Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… ·...
-
Upload
trinhthuan -
Category
Documents
-
view
219 -
download
3
Transcript of Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… ·...
![Page 1: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/1.jpg)
Creating Value Through Chemistry
Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy
Taner SerterAsset Integrity Division, SADARA Chemical Co.April 26th , 2017
![Page 2: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/2.jpg)
OUTLINE
What is MIC?
MIC Causes
Lessons Learned
2
![Page 3: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/3.jpg)
MIC Facts and Numbers: In Industry
3
Source: NACE Corrosion Survey
![Page 4: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/4.jpg)
Microbiologically Induced Corrosion is the term used for the failure mode in which the corrosion is initiated, propagated and/or accelerated by micro-organisms like bacteria, algae, fungi, etc. MIC may occur in all fluids containing some water and nutrients for microorganisms
What is MIC?
4
Schematic diagram of biofilm on an immersed metal surface a
Source:
a – MIC of stainless Steels, Report TN1621 Rolled Alloys.
b – MIC Control in Hydrostatic Testing, Presentation.
Schematic diagram of metabolic process on an immersed metal surface b
![Page 5: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/5.jpg)
The corrosion associated with MIC is usually pit corrosion.
What is MIC?
5
Source:
.
b – MIC Control in Hydrostatic Testing, Presentation.
Tubercles over the pit
Schematic for MIC pitting morphologies b
Sub-Surface/Undercut
Type(Typical APB)
Stair-Stepped Type(Typical SRB)
![Page 6: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/6.jpg)
MIC in Stainless Steel Piping
• Places where MIC can be found• Utility and water piping• Process Piping
• Studies concluded that the leaks were caused by MIC where bacteria was introduced via stagnant hydrotest water and ingress of solid contaminants
6
![Page 7: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/7.jpg)
Inspection and Location Selection Criteria
High MIC susceptibility:
• Low points without drains and horizontal long runs.
• Large Size Pipes
• HAZ in Welds
Inspection at High Susceptibility areas:
10-20% RT to verify the MIC for all high susceptible cases. Incase RT shows indication 100% RT for welds.
GVI,RVI and Boroscopy where accessible.
Low MIC susceptibility:
• Vertical joints have very less susceptibility
7
![Page 8: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/8.jpg)
8
• Defect Definition: Localized Pitting
• Defect Location: Pipe to Pipe/Pipe to Elbow/ HAZ and Weld
• Material Definition: A312 TP 304/304L- Sch10S
• Diameter Range: 4-30 inch(Higher the diameter more susceptible)
Sample Inspection Findings
![Page 9: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/9.jpg)
MIC Samples
9
Source:
Failure analysis reports by ARAMCO and AMCO
![Page 10: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/10.jpg)
MIC Causes
Causes were found:
• Improper Storage
• Design
• Inadequate flushing, draining and drying
• Improper preservation
• Non compliance with hydrostatic testing procedure
10
![Page 11: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/11.jpg)
MIC Lessons Learned
Corrective Actions
• Amended existing Hydrostatic Testing and Lay-Up
procedure for emphasizing more stringent testing and
control requirements
• Carried out extensive VT and RT inspections to
investigate the extent of potential MIC locations
• Conducted inspection assessments for SS piping for
remaining facilities under construction to validate
system integrity
11
![Page 12: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/12.jpg)
MIC Mitigation Approach
• Apply continuous monitoring and frequent inspection of SS
piping systems with MIC risk
• Include use of effective biocides in hydrotest water
• Increase control of water quality
• Ensure adherence to hydrotest procedures
• Ensure adherence lay-up and preservation procedures
• Avoidance of stagnant or no-flow process systems
• Corrosion Management program to capture MIC monitoring and
mitigation strategies
12
![Page 13: Microbiological Induced Corrosion in Stainless Steel ... 2017/PD1/4. Taner-SADARA-MI… · Microbiological Induced Corrosion in Stainless Steel Piping: Mitigation Strategy ... b –MIC](https://reader031.fdocuments.net/reader031/viewer/2022022011/5b154dfb7f8b9a382f8b85b1/html5/thumbnails/13.jpg)
13
Thank You…
Any Questions…