MILDLY FLAMMABLE REFRIGERANTS

19
Working with A2Ls MILDLY FLAMMABLE REFRIGERANTS Stefan Schuessler 18.10.2018

Transcript of MILDLY FLAMMABLE REFRIGERANTS

Page 1: MILDLY FLAMMABLE REFRIGERANTS

Working with A2LsMILDLY FLAMMABLE REFRIGERANTSStefan Schuessler

18.10.2018

Page 2: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

A2L Portfolio

1

All GWP values based on IPCC AR4

Solstice yf

R-455A

GWP 148

R-1234yf

GWP 4

R-1234ze(E)

GWP 6

R-452B

GWP 698

Page 3: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Flammability Properties

2

A2L Refrigerants are difficult to ignite

Probability of Ignition Effect of Ignition

Page 4: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Safety Standards in EU – Overview

3

A2L Included in most Standards

Do

mesti

c

Re

frig

era

tio

n

Co

mm

erc

ial

Re

frig

era

tio

n

Ind

us

tria

l

Sys

tem

s

Tra

ns

po

rt

Re

frig

era

tio

n

Air

-to

-air

Air

Co

nd

itio

ne

rs &

He

at

Pu

mp

s

Wa

ter

He

ati

ng

He

at

Pu

mp

s

He

at

Pu

mp

Tu

mb

le D

rie

rs

Ch

ille

rs

Ve

hic

le A

ir

Co

nd

itio

nin

g

Re

frig

era

ted

Co

nta

ine

rs

Product Safety

Standards

EN 60335-2-11 X

EN 60335-2-24 X

EN 60335-2-40 X X X

EN 60335-2-89 X

ISO 13043 X

ISO 20854 X

Group Safety

StandardEN 378 X X X X X X X X X

Page 5: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Interaction of Standards with Laws, Regulations & Codes

4

EUMember states

Local level

Fire fighting departments

City council, licensing

No particular standards in

place: application is limited as

in general these instances

look at the refrigerant type as

specified in CLP (flammable ,

extremely flammable)

F-gas regulation Building codes

Adaption of standards needed

Codes may refer to EN 378.

But not all building codes do.

(MS do not necessarily follow

standardisation work)

EN 378

EN 60335-2-40

EN 60335-2-89

EN 60335-2-24

Page 6: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Allowable Charge Calculation

5

Safety Classification

(A,B - 1,2L,2,3)

Occupancy

a

Occupancy

c

Occupancy

b

System Location

I

System Location

IV

System Location

III

System Location

II

Look-Up Table

Page 7: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

FLAMMABILITY

1

Non-Flammable

2L

Lower Flammability

2

Flammable

3

Higher Flammability

A

R404A - R407F -

R422D – R452A

R134a – R466A

R1233zd

R448A (N40)

R450A (N13)

R1234yf

R1234ze

R447A (L41)

R444B (L20)

R455A

R32 – R452B

R-152a HC

B R245fa Ammonia

TO

XIC

ITY

Increasing Hazard

Incre

asin

g H

azard

Step 1 – Safety Classification

6

Refrigerants with GWP <150 in red

Page 8: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Manufacturing Facilities e.g. for

Chemicals

Food

Beverage

Ice

Ice-Cream

Refineries

Cold Stores

Dairies

Abattoirs

Non-public Areas in

Supermarkets

Business

Professional Offices

Laboratories

Manufacturing Places

Work Place

Hospitals

Courts

Theatres

Supermarkets

Schools

Airports

Hotels

Dwellings

Restaurants

B) SupervisedA) General Occupancy C) Restricted

Step 2 – Occupancy

7

Page 9: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

IV

Ventilated enclosure

III

All refrigerant

containing parts in

machinery room or

open air

II

Compressor &

pressure vessel in

machinery room or

open air

I

All refrigerant

containing parts in the

occupied space

Step 3 – System Location

8

Special applications

Page 10: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Applying EN-378 to Room AC

9

Step 1:

Select Refrigerant

Class

Step 2:

Select Occupancy

Step 3:

Select System Location

Page 11: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Charge Limit Comparison

10

A larger charge is allowed with 2L refrigerants

0

2

4

6

8

10

12

14

0 50 100 150 200 250

Floor Area (m2)

Ch

arg

e (

kg

)

1234yf -A2L

R152a – A2

HC – A3

Page 12: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

R-455A (A2L) Charge Limits – Refrigeration

11

Room height 2,5 m. LFL 431 g/m3.

0

10

20

30

40

50

60

70

80

90

100

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Allo

wed

ch

arge

(kg

)

Area (m2)

Standard system

+ added construction requirements

(location class II)

+ one additional measure

(safety shut-off valves, alarms,

ventilation)

+ two additional measures

(safety shut-off valves,

alarms, ventilation)

Only secondary (chiller, machinery room)

2,6 kg

16,8 kg

57,7 kg

84,0 kg

No room size

requirements

below 2,6 kg

Page 13: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Maximum Charge Comparison A2L vs A3

12

Larger Refrigerant Charge allowed for A2L

0

10

20

30

40

50

60

70

80

90L40X R290

Room Size RestrictionNo Restriction Room Size Restriction

One Additional measure Two Additional measures

Refr

igera

nt

Charg

e (

kg)

Page 14: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Additional Charge

13

With additional measures, higher A2L refrigerant charges are possible

• Additional charge for 2L refrigerants is possible with alternative risk management

• The charge limits shall be determined by multiplying room volume with RCL, QLMV or

QLAV depending on measure taken.

- RCL: Refrigerant Concentration Limit

- QLMV: quantity limit with minimum ventilation

- QLAV: quantity limit with additional ventilation

The charge is capped to 195 x LFL for HFO > 60kg

Page 15: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Systems HC HFO1

Integral System, <150gr charge

Integral System, =1.5kg charge

Cold room, monoblock system

Cold room cooled by remote condensing unit

Split AC System

Portable AC System

VRV/VRF System

Rooftop Chiller

Machinery room Chiller

DX process cooling

1) A2L with LFL ~ 0.3kg/m3

Table to be used as an indication only.

System Suitability Indication

14

Page 16: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

Conclusions

15

• The A2L Classification is implemented in most standards

• A larger charge is allowed with A2L refrigerants with additional safety

measures. Covering most applications.

• Building Codes and country/regional regulations have to be taken into

consideration

• The Safety Data Sheet (SDS) is the most important documentation to

accompany the product, and should be referred to

Page 17: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

THANK YOU!

Page 18: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

QUESTIONS?

Page 19: MILDLY FLAMMABLE REFRIGERANTS

Honeywell Confidential - © 2018 by Honeywell International Inc. All rights reserved.

www.honeywell.com

DISCLAIMER

Although all statements and information contained herein are believed to be accurate and reliable, they are presented without guarantee or warranty of any kind, expressed or implied.

Information provided herein does not relieve the user from the responsibility of carrying out its own tests and experiments, and the user assumes all risks and liability for use of the information

and results obtained. Statements or suggestions concerning the use of materials and processes are made without representation or warranty that any such use is free of patent infringement

and are not recommendations to infringe on any patents. The user should not assume that all toxicity data and safety measures are indicated herein or that other measures may not be required.