MICROPRO MICROPRO-D - Gallettiord.galletti.com/imagesdb/famiglie/pdf/fc66000775.pdf · 2010. 6....
Transcript of MICROPRO MICROPRO-D - Gallettiord.galletti.com/imagesdb/famiglie/pdf/fc66000775.pdf · 2010. 6....
FC66000775 - Rev.04 1
MICROPROMICROPRO-D
MICROPROCESSOR CONTROLLER FOR FAN COILS
FC66000775 - Rev.04 2
Main features ....................................................................................................... 3
Main functions and equipment: ........................................................................... 3Temperature range ............................................................................................................................................... 4LED indicators. ...................................................................................................................................................... 4
Description of the operating modes .................................................................... 5Room thermostat with air temperature control ........................................................................................................ 5Room thermostat with ON-OFF valve control for two pipe systems ........................................................................... 5Room thermostat with ON-OFF valves control for four pipe system systems .............................................................. 5Manual in built Cooling/Heating switching mode ...................................................................................................... 6Manual remote Cooling/Heating switching mode ..................................................................................................... 6Automatic Cooling/Heating switching mode based on the water temperature ............................................................ 6Automatic Cooling/Heating switching mode based on the air temperature ................................................................ 6Selecting the extempt of the neutral zone ............................................................................................................... 7Time function ........................................................................................................................................................ 7Electric heater control ............................................................................................................................................ 8Fan coil enabling system based on the water temperature ....................................................................................... 8Technical data and operation limits ........................................................................................................................ 8
Possible configurations ....................................................................................... 9C1 (Standard): two pipes ....................................................................................................................................... 9C2: two pipe systems– Remote switching mode ................................................................................................... 10C3: Two pipe systems– One valve ........................................................................................................................ 11C4: Two pipe systems– One valve – Remote switching mode ................................................................................. 11C5: Four pipe systems – Two valves ..................................................................................................................... 12C6: Four pipe systems – Two valves – Remote switching mode ............................................................................. 12C7: Four pipe systems ......................................................................................................................................... 13C8: Four pipe systems – Remote switching mode .................................................................................................. 14C9: Two pipe systems– Electric heater .................................................................................................................. 15C10: Two pipe systems– Electric heater – Remote switching mode ......................................................................... 16C11: Two pipe systems– One valve – Electric heater ............................................................................................. 17C12: Two pipe systems– One valve – Electric heater – Remote switching mode ...................................................... 17C13: Two pipe systems– Automatic switching on water side ................................................................................. 18C14: Two pipe systems– One valve – Automatic switching mode on water side ....................................................... 19C15: Four pipe systems – Automatic switching mode on air side ............................................................................ 20C16: Four pipe systems – Two valves – Automatic switching mode on air side ........................................................ 21C17: Two pipe systems– Electric heater – Automatic switching mode on air side ..................................................... 22C18: Two pipe systems– One valve – Electric heater – Automatic switching mode on air side .................................. 23
Micropro installation instructions ...................................................................... 24Setting the micro-switches: .................................................................................................................................. 24List of the micro-switches and of the relative functions. ......................................................................................... 24Installation on the support and on the fan coil ...................................................................................................... 25Autodiagnosis procedure ...................................................................................................................................... 27Position of the air temperature probe (black) for the éstro unit. ............................................................................. 28Position of the water temperature probe (white) for the éstro unit ......................................................................... 29Position of the water temperature probe (white) for the UTN unit .......................................................................... 30
Wiring diagrams of the Micropro controller for éstro fan coils .......................... 31Key of the symbols of the wiring diagrams: ........................................................................................................... 31
Assembly instructions for the remote panel ...................................................... 36
MicroproD wiring diagrams for éstro fan coil .................................................... 37
MicroproD wiring diagrams for UTN unit ........................................................... 41
FC66000775 - Rev.04 3
Main features
Micropro is a microprocessor controller designed to control fan coils of the éstro series. Together with the Micropro version for in built installation there is also the MicroproD wall-mounted version.
Main functions and equipment: • Regulation of the air temperature via the automatic variation of the fan speed.
• Regulation of the air temperature via the on-off switch of the fan at a fixed speed.
• Time function (not available for MicroproD).
• Control of ON-OFF valves for two or four pipe systems.
• Control of the electric heater as t integration or replacement of the heating circuit with delayed fan stopping.
• Cooling/Heating switching mode in the following way: ♦ Manual – in-built ♦ Manual - remote (centralized) ♦ Automatic – based on the water temperature ♦ Automatic – based on the air temperature
It is also equipped with: • Free contacts for external enabling signal (i.e.: reed contact, remote ON/OFF switch, proximity contact
etc.) that may enable or disable the unit. (closed contact = OFF; open contact = ON) • Free contacts for the centralized Cooling/Heating switching system. (closed contact = Cooling; open
contact = Heating) • Water temperature probe (optional for MicroproD) • Air temperature probe.
The control panel is made of: • Operating mode selector, to turn the fan coil on and off, to choose the type of operating mode
(automatic or at fixed speed) and to control the electric Heating. • Cooling/Heating selector• Operational LEDs indicating the current operating mode in use. • Thermostat to control the room temperature.
Operating mode selector switch
Cooling/Heating selector
Thermostat
Cooling mode running LED
Heating mode running LED
Fig.1
FC66000775 - Rev.04 4
Temperature range
The print around the selector switch of the thermostat represents the temperature range from minimum, to comfort, through to maximum. The range is referred to different temperatures, as illustrated in fig. 2, depending on the operating mode selected – Cooling/Heating.
Temperature range
Cooling mode Heating mode
Warning: When the “Automatic Cooling/Heateing switching mode based on the air temperature” is running, the temperature range of the thermostat is as illustrated in fig. 3.
Temperature range for the “Automatic Cooling/Heating switching mode based on the air temperature”
LED indicators. The various combinations in which the LED light up indicate different procedures and operating status of the controller:
Blue LED lit Indicates that the Cooling mode is running. The fan coil is running or waiting for an input from the thermostat.
Red LED lit Indicates that the Heating mode is running. The fan coil is running or waiting for an input from the thermostat.
Blue and Red LEDs lit Indicates that the fan coil has received no enabling signal: The water temperature doesn’t enable the air cooling or heating functions (see “Enabling signal based on water temperature”) or the temperature of the air is within the neutral zone (see “Automatic Cooling/Heating switching mode based on the air temperature”).
Fig.3
Fig.2
FC66000775 - Rev.04 5
Note: How to realise the operating mode when an enabling signal is missing (Blue and Red LEDs lit):
When the blue and red LEDs are both lit (no enabling signal, see previous section above), to check which operating mode is selected, turn the knob of the thermostat until one of the two LEDs starts to flash and then remains lit. This LED points out the operating mode selected (Blue = Cooling - Red = Heating). Once the operating mode has been established, turn the thermostat back to the desired position.
Double flashing of the blue LED This means that the thermostat has sent an input to the fan coil for it to start in Cooling mode. It flashes when the room temperature and the conditioning temperature set are the same: The temperature of the air in the room can be seen at any time on the thermostat range by turning the knob of the thermostat.
Double flashing of the red LED This means that the thermostat has sent an input to the fan coil for it to start in Heating mode. It flashes when the room temperature and the heating temperature set are the same: The temperature of the air in the room can be seen at any time on the thermostat range by turning the knob of the thermostat
Description of the operating modes
Room thermostat with air temperature control
AUTO✇✇✇The fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room temperature. This function is enabled by turning the speed selector switch to
“Auto”. With the selector switch turned to ✇, ✇, or ✇ the ventilation mode is the on-off type.
Room thermostat with ON-OFF valve control for two pipe systems
AUTO✇✇✇✚The fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room temperature. This function is enabled by turning the speed selector switch to
“Auto”. With the selector switch turned to ✇, ✇, or ✇ the ventilation mode is the on-off type. The water valve is shut-off once the desired temperature is reached. In Cooling mode the fan continues at minimum speed even after the valve has shut-off. In Heating mode the fan is stopped as soon as the valve is shut-off.
Room thermostat with ON-OFF valves control for four pipe system systems
AUTO✇✇✇✚✚The fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room temperature. This function is enabled by turning the speed selector switch to
“Auto”. With the selector switch turned to ✇, ✇, or ✇ the ventilation mode is the on-off type. The water valve is shut-off once the desired temperature is reached. In Cooling mode the fan continues at minimum speed even after the valve of the cooling circuit has shut-off. In heating mode the fan is stopped as soon as the valve of the heating circuit is shut-off.
FC66000775 - Rev.04 6
Manual in built Cooling/Heating switching mode
❄⇔✺MThe microprocessor controller is pre-arranged to operate manually in the desired mode. It is enabled by pressing the selector key. The blue (Cooling) and red (Heating) LEDs point out the operating mode selected.
Manual remote Cooling/Heating switching mode
❄⇔✺MDThe microprocessor controller is pre-arranged to operate manually and remotely in the desired mode. This mode is carried out by connecting the system to a remote switch. Use the special terminals on the electronic PCB of the Micropro system.
Automatic Cooling/Heating switching mode based on the water temperature
❄⇔✺H2OThe microprocessor controller automatically selects the Cooling or Heating mode based on the temperature of the water and according to the following logic:
Water temperature < 17°C: the Cooling mode is set Water temperature > 39°C: the Heating mode is set Water temperature between 17°C and 39°C: the system is disabled
Warning: The water temperature probe is an optional accessory for the MicroproD version.
See figs. 14÷20 of this manual for the assembling instructions of the water temperature probe.
Automatic Cooling/Heating switching mode based on the air temperature
❄⇔✺airThe microprocessor controller automatically selects the Cooling or Heating mode based on the temperature of the air compared to a neutral temperature interval (Neutral zone) centred on the set value of the thermostat.
Warning: When this function is selected, the temperature range of the thermostat refers to the values indicated in fig. 3, both for the Cooling and the Heating.
FC66000775 - Rev.04 7
Selecting the extempt of the neutral zone
The neutral zone is a parameter related to the “Automatic Cooling/Heating switching mode based on the air temperature” function. The neutral zone is a temperature interval astride the set temperature: When the air is warmer than the top limit of the neutral zone, the Cooling mode is selected. When the air is cooler than the lower limit of the neutral zone, the Heating mode is selected.
The following figure illustrates an example with: Neutral zone = 5°C Set room air temperature = 21°C For temperatures above 23.5°C the Cooling operating mode is selected For temperature below 18.5°C the Heating operating mode is selected.
Fig. 4
Micropro is used to select the extempt of the neutral zone at 2°C or 5°C in order to obtain respectively a more or less precise control of the air temperature.
Time function
The time function is used to start the fan at medium speed for 2 minutes at regular intervals (every 10 mins.) once the room temperature has reached the level set on the thermostat. It ensures the constant monitoring of the air temperature in the room. It is only used in summer and only if the enabling signal of the water temperature probe is positive. The time function cycle is also executed when the controller is powered (first start-up or voltage reset). Warning:The thermostat and the operating mode selector switch are disabled when the time function is in use. The time function can be used only for units without valves and only in summer. The time function function is not foreseen for the MicroproD version.
23.5°C
18.5°C
Set=21°C
Neutral zone
Heating
Cooling
FC66000775 - Rev.04 8
Electric heater control
The thermostat controls an Electric heater as integration or replacement of hot water heating system. When the operating mode selector switch is turned to and the Electric heater is turned on, the fan runs continuously at medium speed. For safety reasons the fan is turned off 2 minutes after the Electric heater is turned off, whether this occurs when the desired air temperature is reached or when the Electric heater is turned off manually using the operating mode selector.
Warning:The fan runs only at medium speed when the Electric heater is turned on.
Fan coil enabling system based on the water temperature
The microprocessor controller starts the fan coil according to the following logic based on the water temperature that is detected by a dedicated probe:
Water temperature < 17°C: Cooling mode enabling signal Water temperature > 39°C: Heating mode enabling signal
In installation with the Electric heater, the same probe sends the enabling signal for the Electric heater to turn on according to the following logic:
Water temperature < 39°C: Additional Electric heater enabling signal (This enabling signal is sent only if the operating mode selector switch is turned to ).
Warning: The water temperature probe is an optional accessory for the MicroproD version.
See figs. 16÷20 of this manual for the assembling instructions of the water temperature probe.
Technical data and operation limits Warehouse temperatures: -40°C ÷ +85°C Operation temperatures: 0°C ÷ +40°C Accuracy of temperature probes ± 0,5°C
Maximum current on terminal V1, V2 and V3 (fan speed) 1.1A Maximum current on terminal Rand V(valve and electric heater) 0.15 A
The pages that follow illustrate all the possible configurations of the Micropro controller, each of them indicating the relative sequence of the micro-switches, any operational features and specific notes. Choose which of these better applies to the system characteristics and use it as explained.
FC66000775 - Rev.04 9
Possible configurations The Micropro controller can be set in various way by activating the desired functions amongst those available. The various configurations are obtained by arranging the micro-switches on the electronic PCB accordingly.
C1 (Standard): two pipes System characteristics Number of pipes: 2 Valve: NO Electric heater: NO
List of functions activated in configuration 1:
AUTO✇✇✇ ❄⇔✺M• Room thermostat with air temperature control • Manual in built Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Time function (not available for MicroproD)
Position of the micro-switches for configuration 1: 1 2 3 4 5 6 7 Off Off Off Off Off Off Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000633 MicroproD:UT66000279 MicroproD:FC66000627 Micropro with a number of fan coils in parallel:FC66000634 MicroproD with a number of fan coils in parallel:FC66000628
FC66000775 - Rev.04 10
C2: two pipe systems– Remote switching mode System characteristics Number of pipes: 2 Valve: NO Electric heater: NO
List of the functions activated in configuration 2:
AUTO✇✇✇ ❄⇔✺MD• Room thermostat with air temperature control • Manual remote Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Time function (not available for MicroproD)
Position of the micro-switches for configuration 2: 1 2 3 4 5 6 7 On Off Off Off Off Off Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000633 MicroproD:UT66000279 MicroproD:FC66000627 Micropro with a number of fan coils in parallel:FC66000634 MicroproD with a number of fan coils in parallel:FC66000628
FC66000775 - Rev.04 11
C3: Two pipe systems– One valve System characteristics Number of pipes: 2 Valve: YES Electric heater: NO
List of the functions activated in configuration 3:
AUTO✇✇✇✚ ❄⇔✺M
• Room thermostat with ON-OFF valve for two pipe systems • Manual in built Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD)
Position of the micro-switches for configuration 3: 1 2 3 4 5 6 7 Off Off Off Off On Off Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000635 MicroproD:UT66000280 MicroproD:FC66000629
C4: Two pipe systems– One valve – Remote switching mode System characteristics Number of pipes: 2 Valve: YES Electric heater: NO
List of the functions activated in configuration 4:
AUTO✇✇✇✚ ❄⇔✺MD
• Room thermostat with ON-OFF valve for two pipe systems • Manual remote Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD)
Position of the micro-switches for configuration 4: 1 2 3 4 5 6 7 On Off Off Off On Off Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000635 MicroproD:UT66000280 MicroproD:FC66000629
FC66000775 - Rev.04 12
C5: Four pipe systems – Two valves System characteristics Number of pipes: 4 Valve: YES Electric heater: NO
List of functions activated in configuration 5:
AUTO✇✇✇✚✚ ❄⇔✺M
• Room thermostat with ON-OFF valves control for four pipe systems • Manual in built Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD)
Position of the micro-switches for configuration 5: 1 2 3 4 5 6 7 Off Off Off Off On Off On On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000636 MicroproD:UT66000281 MicroproD:FC66000630
C6: Four pipe systems – Two valves – Remote switching mode System characteristics Number of pipes: 4 Valve: YES Electric heater: NO
List of functions activated in configuration 6:
AUTO✇✇✇✚✚ ❄⇔✺MD
• Room thermostat with ON-OFF valves control for four pipe systems• Manual remote Cooling/Heating switching mode: • Operational enabling signal based on the water temperature (optional for MicroproD)
Position of the micro-switches for configuration 6: 1 2 3 4 5 6 7 On Off Off Off On Off On On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000636 MicroproD:UT66000281 MicroproD:FC66000630
FC66000775 - Rev.04 13
C7: Four pipe systems System characteristics Number of pipes: 4 Valve: NO Electric heater: NO
List of functions activated in configuration 7:
AUTO✇✇✇ ❄⇔✺M
• Room thermostat with control over the air temperature • Manual in built Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Time function (not available for MicroproD):
Position of the micro-switches for configuration 7: 1 2 3 4 5 6 7 Off Off Off Off Off Off On On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000633 MicroproD:UT66000279 MicroproD:FC66000627 Micropro with a number of fan coils in parallel:FC66000634 MicroproD with a number of fan coils in parallel:FC66000628
FC66000775 - Rev.04 14
C8: Four pipe systems – Remote switching mode System characteristics Number of pipes: 4 Valve: NO Electric heater: NO
List of functions activated in configuration 8:
AUTO✇✇✇ ❄⇔✺MD
• Room thermostat with air temperature control • Manual remote Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) (optional for
MicroproD) • Time function (not available for MicroproD):
Position of the micro-switches for configuration 8: 1 2 3 4 5 6 7 On Off Off Off Off Off On On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000633 MicroproD:UT66000279 MicroproD:FC66000627 Micropro with a number of fan coils in parallel:FC66000634 MicroproD with a number of fan coils in parallel:FC66000628
FC66000775 - Rev.04 15
C9: Two pipe systems– Electric heater System characteristics Number of pipes: 2 Valve: NO Electric heater: YES
List of functions activated in configuration 9:
AUTO✇✇✇ ❄⇔✺M
• Room thermostat with air temperature control • Manual in built Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Time function (not available for MicroproD): • Electric heater control
Position of the micro-switches for configuration 9: 1 2 3 4 5 6 7 Off Off Off Off Off On Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000637 MicroproD:UT66000282 (mono phase) MicroproD:FC66000631 MicroproD:UT66000313 (three phase)
FC66000775 - Rev.04 16
C10: Two pipe systems– Electric heater – Remote switching mode System characteristics Number of pipes: 2 Valve: NO Electric heater: YES
List of functions activated in configuration 10:
AUTO✇✇✇ ❄⇔✺MD
• Room thermostat with air temperature control • Manual remote Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Time function (not available for MicroproD): • Electric heater control
Position of the micro-switches for configuration 10: 1 2 3 4 5 6 7 On Off Off Off Off On Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000637 MicroproD:UT66000282 (mono phase) MicroproD:FC66000631 MicroproD:UT66000313 (three phase)
FC66000775 - Rev.04 17
C11: Two pipe systems– One valve – Electric heater System characteristics Number of pipes: 2 Valve: YES Electric heater: YES
List of functions activated in configuration 11:
AUTO✇✇✇✚ ❄⇔✺M
• Room thermostat with ON-OFF valve for two pipe systems • Manual in built Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Electric heater control: during heating operation only the electric heater works
Position of the micro-switches for configuration 11: 1 2 3 4 5 6 7 Off Off Off Off On On Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000638 MicroproD:UT66000283 (mono phase) MicroproD:FC66000632 MicroproD:UT66000314 (three phase)
C12: Two pipe systems– One valve – Electric heater – Remote switching mode System characteristics Number of pipes: 2 Valve: YES Electric heater: YES
List of functions activated in configuration 12:
AUTO✇✇✇✚ ❄⇔✺MD
• Room thermostat with ON-OFF valve for two pipe systems • Manual remote Cooling/Heating switching mode • Operational enabling signal based on the water temperature (optional for MicroproD) • Electric heater control:during heating operation only the electric heater works
Position of the micro-switches for configuration 12: 1 2 3 4 5 6 7 On Off Off Off On On Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000638 MicroproD:UT66000283 (mono phase) MicroproD:FC66000632 MicroproD:UT66000314 (three phase)
FC66000775 - Rev.04 18
C13: Two pipe systems– Automatic switching on water side System characteristics Number of pipes: 2 Valve: NO Electric heater: NO
List of functions activated in configuration 13:
AUTO✇✇✇ ❄⇔✺H2O• Room thermostat with air temperature control • Automatic Cooling/Heating switching mode based on the water temperature (available also for
MicroproD, if equipped with optional water temperature probe) • Time function (not available for MicroproD):
Position of the micro-switches for configuration 13: 1 2 3 4 5 6 7 Off On On Off Off Off Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000633 MicroproD:UT66000279 MicroproD:FC66000627 Micropro with a number of fan coils in parallel:FC66000634 MicroproD with a number of fan coils in parallel:FC66000628
Warning: In this type of configuration the input for the centralised Cooling/Heating switching mode is disabled.
FC66000775 - Rev.04 19
C14: Two pipe systems– One valve – Automatic switching mode on water side System characteristics Number of pipes: 2 Valve: YES Electric heater: NO
List of functions activated in configuration 14:
AUTO✇✇✇✚ ❄⇔✺H2O• Room thermostat with ON-OFF valve for two pipe systems • Automatic Cooling/Heating switching mode based on the water temperature (available also for
MicroproD, if equipped with optional water temperature probe)
Position of the micro-switches for configuration 14: 1 2 3 4 5 6 7 Off On On Off On Off Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000635 MicroproD:UT66000280 MicroproD:FC66000629
Warning: In this type of configuration the input for the centralised Cooling/Heating switching mode is disabled.
FC66000775 - Rev.04 20
C15: Four pipe systems – Automatic switching mode on air side System characteristics Number of pipes: 4 Valve: NO Electric heater: NO
List of functions activated in configuration 15:
AUTO✇✇✇ ❄⇔✺air
• Room thermostat with air temperature control • Automatic Cooling/Heating switching mode based on the air temperature • Choice of the extempt of the neutral zone • Time function (not available for MicroproD):
Position of the micro-switches for configuration 15: 1 2 3 4 5 6 7 Off On Off Off Off Off On On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000633 MicroproD:UT66000279 MicroproD:FC66000627 Micropro with a number of fan coils in parallel:FC66000634 MicroproD with a number of fan coils in parallel:FC66000628
Note: The position of micro-switch no. 4 determines the extempt of the neutral zone for the “Automatic Cooling/Heating switching mode based on the air temperature”.
Position of micro-switch no. 4 Extempt of the neutral zone ON 2 °C OFF 5 °C
Warning: In this type of configuration the input for the centralised Cooling/Heating switching mode is disabled.
FC66000775 - Rev.04 21
C16: Four pipe systems – Two valves – Automatic switching mode on air side System characteristics Number of pipes: 4 Valve: YES Electric heater: NO
List of functions activated in configuration 16:
AUTO✇✇✇✚✚ ❄⇔✺air
• Room thermostat with ON-OFF valves control for four pipe systems • Automatic Cooling/Heating switching mode based on the air temperature • Choice of the extempt of the neutral zone • Operational enabling signal based on the water temperature (optional for MicroproD) •Position of the micro-switches for configuration 16: 1 2 3 4 5 6 7 Off On Off Off On Off On On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000636 MicroproD:UT66000281 MicroproD:FC66000630
Note: The position of micro-switch no. 4 determines the extempt of the neutral zone for the “Automatic Cooling/Heating switching mode based on the air temperature”.
Position of micro-switch no. 4 Extempt of the neutral zone ON 2 °C OFF 5 °C
Note:For configurations with the “Automatic Cooling/Heating switching mode based on the air temperature” in Cooling mode, the fan stops when the valve shuts-off.
Warning:In this type of configuration the input for the centralised Cooling/Heating switching mode is disabled.
FC66000775 - Rev.04 22
C17: Two pipe systems– Electric heater – Automatic switching mode on air side System characteristics Number of pipes: 2 Valve: NO Electric heater: YES
List of functions activated in configuration 17:
AUTO✇✇✇ ❄⇔✺air
• Room thermostat with air temperature control • Automatic Cooling/Heating switching mode based on the air temperature • Choice of the extempt of the neutral zone • Operational enabling signal based on the water temperature (optional for MicroproD) • Time function (not available for MicroproD): • Electric heater control
Position of the micro-switches for configuration 17: 1 2 3 4 5 6 7 Off On Off Off Off On Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000637 MicroproD:UT66000282 (mono phase) MicroproD:FC66000631 MicroproD:UT66000313 (three phase)
Note:The position of micro-switch no. 4 determines the extempt of the neutral zone for the “Automatic Cooling(Heating switching mode based on the air temperature”.
Position of micro-switch no. 4 Extempt of the neutral zone ON 2 °C OFF 5 °C
Warning:In this type of configuration the input for the centralised Cooling/Heating switching mode is disabled.
FC66000775 - Rev.04 23
C18: Two pipe systems– One valve – Electric heater – Automatic switching mode on air side System characteristics Number of pipes: 2 Valve: YES Electric heater: YES
List of functions activated in configuration 18:
AUTO✇✇✇✚ ❄⇔✺air
• Room thermostat with ON-OFF valve for two pipe systems • Automatic Cooling/Heating switching mode based on the air temperature • Choice of the extempt of the neutral zone • Operational enabling signal based on the water temperature (optional for MicroproD) • Electric heater control: during heating operation only the electric heater works
Position of the micro-switches for configuration 18: 1 2 3 4 5 6 7 Off On Off Off On On Off On
Off
Reference wiring diagrams for FC Estro: Reference wiring diagrams for UTN Micropro:FC66000638 MicroproD:UT66000283 (mono phase) MicroproD:FC66000632 MicroproD:UT66000314 (three phase)
Note:The position of micro-switch no. 4 determines the extempt of the neutral zone for the “Automatic Cooling(Heating switching mode based on the air temperature”.
Position of micro-switch no. 4 Extempt of the neutral zone ON 2 °C OFF 5 °C
Warning:In this type of configuration the input for the centralised Cooling/Heating switching mode is disabled.
FC66000775 - Rev.04 24
Micropro installation instructions
Warning: The MICROPRO control panel has been specially designed for the fan coils of the éstro series and for UTN units; if used to control different units make sure that the operation limits are respected. See the paragraph relative to the operation limits.
Setting the micro-switches:
1. Unscrew the screws on the bottom part of the controller cover and remove it.
Warning: To facilitate its re-installation, be careful not to modify the position of the rotating knobs (operating mode selector switch and thermostat) and also that of the relative potentiometers fitted on the electronic PCB.
2. Arrange the micro-switches with the sequence corresponding to one of the configurations explained herein.
Fig.5
List of the micro-switches and of the relative functions. Micro-switch no. Function: Position
OFF ON 1 Cooling/Heating switching: In built Remote 2 Cooling/Heating switching: Manual Automatic
3 Automatic Cooling/Heating switching mode based on the temperature of the: Air Water
4 Extempt of the Neutral Zone for the automatic Cooling/Heating mode based on the air temperature: 5 °C 2°C
5 Valve presence on hydraulic circuit: NO YES 6 Electric heater presence: NO YES 7 Number of pipes of the hydraulic circuit. 2 pipes 4 pipes
microinterruttori
1 2 3 4 5 6 7
On
Off
FC66000775 - Rev.04 25
Warning: if the desired configuration does not include the Electric heaters control function and the operating mode selector switch is turned to the Electric heater symbol, the fan coil will continue to run “automatically” and will regulate the air temperature by means of the fan.
Installation on the support and on the fan coil The Micropro controller can be fitted on both sides of the fan coil using a support and a frame cover.
1. Unscrew the four screws hidden behind the hatches at the end of the grid and remove the fan coil cabinet (fig.6).
Fig.6 2. Remove the blank plastic tabs from one of the two slots of the support to be able reach the “fast-on’s”
of the Micropro unit to be used (Fig.7). (The fast-on’s will face one of the support slots, depending on whether the controller is to be fitted on the RH or LH side of the fan coil).
3. Feed the cables of the probes in one of the slots of the support and secure the support and controller together using the two screws supplied (Fig.8). (Fig. 8 illustrates the installation of the support and controller when the controller is fitted on the RH side of the fan coil. If the controller is fitted on the LH side of the fan coil, the support is to be turned by 180° compared to the drawing).
Fig.7 Fig.8
Warning: Ensure that all the terminals required for the electrical connections foreseen in the configuration chosen (valve, Electric heater, external contacts etc.) can be accessed even after the support has been fitted (see the relative wiring diagram). If this is not the case, remove the protective blank tabs from the base of the support.
4. Complete the electrical connections according to the wiring diagrams provided herein. 5. Once the electrical connections have been completed, it is advisable to execute the autodiagnosis
procedure to check if all the outputs are efficient before you end the installation of the Micropro controller (outputs of the fan at various speeds, of the valves and Electric heaters if installed): Refer to the next section of this manual.
6. Assemble the controller-support unit on the fan coil using the bayonet fittings (Fig.9). 7. Warning: Place the air temperature (black) and water temperature (white) probes (Figs.11÷18)
following the instructions given in the relative sections of this manual.
Blank tabs
Support
FC66000775 - Rev.04 26
8. Fit the cabinet back in place and fix it with the four screws, then insert the fixed covering frame, as illustrated in fig.10.
Fig.9 Fig.10
12
FC66000775 - Rev.04 27
Autodiagnosis procedure
To check the correct operational efficiency of the Micropro controller, when installing it or to search for possible faults, all the outputs foreseen can be operated manually (fan, valves, Electric heater) thanks to the autodiagnosis mode. Proceed as follows to access the autodiagnosis mode and to run the tests:
1. Turn the operating mode selector switch to the “OFF” position. 2. Turn the knob of the thermostat anti-clockwise until it reaches the minimum temperature position: 3. Hold the Cooling/Heating selector down for at least 5 seconds. At this stage both LEDs light up. 4. Within 5 seconds, turn the knob of the thermostat clockwise to the maximum temperature position. The
red LED switches off and the blue LED remains lit to indicate that the autodiagnosis mode has been accessed.
Note: If you wait more than 5 seconds before turning the knob again, the autodiagnosis mode will be automatically exited.
5. In the autodiagnosis mode, each position of the operating mode selector switch corresponds to the simulation of an output, namely:
Position Output Terminals
AUTO Valve N-V ✤ Minimum speed N-V1
✤ Medium speed N-V2
✤ Maximum speed N-V3
Electric heater or second valve N-RE
By running through the various positions of the operating mode selector switch, the electronic controller outputs can be checked one after the other either by observing the relative component (valve, fan, electric heater) or by checking if the corresponding terminals are powered at a voltage of 230 V. Note: If the operating mode selector switch is not moved for more than one minute the autodiagnosis mode is automatically exited.
6. Exit the autodiagnosis mode by turning the operating mode selector switch to the “OFF” position.
Heating mode running LED
Cooling mode running LED
Operating mode selector switch
Thermostat
Cooling/Heating selector
FC66000775 - Rev.04 28
Position of the air temperature probe (black) for the éstro unit.
Use the plastic adhesive probe-holder supplied. The figures below illustrate how to install the air probe for:
Fan coil without base (Fig.11). Fan coil with base (Fig.12) Fan coil in FU version with front in-take (Fig.13).
Fig.11 Fig.12
Fig.13
FC66000775 - Rev.04 29
Position of the water temperature probe (white) for the éstro unit Use the special copper probe-holder for the water temperature probe and arrange it according to the specific case, as described hereafter. Warning: The water temperature probe is an optional accessory for the MicroproD version.
• For fan coils, two pipe systems but without valve, the water temperature probe has to be placed on the heat exchanger (Figs.14 and 15).
Fig.14 Fig.15
• For fan coils, four pipes systems but without valve, the water temperature probe has to be placed on the heat exchanger of the heating circuit. (Fig.16)
Fig.16
• For fan coils, two pipes systems and valve, the water temperature probe has to be placed on the valve inlet, on the branch leading from the system (Fig.17)
Fig.17
FC66000775 - Rev.04 30
• For fan coils, four pipes systems and valve, the water temperature probe has to be placed on the heating valve inlet, on the branch leading from the circuit (Fig.18).
Fig.18
Position of the water temperature probe (white) for the UTN unit Valve fitted on the RH side:
Waterprobe for 2 pipesystem
Water probe for 4 pipe system
AirAir
Fig. 19
FC66000775 - Rev.04 31
Valve fitted on the LH side:
Warning: For UTN units without valve, for 2 pipe systems, the water probe has to be places on the pipe on the inlet of the heat exchanger.
For UTN units without valve, for 4 pipe systems, the water probe has to be places on the pipe on the inlet of the heat exchanger of the heating circuit.
Wiring diagrams of the Micropro controller for éstro fan coils Once the configuration of the Micropro controller has been chosen amongst those listed in the “Possible configurations” section, take a note of the wiring diagram indicated for the solution desired and look it up in the pages that follow. Each fan-coil / thermal-ventilating unit requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).
Key of the symbols of the wiring diagrams:
V1 Minimum speed F Fuse (not supplied) V2 Medium speed IL Line switch (not supplied) V3 Maximum speed CN Fan coil “fast-on” terminal board L Phase RHC Remote Cooling/Heating selector switch (closed contact =
Cooling; open contact = Heating) PE Earth EXT External auxiliary contact (closed contact = OFF; open
contact = ON) N Neutral CRHC Centralised remote Cooling/Heating selector switch RE Elect. heater KP Power board for the control of 4 fan coils V Valve IPM Power board for UTN units
RM Remote control M Fan coil motor EX Auxiliary contact VHC Solenoid valve SW Water probe VC Cooling solenoid valve SA Air probe VH Heating solenoid valve BK Black (Max. speed) TSA Automatic safety thermostat BU Blue (Medium speed) TSM Safety thermal fuse RD Red (Min. speed) SC Cabling box WH White (mutual) …… Electrical connections to be made by the installer
._._._.
Part of diagram valid only for the centralised remote Cooling/Heating selector switch (CRHC)
Water probe for 4 pipe system
Water probe for 2 pipe system
Air Air
Fig.20
FC66000775 - Rev.04 32
M1
987654
CN
LN
IL
230V 1 50Hz
MICROPRO V3
V2
V1
L
N
N
RE
V
RM
RM
EX
EX
LN
RHC IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
PE
F
F
EXT
RDBUBKWH
SWSA
FC66000633
FC66000775 - Rev.04 33
M 1
987654 CN
M 1
987654 CN
M 1
987654 CN
M 1
987654 CN
RE
LE'D
IPO
TEN
ZAPO
WE
RR
ELAY
3A25
0V
RE
LE'D
IPO
TEN
ZAPO
WE
RR
ELAY
3A25
0V
RE
LE'D
IPO
TEN
ZAPO
WE
RR
ELAY
3A25
0V
13L
14N
15L
16N
2 3 4 5
C 1 2 3
1234
V3
V2 V1 L N N RE V RM
RM
EX EX
KP
MIC
RO
PRO
PE
L N
ILF
230V
150
Hz
RHC
RM
RM
MICROPRO
RM
RM
CR
HC
MICROPROD
L N
ILF
230V
150
Hz
EX
T
RD
BUBKWH
333234 31
RD
BUBKWH
27 28 2930
RD
BUBKWH
23 24 252619 20 2122
RD
BUBKWH
SW
SA
FC66000634
FC66000775 - Rev.04 34
M1
987654
CN
LN
IL
230V 1 50Hz
MICROPRO V3
V2
V1
L
N
N
RE
V
RM
RM
EX
PE
EX
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
LN
RHC IL
230V 1 50Hz
EXT
RDBUBKWH
F
F
SWSA
VHC
FC66000635
M1
987654
CN
LN
IL
230V 1 50Hz
LN
RHC IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
MICROPRO V3
V2
V1
L
N
N
RE
V
RM
RM
EX
PE
EXEXT
RDBUBKWH
F
F
VC VH
SWSA
FC66000636
FC66000775 - Rev.04 35
1
0
RDWH
BUBK
M1
MICROPRO V3
V2
V1
L
N
N
LN
230V 1 50Hz
IL
PE
TSA
TSM RE
SC
F
RE
V
RM
RM
EX
EX
LN
RHC IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
F
EXT
SA
2 6
4 8
SW
LNLNTSTS
FC66000637
1
0
LN
RDWH
BUBK
M1
LN
230V 1 50Hz
IL
TSA
TSM RE
SC
F
MICROPRO V3
V2
V1
L
N
N
PE
RE
V
RM
RM
EX
EX
LN
RHC IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
F
EXT
8
62
4VC
SWSA
LNTSTS
FC66000638
FC66000775 - Rev.04 36
Assembly instructions for the remote panel
1. Remove the control lock screw (fig. 21).
Fig.21 Fig.22
2. Make sure that the speed switch is in OFF position, and the temperature switch is in comfort position; then, remove the control upper part (fig. 22).
3. Bore the wall where the control shall be installed, at the same level of the fixing slots (5 x 8 mm) located at the control base (fig.23).
130
9.3
7
93
17.7
7
19
10
5 x 8
5 x 8
Fig.23
FC66000775 - Rev.04 37
4. Make the electric connections to the control terminal board.
5. By means of screws, fix the control base to the wall previously bored.
6. Reassemble the control upper part and make sure the switches are in the same position as they were upon disassembly (see point 2). Put the control lock screw at its place again.
7. Make the electric connections to the fan coil by following the wiring diagram relevant to the working configuration selected.
MicroproD wiring diagrams for éstro fan coil After selecting a MicroproD configuration among those contained in chapter “Possible configurations”, write down the number of diagram specified for the desired solution and find it below. The symbol legend for wiring diagrams is at page 25 of this handbook.
M1
987654
CN
LN
IL
230V 1 50Hz
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SA
SW
PEF
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
LN
RHC ILF
EXT
RDBUBKWH
FC66000627
FC66000775 - Rev.04 38
M 1
987654 CN
M 1
987654 CN
M 1
987654 CN
M 1
987654 CN
RE
LE'D
IPO
TEN
ZAPO
WE
RR
ELA
Y
3A25
0V
RE
LE'D
IPO
TEN
ZAPO
WE
RR
ELA
Y
3A25
0V
RE
LE'D
IPO
TEN
ZAPO
WE
RR
ELA
Y
3A25
0V
13L
14N
15L
16N
2 3 4 5
C 1 2 3
1234
V3
V2 V1 L N N N RE V RM
RM
EX
EX
MIC
RO
PR
OD
SW
KP
PE
L N
ILF
230V
150
Hz
RHC
RM
RM
MICROPRO
RM
RM
CR
HC
MICROPROD
L
ILF
230V
150
Hz
N
EXT
RD
BU
BK
WH
32 333134
RD
BU
BK
WH
27 28 2930
RD
BU
BK
WH
23 24 2526
RD
BU
BK
WH
19 2022 21
SA
FC66000628
FC66000775 - Rev.04 39
M1
987654
CN
LN
RHC
LN
IL
230V 1 50Hz
IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SW
PE
EXT
F
F
VHC
RDBUBKWH
SA
FC66000629
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SA
SW
M1
987654
CN
LN
RHC
LN
IL
230V 1 50Hz
IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
PE
EXT
F
FRDBUBKWH
VC VH
FC66000630
FC66000775 - Rev.04 40
1
0
LN
RHC IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SA
SW
LN
230V 1 50Hz
IL
PE
TSA
TSM
EXT
RE
SC
F
F
8
62
4
M1
987654
CN
RDBUBKWH
LNLNTSTS
FC66000631
1
0
LN
M1
987654
CN
LN
RHC IL
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
LN
230V 1 50Hz
IL
TSA
TSM
EXT
RE
SC
F
F
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SA
SW
PE
VC8
62
4
RDBUBKWH
LNTSTS
FC66000632
FC66000775 - Rev.04 41
MicroproD wiring diagrams for UTN unit
V3V2V1L
NNN
REV
RMRMEXEX
MICROPROD
PE
1234
14 L15 L16 N17 N IPM
CV3V2V1
V1V2V3
C
EXT
LN
IL F
230V 1 50Hz
RH
C
RMRMM
ICR
OPR
O
RMRM
CRHC
MIC
RO
PRO
D
LN
IL F
230V 1 50Hz
M1
987654
CN
SA
SW
BU or GY
WH
RD
BK
26
28
25
27
UT66000279
CV1V2V3
1234 C
V3V2V1
28272625
LLNN
14151617
LN
RHC
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
LN
230V 1 50Hz
IPM
M1
987654
CN
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SA
SW
PE
EXT
F
F IL
IL
BU or GYRD
BKWH
VHC
UT66000280
FC66000775 - Rev.04 42
CV1V2V3
1234 C
V3V2V1
28272625
LLNN
14151617
LN
RHC
230V 1 50Hz
MICROPRO
RMRM
MICROPROD
RMRM
CRHC
LN
230V 1 50Hz
IPM
M1
987654
CN
MICROPROD V3
V2
V1
L
N
N
N
RE
V
RM
RM
EX
EX
SW
PE
VH VC
EXT
RDBU or GY
BKWH
SA F IL
F IL
UT66000281
FC66000775 - Rev.04 43
A1
A2
NL
TSTS
NL
C V1
V2
V3
1 2 3 4C V3
V2 V1
28 27 26 25L L N N
14 15 16 17
L N
RH
C
230V
150
Hz
MIC
RO
PRO
RM
RM
MIC
RO
PR
OD
RM
RM
CR
HC
MIC
RO
PR
OD
V3 V2 V1 L N N N RE V RM
RM
EX EX
SA
SW
PE
TSA
M 1
987654 CN
IPM
EX
T
SC
L N
230V
150
Hz
RE
TSM
24 3
1
FIL IL
F
RD
BU
orG
YB
KW
H
UT66000282
FC66000775 - Rev.04 44
TSN
RS
TR
N
C V1
V2
V3
1 2 3 4C V3
V2 V1
28 27 26 25L L N N
14 15 16 17
MIC
RO
PR
OD
V3
V2 V1 L N N N RE V RM
RM
EX
EX
SA
SW
PE
L N
RH
C
230V
150
Hz
MIC
RO
PR
O
RM
RM
MIC
RO
PR
OD
RM
RM
CR
HC
M 1
987654 CN
IPM
T S R
400V
3+N
50H
z
ILF
N
EX
T
FIL
TSA
TSM
A2A1
24
6
13
5RE
RE
RE
RD
BU
orG
YB
KW
H
SC
UT66000313
FC66000775 - Rev.04 45
UT66000283
� �
��
����
��
� ��
��
� �� �� ��
� � �� � � �
�� �� �� �
���������
�
� �� � � � � �� � ��
��
��
��
��
��
��
� �
���
�������������
��������
��
��
���������
����
����
� �
�� ��� ��
���
���
���
��
��� �
�������������
��
���
��
��� �
�
��
��
��
� �!"�#$
�%
FC66000775 - Rev.04 46
TSN
RS
TR
N
C V1
V2
V3
1 2 3 4C V3
V2 V1
28 27 26 25L L N N
14 15 16 17
MIC
RO
PR
OD
V3 V2 V1 L N N N RE V RM
RM
EX
EX
SA
SW
PE
L N
RH
C
230V
150
Hz
MIC
RO
PR
O
RM
RM
MIC
RO
PRO
D
RM
RM
CR
HC
M 1
987654 CN
IPM
T S R
400V
3+N
50H
z
ILF
N
EX
T
FIL
TSA
TSM
SC
A2A12
46
13
5RE
RE
RE
RD
BU
orG
YB
KW
H
VC
UT66000314
FC66000775 - Rev.04 47
Remarks:
FC66000775 - Rev.04 48