7th EDITION — MICA NATIONAL INSULATION STANDARDS Plate 4-620 Head Insulation, Securement and Cover Fabrication VESSELS, TANKS, AND EQUIPMENT 3 4 2 13 A 3 4 5 7 6 1 B ©2011 MICA 8 9 10 C 11 12 13 15 14 D Head insulation on large diameter vessels must follow the curvature of the vessel head as opposed to the head treatment illustrated on Plate 4-120. Securement of the insulation material can follow the applications illustrated on Plate 4-610 for bottom heads, or it can be secured with a floating ring of cable as illus- trated here. Weatherproofing of the head can be a fabricated protective jacket, or layers of reinforced mastic. Rigid blocks or board are recommended on flat vessel heads where foot traffic is likely. Detail A — Floating ring of bands and cable Detail B — Floating ring of bands and cable (Detail) Detail C — Fabrication of metal head insulation cover Detail D — Insulation of flat vessel head with I-beams and walkway Materials: Cable, bands, jacketing, mechanical fasteners, insulation, mastic and reinforcing mesh. 1. Vessel wall. 2. Insulation. 3. Floating ring of cable. 4. Bands. 5. Shell insulation. 6. Insulation support ring (not required for horizontal vessels). 7. Expansion joint between support ring and shell insulation packed with insulation. 8. Jacketing cut in gores, to overlap and conform to the surface of the head insulation. 9. Band at base of head insulation cover. 10. Mechanical fasteners. 11. Heavy density insulation for walkway. 12. Reinforced mastic over flashing. 13. Caulking and flashing as required; installed to insure water runoff away from insulation system. 14. Banding to secure rim angle. 15. Metal I-beams used to stiffen structure (by others).

description

mica

Transcript of MICA_4-620

Page 1: MICA_4-620

7th edition — mica national insulation standards

Plate 4-620Head Insulation, Securement and Cover FabricationVessels, tanks, and equiPment

3

4

2

13

A

3 4

5

7

6

1

B

©20

11 M

ICA

8

9

10

C

11

12

13

15

14

D

Head insulation on large diameter vessels must follow the curvature of the vessel head as opposed to the head treatment illus trated on Plate 4-120. securement of the insulation material can follow the applications illustrated on Plate 4-610 for bottom heads, or it can be secured with a floating ring of cable as illus-trated here. Weatherproofing of the head can be a fabricated protective jacket, or layers of reinforced mastic. rigid blocks or board are recommended on flat vessel heads where foot traffic is likely.

detail A — Floating ring of bands and cable

detail B — Floating ring of bands and cable (detail)

detail C — Fabrication of metal head insulation cover

detail D — insulation of flat vessel head with i-beams and walkway

Materials: cable, bands, jacketing, mechanical fasteners, insulation, mastic and reinforcing mesh.

1. Vessel wall.

2. insulation.

3. Floating ring of cable.

4. Bands.

5. shell insulation.

6. insulation support ring (not required for horizontal vessels).

7. expansion joint between support ring and shell insulation packed with insulation.

8. Jacketing cut in gores, to overlap and conform to the surface of the head insulation.

9. Band at base of head insulation cover.

10. mechanical fasteners.

11. Heavy density insulation for walkway.

12. reinforced mastic over flashing.

13. caulking and flashing as required; installed to insure water runoff away from insulation system.

14. Banding to secure rim angle.

15. metal i-beams used to stiffen structure (by others).