terra prevista sul dispositivo. (Vedi dis. 60-20A/05 allegato) Installare utilizzare ed eseguire la manutenzione di questi dispositivi in conformit a: - EN50281-1-2 materiali elettrici destinati allutilizzo in presenza di polvere combustibile; - IEC 60364: Impianti elettrici a bassa tensione; - Regole tecniche relative allinstallazione della (e) zona (e) per le quali il dispositivo stato progettato. NOTA:Thermo Ramsey non pu essere ritenuta responsabile per installazioni in luoghi con pericolo di esplosione (zona 21/22) non conformi alle indicazioni riportate nel paragrafo 4.

    4. ATEX: Instructions for a safety use in POTENTIALLY EXPLOSIVE ATMOSPHERES

    4.1 Introduction For Installation in potentially explosive atmospheres classified as zone 21 / 22, read, understand and apply everything described in this ATEX paragraph.

    4.2 Marking Logo:

    CE II 2D EEx tD A21 IP68 T90C Ambient Temperature : -20C + 60C 4.3 Electric connection

    DO NOT OPEN UNDER VOLTAGE

    Electrical connections must be executed by conduit or flexible, through cable gland installed on the device frame. To keep the original degree of protection, the cable gland should have the following features: - degree of protection IP68 - cable gland gasketed - thread as indicated in general features. Make sure that, once installed, the cable gland is blocked firmly on the housing. It is Mandatory to connect the ground of the sensor (See dwg 60-29A/05 attached). These devices must be installed, used and maintained in accordance with: - EN50281-1-2 Electrical apparatus for use in the presence of combustible dust; - IEC 60364: Low voltage electrical installations; - Regulations governing setup of the zone or zones for which the devices were designed. NOTE: Thermo Ramsey is not responsible for installation in potentially explosive zone (zone 21/22) that are not complied with the indication reported in paragraph 4, or for failure to observe these regulations..

  • 9

    ATMOSFERE POTENZIALMENTE ESPLOSIVE: INDICAZIONI DI INSTALLAZIONE POTENTIALLY EXPLOSIVE ATMOSPHERES: INSTALLATION INSTRUCTIONS

  • 10

  • 11

    MODEL 6029-ATEX21: SENSOR CONFORMITY DECLARATION

  • Le illustrazioni e i dati tecnici riportati nella presente pubblicazione non sono impegnativi e possono essere variati in qualsiasi momento senza preavviso. The pictures and technical data shown in this document are not binding and can be changed at any time without notice.