    FR-A700INSTALLATION GUIDELINEFR-A720-00030 to 03460-NA

    FR-A740-00015 to 09620-NAFR-A720-00030 to 00330-N4

    FR-A740-00015 to 00170-N4FR-A760-00017 to 04020-NA

    INVERTER

    700

    CONTENTSINSTALLATION OF THE INVERTER AND INSTRUCTIONS................. 1

    OUTLINE DIMENSION DRAWING ......................................................... 3

    WIRING.................................................................................................... 6

    PRECAUTIONS FOR USE OF THE INVERTER................................... 22

    PARAMETER LIST................................................................................ 24

    TROUBLESHOOTING........................................................................... 32

    Thank you for choosing this Mitsubishi Inverter.

    Please read through this Installation Guideline and a CD-ROM enclosed to operate this inverter correctly.

    Do not use this product until you have a full knowledge of the equipment, safety information and

    instructions.

    Please forward this Installation Guideline and the CD-ROM to the end user.

    1

    2

    3

    4

    5

    6

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    2/41

    A-1

    4. Additional InstructionsAlso note the following points to prevent an accidental failure, injury, electricshock, etc.

    This section is specifically about safety mattersDo not attempt to install, operate, maintain or inspect the inverter until youhave read through this Installation Guideline and appended documentscarefully and can use the equipment correctly. Do not use the inverter untilyou have a full knowledge of the equipment, safety information andinstructions. In this Installation Guideline, the safety instruction levels areclassified into "WARNING" and "CAUTION".

    Assumes that incorrect handling may cause hazardousconditions, resulting in death or severe injury.

    Assumes that incorrect handling may causehazardous conditions, resulting in medium or slight

    injury, or may cause physical damage only.Note that even the level may lead to a serious consequence

    according to conditions. Please follow strictly the instructions of both levelsbecause they are important to personnel safety.

    1. Electric Shock Prevention

    While power is on or when the inverter is running, do not open the front cover.Otherwise you may get an electric shock.

    Do not run the inverter with the front cover or wiring cover removed.Otherwise, you may access the exposed high-voltage terminals or the chargingpart of the circuitry and get an electric shock.

    Even if power is off, do not remove the front cover except for wiring or periodicinspection.You may access the charged inverter circuits and get an electric shock.

    Before starting wiring or inspection, check to make sure that the operation panelindicator is off, wait for at least 10 minutes after the power supply has beenswitched off, and check that there are no residual voltage using a tester or thelike. The capacitor is charged with high voltage for some time after power off andit is dangerous.

    This inverter must be earthed (grounded). Earthing (Grounding) must conform tothe requirements of national and local safety regulations and electrical codes.

    (NEC section 250, IEC 536 class 1 and other applicable standards) Any person who is involved in the wiring or inspection of this equipment shouldbe fully competent to do the work.

    Always install the inverter before wiring. Otherwise, you may get an electric shockor be injured.

    Perform setting dial and key operations with dry hands to prevent an electricshock. Otherwise you may get an electric shock.

    Do not subject the cables to scratches, excessive stress, heavy loads orpinching. Otherwise you may get an electric shock.

    Do not replace the cooling fan while power is on. It is dangerous to replace thecooling fan while power is on.

    Do not touch the printed circuit board with wet hands. You may get an electric shock. When measuring the main circuit capacitor capacity, the DC voltage is applied to

    the motor for 1s at powering off. Never touch the motor terminal, etc. right afterpowering off to prevent an electric shock.

    2. Fire Prevention Install the inverter on an incombustible wall without holes, etc.

    Mounting it to or near combustible material can cause a fire. If the inverter has become faulty, switch off the inverter power.

    A continuous flow of large current could cause a fire. When using a brake resistor, make up a sequence that will turn off power when

    an alarm signal is output.Otherwise, the brake resistor may excessively overheat due to damage of thebrake transistor and such, causing a fire.

    Do not connect the resistor directly to the DC terminals P/+ and N/-. This could cause a fire.

    3. Injury Prevention Apply only the voltage specified in the instruction manual to each terminal.

    Otherwise, burst, damage, etc. may occur. Ensure that the cables are connected to the correct terminals. Otherwise, burst,

    damage, etc. may occur. Always make sure that polarity is correct to prevent damage, etc. Otherwise,

    burst, damage, etc. may occur. While power is on or for some time after power-off, do not touch the inverter as it

    is hot and you may get burnt.

    (1) Transportation and installation

    When carrying products, use correct lifting gear to prevent injury. Do not stack the inverter boxes higher than the number recommended. Ensure that installation position and material can withstand the weight of the

    inverter. Install according to the information in the instruction manual. Do not install or operate the inverter if it is damaged or has parts missing. This can

    result in breakdowns. When carrying the inverter, do not hold it by the front cover or setting dial; it may

    fall off or fail. Do not stand or rest heavy objects on the product. Check the inverter mounting orientation is correct. Prevent other conductive bodies such as screws and metal fragments or other

    flammable substance such as oil from entering the inverter. As the inverter is a precision instrument, do not drop or subject it to impact. Use the inverter under the following environmental conditions. Otherwise, the

    inverter may be damaged.

    WARNING

    CAUTION

    CAUTION

    WARNING

    CAUTION

    CAUTION

    CAUTION

    Environment

    Ambienttemperature*1

    LD, ND (initialsetting), HD

    -10C to +50C (14F to 122F)(non-freezing)

    SLD -10C to +40C (14F to 104F)(non-f reezing)

    Ambient humidity 90% RH or less (non-condensing)

    Storage temperature -20C to +65C *2 (-4F to 149F)

    AtmosphereIndoors (free from corrosive gas, flammable gas, oilmist, dust and dirt)

    Altitude, vibration

    Maximum 1000m (3280.80feet) above sea level for

    standard operation. After that derate by 3% for everyextra 500m (1640.40feet) up to 2500m (8202feet)

    (92%) 5.9m/s2 or less *3

    *1 For the FR-A760, the ambient temperature is -10C to +40C (14F to 104F)(For the FR-A760-00061 or less with SLD set, the temperature is -10C to+30C (14F to 86F))

    *2 Temperature applicable for a short time, e.g. in transit.

    *3 2.9m/s2 or less for the FR-A740-03250 (FR-A760-02020) or more.

    (2) Wiring Do not install a power factor correction capacitor or surge suppressor/radio

    noise filter (capacitor type filter) on the inverter output side. The connection orientation of the output cables U, V, W to the motor will affect

    the direction of rotation of the motor.

    (3) Test operation and adjustment

    Before starting operation, confirm and adjust the parameters. A failure to do somay cause some machines to make unexpected motions.

    (4) Operation When you have chosen the retry function, stay away from the equipment as it

    will restart suddenly after an alarm stop.

    Since the key is valid only when functions are set (refer to the Instruction

    Manual), provide a circuit and switch separately to make an emergency stop(power off, mechanical brake operation for emergency stop, etc).

    Make sure that the start signal is off before resetting the inverter alarm. A failureto do so may restart the motor suddenly.

    The load used should be a three-phase induction motor only. Connection of anyother electrical equipment to the inverter output may damage the inverter as well asequipment.

    Performing pre-excitation (LX signal and X13 signal) under torque control (realsensorless vector control) may start the motor running at a low speed evenwhen the start command (STF or STR) is not input. The motor may run also at alow speed when the speed limit value = 0 with a start command input. Performpre-excitation after making sure that there will be no problem in safety if themotor runs.

    Do not modify the equipment. Do not perform parts removal which is not instructed in manuals. Doing so may

    lead to fault or damage of the inverter.

    The electronic thermal relay function does not guarantee protection of the motorfrom overheating.

    Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.

    Use a noise filter to reduce the effect of electromagnetic interference. Otherwisenearby electronic equipment may be affected.

    Take measures to suppress harmonics. Otherwise power supply harmonics fromthe inverter may heat/damage the power factor correction capacitor andgenerator.

    When a 400V class motor is inverter-driven, please use an insulation-enhancedmotor or measures taken to suppress surge voltages. Surge voltagesattributable to the wiring constants may occur at the motor terminals,deteriorating the insulation of the motor.

    When a 600V class motor is inverter-driven, it should be insulation-enhanced orsurge voltages suppressed. Surge voltages attributable to the wiring constantsmay occur at the motor terminals, deteriorating the insulation of the motor.

    When parameter clear or all clear is performed, reset the required parametersbefore starting operations. Each parameter returns to the initial value.

    The inverter can be easily set for high-speed operation. Before changing itssetting, fully examine the performances of the motor and machine.

    In addition to the inverter's holding function, install a holding device to ensuresafety.

    Before running an inverter which had been stored for a long period, alwaysperform inspection and test operation.

    For prevention of damage due to static electricity, touch nearby metal beforetouching this product to eliminate static electricity from your body.

    (5) Emergency stop Provide a safety backup such as an emergency brake which will prevent the

    machine and equipment from hazardous conditions if the inverter fails. When the breaker on the inverter input side trips, check for the wiring fault (short

    circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip,then remove the cause and power on the breaker.

    When the protective function is activated, take the corresponding correctiveaction, then reset the inverter, and resume operation.

    (6) Maintenance, inspection and parts replacement

    Do not carry out a megger (insulation resistance) test on the control circuit of theinverter.

    (7) Disposing of the inverter

    Treat as industrial waste.

    General instructions

    Many of the diagrams and drawings in instruction manuals show the inverterwithout a cover, or partially open. Never run the inverter in this status. Alwaysreplace the cover and follow instruction manuals when operating the inverter.

    CAUTION

    CAUTION

    WARNING

    CAUTION

    CAUTION

    CAUTION

    CAUTION

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    3/41

    1

    INSTALLATION OF THE INVERTERAND INSTRUCTIONS

    1 INSTALLATION OF THE INVERTER AND INSTRUCTIONS

    Capacity plate

    Inverter type Serial number

    Capacity plate

    Rating plate

    00175 NA

    FR-A720-00175-NA

    -FR - -A720

    Symbol

    A720

    Voltage Class

    Three-phase200V class

    A740

    A760

    Three-phase400V class

    Three-phase600V class

    Symbol

    200V class00030 to 03460 Displays the

    rated current

    Type number

    400V class00015 to 03250

    600V class00017 to 04020

    Rating plateInverter typeInput rating

    Output rating

    Serial number

    FR-A720-00175-NA

    LD (50 C) XXA

    SLD (40 C) XXA

    ND (50 C) XXA

    HD (50 C) XXA

    30 C (86 F) (00061 or less)

    40 C (104 F) (00120 or more)

    40 C (104 F) (00840 or less)

    50 C (122 F) (01040 or more)

    40 C (104 F) (00840 or less)

    50 C (122 F) (01040 or more)

    40 C (104 F) (00840 or less)

    50 C (122 F) (01040 or more)

    Inverter Type

    Overload currentrating

    Ambient temperatureFR-A720/A740 FR-A760

    40 C (104 F)

    50 C (122 F)

    50 C (122 F)

    50 C (122 F)

    110% 60s, 120% 3s

    120% 60s, 150% 3s

    150% 60s, 200% 3s

    200% 60s, 250% 3s

    SLD

    LD

    ND

    HD

    Symbol

    NA U.S. Specifications

    Specifications

    N4 U.S. Specifications (UL Type 1)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    4/41

    2

    INSTALLATION OF THEINVERTER AND INSTRUCTIONS

    Installation of the inverter

    Note - Some inverter models may be installed outside an enclosure. See Appendix 2 for details.

    General Precaution

    The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for morethan 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazardof electrical shock. Environment

    Before installation, check that the environment meets following specifications.

    Installation on the enclosure

    REMARKS

    To use an enclosed brake resistor for the FR-A760-00061 or less, refer to page 8.

    Ambient temperature

    FR-A720/A740

    LD, ND (initial setting),HD:-10C to + 50C (14F to 122F) (non-freezing)

    SLD: -10C to + 40C (14F to 104F) (non-freezing)

    FR-A760

    LD, ND (initial setting),HD:

    -10C to +40C (14F to 104F) (non-freezing) (00840 or less)

    -10C to +50C (14F to 122F) (non-freezing) (01040 or more)

    SLD:

    -10C to +30C (14F to 86F) (non-freezing) (00061 or less)

    -10C to +40C (14F to 104F) (non-freezing) (00120 or more)

    Ambient humidity 90%RH or less (non-condensing)

    Storage temperature -20C to +65C (-4F to 149F)

    Ambience Indoors (No corrosive and flammable gases, oil mist, dust and dirt.)

    Altitude, vibration Below 1000m, 5.9m/s2 or less (2.9m/s2 or less for the FR-A740-03250 (FR-A760-02020) or more)

    CAUTION Install the inverter on a strong surface securely and vertically with bolts. Leave enough clearances and take cooling measures. Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity. Install the inverter on a non-combustible wall surface.

    FR-A720-00900 or lessFR-A740-00440 or lessFR-A760-00330 or less

    FR-A720-01150 or moreFR-A740-00570 or moreFR-A760-00550 or more

    Fix six positions for the FR-A740-03250 to06830 (FR-A760-02020 to 04020) and fixeight positions for the FR-A740-07700 to09620.

    CAUTION When encasing multiple inverters, install them in

    parallel as a cooling measure. Install the inverter vertically.

    5cm(1.97inches) ormore *1

    10cm(3.94inches)or more *2

    10cm(3.94inches)

    or more *2

    *1 1cm or more for FR-A720-00175

    (FR-A740-00090, FR-A760-00061) or less

    10cm or more for FR-A720-02880

    (FR-A740-01440, FR-A760-01040) or more

    *2 20cm or more for FR-A720-02880

    (FR-A740-01440, FR-A760-01040) or more

    Vertical

    5cm

    (1.97inches)

    5cm

    (1.97inches)

    5cm

    (1.97inches)

    Measurement

    position

    Measurement

    position

    Inverter

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    5/41

    3

    OUTLINE DIMENSION DRAWING

    2 OUTLINE DIMENSION DRAWING

    200V class

    (Unit:mm(inches))

    Inverter Type W W1 H H1 D

    FR-A720-00030-NA110 (4.33) 95 (3.74)

    260 (10.24) 245 (9.65)

    110 (4.33)

    FR-A720-00050-NA 125 (4.92)

    FR-A720-00080-NA

    150 (5.91) 125 (4.92) 140 (5.51)FR-A720-00110-NA

    FR-A720-00175-NA

    FR-A720-00240-NA

    220 (8.66) 195 (7.68)170 (6.69)

    FR-A720-00330-NA

    FR-A720-00460-NA 300 (11.81) 285 (11.22)

    190 (7.48)FR-A720-00610-NA

    250 (9.84) 230 (9.06) 400 (15.75) 380 (14.96)FR-A720-00760-NA

    FR-A720-00900-NA

    FR-A720-01150-NA 325 (12.8) 270 (10.63)550 (21.65)

    530 (20.87) 195 (7.68)FR-A720-01450-NA

    435 (17.13) 380 (14.96) 525 (20.67)250 (9.84)FR-A720-01750-NA

    FR-A720-02150-NA

    465 (18.31)

    410 (16.14) 700 (27.56) 675 (26.57)

    FR-A720-02880-NA400 (15.75) 740 (29.13) 715 (28.15) 360 (14.17)

    FR-A720-03460-NA

    FR-A720-00030-N4110 (4.33) 95 (3.74)

    260 (10.24) 245 (9.65)

    122 (4.80)

    FR-A720-00050-N4 137 (5.39)

    FR-A720-00080-N4

    150 (5.91) 125 (4.92) 152 (5.98)FR-A720-00110-N4

    FR-A720-00175-N4

    FR-A720-00240-N4220 (8.66) 195 (7.68) 182 (7.17)

    FR-A720-00330-N4

    WW1 W1 W1

    WW1 W1

    H

    1HH

    1HH

    WW1

    D

    H

    1

    FR-A720-00030 to03460-NA

    FR-A740-00015 to

    02600-NAFR-A720-00030 to00330-N4

    FR-A740-00015 to00170-N4

    FR-A740-03250 to06830-NAFR-A760-02020 to04020-NA

    FR-A740-07700 to09620-NA

    FR-A760-00017 to01520-NA

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    6/41

    4

    OUTLINE DIMENSION DRAWING

    400V class

    Inverter Type W W1 H H1 D

    FR-A740-00015-NA

    150 (5.91) 125 (4.92)

    260 (10.24) 245 (9.65)

    140 (5.51)

    FR-A740-00025-NA

    FR-A740-00040-NA

    FR-A740-00060-NA

    FR-A740-00090-NA

    FR-A740-00120-NA

    220 (8.66) 195 (7.68)

    170 (6.69)FR-A740-00170-NA

    FR-A740-00230-NA300 (11.81) 285 (11.22) 190 (7.48)

    FR-A740-00310-NA

    FR-A740-00380-NA250 (9.84) 230 (9.06) 400 (15.75) 380 (14.96) 190 (7.48)

    FR-A740-00440-NA

    FR-A740-00570-NA 325 (12.8) 270 (10.63) 550 (21.65) 530 (20.87) 195 (7.68)

    FR-A740-00710-NA

    435 (17.13) 380 (14.96) 550 (21.65) 525 (20.67) 250 (9.84)FR-A740-00860-NA

    FR-A740-01100-NA

    FR-A740-01440-NA

    465 (18.31) 400 (15.75)

    620 (24.41) 595 (23.43) 300 (11.81)FR-A740-01800-NA

    FR-A740-02160-NA740 (29.13) 715 (28.15) 360 (14.17)

    FR-A740-02600-NA

    FR-A740-03250-NA498 (19.6) 200 (7.87)

    1010 (39.76) 985 (38.78) 380 (14.96)

    FR-A740-03610-NA

    FR-A740-04320-NA

    680 (26.77) 300 (11.81)FR-A740-04810-NA

    FR-A740-05470-NA

    FR-A740-06100-NA790 (31.1) 315 (12.4) 1330 (52.36) 1300 (51.18)

    440 (17.32)

    FR-A740-06830-NA

    FR-A740-07700-NA

    995 (39.17) 300 (11.81) 1580 (62.2) 1550 (61.02)FR-A740-08660-NA

    FR-A740-09620-NA

    FR-A740-00015-N4

    150 (5.91) 125 (4.92)

    260 (10.24) 245 (9.65)

    152 (5.98)

    FR-A740-00025-N4

    FR-A740-00040-N4

    FR-A740-00060-N4

    FR-A740-00090-N4

    FR-A740-00120-N4220 (8.66) 195 (7.68) 182 (7.17)

    FR-A740-00170-N4

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    7/41

    5

    OUTLINE DIMENSION DRAWING

    600V class

    zWhen an enclosed brake resistor is used (FR-A760 only)

    Inverter Type W W1 H H1 D

    FR-A760-00017-NA

    150 (5.91) 125 (4.92)260 (10.24) 245 (9.65)

    140 (5.51)FR-A760-00040-NA

    FR-A760-00061-NA

    FR-A760-00120-NA220 (8.66) 195 (7.68)

    170 (6.69)

    FR-A760-00220-NA 300 (11.81) 285 (11.22) 190 (7.48)

    FR-A760-00330-NA 250 (9.84) 230 (9.06) 400 (15.75) 380 (14.96) 190 (7.48)

    FR-A760-00550-NA435 (17.13) 380 (14.96) 550 (21.65) 525 (20.67) 250 (9.84)

    FR-A760-00840-NA

    FR-A760-01040-NA

    465 (18.31) 400 (15.75) 620 (24.41) 595 (23.43) 300 (11.81)FR-A760-01310-NA

    FR-A760-01520-NA

    FR-A760-02020-NA498 (19.6) 200 (7.87)

    1010 (39.76) 985 (38.78) 380 (14.96)FR-A760-02550-NA

    FR-A760-03040-NA 680 (26.77) 300 (11.81)

    FR-A760-04020-NA 790 (31.1) 315 (12.4) 1330 (52.36) 1300 (51.18) 440 (17.32)

    (Unit:mm(inches))

    195 (7.68)

    220 (8.66)

    160 (6.29)

    260

    (10.

    23)

    24

    5

    0.

    3

    (9.

    64

    0.

    01)

    FR-A760-00017 to 00061-NA

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    8/41

    6

    Terminal connection diagram (FR-A720/740)

    3 WIRING

    3.1 Terminal connection diagram (FR-A720/740)

    CAUTION

    To prevent a malfunction due to noise, keep the signal cables more than 10cm (3.94inches) away from the power cables. After wiring, wire offcuts must not be left in the inverter.

    Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.

    Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.

    R/L1

    S/L2

    T/L3

    R1/L11

    S1/L21

    PC

    10E(+10V)

    10(+5V)

    2

    (Analog common)

    23

    1

    1

    4

    Jumper

    C1

    B1

    A1

    U

    V

    W

    P1

    0 to 10VDC

    *1

    0 to 5VDC0 to 10VDC

    MC

    Main circuit

    Control circuit

    C2

    B2

    A2

    IM

    0 to 20mADC

    AU

    PTC

    TXD+

    TXD-

    RXD+

    RXD-

    SGGND

    SINK

    SOURCE

    *4

    *3

    *5

    STF

    STR

    STOP

    RH

    RM

    RL

    JOG

    RT

    MRS

    RES

    AU

    CS

    SD

    RUN

    SU

    IPF

    OL

    FU

    SE

    (+)(-)

    5

    ON

    OFF

    VCC

    (+)(-)

    5V

    *2 Earth (Ground)

    PX PR N/-P/+

    *8

    *3. JOG terminal can be usedas pulse train input terminal.UsePr. 291 to selectJOG/pulse.

    Main circuit terminal

    Control circuit terminal

    Three-phase AC

    power supply

    MCCB

    Jumper

    Earth

    (Ground)

    EMC filter

    ON/OFF

    connecter

    Earth(Ground)

    selected

    selected0 to 5VDC *5

    4 to 20mADC

    0 to 5VDC

    0 to 10VDCselected *5

    Option connector 1

    Option connector 2

    Option connector 3

    Connector

    for plug-in option

    connection

    Frequency setting signal (Analog)

    Frequency setting

    potentiometer1/2W1k

    *6

    Control input signals (No voltage input allowed)Forward

    rotationstart

    Reverserotation

    start

    Start self-holding selection

    Terminal functions vary withthe input terminal

    assignment (Pr. 178 to Pr. 189)

    Middlespeed

    High speed

    Low speed

    Multi-speed

    selection

    Jog mode

    Second function selection

    Output stop

    Reset

    Terminal 4 input selection(Current input selection)

    Selection of automatic restartafter instantaneous

    power failure

    USB

    connector

    PU

    connector

    Terminatingresistor

    Data reception

    Data transmission

    RS-485 terminals

    Open collector output common

    Sink/source common

    Frequency detection

    Running

    Up to frequency

    Instantaneous

    power failure

    Overload

    Terminal functions

    vary with the output

    terminal assignment

    (Pr. 190 to Pr. 194)

    Open collector output

    (Permissible load

    current 100mA)

    Relay output 2

    Relay output 1

    (Alarm output)

    Terminal functionsvary with the output

    terminal assignment

    (Pr. 195, Pr. 196)

    Relay output

    Motor

    *4. AU terminal can be

    used as PTC inputterminal.

    *2. To supply power to thecontrol circuit separately,remove the jumper acrossR1/L11 and S1/L21.

    *10. It is not necessarywhen calibrating theindicator from theoperation panel.

    *6. It is recommended to use 2W1kwhen the frequency setting signalis changed frequently.

    Jumper

    (Initial value)

    (Initial value)

    (Initial value)

    ON4 2

    OFF

    Voltage/currentinput switch

    *5

    Auxiliaryinput

    Terminal4 input

    (Currentinput)

    Brake unit(Option)

    CN8*7

    Jumper

    *5. Terminal input specificationscan be changed by analoginput specificationsswitchover (Pr. 73, Pr. 267).Set the voltage/current inputswitch in the OFF position toselect voltage input (0 to 5V/0to10V) and ON to selectcurrent input (4 to 20mA).

    R

    R

    *1. DC reactor (FR-HEL)Be sure to connect the DC reactorsupplied with the FR-A720-02880 (FR-

    A740-01440) or more.When using the FR-A720-02150 (FR-

    A740-01100) with LD or SLD set,always use a DC reactor (option).When a DC reactor is connected to theFR-A720-02150 (FR-A740-01100) orless, remove the jumper across P1-P/+.

    *7. A CN8 connector is provided with the FR-A720-02880 (FR-A740-01440) or more.

    Sink logic

    *8. Brake resistor (FR-ABR)

    Remove the jumper across terminal PR-PXwhen connecting a brake resistor.(FR-A720-00030 to 00330 (FR-A740-00015 to 00170))Terminal PR is provided for the FR-A720-00030to 00900 (FR-A740-00015 to 00440).Install a thermal relay to prevent an overheatand burnout of the brake resistor.

    *9

    *9.The FR-A720-00030 and 00050

    are not provided with the EMC

    filter ON/OFF connector. (Always on)

    24VDC power supply

    (Common for external power supply transistor)

    Contact input common

    FM

    SD

    + -

    AM

    5

    *11

    *11. FM terminal canbe used for pulsetrain output of opencollector outputusingPr. 291.

    (+)

    (-)(0 to 10VDC)

    Analog signal output

    Moving-coil type

    1mA full-scale

    (Frequency meter, etc.)

    Indicator

    Calibration

    resistor*10

    (Refer to the Instruction Manual)

    (Refer to the InstructionManual)

    (Refer to theInstruction Manual)

    (Refer to the

    Instruction Manual)

    (Refer to the InstructionManual)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    9/41

    7

    WIRING

    3.2 Terminal connection diagram (FR-A760)

    CAUTION To prevent a malfunction due to noise, keep the signal cables more than 10cm (3.94inches) away from the power cables. After wiring, wire offcuts must not be left in the inverter.

    Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.

    Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.

    R/L1

    S/L2

    T/L3

    R1/L11

    S1/L21

    PC

    10E(+10V)

    10(+5V)

    2

    (Analog common)

    23

    1

    1

    4

    Jumper

    C1

    B1

    A1

    U

    V

    W

    P1

    0 to 10VDC

    *1

    0 to 5VDC0 to 10VDC

    MC

    Main circuit

    Control circuit

    C2

    B2

    A2

    IM

    0 to 20mADC

    AU

    PTC

    TXD+

    TXD-

    RXD+

    RXD-

    SGGND

    SINK

    SOURCE

    *4

    *3

    *5

    STF

    STR

    STOP

    RH

    RM

    RL

    JOG

    RT

    MRS

    RES

    AU

    CS

    SD

    RUN

    SU

    IPF

    OL

    FU

    SE

    (+)(-)

    5

    VCC

    (+)(-)

    5V

    *2 Earth (Ground)

    R

    PX PR N/-P/+

    *7

    *3. JOG terminal can be usedas pulse train input terminal.UsePr. 291 to selectJOG/pulse.

    Main circuit terminal

    Control circuit terminal

    Three-phase AC

    power supply

    MCCB

    Jumper

    Earth

    (Ground)

    Earth(Ground)

    selected

    selected0 to 5VDC *5

    4 to 20mADC

    0 to 5VDC

    0 to 10VDCselected *5

    Option connector 1

    Option connector 2

    Option connector 3

    Connector

    for plug-in option

    connection

    Frequency setting signal (Analog)

    Frequency setting

    potentiometer1/2W1k

    *6

    Control input signals (No voltage input allowed)Forwardrotation

    startReverserotation

    start

    Start self-holding selection

    Terminal functions vary with

    the input terminal

    assignment (Pr. 178 to Pr. 189)

    Middlespeed

    High speed

    Low speed

    Multi-speed

    selection

    Jog mode

    Second function selection

    Output stop

    Reset

    Terminal 4 input selection(Current input selection)

    Selection of automatic restartafter instantaneous

    power failure

    USB

    connector

    PU

    connector

    Terminatingresistor

    Data reception

    Data transmissionRS-485 terminals

    Open collector output common

    Sink/source common

    Frequency detection

    Running

    Up to frequency

    Instantaneouspower failure

    Overload

    Terminal functions

    vary with the output

    terminal assignment

    (Pr. 190 to Pr. 194)

    Open collector output

    (Permissible load

    current 100mA)

    Relay output 2

    Relay output 1

    (Alarm output)

    Terminal functions

    vary with the output

    terminal assignment

    (Pr. 195, Pr. 196)

    Relay output

    Motor

    *4. AU terminal can be

    used as PTC input

    terminal.

    *2. To supply power to thecontrol circuit separately,remove the jumper acrossR1/L11 and S1/L21.

    *8. It is not necessarywhen calibrating theindicator from theoperation panel.

    *6. It is recommended to use 2W1kwhen the frequency setting signalis changed frequently.

    (Initial value)

    (Initial value)

    (Initial value)

    ON4 2

    OFF

    Voltage/currentinput switch

    *5

    Auxiliaryinput

    Terminal4 input

    (Currentinput)

    Brake unit(Option)

    *5. Terminal input specificationscan be changed by analoginput specificationsswitchover (Pr. 73, Pr. 267).Set the voltage/current input

    switch in the OFF position toselect voltage input (0 to 5V/0to10V) and ON to selectcurrent input (4 to 20mA).

    Sink logic*7. Brake resistor (Accessories)

    The brake resistor is provided with the FR-A760-00017 to 00061. Connect the accessorybrake resistor to P/+-PR.Terminal PR is provided for the FR-A760-00017to 00330.Install a thermal relay to prevent an overheatand burnout of the brake resistor.

    24VDC power supply

    (Common for external power supply transistor)

    Contact input common

    FM

    SD

    + -

    AM

    5

    *9

    *9. FM terminal can beused for pulse trainoutput of open collectoroutput usingPr. 291.

    (+)

    (-)(0 to 10VDC)

    Analog signal output

    Moving-coil type

    1mA full-scale

    (Frequency meter, etc.)

    Indicator

    Calibration

    resistor*8*10

    *10. USB connector is not used.

    Jumper

    *1. DC reactorBe sure to connect the DC reactorsupplied with the FR-A760-01040 or more.When using the FR-A760-00840 with LDor SLD set, always use a DC reactor(option).When a DC reactor is connected to theFR-A760-00840 or less, remove the

    jumper across P1-P/+.

    (Refer to the Instruction Manual)

    (Refer to the InstructionManual)

    (Refer to theInstruction Manual)

    (Refer to theInstruction Manual)

    (Refer to the InstructionManual)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    10/41

    8

    WIRING

    3.3 Connection of provided brake resistor (FR-A760 only)

    Connecting the brake resistor enclosed with the unit to the FR-A760-00017 to 00061 will improve regeneration

    capability.

    (1) Installation procedure

    Connect the brake resistor to the inverter with provided screws.

    (2) Connection

    Wiring cover and Handling (FR-A760-00061 or less)

    1)Remove the wiring cover of the inverter. Punch out a knockout by firmly tapping it with such as a hammer. Remove

    any sharp edges and burrs from knockout holes of the wiring cover.

    REMARKS

    Connecting the brake resistor changes the protective structure to OPEN type (NEMA1).

    Wiring cover

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    11/41

    9

    WIRING

    2)Attach protective bushes provided to the wiring cover and cut with nippers or a cutter before running the cables.

    Connect the wire with red sleeve to PR terminal. Connect the wire with transparent sleeve to P/+.

    (3) Installation of the inverter

    CAUTIONWhen handling the wiring cover, care must be taken not to cut fingers or hands with sharp edges and burrs.

    Avoide wire offcuts and other foreign matter from entering the inverter.

    WARNING

    Do not wire without using protective bushes. Otherwise, the cable sheathes may be scratched by the wiring

    cover edges, resulting in a short circuit or ground fault.

    (Transparent sleeve)To P/+ terminal.

    (Red sleeve)To PR terminal.

    Protective bushes(Accessory)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    12/41

    10

    WIRING

    3.4 Main circuit terminal

    (1) Terminal layout and wiring

    200V class

    FR-A720-00030, 00050-NA/N4 FR-A720-00080, 00110, 00175-NA/N4

    FR-A720-00240, 00330-NA/N4

    * Screw size of terminal R1/L11, S1/L21, PR, and PX is M4.

    FR-A720-00460-NA

    FR-A720-00610, 00760, 00900-NA FR-A720-01150, 01450, 01750-NA

    R/L1 S/L2 T/L3

    N/- P/+

    PR

    PXR1/L11 S1/L21

    Charge lamp

    As this is an inside cover fixing screw,

    do not remove it.

    Jumper

    Screw size (M4)

    Screw size

    (M4)

    Jumper

    MotorPower supply

    IM

    R/L1 S/L2 T/L3 N/- P/+ PR

    PXR1/L11 S1/L21

    IMCharge lamp

    Jumper

    Screw size (M4)

    Screw size

    (M4)

    Jumper

    MotorPowersupply

    R/L1 S/L2 T/L3

    N/- P/+ PR

    PX

    R1/L11 S1/L21

    IM

    Screw size

    (M5)

    Screw size (M5)

    JumperJumper

    Charge lamp

    MotorPower supply

    * **

    *

    R1/L11 S1/L21

    R/L1 S/L2 T/L3 N/-

    P/+

    PR

    Charge lamp

    Jumper

    Jumper

    Screw size(M4)

    Screw size (M5)

    Screw size (M5)

    Power supply

    IMMotor

    R/L1 S/L2 T/L3 N/- P/+

    PR

    R1/L11 S1/L21

    IM

    Screw size (M4)

    Screw size (M6)

    Jumper

    Jumper

    Charge lamp

    MotorPower supply

    Screw size

    (00610:M6, 00760, 00900:M8)

    R/L1 S/L2 T/L3 N/- P/+

    R1/L11 S1/L21

    IM

    Screw size

    (M4)

    Jumper

    Jumper

    Charge lamp

    MotorPowersupply

    Screw size

    (01150:M6,

    01450/01750:M8)

    Screw size

    (01150:M8, 01450, 01750:M10)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    13/41

    11

    WIRING

    400V class

    FR-A720-02150-NA

    * When using the inverter with LD or SLD set, remove a jumper

    between P/+ and P1 and connect a DC reactor (FR-HEL-75Koption).

    FR-A720-02880, 03460-NA

    FR-A740-00015 to 00090-NA/N4 FR-A740-00120, 00170-NA/N4

    FR-A740-00230, 00310-NA FR-A740-00380, 00440-NA

    Power supply

    IMMotor

    Screw size (M8)

    R/L1 S/L2 T/L3 N/-

    Screw size (M12)

    Jumper

    Jumper *

    Charge lamp

    Screw size (M4)R1/L11 S1/L21

    P/+ R/L1 S/L2 T/L3 N/-

    P/+

    R1/L11 S1/L21

    P/+

    P/+

    IM

    Screw size (M4)

    Screw size (M12)

    Screw size(M10)

    Jumper

    Charge lamp

    MotorPower supply

    Screw size (M12)

    (for option)

    DC reactor

    R/L1 S/L2 T/L3 N/- P/+ PR

    PXR1/L11 S1/L21

    IMCharge lamp

    JumperScrew size (M4)

    Screw size(M4)

    Jumper

    MotorPowersupply

    R/L1 S/L2 T/L3

    N/- P/+ PR

    PX

    R1/L11 S1/L21

    IM

    Screw size

    (M4)

    Screw size

    (M4)

    Jumper Jumper

    Charge lamp

    MotorPower supply

    R1/L11 S1/L21

    R/L1 S/L2 T/L3 N/-

    P/+

    PR

    Charge lamp

    Jumper

    Jumper

    Screw size(M4)

    Screw size (M5)

    Screw size (M5)

    Power supply IMMotor

    R/L1 S/L2 T/L3 N/- P/+

    PR

    R1/L11 S1/L21

    IM

    Screw size (M4)

    Screw size (M6)

    Screw size (M6)

    Jumper

    Jumper

    Charge lamp

    Power supply Motor

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    14/41

    12

    WIRING

    FR-A740-00570, 00710, 00860-NA FR-A740-01100-NA

    * When using the inverter with LD or SLD set, remove a jumperbetween P/+ and P1 and connect a DC reactor (FR-HEL-H

    90K option).

    FR-A740-01440, 01800-NA FR-A740-02160, 02600-NA

    IM

    Jumper

    Jumper

    Charge lamp

    Screw size(M4)

    Powersupply Motor

    R/L1 S/L2 T/L3 N/- P/+

    R1/L11 S1/L21

    Screw size

    (00570: M6

    00710/00860: M8)

    Screw size

    (00570: M6

    00710, 00860: M8)

    IM

    Jumper

    Charge lampScrew size (M4)

    Powersupply

    Motor

    R /L1 S /L2 T/L3 N /-

    R1/L11 S1/L21

    Screw size (M8) Screw size (M10) Screw size (M8)

    Jumper *P/+

    Screw size (M8)

    IM

    R/L1 S/L2 T/L3 N/- P/+

    R1/L11 S1/L21

    DC reactor

    Screw size (M4)

    Powersupply

    Motor

    Jumper

    Charge lamp

    P/+

    Screw size

    (M10)

    Screw size(M10)

    IM

    R/L1 S/L2 T/L3 N/-

    P/+

    R1/L11 S1/L21

    P/+

    P/+

    Screw size (M4)

    Jumper

    Charge lamp

    Screw size(M10)

    Motor

    Screw size (M12)

    (for option)

    Power supply

    DC reactor

    Screw size (M10)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    15/41

    13

    WIRING

    600V class

    FR-A740-03250, 03610-NA FR-A740-04320 to 09620-NA

    FR-A760-00017 to 00061-NA FR-A760-00120-NA

    FR-A760-00220-NA FR-A760-00330-NA

    IM

    R/L1 S/L2 T/L3 N/-

    P/+

    R1/L11 S1/L21

    P/+

    P/+

    Screw size (M4)

    Jumper

    Charge lamp

    Screw size (M12)

    Screw size(M10)

    Motor

    Screw size (M12)

    (for option)

    Power supply

    DC reactor IM

    R/L1 S/L2 T/L3 N/-

    R1/L11 S1/L21

    P/+

    P/+

    Screw size (M4)

    Jumper

    Charge lamp

    MotorPower supplyDC reactor

    Screw size (M12)

    Screw size (M10)

    R/L1 S/L2 T/L3 N/- P/+ PR

    PXR1/L11 S1/L21

    IMCharge lamp

    Jumper

    Screw size (M4)

    Screw size

    (M4)

    Jumper

    MotorPowersupply

    R/L1 S/L2 T/L3

    N/- P/+ PR

    PX

    R1/L11 S1/L21

    IM

    Screw size

    (M4)

    Screw size

    (M4)

    JumperJumper

    Charge lamp

    MotorPower supply

    R1/L11 S1/L21

    R/L1 S/L2 T/L3 N/-

    P/+

    PR

    Charge lamp

    Jumper

    Jumper

    Screw size(M4)

    Screw size (M5)

    Screw size (M5)Power supply

    IM

    Motor

    R/L1 S/L2 T/L3 N/- P/+

    PR

    R1/L11 S1/L21

    IM

    Screw size (M4)

    Screw size (M6)

    Screw size (M6)

    Jumper

    Jumper

    Charge lamp

    Power supply Motor

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    16/41

    14

    WIRING

    FR-A760-00550-NA FR-A760-00840-NA

    * When using the inverter with LD or SLD set, remove a jumperbetween P/+ and P1 and connect a DC reactor.

    FR-A760-01040, 01310, 01520-NA FR-A760-02020, 02550-NA

    IM

    Jumper

    Jumper

    Charge lamp

    Screw size(M4)

    Powersupply Motor

    R/L1 S/L2 T/L3 N/- P/+

    R1/L11 S1/L21

    Screw size(M8)

    Screw size(M8)

    IM

    Jumper

    Charge lampScrew size (M4)

    Powersupply

    Motor

    R /L1 S /L2 T/L3 N /-

    R1/L11 S1/L21

    Screw size (M8)

    Jumper *P/+

    Screw size (M8)

    IM

    R/L1 S/L2 T/L3 N/- P/+

    R1/L11 S1/L21

    DC reactor

    Screw size (M4)

    Powersupply

    Motor

    Jumper

    Charge lamp

    P/+

    Screw size

    (M10)

    Screw size(M10)

    IM

    R/L1 S/L2 T/L3 N/-

    P/+

    R1/L11 S1/L21

    P/+

    P/+

    Screw size (M4)

    Jumper

    Charge lamp

    Screw size (M12)

    Screw size(M10)

    Motor

    Screw size (M12)

    (for option)

    Power supply

    DC reactor

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    17/41

    15

    WIRING

    FR-A760-03040, 04020-NA

    CAUTION The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W of the inverter.

    Doing so will damage the inverter. (Phase sequence needs not to be matched.) Connect the motor to U, V, W. At this time, turning on the forward rotation switch (signal) rotates the motor in the

    counterclockwise direction when viewed from the motor shaft. When wiring the inverter main circuit conductor of the FR-A740-04320 (FR-A760-03040) or more, tighten a nut from the right

    side of the conductor. When wiring two wires, place wires on both sides of the conductor. (Refer to the drawing below.) Forwiring, use bolts (nuts) provided with the inverter.

    IM

    R/L1 S/L2 T/L3 N/-

    R1/L11 S1/L21

    P/+

    P/+

    Screw size (M4)

    Jumper

    Charge lamp

    MotorPower supplyDC reactor

    Screw size (M12)

    Screw size (M10)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    18/41

    16

    WIRING

    (2) Applied cable sizeSelect the recommended cable size to ensure that a voltage drop will be 2% max.If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motortorque to decrease especially at the output of a low frequency.The following table indicates a selection example for the wiring length of 20m (65.62feet).

    200V class (when input power supply is 220V)

    Applicable InverterType

    Terminal

    Screw

    Size *4

    Tightening

    Torque

    Nm

    Crimping

    Terminal

    Cable Sizes

    HIV, etc. (mm2

    ) *1 AWG/MCM *2 PVC, etc. (mm2

    ) *3R/L1,S/L2,T/L3

    U, V, WR/L1,S/L2,T/L3

    U, V, W P/+, P1Earth

    (Ground)cable

    R/L1,S/L2,T/L3

    U, V, WR/L1,S/L2,T/L3

    U, V, WEarth

    (Ground)cable

    FR-A720-00030 to

    00110-NA/N4M4 1.5 2-4 2-4 2 2 2 2 14 14 2.5 2.5 2.5

    FR-A720-00175-NA/

    N4M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 3.5 12 12 4 4 4

    FR-A720-00240-NA/

    N4M5 2.5 5.5-5 5.5-5 5.5 5.5 5.5 5.5 10 10 6 6 6

    FR-A720-00330-NA/

    N4M5 2.5 14-5 8-5 14 8 14 14 6 8 16 10 16

    FR-A720-00460-NA M5 2.5 14-5 14-5 14 14 14 14 6 6 16 16 16

    FR-A720-00610-NA M6 4.4 22-6 22-6 22 22 22 14 4 4 25 25 16

    FR-A720-00760-NA M8-M6 7.8 38-8 38-8 38 38 38 22 2 2 35 35 25FR-A720-00900-NA M8-M6 7.8 38-8 38-8 38 38 38 22 2 2 35 35 25

    FR-A720-01150-NA M8-M6 7.8 60-8 60-8 60 60 60 38 1/0 1/0 50 50 25

    FR-A720-01450-NA M10-M8 14.7 80-10 80-10 80 80 80 38 3/0 3/0 70 70 35

    FR-A720-01750-NA M10-M8 14.7 100-10 100-10 100 100 100 60 4/0 4/0 95 95 50

    FR-A720-02150-NA M12-M8 24.5 100-12 100-12 100 100 100 60 4/0 4/0 95 95 50

    FR-A720-02880-NA M12-M10 24.5 150-12 150-12 125 125 125 38 250 250

    FR-A720-03460-NA M12-M10 24.5 150-12 150-12 150 150 150 60 300 300

    *1 For the 02150 or less, the cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum

    permissible temperature of 75C (167F). Assumes that the ambient temperature is 50C (122F) or less and the wiring distance is 20m

    (65.62feet) or less.

    For the 02880 or more, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable)

    etc.) with continuous maximum permissible temperature of 90C (194F). Assumes that the ambient temperature is 50C (122F) or less and

    wiring is performed in an enclosure.

    *2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75C (167F). Assumesthat the ambient temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less.

    (Selection example for use mainly in the United States.)

    *3 For the 00610 or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70C

    (158F). Assumes that the ambient temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less.

    For the 00760 or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90C

    (194F). Assumes that the ambient temperature is 40C (104F) or less and wiring is performed in an enclosure.

    (Selection example for use mainly in Europe.)

    *4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding). For the 00760 or more,

    screw sizes are different. ( - < a screw for earthing (grounding)>)

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    19/41

    17

    WIRING

    400V class (when input power supply is 440V)

    Applicable Inverter

    Type

    Terminal

    Screw

    Size *4

    Tightening

    Torque

    Nm

    Crimping

    Terminal

    Cable Sizes

    HIV, etc. (mm2) *1 AWG/MCM *2 PVC, etc. (mm2) *3

    R/L1,S/L2,T/L3

    U, V, WR/L1,S/L2,T/L3

    U, V, W P/+, P1Earth

    (Ground)Cable

    R/L1,S/L2,T/L3

    U, V, WR/L1,S/L2,T/L3

    U, V, WEarth

    (Ground)Cable

    FR-A740-00015 to

    00090-NA/N4M4 1.5 2-4 2-4 2 2 2 2 14 14 2.5 2.5 2.5

    FR-A740-00120-NA/N4

    M4 1.5 2-4 2-4 2 2 3.5 3.5 12 14 2.5 2.5 4

    FR-A740-00170-NA/

    N4M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 3.5 12 12 4 4 4

    FR-A740-00230-NA M5 2.5 5.5-5 5.5-5 5.5 5.5 5.5 8 10 10 6 6 10

    FR-A740-00310-NA M5 2.5 8-5 8-5 8 8 8 8 8 8 10 10 10

    FR-A740-00380-NA M6 4.4 14-6 8-6 14 8 14 14 6 8 16 10 16

    FR-A740-00440-NA M6 4.4 14-6 14-6 14 14 22 14 6 6 16 16 16

    FR-A740-00570-NA M6 4.4 22-6 22-6 22 22 22 14 4 4 25 25 16

    FR-A740-00710-NA M8 7.8 22-8 22-8 22 22 22 14 4 4 25 25 16

    FR-A740-00860-NA M8 7.8 38-8 38-8 38 38 38 22 1 2 50 50 25

    FR-A740-01100-NA M8 7.8 60-8 60-8 60 60 60 22 1/0 1/0 50 50 25

    FR-A740-01440-NA M10 14.7 60-10 60-10 60 60 60 38 1/0 1/0 50 50 25

    FR-A740-01800-NA M10 14.7 60-10 60-10 60 60 80 38 3/0 3/0 50 50 25FR-A740-02160-NA M10-M12 14.7 80-10 80-10 80 80 80 38 3/0 3/0 70 70 35

    FR-A740-02600-NA M10-M12 14.7 100-10 100-10 100 100 100 38 4/0 4/0 95 95 50

    FR-A740-03250-NA M12-M10 24.5 150-12 150-12 125 150 150 38 250 250 120 120 70

    FR-A740-03610-NA M12-M10 24.5 150-12 150-12 150 150 150 38 300 300 150 150 95

    FR-A740-04320-NA M12-M10 24.5 100-12 100-12 2100 2100 2100 60 24/0 24/0 295 295 95

    FR-A740-04810-NA M12-M10 24.5 100-12 100-12 2100 2100 2125 60 24/0 24/0 295 295 95

    FR-A740-05470-NA M12-M10 24.5 150-12 150-12 2125 2125 2125 60 2250 2250 2120 2120 120

    FR-A740-06100-NA M12-M10 24.5 150-12 150-12 2150 2150 2150 100 2300 2300 2150 2150 150

    FR-A740-06830-NA M12-M10 24.5 C2-200 C2-200 2200 2200 2200 100 2350 2350 2185 2185 295

    FR-A740-07700-NA M12-M10 24.5 C2-200 C2-200 2200 2200 2200 100 2400 2400 2185 2185 295

    FR-A740-08660-NA M12-M10 24.5 C2-250 C2-250 2250 2250 2250 100 2500 2500 2240 2240 2120

    FR-A740-09620-NA M12-M10 24.5 C2-200 C2-250 3200 2250 3200 2100 2500 2500 2240 2240 2120

    *1 For the 01100 or less, the cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximumpermissible temperature of 75C (167F). Assumes that the ambient temperature is 50C (122F) or less and the wiring distance is 20m

    (65.62feet) or less.

    For the 01440 or more, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable)

    etc.) with continuous maximum permissible temperature of 90C (194F). Assumes that the ambient temperature is 50C (122F) or less and

    wiring is performed in an enclosure.

    *2 For the 00860 or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75C

    (167F). Assumes that the ambient temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less.

    For the 01100 or more, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of

    90C (194F). Assumes that the ambient temperature is 40C (104F) or less and wiring is performed in an enclosure.

    (Selection example for use mainly in the United States.)

    *3 For the 00860 or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70C

    (158F). Assumes that the ambient temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less.

    For the 01100 or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90C

    (194F). Assumes that the ambient temperature is 40C (104F) or less and wiring is performed in an enclosure.

    (Selection example for use mainly in Europe.)

    *4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).For the 02160 and 02600, screw sizes are different ( - )

    For the 03250 or more, screw sizes are different. ( - )

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    20/41

    18

    WIRING

    600V class (when input power supply is 575V)

    The line voltage drop can be calculated by the following formula:

    line voltage drop [V]=

    Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torquereduction) in the low speed range.

    Applicable

    Inverter Type

    Terminal

    Screw

    Size *2

    Tightening

    Torque

    Nm

    Crimping TerminalCable Sizes*1

    HIV, etc. (mm2) AWG

    R/L1,S/L2,T/L3

    U, V, W P/+, P1

    Earth

    (Ground)

    Cable

    R/L1,S/L2,T/L3

    U, V, W P/+, P1

    Earth

    (Ground)

    Cable

    R/L1,S/L2,T/L3

    U, V, W P/+, P1

    Earth

    (Ground)

    Cable

    FR-A760-00017-NA M4 1.5 2-4 2-4 2-4 2-4 2 2 2 2 14 14 14 14

    FR-A760-00040-NA M4 1.5 2-4 2-4 2-4 2-4 2 2 2 2 14 14 14 14

    FR-A760-00061-NA M4 1.5 2-4 2-4 2-4 2-4 2 2 2 2 14 14 14 14

    FR-A760-00120-NA M4 1.5 3.5-4 2-4 3.5-4 3.5-4 3.5 2 3.5 3.5 12 14 10 12

    FR-A760-00220-NA M5 2.5 5.5-5 5.5-5 8-5 5.5-4 5.5 5.5 8 5.5 10 10 8 10

    FR-A760-00330-NA M6 4.4 14-6 14-6 14-6 14-6 14 14 14 14 6 6 4 6

    FR-A760-00550-NA M8 7.8 22-8 22-8 22-8 22-8 22 22 22 22 4 4 2 4

    FR-A760-00840-NA M8 7.8 38-8 38-8 38-8 22-8 38 38 38 22 2 2 1/0 4

    FR-A760-01040-NA M10 14.7 60-10 60-10 60-10 38-10 60 60 60 38 2 2 1/0 1

    FR-A760-01310-NA M10 14.7 60-10 60-10 60-10 38-10 60 60 60 38 1/0 1/0 2/0 1

    FR-A760-01520-NA M10 14.7 60-10 60-10 60-10 38-10 60 60 60 38 2/0 2/0 3/0 1

    FR-A760-02020-NA M12-M10 24.5 80-12 80-12 80-12 38-10 80 80 80 38 4/0 250 300 1

    FR-A760-02550-NA M12-M10 24.5 100-12 100-12 125-12 38-10 100 100 125 38 250 300 22/0 1

    FR-A760-03040-NA M12-M10 24.5 125-12 125-12 150-12 60-10 125 125 150 60 22/0 23/0 24/0 1/0

    FR-A760-04020-NA M12-M10 24.5 280 280 2100 100-10 280 280 2100 100 24/0 2250 2300 4/0

    *1 The cables used should be 75C (167F) copper cables.

    *2 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, a screw for earthing (grounding), and P/+ for option connection.

    For the 02020 or more, screw sizes are different. ( - )

    CAUTION Tighten the terminal screw to the specified torque.

    A screw that has been tighten too loosely can cause a short circuit or malfunction.A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.

    Use crimping terminals with insulation sleeve to wire the power supply and motor.

    3 wire resistance[m/m] wiring distance[m] current[A]

    1000

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    21/41

    19

    WIRING

    (3) Total wiring length (FR-A720/A740)The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below. (The wiring length should be 100m (328.08feet) maximum for vector control.)

    When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at themotor terminals, deteriorating the insulation of the motor.Take the following measures 1) or 2) in this case.

    1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency inPr. 72 PWM frequency selection

    according to wiring length

    2) Connect the surge voltage suppression filter (FR-ASF-H) to the FR-A720-02150 (FR-A740-01100) or less and

    the sine wave filter (MT-BSL/BSC) to the FR-A720-02880 (FR-A740-01440) or more on the inverter output side.

    Pr. 72 PWM frequency selection setting(carrier frequency)

    FR-A720-00030FR-A740-00015

    FR-A720-00050FR-A740-00025

    FR-A720-00080 or moreFR-A740-00040 or more

    2 (2kHz) or less300m

    (984.25 feet)500m

    (1640.42 feet)500m

    (1640.42 feet)

    3 to 15 (3kHz to 14.5kHz) 200m(656.19 feet) 300m(984.25 feet) 500m(1640.42 feet)

    CAUTION Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the

    wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction orfault of the equipment connected on the inverter output side. If fast response current limit function malfunctions, disable this

    function. (ForPr. 156 Stall prevention operation selection, refer to Instruction Manual.)

    For details ofPr. 72 PWM frequency selection , refer to Instruction Manual. (When using an option sine wave filter (MT-BSL/BSC) for the FR-A720-02880(FR-A740-01440) or more, set "25" (2.5kHz) inPr. 72.)For explanation of surge voltage suppression filter (FR-ASF-H) and sine wave fi lter (MT-BSL/BSC), refer to the manual of eachoption.

    Do not perform vector control with a surge voltage suppression filter (FR-ASF-H) or sine wave filer (MT-BSL/BSC) connected.

    Wiring Length

    50m (164.04feet) orless

    50m (164.04feet) to100m (328.08feet)

    exceeding 100m(328.08feet)

    Carrier frequency 14.5kHz or less 9kHz or less 4kHz or less

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    22/41

    20

    WIRING

    (4) Total wiring length (FR-A760)The overall wiring length for connection of a single motor or multiple motors should be within the value in the tablebelow.(The wiring length should be 100m (328.08feet) maximum for vector control.)

    When fast response current limit is enabled, the wiring length should be within the value in the table

    below (*Pr. 156= 0, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30).

    ND/HD Rated

    LD/SLD Rated

    When fast response current limit is disabled, the wiring length should be within the value in the table

    below (*Pr. 156= 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29).

    (5) Cable size of the control circuit power supply (terminal R1/L11, S1/L21) Terminal screw size: M4

    Cable size: 0.75mm2 to 2mm2

    Tightening torque: 1.5Nm

    Pr. 72 PWM frequency selection setting(carrier frequency)

    FR-A760-00017 FR-A760-00040 FR-A760-00061FR-A760-00120

    or more

    2 (2kHz) or less100m

    (328.08feet)300m

    (984.25feet)300m

    (984.25feet)500m

    (1640.42feet)

    3 to 15 (3kHz to 14.5kHz)100m

    (328.08feet)200m

    (656.16feet)300m

    (984.25feet)500m

    (1640.42feet)

    Pr. 72 PWM frequencyselection setting

    (carrier frequency)

    FR-A760-00017

    FR-A760-00040

    FR-A760-00061

    FR-A760-00120FR-A760-00220

    or more

    2 (2kHz) or less

    100m

    (328.08feet)

    200m

    (656.16feet)

    300m

    (984.25feet)

    500m

    (1640.42feet)

    500m

    (1640.42feet)

    3 to 15 (3kHz to 14.5kHz)100m

    (328.08feet)100m

    (328.08feet)200m

    (656.16feet)

    ND, HD500m

    (1640.42feet) 500m(1640.42feet)

    LD, SLD400m

    (1312.33feet)

    FR-A760-00017 FR-A760-00040 FR-A760-00061FR-A760-00120

    or more

    100m(328.08feet)

    300m(984.25feet)

    500m(1640.42feet)

    500m(1640.42feet)

    CAUTION Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the

    wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction or

    fault of the equipment connected on the inverter output side. If fast-response current limit function malfunctions, disable this

    function. (ForPr. 156 Stall prevention operation selection, refer to Instruction Manual.)

    For details ofPr. 72 PWM frequency selection , refer to Instruction Manual.

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    23/41

    21

    WIRING

    3.5 Control circuit terminals

    (1) Terminal layout

    (2) Instructions for wiring of the control circuit terminal1) Terminals 5, SD and SE are common to the I/O signals and isolated from each other. Do not earth (ground).

    Avoid connecting the terminal SD and 5 and the terminal SE and 5.2) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and

    power circuits (including the 200V relay sequence circuit).3) Use two or more parallel micro-signal contacts or twin contacts to

    prevent a contact faults when using contact inputs since thecontrol circuit input signals are micro-currents.

    4) Do not apply a voltage to the contact input terminals (e.g. STF) ofthe control circuit.

    5) Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp, etc.

    6) It is recommended to use the cables of 0.75mm2 gauge for connection to the control circuit terminals.

    If the cable gauge used is 1.25mm2 or more, the front cover may be lifted when there are many cables running orthe cables are run improperly, resulting in an operation panel contact fault.

    7) The wiring length should be 30m (98.43feet) maximum.

    Terminal screw size: M3.5

    Tightening torque: 1.2Nm A1 B1 C1 A2 B2 C2 10E 10 2 5 4

    1AMSDRESMRSSTOPAURTRHRMRL

    PCCSJOGSTRSTFSDSDFUOLIPFSURUNSE

    FM

    Micro signal contacts Twin contacts

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    24/41

    22

    PRECAUTIONS FOR USE OFTHE INVERTER

    4 PRECAUTIONS FOR USE OF THE INVERTER

    The FR-A700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling methodmay shorten the product life or damage the product.Before starting operation, always recheck the following items.

    (1) Use crimping terminals with insulation sleeve to wire the power supply and motor.

    (2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring.

    (3) After wiring, wire offcuts must not be left in the inverter.

    Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes inan enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.

    (4) Use cables of the size to make a voltage drop 2% maximum.

    If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torqueto decrease especially at the output of a low frequency.Refer topage16for the recommended cable sizes.

    (5) The overall wiring length should be 500m (1640.4 feet) maximum.(The wiring length should be 100m (328.1 feet) maximum for vector control.)

    Especially for long distance wiring, the fast response current limit function may decrease or the equipment connected tothe secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacityof the wiring. Therefore, note the overall wiring length. (Refer to page 19.)

    (6) Electromagnetic wave interference

    The input/output (main circuit) of the inverter includes high frequency components, which may interfere with thecommunication devices (such as AM radios) used near the inverter. In this case, set the EMC filter valid to minimizeinterference. (Only the FR-A720/A740 are provided with an EMC filter.)

    (7) Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the inverter output side.

    This will cause the inverter to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices isinstalled, immediately remove it.

    (8) Before starting wiring or other work after the inverter is operated, wait for at least 10 minutes after the power supply hasbeen switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged withhigh voltage for some time after power off and it is dangerous.

    (9) A short circuit or earth (ground) fault on the inverter output side may damage the inverter modules.

    Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused byperipheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation

    resistance may damage the inverter modules. Fully check the to-earth (ground) insulation and phase to phase insulation of the inverter output side before power-on.

    Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.

    (10) Do not use the inverter input side magnetic contactor to start/stop the inverter.

    Always use the start signal (ON/OFF of STF and STR signals) to start/stop the inverter.

    (11) Across P/+ and PR terminals, connect only an external regenerative brake discharge resistor.Do not connect a mechanical brake.

    (12) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.Application of permissible voltage to the inverter I/O signal circuit and incorrect polarity may damage the I/O terminal.Especially check the wiring to prevent the speed setting potentiometer from being connected incorrectly to short

    terminals 10E-5.

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    25/41

    23

    PRECAUTIONS FOR USE OF THEINVERTER

    (13) Provide electrical and mechanical interlocks for MC1 and

    MC2 which are used for bypass operation.When the wiring is incorrect and if there is a bypassoperation circuit as shown right, the inverter will be

    damaged when the power supply is connected to theinverter U, V, W terminals, due to arcs generated at the

    time of switch-over or chattering caused by a sequence

    error.

    (Commercial operation can not be performed with thevector dedicated motor (SF-V5RU, SF-THY).)

    (14) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in theinverter's input side and also make up a sequence which will not switch on the start signal.If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the

    power is restored.

    (15) Instructions for overload operationWhen performing an operation of frequent start/stop with the inverter, rise/fall in the temperature of the transistor element

    of the inverter will repeat due to a continuous flow of large current, shortening the life from thermal fatigue. Since thermalfatigue is related to the amount of current, the life can be increased by reducing current at locked condition, startingcurrent, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and

    the inverter may not start. Therefore, choose the inverter which has enough allowance for current (up to 2 rank larger in

    capacity).

    (16) Make sure that the specifications and rating match the system requirements.

    (17) A motor with encoder is necessary for vector control. In addition, connect the encoder directly to the backlash-free motorshaft. An encoder is not necessary for real sensorless vector control.

    MC2

    MC1

    U

    V

    W

    R/L1

    S/L2

    T/L3

    IMPower supply

    InverterUndesirable current

    Interlock

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    26/41

    24

    PARAMETER LIST

    5 PARAMETER LIST

    5.1 Parameter list

    For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the

    necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be madefrom the operation panel (FR-DU07).

    REMARKS

    indicates simple mode parameters. (initially set to extended mode)

    The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter writeselection.

    Parameter NameSettingRange

    InitialValue

    0 Torque boost 0 to 30%6/5/4/3/2/1% *1

    1 Maximum frequency 0 to 120Hz120/

    60Hz *2

    2 Minimum frequency 0 to 120Hz 0Hz

    3 Base frequency 0 to 400Hz 60Hz

    4Multi-speed setting (highspeed)

    0 to 400Hz 60Hz

    5Multi-speed setting (middlespeed)

    0 to 400Hz 30Hz

    6Multi-speed setting (lowspeed)

    0 to 400Hz 10Hz

    7 Acceleration time 0 to 3600/360s 5/15s *3

    8 Deceleration time 0 to 3600/360s 5/15s *3

    9 Electronic thermal O/L relay0 to 500/0 to 3600A *2

    Ratedinvertercurrent

    10DC injection brake operation

    frequency

    0 to 120Hz,

    99993Hz

    11

    DC injection brake operation

    time 0 to 10s, 8888 0.5s

    12DC injection brake operation

    voltage0 to 30% 4/2/1%

    *4

    13 Starting frequency 0 to 60Hz 0.5Hz

    14 Load pattern selection 0 to 5 0

    15 Jog frequency 0 to 400Hz 5Hz

    16Jog acceleration/

    deceleration time0 to 3600/360s 0.5s

    17 MRS input selection 0, 2, 4 0

    18High speed maximumfrequency

    120 to 400Hz120/

    60Hz*2

    19 Base frequency voltage0 to 1000V,

    8888, 9999

    9999

    20Acceleration/decelerationreference frequency

    1 to 400Hz 60Hz

    21Acceleration/deceleration timeincrements

    0, 1 0

    22Stall prevention operationlevel(torque limit level )

    0 to 400% 150%

    23Stall prevention operationlevel compensation factor atdouble speed

    0 to 200%,9999

    9999

    24 to 27Multi-speed setting (4 speed

    to 7 speed)

    0 to 400Hz,

    99999999

    28 Multi-speed inputcompensation selection

    0, 1 0

    29

    Acceleration/deceleration

    pattern selection 0 to 5 0

    30 Regenerative functionselection0, 1, 2, 10, 11,

    20, 210

    31 Frequency jump 1A0 to 400Hz,

    99999999

    32 Frequency jump 1B0 to 400Hz,

    99999999

    33 Frequency jump 2A0 to 400Hz,

    99999999

    34 Frequency jump 2B0 to 400Hz,

    99999999

    35 Frequency jump 3A0 to 400Hz,

    99999999

    36 Frequency jump 3B0 to 400Hz,

    99999999

    37 Speed display 0, 1 to 9998 0

    41 Up-to-frequency sensitivity 0 to 100% 10%

    42 Output frequency detection 0 to 400Hz 6Hz

    43Output frequency detection forreverse rotation

    0 to 400Hz,

    99999999

    44Second acceleration/

    deceleration time0 to 3600/360s 5s

    45 Second deceleration time0 to 3600/

    360s, 9999

    9999

    46 Second torque boost 0 to 30%, 9999 9999

    47 Second V/F (base frequency)0 to 400Hz,

    99999999

    48Second stall preventionoperation current

    0 to 220% 150%

    49Second stall preventionoperation frequency

    0 to 400Hz,

    99990Hz

    50Second output frequency

    detection0 to 400Hz 30Hz

    51Second electronic thermal

    O/L relay

    0 to 500A,

    9999/

    0 to 3600A,

    9999 *2

    9999

    52 DU/PU main display dataselection

    0, 5 to 14, 17

    to 20, 22 to 25,32 to 35,

    50 to 57, 100

    0

    54FM terminal function

    selection

    1 to 3, 5 to 14,

    17, 18, 21, 24,

    32 to 34, 50,

    52, 53, 70

    1

    55Frequency monitoring

    reference0 to 400Hz 60Hz

    56Current monitoring

    reference

    0 to 500/0 to

    3600A*2

    Ratedinvertercurrent

    57 Restart coasting time

    0, 0.1 to 5s,

    9999/

    0, 0.1 to 30s,

    9999 *2

    9999

    58 Restart cushion time 0 to 60s 1s

    59 Remote function selection 0, 1, 2, 3 0

    Parameter NameSettingRange

    InitialValue

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    27/41

    25

    PARAMETER LIST

    60Energy saving control

    selection0, 4 0

    61 Reference current

    0 to 500A,

    9999/

    0 to 3600A,

    9999 *2

    9999

    62

    Reference value at

    acceleration

    0 to 220%,

    9999 9999

    63Reference value at

    deceleration

    0 to 220%,

    99999999

    64Starting frequency for

    elevator mode

    0 to 10Hz,

    99999999

    65 Retry selection 0 to 5 0

    66Stall prevention operation

    reduction starting frequency0 to 400Hz 60Hz

    67Number of retries at alarm

    occurrence

    0 to 10,

    101 to 1100

    68 Retry waiting time 0 to 10s 1s

    69 Retry count display erase 0 0

    70 Special regenerative brakeduty

    0 to 30%/0 to 10% *2

    0%

    71 Applied motor

    0 to 8, 13 to

    18, 20, 23, 24,

    30, 33, 34, 40,

    43, 44, 50, 53,

    54

    /0 to 8, 13 to

    18, 30, 33, 34

    *5

    0

    72 PWM frequency selection0 to 15/

    0 to 6, 25*22

    73 Analog input selection 0 to 7, 10 to 17 1

    74 Input filter time constant 0 to 8 1

    75Reset selection/disconnected PU detection/

    PU stop selection

    0 to 3, 14 to17, 100 to 103,

    114 to 117

    14

    76 Alarm code output selection 0, 1, 2 0

    77 Parameter write selection 0, 1, 2 0

    78Reverse rotation prevention

    selection0, 1, 2 0

    79 Operation mode selection0, 1, 2, 3, 4, 6,

    70

    80 Motor capacity

    0.4 to 55kW,

    9999/

    0 to 3600kW,

    9999 *2

    9999

    81 Number of motor poles

    2, 4, 6, 8, 10,

    12, 14, 16, 18,20, 9999

    9999

    82 Motor excitation current

    0 to 500A,

    9999/

    0 to 3600A,

    9999 *2

    9999

    83 Motor rated voltage 0 to 1000V 200/400/575V *6

    84 Rated motor frequency 10 to 120Hz 60Hz

    89Speed control gain (advanced

    magnetic flux vector)

    0 to 200%,

    99999999

    90 Motor constant (R1)

    0 to 50,

    9999/

    0 to 400m,

    9999 *2

    9999

    91 Motor constant (R2)0 to 50

    ,9999/

    0 to 400m,

    9999 *2

    9999

    Parameter NameSettingRange

    InitialValue

    92 Motor constant (L1)

    0 to 50

    (0 to 1000mH), 9999/

    0 to 3600m

    (0 to 400mH), 9999*2

    9999

    93 Motor constant (L2)

    0 to 50

    (0 to 1000mH), 9999/

    0 to 3600m(0 to 400mH), 9999*2

    9999

    94 Motor constant (X)

    0 to 500(0 to 100%), 9999/

    0 to 100

    (0 to 100%), 9999*2

    9999

    95 Online auto tuning selection 0 to 2 0

    96 Auto tuning setting/status 0, 1, 101 0

    100 V/F1(first frequency)0 to 400Hz,

    99999999

    101 V/F1(first frequency voltage) 0 to 1,000V 0V

    102 V/F2(second frequency)0 to 400Hz,

    9999

    9999

    103V/F2(second frequency

    voltage)0 to 1,000V 0V

    104 V/F3(third frequency)0 to 400Hz,

    99999999

    105V/F3(third frequency

    voltage)0 to 1,000V 0V

    106 V/F4(fourth frequency)0 to 400Hz,

    99999999

    107V/F4(fourth frequency

    voltage)0 to 1,000V 0V

    108 V/F5(fifth frequency)0 to 400Hz,

    99999999

    109 V/F5(fifth frequency voltage) 0 to 1,000V 0V

    110

    Third acceleration/

    deceleration time

    0 to 3600/

    360s, 9999 9999

    111 Third deceleration time0 to 3600/

    360s, 99999999

    112 Third torque boost 0 to 30%, 9999 9999

    113 Third V/F (base frequency)0 to 400Hz,

    99999999

    114Third stall prevention

    operation current0 to 220% 150%

    115Thrid stall prevention

    operation frequency0 to 400Hz 0

    116Third output frequency

    detection0 to 400Hz 60Hz

    117PU communication station

    number0 to 31 0

    118 PU communication speed 48, 96, 192,384

    192

    119PU communication stop bit

    length0, 1, 10, 11 1

    120PU communication parity

    check0, 1, 2 2

    121Number of PU

    communication retries0 to 10, 9999 1

    122PU communication check

    time interval

    0, 0.1 to

    999.8s, 99999999

    123PU communication waiting

    time setting

    0 to 150ms,

    99999999

    124PU communication CR/LF

    selection0, 1, 2 1

    125Terminal 2 frequency setting

    gain frequency0 to 400Hz 60Hz

    126Terminal 4 frequency setting

    gain frequency0 to 400Hz 60Hz

    Parameter NameSettingRange

    InitialValue

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    28/41

    26

    PARAMETER LIST

    127PID control automaticswitchover frequency

    0 to 400Hz,

    99999999

    128 PID action selection

    10, 11, 20, 21,50, 51, 60, 61,70, 71, 80, 81,90, 91, 100,101

    10

    129 PID proportional band 0.1 to 1000%,9999 100%

    130 PID integral time0.1 to 3600s,

    99991s

    131 PID upper limit0 to 100%,

    99999999

    132 PID lower limit0 to 100%,

    99999999

    133 PID action set point0 to 100%,

    99999999

    134 PID differential time0.01 to 10.00s,

    99999999

    135Electronic bypass sequenceselection

    0, 1 0

    136MC switchover interlock

    time

    0 to 100s 1s

    137 Start waiting time 0 to 100s 0.5s

    138 Bypass selection at an alarm 0, 1 0

    139Automatic switchoverfrequency from inverter tobypass operation

    0 to 60Hz,

    99999999

    140Backlash accelerationstopping frequency

    0 to 400Hz 1Hz

    141Backlash accelerationstopping time

    0 to 360s 0.5s

    142Backlash decelerationstopping frequency

    0 to 400Hz 1Hz

    143Backlash decelerationstopping time

    0 to 360s 0.5s

    144 Speed setting switchover0, 2, 4, 6, 8,10, 102, 104,106, 108, 110

    4

    145PU display language

    selection0 to 7 1

    148Stall prevention level at 0V

    input0 to 220% 150%

    149Stall prevention level at 10V

    input0 to 220% 200%

    150Output current detection

    level0 to 220% 150%

    151Output current detection

    signal delay time0 to 10s 0s

    152 Zero current detection level 0 to 220% 5%

    153 Zero current detection time 0 to 1s 0.5s

    154

    Voltage reduction selection

    during stall prevention

    operation

    0, 1 1

    155RT signal function validity

    condition selection0, 10 0

    156Stall prevention operation

    selection

    0 to 31, 100,

    1010

    157 OL signal output timer 0 to 25s, 9999 0s

    158AM terminal function

    selection

    1 to 3, 5 to 14,17, 18, 21, 24,32 to 34, 50,52, 53, 70

    1

    159Automatic switchoverfrequency range frombypass to inverter operation

    0 to 10Hz,

    99999999

    160 User group read selection 0, 1, 9999 0

    161Frequency setting/key lockoperation selection

    0, 1, 10, 11 0

    Parameter NameSettingRange

    InitialValue

    162

    Automatic restart after

    instantaneous power failure

    selection

    0, 1, 2, 10, 11,

    120

    163 First cushion time for restart 0 to 20s 0s

    164First cushion voltage for

    restart0 to 100% 0%

    165Stall prevention operation

    level for restart 0 to 220% 150%

    166Output current detection

    signal retention time0 to 10s, 9999 0.1s

    167Output current detection

    operation selection0, 1 0

    168Parameter for manufacturer setting. Do not set.

    169

    170 Watt-hour meter clear 0, 10, 9999 9999

    171 Operation hour meter clear 0, 9999 9999

    172User group registered

    display/batch clear9999, (0 to 16) 0

    173 User group registration 0 to 999, 9999 9999

    174 User group clear 0 to 999, 9999 9999

    178STF terminal function

    selection

    0 to 20, 22 to

    28, 42 to 44,

    50, 60, 62, 64

    to 71, 74, 9999

    60

    179 STR terminal functionselection

    0 to 20, 22 to

    28, 42 to 44,50, 61, 62, 64

    to 71, 74, 9999

    61

    180RL terminal function

    selection

    0 to 20, 22 to

    28, 42 to 44,

    50, 62, 64 to

    71, 74, 9999

    0

    181RM terminal function

    selection1

    182RH terminal function

    selection2

    183RT terminal function

    selection3

    184AU terminal function

    selection

    0 to 20, 22 to

    28, 42 to 44,

    50, 62 to 71,

    74, 9999

    4

    185JOG terminal function

    selection

    0 to 20, 22 to

    28, 42 to 44,

    50, 62, 64 to

    71, 74, 9999

    5

    186CS terminal function

    selection6

    187MRS terminal function

    selection24

    188STOP terminal function

    selection25

    189RES terminal function

    selection62

    Parameter NameSettingRange

    InitialValue

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    29/41

    27

    PARAMETER LIST

    190RUN terminal function

    selection

    0 to 8, 10 to

    20, 25 to 28,

    30 to 36, 39,

    41 to 47, 64,

    70, 84, 85, 90

    to 99,

    100 to 108,

    110 to 116,120, 125 to

    128, 130 to

    136, 139, 141

    to 147, 164,

    170, 184, 185,

    190 to 199,

    9999

    0

    191SU terminal function

    selection1

    192

    IPF terminal function

    selection 2

    193OL terminal function

    selection3

    194FU terminal function

    selection4

    195ABC1 terminal function

    selection

    0 to 8, 10 to

    20, 25 to 28,

    30 to 36, 39,

    41 to 47, 64,

    70, 84, 85, 90,

    91, 94 to 99,

    100 to 108,

    110 to 116,

    120, 125 to

    128, 130 to

    136, 139, 141

    to 147, 164,

    170, 184, 185,

    190, 191, 194

    to 199, 9999

    99

    196ABC2 terminal function

    selection9999

    232 to

    239

    Multi-speed setting (8 speed

    to 15 speed)

    0 to 400Hz,

    99999999

    240Soft-PWM operation

    selection0, 1 1

    241Analog input display unit

    switchover0, 1 0

    242

    Terminal 1 added

    compensation amount

    (terminal 2)

    0 to 100% 100%

    243

    Terminal 1 added

    compensation amount

    (terminal 4)

    0 to 100% 75%

    244Cooling fan operation

    selection0, 1 1

    245 Rated slip 0 to 50%, 9999 9999

    246Slip compensation time

    constant0.01 to 10s 0.5s

    247Constant-power range slip

    compensation selection0, 9999 9999

    250 Stop selection0 to 100s,1000to 1100s

    8888, 9999

    9999

    251Output phase loss

    protection selection0, 1 1

    252 Override bias 0 to 200% 50%

    253 Override gain 0 to 200% 150%

    255 Life alarm status display (0 to 15) 0

    256Inrush current limit circuit

    life display(0 to 100%) 100%

    257Control circuit capacitor life

    display(0 to 100%) 100%

    258Main circuit capacitor life

    display(0 to 100%) 100%

    259 Main circuit capacitor lifemeasuring

    0, 1 0

    260PWM frequency automatic

    switchover0, 1 1

    Parameter NameSettingRange

    InitialValue

    261 Power failure stop selection 0, 1, 2, 11, 12 0

    262Subtracted frequency at

    deceleration start0 to 20Hz 3Hz

    263Subtraction starting

    frequency

    0 to 120Hz,

    999960Hz

    264Power-failure deceleration

    time 10 to 3600/360s 5s

    265Power-failure deceleration

    time 2

    0 to 3600s/

    360s, 99999999

    266Power failure deceleration

    time switchover frequency0 to 400Hz 60Hz

    267 Terminal 4 input selection 0, 1, 2 0

    268Monitor decimal digits

    selection0,1, 9999 9999

    269 Parameter for manufacturer setting. Do not set.

    270

    Stop-on contact/load torque

    high-speed frequency

    control selection

    0, 1, 2, 3 0

    271High-speed setting

    maximum current0 to 220% 50%

    272Middle-speed setting

    minimum current0 to 220% 100%

    273 Current averaging range0 to 400Hz,

    99999999

    274Current averaging filter time

    constant1 to 4000 16

    275

    Stop-on contact excitation

    current low-speed

    multiplying factor

    0 to 1000%,

    99999999

    276PWM carrier frequency at

    stop-on contact

    0 to 9, 9999/

    0 to 4, 9999 *29999

    278 Brake opening frequency 0 to 30Hz 3Hz

    279 Brake opening current 0 to 220% 130%

    280Brake opening current

    detection time0 to 2s 0.3s

    281 Brake operation time at start 0 to 5s 0.3s

    282 Brake operation frequency 0 to 30Hz 6Hz

    283 Brake operation time at stop 0 to 5s 0.3s

    284Deceleration detection

    function selection0, 1 0

    285

    Overspeed detection

    frequency

    (Excessive speed deviation

    detection frequency)

    0 to 30Hz,

    99999999

    286 Droop gain 0 to 100% 0%

    287 Droop filter time constant 0 to 1s 0.3s

    288Droop function activation

    selection0, 1, 2, 10, 11 0

    291 Pulse train I/O selection0, 1, 10, 11,

    20, 21, 1000

    292Automatic acceleration/

    deceleration

    0, 1, 3, 5 to 8,

    110

    293Acceleration/deceleration

    separate selection0 to 2 0

    294 UV avoidance voltage gain 0 to 200% 100%

    299Rotation direction detection

    selection at restarting0, 1, 9999 0

    331

    RS-485 communication

    station number

    0 to 31

    (0 to 247) 0

    332RS-485 communicationspeed

    3, 6, 12, 24,48, 96, 192,384

    96

    Parameter NameSettingRange

    InitialValue

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    30/41

    28

    PARAMETER LIST

    333RS-485 communication stopbit length

    0, 1, 10, 11 1

    334RS-485 communicationparity check selection

    0, 1, 2 2

    335RS-485 communication retrycount

    0 to 10, 9999 1

    336RS-485 communicationcheck time interval

    0 to 999.8s,9999

    0s

    337RS-485 communicationwaiting time setting

    0 to 150ms,9999

    9999

    338Communication operationcommand source

    0, 1 0

    339Communication speedcommand source

    0, 1, 2 0

    340Communication startupmode selection

    0, 1, 2, 10, 12 0

    341RS-485 communication CR/LF selection

    0, 1, 2 1

    342Communication EEPROMwrite selection

    0, 1 0

    343 Communication error count 0

    350 *7Stop position command

    selection0, 1, 9999 9999

    351 *7 Orientation speed 0 to 30Hz 2Hz

    352 *7 Creep speed 0 to 10Hz 0.5Hz

    353 *7 Creep switchover position 0 to 16383 511

    354 *7Position loop switchover

    position0 to 8191 96

    355 *7DC injection brake start

    position0 to 255 5

    356 *7Internal stop position

    command0 to 16383 0

    357 *7 Orientation in-position zone 0 to 255 5

    358 *7 Servo torque selection 0 to 13 1

    359 *7 Encoder rotation direction 0, 1 1

    360 *7 16 bit data selection 0 to 127 0

    361 *7 Position shift 0 to 16383 0

    362 *7Orientation position loopgain

    0.1 to 100 1

    363 *7Completion signal output

    delay time0 to 5s 0.5s

    364 *7 Encoder stop check time 0 to 5s 0.5s

    365 *7 Orientation limit 0 to 60s, 9999 9999

    366 *7 Recheck time 0 to 5s, 9999 9999

    367 *7 Speed feedback range0 to 400Hz,9999

    9999

    368 *7 Feedback gain 0 to 100 1

    369 *7 Number of encoder pulses 0 to 4096 1024

    374 Overspeed detection level 0 to 400Hz 140Hz

    376 *7

    Encoder signal loss

    detection enable/disable

    selection

    0, 1 0

    380 Acceleration S-pattern 1 0 to 50% 0

    381 Deceleration S-pattern 1 0 to 50% 0

    382 Acceleration S-pattern 2 0 to 50% 0

    383 Deceleration S-pattern 2 0 to 50% 0

    384Input pulse division scaling

    factor0 to 250 0

    385Frequency for zero input

    pulse0 to 400Hz 0

    386Frequency for maximum

    input pulse0 to 400Hz 60Hz

    393 *7 Orientation selection 0, 1, 2 0

    396 *7Orientation speed gain (P

    term)

    0 to 1000 60

    397 *7Orientation speed integral

    time0 to 20s 0.333s

    Parameter NameSettingRange

    InitialValue

    398 *7Orientation speed gain (D

    term)0 to 100 1

    399 *7Orientation deceleration

    ratio0 to 1000 20

    414PLC function operation

    selection0, 1 0

    415

    Inverter operation lock mode

    setting 0, 1 0

    416 Pre-scale function selection 0 to 5 0

    417 Pre-scale setting value 0 to 32767 1

    419 *7Position command source

    selection0, 2 0

    420 *7Command pulse scaling

    factor numerator0 to 32767 1

    421 *7Command pulse scaling

    factor denominator0 to 32767 1

    422 *7 Position loop gain 0 to 150sec-1 25sec-1

    423 *7 Position feed forward gain 0 to 100% 0

    424 *7

    Position command

    acceleration/deceleration

    time constant

    0 to 50s 0s

    425 *7Position feed forward

    command filter0 to 5s 0s

    426 *7 In-position width0 to

    32767pulse100

    427 *7 Excessive level error0 to 400K,9999

    40K

    428 *7 Command pulse selection 0 to 5 0

    429 *7 Clear signal selection 0, 1 1

    430 *7 Pulse monitor selection 0 to 5, 9999 9999

    450 Second applied motor

    0 to 8, 13 to

    18, 20, 23, 24,

    30, 33, 34, 40,

    43, 44, 50, 53,

    54, 9999/0 to 8,

    13 to 18, 30,

    33, 34, 9999 *5

    9999

    451Second motor control

    method selection

    10, 11, 12, 20,

    99999999

    453 Second motor capacity

    0.4 to 55kW,

    9999/

    0 to 3600kW,

    9999 *2

    9999

    454Number of second motor

    poles

    2, 4, 6, 8, 10,

    99999999

    455Second motor excitation

    current

    0 to 500A,

    9999/

    0 to 3600A,

    9999 *2

    9999

    456 Rated second motor voltage 0 to 1000V 200/400/575V *6

    457Rated second motor

    frequency10 to 120Hz 60Hz

    458 Second motor constant (R1)

    0 to 50,

    9999/

    0 to 400m,

    9999 *2

    9999

    459 Second motor constant (R2)

    0 to 50,

    9999/

    0 to 400m,

    9999 *2

    9999

    460 Second motor constant (L1)

    0 to 50

    (0 to 1000mH), 9999/

    0 to 3600m

    (0 to 400mH), 9999*2

    9999

    Parameter NameSettingRange

    InitialValue

  • 7/29/2019 Mitsubishi FR-A700 Installation Guide

    31/41

    29

    PARAMETER LIST

    461 Second motor constant (L2)

    0 to 50

    (0 to 1000mH), 9999/

    0 to 3600m

    (0 to 400mH), 9999*2

    9999

    462 Second motor constant (X)

    0 to 500(0 to 100%), 9999/

    0 to 100(0 to 100%), 9999*2

    9999

    463Second motor auto tuning

    setting/status0, 1, 101 0

    464 *7

    Digital position control

    sudden stop deceleration

    time

    0 to 360.0s 0

    465 *7First position feed amount

    lower 4 digits0 to 9999 0

    466 *7First position feed amount

    upper 4 digits0 to 9999 0

    467 *7Second position feed amount

    lower 4 digits0 to 9999 0

    468 *7Second position feed amount

    upper 4 digits

    0 to 9999 0

    469 *7Third position feed amoun