Metal RoofsDamage Assessment
Seminar Handout
TM
- - i
Seminar Participants We appreciate your interest and participation in our seminar presentations which have been based on extended research in the industry, analysis, and field examinations. This presentation is provided for educational purposes only. We do not provide testing or evaluation of your understanding of the material presented by written or oral examination. We do not confer or issue written or implied documentation relative to certification of your ability or understanding of the subject matter. Reference to "certification" by Haag Engineering Co. in any form of correspondence, advertisement, or marketing material, either written or oral, is strictly prohibited. Haag Engineering Co. reserves the right to pursue all legal rights to protect against any unauthorized use of our name, trademark, and privileges to the material and its application. --Haag Engineering Co.
About Haag Haag is a worldwide diverse firm encompassing forensic engineering, construction consulting, and research and testing. Haag offers outstanding educational programs and publications. Haag handles all aspects of civil, structural, mechanical, electrical, metallurgical, construction defect, slip/fall, and transportation cases. Haag has been in business since 1924 and we continually strive to be the best.
Instructor Profile
Carlos Lopez, Ph.D, E.I.T. Ph.D. Civil Engineering
M.S. Civil Engineering
B.S. Civil Engineering Carlos Lopez graduated from University of Florida with a B.S., M.S., and Ph.D. in Civil Engineering. Currently, he is a member of the American Society of Civil Engineering, the American Concrete Institute, and the American Association for Wind Engineering. Carlos has been with Haag Engineering since 2012 and has inspected and assessed damage to hundreds of roofs. His primary areas of consulting are structural evaluations and general damage assessment. ©Copyright 2014 by Haag Engineering Co. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical, photocopying, recording, or otherwise, without prior written permission from Haag Engineering Co., 4949 West Royal Lane, Irving, TX 75063.
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.1
1
Metal Roofs Damage AssessmentMetal Roofs Damage Assessment
2
Metal Roofing References‐• NRCA (National Roofing Contractors Association)
3
Metal Roofing References‐• MBMA (Metal Building Manufacturers Association)
4
Topics:
1. Product description and manufacturing
2. Installation and roof details
3. Problems‐manufacturing, design/installation, weathering, and mechanical
4. Damage assessment‐ hail and wind
5. Repair methods
5
1. Product description and manufacturing
6
Advantages of metal roofing‐
• Durable‐‐warranties to 50 years
• Wind resistant
• Hail resistant (Class 4)
• Fire resistant
• Insect resistant
• Lightweight‐‐100 to 200 lbs/sq (compare asphalt shingles‐‐240 to 400 lbs/sq)
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.2
7
Disadvantages of metal roofing‐
• First cost can be high
• Steeper roofs cannot be walked on
• Common problems with details at penetrations
• Can be noisy with changes in temperature, and rain and hail
• Can be difficult to repair‐‐many systems are interlocked
8
Types of metals‐
1. Naturally weathering metals
2. Metallic‐coated steels
3. Protective coatings
9
1. Naturally weathering metals
• Aluminum
• Copper
• Lead
• Stainless steel
• Zinc
• Lead‐coated copper
• Terne‐coated stainless steel (terne is lead and tin, or zinc and tin)
Copper panels
10
Copper‐
• A malleable metal that can be formed easily
• Oxidizes from brown to green colors (patina) over time.
• Nominal 16‐20 ounces per sq ft
11
The patina of copper over time‐
12
2. Metallic‐coated steels
• Aluminized steel
• Aluminum/zinc (Galvalume®)
• Galvanized steel
• Terne metal
Galvalume®-coated steel
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.3
13
Galvanized steel‐
• The most common coating for steel panels
• Steel is hot dipped in molten zinc (~1,000 ºF)
• Zinc is metallurgically bonded to the steel
• ASTM G60 and G90 applies 0.60 and 0.90 oz. per sq. ft. to the steel (G90 is ~1 mil thick)
• Zinc is water soluble and “sacrificial” protection
• Sometimes distinguished by bold spangle
14
Galvanized steel‐
15
Galvalume‐coated steel‐
• Invented by Bethlehem Steel in 1972
• Steel hot dipped in mixture 55% aluminum and 45% zinc
• Greater corrosion resistance than galvanized
• Normally bright finish and small spangle
16
Galvalume‐coated steel‐
17
Spangle‐
Galvanized Galvalume
18
3. Protective coatings
• Fluoropolymer (PVDF: Kynar 500® and Hylar5000®)
• Siliconized acrylic and polyester
• Pearlescent and metallic additives
• Clear‐coat finishes
• Laminates
• Anodizing
Fluoropolymer paint
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.4
19
Paint application‐
1. Individual panel spray
2. Continuous coil coat
20
Paint application specifics‐
1. Clean steel‐‐remove dirt and oil
2. Chemical conversion (prep) coat
3. Prime coat ~0.25 mil, then heat cure
4. Top coat ~0.75 mil, then heat cure
5. Total paint thickness is ~1 mil
21Paint application‐ 22
Manufacture of panels‐
1. Panels from sheets
2. Panels from coil stock
23
1. Panels from sheets‐
• Panels bent to form profile in brake
24
2. Panels from coil stock‐
• Panels are cold formed in a roll former
• Coil is coated/painted before rolling
• Panels can be roll formed in a factory or in the field by portable equipment
• Steel coil is bent to form profile by a series of 20 to 25 dies in a factory; by 7 to 8 dies in the field
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.5
25
Factory roll former‐
26
Dies bend coil stock‐
27
Portable roll former‐
28
Panel profiles‐
1. Flat
2. Corrugated
3. Raised rib
4. Standing seam
29
1. Flat profile
• Used on flat surfaces, vertical walls, as well as conical or curved surfaces of spires, domes, and cupolas
30
1. Flat seam
• Not soldered
• Soldered
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.6
31
2. Corrugated profile
32
3. Raised rib profile
33
4. Standing seam types‐34
Standing seam attachment
• Fixed clips
• Expansion (moveable) clips
35
Standing seam installation‐36
Mechanically seamed‐
• Hand seams
• Tongs
• Electrical roll former
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.7
37
Snap together‐
38
Types of metal roofing systems‐
1. Architectural panels
2. Structural panels
3. Metal shingles or shingle panels
39
1. Architectural panels‐
Copper architectural panels
40
2. Structural panels
1. Water barrier (hydrostatic)
2. Often slope <3:12 (low slope)
3. Often Standing seams >1‐1/2” tall
4. Often Non‐curing and non‐skinning sealant (butyl) tape within seams
5. Span between structural supports, normally purlins
41
Structural panels‐
Frames/purlins
Painted steel structural panels
42
Structural panel seam tape‐
Butyl tape within standing seam
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.8
43
3. Metal shingles and shingle panels‐
1. Water shedding
2. Slope >3:12 (steep slope)
3. Interlocked or overlapped
4. Applied over structural decking with underlayment
5. Press‐formed to mimic multiple asphalt or wood shingles, tiles, or slates
44
Paint + granules application‐
• Steel shingle panel
45
Metal shingles and shingle panels‐
46
Thinking about metal…
• Expect large expansions or contractions with changes in temperature
47
Thinking about metal…• Expect oil‐canning (distortions in the flatness of the metal)
• Inherent in flat panels
48Oil‐Canning Mitigation...• Identify problems with coil prior to installation
• Do not use roofing pans wider than 18”
• Use heavier‐gauge metal
• Use minor ribs or striations in pan profile
• Use lower gloss finish
• Apply architectural panels over solid deck rather than over foam insulation or existing roofing materials
• Account for thermal expansion and contraction
• Maintain on‐site roll forming machines in good working condition
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.9
49
2. Installation and Roof Details
50
Architectural panel application‐
51
Architectural panel valley detail‐52
Structural panel application‐
53
Structural application‐54
Structural panel eave detail‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.10
55
Small penetration (soil stack) detail‐Avoid placement in standing seams
56
Large penetration (curb) detail‐
57
Drill screws‐
• Elastomeric washers form water-tight seal
58
3. Problems ‐Manufacture, Design, or
Installation
59
Galvanized coating problem‐60
Too shallow for drainage‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.11
61
Panel slippage due to missing fasteners‐
Upslope edge Down slope edge
62
Screw missing‐
63
Improper fastener installation‐
Over-torqued Skewed
Under-driven Missed purlin
64
Improper fastener installation‐
Over-driven screw
65
Scupper too high (panel closure along eave flooded) ‐
66
Non‐standard detail‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.12
67
Dead valley‐68
Gutter too small‐
69
Ridge misaligned‐70
Non‐standard termination at vertical projection‐
71
Counterflashing missing‐72
Small penetrations non‐standard‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.13
73
No flashing at stack penetrations‐74
Small penetration details‐
Stack dams runoff Stack does not impede runoff
75
No crickets at large penetrations‐76
Large appurtenance not supported by structure below‐
77
Abutting roof systems require special details‐
78
3. Problems‐Weathering
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.14
79
Galvanized steel stack corroded away‐80
Coating deteriorated‐
81
Coating deteriorated‐82
Environmental problems‐
• Acid rain
• Salt spray
• Bird droppings
• Process chemicals
83
Red rust on galvanized steel after zinc is depleted‐
84
Manufacturing processes‐
Acid etching
Stacks atop roof
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.15
85
Manufacturing processes‐86
3. Problems‐Mechanical
87
Cripples are buckles in upper troughs of panels‐
88
Mechanically caused dents in panels‐
89
Abrasions in panel due to seamer‐90
Scratches in panel‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.16
91
Cuts precipitated corrosion and peeled paint‐
92
4. Damage assessment‐Hail
93
Functional damage–
1. Reduction of water‐shedding capability
2. Reduction in expected long‐termservice life
94
Functional hail‐caused damage to metal roofing‐
• Rupturing the metal
• Disengaging a lap element
• Disengaging a fastener
• Disrupting the protective surfacing (if present)
95
Thresholds for functional hail‐caused damage to metal roofing‐
• Steel panels > 2‐1/2” (64 mm)
• Aluminum panels > 1‐1/2” (38 mm)
Hard hailstones, perpendicular impacts, and materials in relatively good or mid‐life conditions
96
Importantly‐
• Dents in metal are not functional damage
• Hail‐caused dents do not appreciably thin the metal
• Factory‐applied coatings are not debonded or broken by hailstone impacts
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.17
97
Rupturing the metal‐98
Rupturing the metal‐
Inside out corrosion (from the building interior)
Corroded thin panel broken by hail
99
Disengaging a lap element‐
Obvious gap in roofing
100Disengaging a lap element‐
Gap in seaming tape within lap seam
101Disengaging a fastener‐ 102
What size hail dented this painted steel panel roof?
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.18
Stone-coated Steel Panels103
Class 4 Impact Rated
104
Hail-caused dents stone-coated steel panels
105
Stone‐coated Steel
Overview – Granules missing where dented by hail
Close view of dent
106
Hail-caused dents stone-coated aluminum panels-
Note that dents did not align with peeled surface coating
107
Factory coatings are tough‐
Analysis of material within dents described as "dirt"
108
Factory coatings are tough‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.19
109
Disruption of Protective Coating
Hail‐caused fractures in field‐applied paint on terne‐coated steel.
110
Hail‐caused spatter marks on galvanized steel panels‐
111
Hail‐caused spatter on Galvalume®‐coated stell panels‐
112
4. Damage assessment‐Wind
113
Functional wind‐caused damage to metal roofing‐
Direct wind‐caused damage
• Tearing panels from roof slopes
• Disengaging a lap element
• Disengaging a fastener
Indirect wind‐caused damage
• Rupturing the metal
• Disrupting the protective surfacing (if present)
114
Where to look for wind‐caused damage‐
• Look high since wind speeds increase with height
• Look where wind is deflected away from the structure since these are areas of greatest negative pressures (uplifts)
• Greatest negative pressures (uplifts) are generated at windward eaves and corners, and leeward sides of ridges
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.20
115
Painted steel architectural panels torn from windward slopes‐
116
Panels could be lifted by hand with little effort, note nail at finger‐
117
Only one small nail secured clip‐118
Painted steel architectural panels failed, note screws were too small‐
Specified Installed
119
Painted steel structural panels torn away along windward eave‐
120
Painted steel structural panels torn away and steel purlins buckled from wind uplift‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.21
121
Painted steel structural panels torn away at failed overhead doors‐
122
Painted steel structural panels failed, note only one screw per clip‐
123
Galvalume® steel structural panels uplifted and standing seam disengaged‐
Underside of deformed panels
124
Structural panels “unfolded” from clip‐
125
Wind speed increases with height and greatest uplifts occur at windward edges and corners‐
126
Indirect wind‐caused damage(impacts by wind‐borne debris)‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.22
127
5. Repair methods
128
Repair v replacement‐
• Assess hail‐ or wind‐caused damage
• Identify damaged panels
• Cost repair, cost replacement
• Make economic choice
• The complexity of many repairs will require bids by contractors
• Most systems can be repaired
129
Repairing a hole or tear in a metal panel‐130
Repair structural panel‐
Metal Roofs: Repair131
Permanent repairTemporary patch
132
Structural steel panel re‐cover (overlay)‐
Metal Roofs Damage Assessment
© 2013, Haag Engineering Co.23
133
Questions?
Thank you!
www.HaagEducation.comwww.HaagGlobal.com