messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components...

17
submittal messana zone 1 November 2018 mZone is a fully programmable zone controller available in two different sizes: 8 and 12 zones. It is assembled with industrial grade components for commercial and residential high-end applications. It connects with mBox via Ethernet or, alternatively, via serial bus (RS485 slave) and integrates with the Messana climate control platform developed with more then 20 years of experience in radiant cooling and heating technology. Job _________________________ Designer_____________________ Contact_________________________ W1 W2 D H W1 W2 D H Features Controlled by mBox; connects with mSense; PID temperature control; thermal actuator staggered activation; programmable analog I/Os; opto-insulated I/Os; additional graphic display (optional); powered by Emerson Climate I/O controller. Size and weight 1 size mZone 8 W1: 10 inches (254 mm) W2: 8 inches (203 mm) D: 3 1/2 inches (90 mm) H: 10 1/2 inches (267 mm) weight 8.5 lb (4 kg) size mZone 12 W1: 14 inches (357 mm) W2: 12 inches (305 mm) D: 3 1/2 inches (90 mm) H: 10 1/2 inches (267 mm) weight 11.5 lb (5.5 kg) Casing Mounting type Fixed mounting brackets Protection grade NEMA 4X (IP65) Color and finish Arctic white metal enclosure Environmental requirements Operating ambient temperature 36° to 110°F (2° to 45°C) Relative humidity (indoor use only) <90%, non condensing

Transcript of messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components...

Page 1: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

submittalmessana zone

1

Nov

embe

r 201

8

mZone is a fully programmable zone controller available in two different sizes: 8 and 12 zones. It is assembled with industrial grade components for commercial and residential high-end applications. It connects with mBox via Ethernet or, alternatively, via serial bus (RS485 slave) and integrates with the Messana climate control platform developed with more then 20 years of experience in radiant cooling and heating technology.

Job _________________________ Designer _____________________ Contact _________________________

W1

W2

D

H

W1

W2

D

H

Features Controlled by mBox; connects with mSense; PID temperature control; thermal actuator staggered activation; programmable analog I/Os; opto-insulated I/Os; additional graphic display (optional); powered by Emerson Climate I/O controller.

Size and weight 1 size mZone 8W1: 10 inches (254 mm)W2: 8 inches (203 mm)D: 3 1/2 inches (90 mm)H: 10 1/2 inches (267 mm)

weight8.5 lb (4 kg)

size mZone 12W1: 14 inches (357 mm)W2: 12 inches (305 mm)D: 3 1/2 inches (90 mm) H: 10 1/2 inches (267 mm)

weight11.5 lb (5.5 kg)

Casing Mounting type Fixed mounting brackets

Protection grade NEMA 4X (IP65)

Color and finish Arctic white metal enclosure

Environmental requirements Operating ambient temperature 36° to 110°F (2° to 45°C)

Relative humidity (indoor use only) <90%, non condensing

Page 2: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

2

Nov

embe

r 201

8

mZone 8 mZone 12

Inputs 2 Analog Inputs (AI) 3

Temperature probes, pressure sensors, flow meters, feedback

Resolution 10-bit A/D converterNTC 10kΩ@25°C Beta 3435 (for supply and return temp) 2 (AI NTC SUP/AI1 RET/AI2) 2 (AI NTC SUP/AI1 RET/AI2)

Auxiliary programmable AI 1 (AI AUX/AI3) 1 (AI AUX/AI3)

Additional 2 programmable AI 3 (AI4-AI6) 7 (AI4-AI10)

Digital Inputs (DI) 4

Presence or window sensors, H/C changeover, alarms, On/Off

Auxiliary dry contact DI - 1 (DI AUX/DI1)

Additional 2 dry contact DI 11 (DI1-DI11) 15 (DI2-DI16)

Outputs 2 Digital Outputs (DO) 5

Thermal actuators, zone valves, pumps, actuators, activations

24VDC/5Amp wet contacts (DO) for zone valve/actuators 8 (DO1-DO8) 12 (DO1-DO12)

Number of thermal actuators (staggered activation) 6 up to 10 (18) up to 17 (34)

Dry contacts (with miniature power relays) 7 - 2 (DO13-DO14)

110/220VAC 50-60Hz wet contacts for pumps 8 1 (DO8 PWR) 10 1 (DO15 PWR)

Analog Outputs (AO) 9

Mixing valves, servo motors, actuators, fan-coils

Resolution/Accuracy 8 bit converter (2%)

2-10V with 24VDC power supply for mix-valve 1 (AO1 MIX / 24V/0V/Y) 1 (AO1 MIX / 24V/0V/Y)

Auxiliary programmable AO (0-10V default) – 1 (AO2 AUX)

Additional 2 programmable AO 3 (AO2-AO4) 4 (AO3-AO6)

Zone Bus RS485 master with shield and 24VDC sensor power supply up to 8 mSense up to 12 mSense(ZONE BUS SHD/0V/24V/D+/D-)

Communication With Messana mBox module Ethernet (Modbus TCP) or RS485 (Modbus RTU) 11

With mSense room sensors RS485 Zone Bus (Modbus RTU)

Power Supply 110/220VAC 50-60 Hz (15Amps outlet) 85 W (4A fuse) 120 W (4A fuse)

Notes 1. Size, weights and technical characteristics may vary without prior notice.2. There are two different types of I/O connectors: the standard I/Os rail-mounted terminal blocks with Push-in

CAGE CLAMP® (with exception of the power relays mZone8DO8 and mZone12DO12-DO15 ) and the additional programmable I/Os push-in connectors (indicated as “additional”) located on the embedded Emerson controller that need to be wired directly on the controller.

3. Analog Inputs can be programmed as: NTC or PTC, 0-20mA, 4-20mA, 0-10V, 0-1V or 0-5V, Digital Input.4. Digital Inputs are opto-insulated and are dry contacts.5. Digital Outputs mZone8DO1-DO8 and mZone12DO1-DO12 are normally open 24VDC wet contacts (max 5Amps). They

are used control zone valves and/or thermal actuators (24VDC). Digital Outputs mZone8DO8 and mZone12DO13-DO15 are used to control the 24VDC coils of the miniature power relays labeled mZone8DO8 (PWR) and mZone12DO13-DO15 (PWR). mZone8DO8 can only have one usage: either DO8 (24VDC) or power relay DO8 (PWR).

6. Based on Messana two-wire (1W) thermal actuators. Max 3 actuators per digital contact (DO).7. Relay sockets pre-wired as dry contacts. Require Finder 44.52.9.024 miniature power relays (not included) rated

250VAC/6A (max 400VAC/10A). Can be reconfigured as 24VDC or 110/220VAC wet contacts.8. Relays socket pre-wired as 110/220VAC wet contact. Voltage depends on the mZone AC power and the main fuse

is sized for max 3A available for DO8 (PWR)/DO15 (PWR). Require Finder 44.52.9.024 miniature industrial relay (not included) rated 250VAC/6A (max 400VAC/10A). Can be reconfigured as 24VDC wet contact or dry contact.

9. Analog Outputs are opto-insulated and can be programmed as: 0-10V, 2-10V or 4-20mA.10. Can be used either for the thermal actuator of zone 8 or for the activation of a circulator pump on the relay DO8 (PWR).11. If connected to mBox via serial bus RS485, remote access to the device is not supported.

Technical specifications 1

Page 3: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

3

Nov

embe

r 201

8

10.7

5 (2

74 m

m)

8.5

(214

mm

)

10 (254 mm)

8 (206 mm)

9.75

(25

0 m

m)

10.5

(26

7 m

m)

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

2

61

4 5

3

DO1 DO2 DO3 DO4

ZONE THERMAL ACTUATORS (24VDC)

DO6 DO7 DO8DO5 SHD 0V 24V D+ D– 0V 24V Y SUPPLY RETURN DI1 24V0V

ZONE BUSSYNC W/DO8 (PWR) AO1 MIX AI NTC DI AUX 24 VDC

GND

DO8 (PWR)

N L

Relay HoldersI/O contacts

mZone 8 components and 2D footprint

Components Legend

1 Ethernet connection 2 Emerson iProGENIUS I/O controller (IPG208D) 3 A/C Power Supply 85W (30W available for outputs)

4 DIN rail-mounted terminal blocks with Push-in CAGE CLAMP® I/O contacts 5 DIN rail-mounted relay holders and power relays 6 Inlet male power socket with switch and fuse holder (IEC 320 C14)

Page 4: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

4

Nov

embe

r 201

8

10.7

5 (2

74 m

m)

8.5

(214

mm

)

14 (356 mm)

12 (305 mm)

9.75

(25

0 m

m)

10.5

(26

7 m

m)

GND

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

2

61

4 5

3

DO1 DO2 DO3 DO4

ZONE THERMAL ACTUATORS (24VDC)

DO6 DO7DO5 DO9 D10DO8 DO12DO11 SHD 0V 24V D+ D– 0V 24V Y SUPPLY RETURN DI1 24V0V

ZONE BUS AO1 MIX AI NTC DI AUX 24 VDC

0V 24V

AO2 AUX

DO15 (PWR)

N LDO14

DRY CONTACTDO13

DRY CONTACT

Relay HoldersI/O contacts

mZone 12 components and 2D footprint

Legend

1 Ethernet connection 2 Emerson iProGENIUS I/O controller (IPG215D) 3 A/C Power Supply 120W (65W available to I/O)

4 DIN rail-mounted terminal blocks with Push-in CAGE CLAMP® I/O contacts 5 DIN rail-mounted relay holders and power relays 6 Inlet male power socket with switch and fuse holder (IEC 320 C14)

Page 5: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

5

Nov

embe

r 201

8

zone 2 zone 3 zone 4 zone 5zone 1 (1/3)

zone 1 (2/3)

zone 1 (3/3)

zone 6 zone 7 zone 8 zone 12

DO1 DO2 DO3 DO4

ZONE THERMAL ACTUATORS (24 VDC)

DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12DO1 DO2 DO3 DO4

ZONE THERMAL ACTUATORS (24 VDC)

DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12

mZone 8

mZone 12

max 3 actuators

SHD 0V 24V D+ D–

ZONE BUS

mZone

max 300ftn ≤ 12

max 300ftn ≤ 12

max 300ftm < n

mSenseID 1

mSenseID 2

mSense ID m

Termination ON

mSenseID 1

mSenseID n

Termination ON

mSenseID m+1

mSenseID m+2

mSenseID n

Termination ON

Each digital outputs is a 24VDC normally open contact with max 5Amps. It is possible to connect up to 3 actuators to each Digital Output with a maximum of 10 actuators for mZone 8 and 17 actuators for mZone 12.

The maximum number of thermal actuators supported by one mZone can be expanded from 10 to 18 (mZone 8) and from 17 to 34 (mZone 12) using the staggered activation logic. This function must be programmed in the mBox unit that controls the mZone.

Do not connect more then 3 Messana two-wire (1W) thermal actuators for each digital output and do not drawn more then 5 Amps for each digital output.

DO8 mZone 8 digital output DO8 can be used either for the actuation of zone number 8 or as a power relay DO8 (PWR) to activate a circulator pump or other high voltage device. The DO8 (PWR) power relay can also be rewired as a dry contact or 24VDC contact.

ZONE THERMAL ACTUATORS (24VDC) (mZone8DO1-DO8 and mZone12DO1-DO12)

mZone 8 features eight digital outputs (DO1-DO8) and mZone 12 twelve digital outputs (DO1-DO12), dedicated to the activation of zone thermal actuators or zone valves.

ZONE BUS (SHD, 0V, 24V, D+, D-)Zone Bus is a RS485 bus used to communicate with mSense room sensors (up to 12) over Modbus RTU protocol.

SHD is dedicated to the connection of the serial communication cable shield (at one end only) and provides shielding against induced noise. If the serial cable has is a foil shield, then use the shield drain wire.

Without SHD connection, reliability of the protocol can be significantly degraded. Always connect the shield drain wire to the mZone SHD terminal and make sure the continuity is maintained on each mSense split connection by twisting together the shield drain wires of the two shielded cables.

0V and 24V terminals are used to supply 24VDC power to the mSense sensors attached on the BUS. Up to 12 sensors can be installed with max 300ft of wire (22AWG).

D+ and D- are the signal bus terminals. These two signals, along with the shield (SHD), are the mSense serial BUS. The mZone acts as a master and the mSense sensors are slaves. To achieve bi-directional communications the BUS is shared between transmitting and receiving. Polarity between the signals D+ and D-, must be respected.

The last sensor on the bus must be terminated by setting the dip-switch ID#9 to ON.

The mZone module can also be installed in the middle of the bus with two different terminated branches.

Inputs / Outputs contacts

Page 6: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

6

Nov

embe

r 201

8

0V 24V Y

AO1 MIX

BK RD WH OG

Belimo actuatormodels

LRB24-SR-TARB24-SR-T

SUPPLY RETURN

AI NTC

S R

AO2 AUX

0V Y

0-10VAnalog Device

AO1 MIX (available on both mZone 8 and mZone 12) is typically used to control a motorized proportional mix valve to adjust the radiant fluid temperature.

0V, 24V are the terminals to supply power to the valve actuator. Y is the 2-10V (or 0-10V) signal terminal to control the position of the proportional mixing valve.

Y can be program as a 0-10V or 2-10V analog output. AO MIX default value is 2-10V.

Messana suggests the use of the Belimo B3 series 3-Way mixing valves with 2-10V proportional control actuators: LRB24-SR-T (B307-B325 valves) and ARB24-SR-T (B329-B352 valves).

mZone12AO2 AUX (available only on mZone 12) is a general purpose analog output.

0V, Y are the 0-10V (or 2-10V) signal terminals to control analog devices (servo motors, actuators, fan-coils, etc.).

Y can be program as a 0-10V or 2-10V analog output. AO AUX default value is 0-10V..

AO1 MIX (0V, 24V, Y) and mZone12AO2 AUX0-10V or 2-10V programmable opto-insulated analog outputs for controlling motorized mixing valves, servo motors, actuators, fan-coils, and other analog devices. Can also be reprogrammed as 4-20mA.

Inputs / Outputs contacts

AI NTC (SUPPLY / RETURN)Analog Inputs for temperature probes (NTC 10kΩ@25°C Beta 3435). Can also be reprogrammed for pressure sensors, flow meters, feedback signals.

AI NTC are dedicated to NTC probes to measure supply and return temperatures of the radiant fluid at the manifold at the manifold.

S SUPPLY terminals are used for supply fluid NTC temperature probe.

R RETURN terminals are used for return fluid NTC temperature probe.

The SUPPLY thermistors must be installed after the circulator pump.

Analog Inputs can be reprogrammed as PTC, 0-20mA, 4-20mA, 0-10V, 0-1V or 0-5V or digital inputs.

Do not use PT1000 temperature probes. Use only 3435 K 10 kOhms NTC thermistors.

Notes

1. Digital Outputs mZone8DO1-DO8 and mZone12DO1-DO12 are normally open 24VDC wet contacts (max 5Amps). They are used control zone valves and/or thermal actuators (24VDC). Digital Outputs mZone8DO8 and mZone12DO13-DO15 are used to control the 24VDC coils of the miniature power relays labeled mZone8DO8 (PWR) and mZone12DO13-DO15 (PWR). mZone8DO8 can only have one usage: either DO8 (24VDC) or power relay DO8 (PWR).

2. Refer to “Relay holders and power relays” in this document for more details.

Page 7: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

7

Nov

embe

r 201

8

Inputs / Outputs contacts

DI AUX

DI1

GND

110/220VAC50/60Hz

Fuse holder switch

N L

NO

ExternalDevice

NO

DI1 is a dry contact digital input for external devices (alarm system, fire alarm, window sensor, presence sensor, etc.). It can also be used with an external switch to select the system mode between heating and cooling or to force the device ON and OFF.

mZone 8 do not offer any digital input pre-wired on the terminal blocks on the DIN bar. Additional 11 Digital Inputs (DI1-DI11) are available directly on the embedded Emerson I/O controller and need to be wired directly on the push-in connectors located on the controller.

mZone 12 offers one digital input, DI1, pre-wired on the terminal blocks on the DIN bar. Additional 15 Digital Inputs (DI2-DI16) are available directly on the embedded Emerson I/O controller and need to be wired directly on the push-in connectors located on the controller.

DI1 AUX (mZone 12 only)Digital Inputs (DI) are opto-insulated dry contacts. DI are used to communicate the status of external devices to the mZone module.DI can be programmed to be triggered by normally open (NO) or normally close (NC) external contacts. By default a DI is preset to work with a NO contact. In case of event, an external contact is closed and acknowledged by the DI.

N (neutral), L (line) and GND (ground/earth) are the terminals to connect a power cord (not included) to the mZone.

The fuse holder and disconnect switch can also be used as a fused switch to shut off power to the device by safely extracting the fuse holder.

Both mZone 8 and mZone 12 are supplied with a 4A fuse and one spare fuse (in the fuse holder). 1 Amp is absorbed by the mZone itself and the remaining 3 Amps are available for the power relays mZone8DO8

(PWR) and mZone12DO15 (PWR). If more then 3 Amps are required, main fuse must be upgraded accordingly.

Use ceramic fuse cartridge (8.5x31.5mm).

N/L/GND Fuse holder and disconnect switchThis block allows for a safe connection to the power line (110V/220VAC 50/60Hz) and offers a fuse circuit protection.

Power contacts

Page 8: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

8

Nov

embe

r 201

8

FinderRelay

44.52.9.024(suppliedby others)

DO8 (PWR)

N L

P2 Pump110V/60Hz

14 24

N L

12 22

Devicebeing

controlledAC power

P1 Pump110V/60Hz

N L

DO14DRY CONTACT

DO13DRY CONTACT

DO15 (PWR)

N L

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

FinderRelay

44.52.9.024(suppliedby others)

14 14

11 11

14 24

12 12

Notes

1. Digital Outputs mZone8DO1-DO8 and mZone12DO1-DO12 are normally open 24VDC wet contacts (max 5Amps). They are used control zone valves and/or thermal actuators (24VDC). Digital Outputs mZone8DO8 and mZone12DO13-DO15 are used to control the 24VDC coils of the miniature power relays labeled mZone8DO8 (PWR) and mZone12DO13-DO15 (PWR). mZone8DO8 can only have one usage: either DO8 (24VDC) or power relay DO8 (PWR).

2. Refer to “Relay holders and power relays” in the user manual for more details.

The DO13-DO15 of the Emerson I/O controller are 24VDC wet normally open contacts connected to the coil terminals of three relays holders to provide three contacts that can be singularly wired as dry or wet contacts.

DO13 and DO14 (DRY CONTACTS) are pre-wired as dry contacts. Use the 11 as common and 14 as normally open (or 12 as normally closed).

Double pole dry contact relay 2

If a double pole relay is required, use COM 21 as common and NO 24 as normally open (or NC 22 as normally closed) for an additional pole. The two poles (11 - 14/12 and 21 - 24/22) are electrically isolated but are activated at the same time by DO13 or DO14 powering the common coil.

DO15 (PWR) is used to power a circulator pump (or other high voltage devices) with a normally open control using 14 , as neutral (N) and 24 as hot terminal (L) (or 12 as neutral (N) and 22 as hot terminal (L), for a normally closed control).

The voltage supplied by the relay DO8 (PWR) is 110VAC or 220VAC, depending on the mZone AC power, and is protected by the same fuse of the mZone 8.

Any high voltage device connected to DO15 (PWR) will be powered by the same mZone AC power supply and will be protected by the same fuse. The mZone is supplied with a 4A fuse. 1 Amp is absorbed by the mZone itself and the remaining 3 Amps are available for the power relay DO15 (PWR). If more then 3 Amps are required, the main fuse must be upgraded accordingly. Power relay is rated 250VAC/6A (max 400VAC/10A).

The DO8 of the Emerson I/O controller is a 24 VDC wet contact that is wired in parallel as ZONE THERMAL ACTUATORS DO8 and as power relay DO8 (PWR).

The mZone 8 Digital Output DO8 can be used:

• to control the thermal actuator or zone valve of the zone number 8

or, if the number of zones to control are less then 8,

• to control the DO8 (PWR) power relay to activate a circulator pump or another high voltage devices.

DO8 (PWR) is used to power a circulator pump (or other high voltage devices) with a normally open control using 14 , as neutral (N) and 24 as hot terminal (L) (or 12 as neutral (N) and 22 as hot terminal (L), for a normally closed control).

The voltage supplied by the relay DO8 (PWR) is 110VAC or 220VAC, depending on the mZone AC power, and is protected by the same fuse of the mZone 8.

Any high voltage device connected to DO8 (PWR) will be powered by the same mZone AC power supply and will be protected by the same fuse. The mZone is supplied with a 4A fuse. 1 Amp is absorbed by the mZone itself and the remaining 3 Amps are available for the power relay. If more then 3 Amps are required, the main fuse must be upgraded accordingly. Power relay is rated 250VAC/6A (max 400VAC/10A).

If you use DO8 (PWR) to control a circulator pump, only up to seven different zones can be controlled. If more then 7 zones are need, use mZone 12.

DO8 (PWR) (mZone 8 only)Reconfigurable digital output 1 with power relays 2.

DO13-DO14 (DRY CONTACTS), DO15 (PWR) (mZone 12 only)Reconfigurable digital outputs 1 with power relays 2.

Inputs / Output power relays

Page 9: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

9

Nov

embe

r 201

8

A2

22

21

24

A1

12

11

14

COM

NO

COIL

NC

COM

NO

COIL

NC

0V 24V

DO

Relay holder pinout(top view)

Relay pinout diagram(bottom view)

A2

22

21

24 14

11

12

A1

Model: Finder 44.52.9.024Coil voltage: 24VDCRated voltage/max: 250/400 VACRated current/max: 6A/10A

Finder mini relays model 44.52.9.024 are not included in the mZone.

Relays can be purchased separately.

Notes

1. Digital Outputs mZone8DO1-DO8 and mZone12DO1-DO12 are normally open 24VDC wet contacts (max 5Amps). They are used control zone valves and/or thermal actuators (24VDC). Digital Outputs mZone8DO8 and mZone12DO13-DO15 are used to control the 24VDC coils of the miniature power relays labeled mZone8DO8 (PWR) and mZone12DO13-DO15 (PWR). mZone8DO8 can only have one usage: either DO8(24VDC) or power relay DO8 (PWR).

Relay holders and miniature power relays

External miniature power relays for mZone8DO8 and mZone12DO13-DO15 digital outputs 1.

The digital outputs mZone8DO8 and mZone12DO13-DO15 are pre-wired to control the 24VDC coils (A1 and A2 COIL) of Finder relays (model 44.52.9.024, not supplied).

Each miniature power relay features two separate poles (“1” left side and “2” right side, top view) operated by the same coil (A1-A2).

Each pole come with:

• one normally closed (NC) contact between common COM 11 (or 21) and NC 12 (or 22)

• one normally open (NO) contact between common COM 11 (or 21) and NO 14 (or 24) The two poles are electrically insulated and can be used as a double-pole switch.

Miniature relay Installation

To use the digital outputs mZone8DO8 and mZone12DO13-DO15, a relay must be insert in the relay holder and secured by pulling-up the holding band.

Use only Finder mini relay model 44.52.9.024.

Page 10: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

10

Nov

embe

r 201

8

Relay pinout diagram(top view)

pole

1

pole

2

A2

22

21

24 14

11

12

A1

DODRY CONTACT

FinderRelay

44.52.9.024(suppliedby others)

N

L24V

0V

DODRY CONTACT

FinderRelay

44.52.9.024(suppliedby others)

110/220VACdevice

N L

Two different voltage devices Line and neutral interruption

Double-pole dry contact relay

The Finder relay features two columns of terminals, COM 11, NC 12, NO 14 (pole 1) and COM 21, NC 22, NO 24 (pole 2) equivalent to two single-pole relays actuated by a single coil 24VDC (A1, A2).

The two poles are electrically insulated and activated by the same digital output.

Examples of usage:

Page 11: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

11

Nov

embe

r 201

8

FinderRelay

44.52.9.024(suppliedby others)

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12

ZONE THERMAL ACTUATORS (24 VDC) ZONE BUS

SHD

AO1 MIX AI NTC AO2 AUX DI AUX

0V 24V D+ D– 0V 24V Y SUPPLY RETURN 0V Y DI1

DO13DRY CONTACT

DO14DRY CONTACT

DO15 (PWR)

N L

110/220VAC50/60Hz

2414

24VDC device

A2

22

21

24

A1

12

11

14

COM

NO

COIL

NC

COM

NO

COIL

NC

0V 24V

DO

Relay holder pinout(top view)

Relay pinout diagram(bottom view)

A2

22

21

24 14

11

12

A1

Connect 24VDC from the AO MIX terminal blocks (0V and 24V) to the COM 11 (0VDC) and COM 21 (24VDC) on the DO13 and/or DO14 relay holder/s.

To control a 24VDC device use the terminals:

14 (0VDC) and 24 (24VDC)or

12 (0VDC) and 22 (24VDC)

for a normally open contact with 24VDC for a normally closed contact with 24VDC

2414

11 21

22 2212 12

2414

11 21

Notes

1. Max 8W for all 24VDC wet contacts supplied by the mZone AC/DC power supply. For more then 8W, use an additional DC power supply.

To use these contacts, insert a Finder mini relay model 44.52.9.024 (not included) in the relay holder and pull-up the holding band.

24VDC wet contacts 1

(24VDC is supplied from the mBox AC/DC power supply)

Rewiring mZone12DO13-DO14 from dry contacts to 24VDC wet contacts 1

mZone 12 features two auxiliary digital outputs (DO13 and DO14) for general purpose that are pre-wired a on two relays holders as dry contacts. To use these two contacts, a miniature power relay is required (Finder relay model 44.52.9.024, not included).

One or both dry contacts (DO13 and/or DO14) can be rewired as 24VDC wet contact 1 following the schematic below.

Before proceeding disconnect power. When completed, mark off the “DRY CONTACT” text on the label to avoid future errors.

Page 12: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

12

Nov

embe

r 201

8

FinderRelay

44.52.9.024(suppliedby others)

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12

ZONE THERMAL ACTUATORS (24 VDC) ZONE BUS

SHD

AO1 MIX AI NTC AO2 AUX DI AUX

0V 24V D+ D– 0V 24V Y SUPPLY RETURN 0V Y DI1

DO13DRY CONTACT

DO14DRY CONTACT

DO15 (PWR)

N L

11 21 11 21

14 1424 24

12 1222 22

2414

110/220VAC device

NL

A2

22

21

24

A1

12

11

14

COM

NO

COIL

NC

COM

NO

COIL

NC

0V 24V

DO

Relay holder pinout(top view)

Relay pinout diagram(bottom view)

A2

22

21

24 14

11

12

A1

mZone AC power110/220VAC

50/60Hz

Add. AC power 110/220VAC

50/60Hz

Notes

1. The AC power wires can be derived from the mZone mains or, alternatively, from the adjacent DO15 relay holder, COM 11 (N) and COM 21 (L). In this case the controlled device will be under the same fuse of the mZone. Fuse might be upgraded based on the controlled device load.

To use these contacts, insert a Finder mini relay model 44.52.9.024 (not included) in the relay holder and pull-up the holding band.

Rewiring mZone12DO13-DO14 from dry contacts to high voltage (110/220VAC) wet contacts

mZone 12 features two auxiliary digital outputs (DO13 and DO14) for general purpose that are pre-wired a on two relays holders as dry contacts. To use these two contacts, a miniature relay is required (Finder relay model 44.52.9.024, not included).

One or both dry contacts (DO13 and/or DO14) can be wired as high voltage (110/220VAC) wet contact/s following the instructions below.

Before proceeding disconnect power. When completed, mark off the “DRY CONTACT” text on the label to avoid future errors.

High voltage (110/220VAC) wet contacts(Additional AC power)

Connect an additional AC power circuit to the COM 11 (N) and COM 21 (L ) on the DO13/DO14 relay holder/s, as shown on the electric schematic above 1.

And additional AC power with a dedicated circuit breaker must be added.

To control a 110/220VAC 1 device use the terminals:

14 (N) and 24 (L)or

12 (N) and 22 (L)

for a normally open contact for a normally closed contact.

Page 13: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

13

Nov

embe

r 201

8

FinderRelay

44.52.9.024(suppliedby others)

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12

ZONE THERMAL ACTUATORS (24 VDC) ZONE BUS

SHD

AO1 MIX AI NTC AO2 AUX DI AUX

0V 24V D+ D– 0V 24V Y SUPPLY RETURN 0V Y DI1

DO13DRY CONTACT

DO14DRY CONTACT

DO15 (PWR)

N L

14

22

24

11

dry contactrelay

DO14

11

Devicebeing

controlledAC power

A2

22

21

24

A1

12

11

14

COM

NO

COIL

NC

COM

NO

COIL

NC

0V 24V

DO

Relay holder pinout(top view)

Relay pinout diagram(bottom view)

A2

22

21

24 14

11

12

A1

110/220VAC50/60Hz

12

21

21

Notes

1. 110VAC or 208VAC or 220VAC or 230VAC (50 or 60Hz) depending on the mZone AC power.

Disconnect the neutral (N) and line (L) wires connected to the relay holder on terminals COM 11 (0VAC) and COM 21 (110/220VAC 1).

Cover the exposed neutral (N) and line (L) wires with twist-on connectors and tape over the wire nut for extra assurance.

Use the COM 11 as common and NO 14 as normally open or NC 12 as normally closed dry contact. Alternatively, or in addition, use the COM 21 as common and NO 24 as normally open or NC 22 as normally closed dry contact.

The two dry contacts ( 11 - 14 / 12 and 21 - 24 / 22 ) are electrically isolated but activated at the same time by mZone8DO8 or mZone12DO15.

To activate these contacts, insert a Finder mini relay model 44.52.9.024 (not included) in the relay holder and pull-up the holding band.

Rewiring mZone8DO8 and mZone12DO15 from 110/220VAC 1 wet contacts to dry contacts

mZone module features one digital output (DO8 for mZone 8 and DO15 for mZone 12) wired as normally open 110/220VAC 1 wet contacts dedicated to directly activate a circulator pump or other high voltage devices. The circulator pump connected to the wet contacts NO 14 (N) and NO 24 (L) will be turned on and off by the relay based on the status of its related digital output (mZone8DO8 and mZone12DO15).

In case the circulator pump or another device need to be controlled with an on/off potential-free contact or a 24VDC contact, the mZone8DO8 or mZone12DO15 digital output must be re-wired accordingly.Follow the instructions below to rewire the two wet 110/220VAC 1 contacts into dry contacts.

Before proceeding disconnect power. When completed, mark off the “PWR N | L” text on the label to avoid future errors.

Dry contacts(250VAC/6A power relays)

Page 14: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

14

Nov

embe

r 201

8

FinderRelay

44.52.9.024(suppliedby others)

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12

ZONE THERMAL ACTUATORS (24 VDC) ZONE BUS

SHD

AO1 MIX AI NTC AO2 AUX DI AUX

0V 24V D+ D– 0V 24V Y SUPPLY RETURN 0V Y DI1

DO13DRY CONTACT

DO14DRY CONTACT

DO15 (PWR)

N L

2414

24VDC device

A2

22

21

24

A1

12

11

14

COM

NO

COIL

NC

COM

NO

COIL

NC

0V 24V

DO

Relay holder pinout(top view)

Relay pinout diagram(bottom view)

A2

22

21

24 14

11

12

A1

24VDC wet contacts(24VDC is supplied from the mBox AC/DC power supply 2)

110/220VAC50/60Hz

24

22

14

12

2111

Notes

1. 110VAC or 208VAC or 220VAC or 230VAC (50 or 60Hz) depending on the mZone AC power. 2. Max 8W for all 24VDC wet contacts supplied by the mZone AC/DC power supply. For more then 8W, use an additional DC power supply.

To use these contacts, insert a Finder mini relay model 44.52.9.024 (not included) in the relay holder and pull-up the holding band.

Rewiring mZone8DO8 and mZone12DO15 from 110/220VAC 1 wet contacts to 24VDC wet contacts

mZone module features one digital output (DO8 for mZone 8 and DO15 for mZone 12) wired as normally open 110/220VAC 1 wet contacts dedicated to directly activate a circulator pump or other high voltage devices. The circulator pump connected to the wet contacts NO 14 (N) and NO 24 (L) will be turned on and off by the relay based on the status of its related digital output (mZone8DO8 and mZone12DO15).

In case the circulator pump or another device need to be controlled with 24VDC wet contacts, the mZone8DO8 and mZone12DO15 digital output must be re-wired accordingly. Follow the instructions below to rewire the two wet 110/220VAC 1 contacts into 24VDC wet contacts 2.

Before proceeding disconnect power. When completed, mark off the “DRY CONTACT” text on the label to avoid future errors.

Disconnect the neutral (N) and line (L) wires connected to the relay holder on terminals COM 11 (N) and COM 21 (L).

Cover the exposed neutral (N) and line (L) wires with twist-on connectors and tape over the wire nut for extra assurance.

Connect 24VDC from the AO MIX terminal blocks (0V and 24VDC) to the COM 11 (0V) and COM 21 (24VDC) on the mZone/DO8 and/or mZone/DO15 relay holder/s.

To control a 24VDC device, use the following terminals:

NO 14 (0VDC) and NO 24 (24VDC)or

NC 12 (0VDC) and NC 22 (24VDC)

for 24VDC normally open contacts 2 for 24VDC normally closed contacts 2

Page 15: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

110V/60Hz

15

Nov

embe

r 201

8

FinderRelay

44.52.9.024(suppliedby others)

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8

ZONE THERMAL ACTUATORS (24 VDC) ZONE BUS

SHD

AO1 MIX AI NTC

0V 24V D+ D- 0V 24V Y SUPPLY RETURN

DO8 (PWR)

N L

MV1

S Rzone

7zone

1zone

2zone

3zone

4zone

5zone

6P1 Pump

110V/60Hz

times-square times-square

Electrical drawing

R

S

C/H WR C/H WS

MV1 P1

Manifold

To Radiant Panels

zone 8

mZone 8

Up to 7 zones, DO1 through D07, when the relay DO8 (PWR) is used for the circulator pump activation (P1)

Mechanical drawing

mSense ID 1

mSenseID 7

Termination ON

mZone 8 sample application drawing

Below is a sample application drawing for this product. This application may include other Messana products that are required for installation. More sample applications can be found at radiantcooling.com.

DO8 If the power relay DO8 (PWR) is wired to the circulator pump, the digital output DO8 cannot be used for zoning.

DO8

Page 16: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

16

Nov

embe

r 201

8

R

S

C/H WR C/H WS

MV1 P1

Manifold

To Radiant Panels

zone 12

mZone 12

Up to 12 zones

Mechanical drawing

FinderRelay

44.52.9.024(suppliedby others)

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO11 DO12

ZONE THERMAL ACTUATORS (24 VDC) ZONE BUS

SHD

AO1 MIX AI NTC AO2 AUX DI AUX

0V 24V D+ D– 0V 24V Y SUPPLY RETURN 0V Y DI1

DO13DRY CONTACT

DO14DRY CONTACT

DO15 (PWR)

N L

MV1 P1 Pump110/220V

S Rzone

1zone

7zone

8zone

9zone

10zone

11zone

12zone

6zone

5zone

4zone

3zone

2110/220Vac

50/60Hz

Electrical drawing

mSense ID 1

mSense ID 12

mZone 12 sample application drawing

Below is a sample application drawing for this product. This application may include other Messana products that are required for installation. More sample applications can be found at radiantcooling.com.

Page 17: messana zone submittal - Messana Radiant Cooling · 2018-11-23 · with industrial grade components for commercial and residential high-end applications. It connects with mBox via

Messana Radiant Cooling - 4105 Soquel Dr, Suite B - Soquel, CA 95073 - USA

Nov

embe

r 201

8

The original end-user consumer (the “Purchaser”), by taking receipt of any Messana, Inc. (“Messana”) controls product (the “Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands the same.

The Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with Messana’s instructions, ordinary wear and tear is expected.

The pass-through warranty period is for a period of (i) two (2) years form the production date if the Product is not installed during that period, (ii) or one (1) year from the documented date of installation if installed within two (2) years from the production date.(a)The liability of Messana under the Limited Warranty shall be limited to, at Messana’s sole discretion: (i) the cost of parts and labor provided by Messana to repair defects in materials and/or workmanship of the defective product; (ii) or to the exchange of the defective product for a warranty replacement product; (iii) or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from Messana.(b) Without limiting the foregoing in any way, Messana is not responsible, in contract, tort or strict product liability, for any other (i) losses, (ii) costs, (iii) expenses, (iv) inconveniences, or (v) damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.

The pass-through Limited Warranty applies only to those defective Products during the Warranty Period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.

Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the Messana Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold Messana harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.

The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than Messana, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by Messana; or if the Product was not installed in compliance with Messana’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with Messana’s instructions.

LIMITATION OF LIABILITYTHIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWO (2) YEARS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.

MESSANA EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL, INCIDENTAL, INDIRECT OR PUNITIVE DAMAGES FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.This warranty gives the Purchaser specific legal rights, and the Purchaser may also have other rights, which may vary, from state to state and by province.

VARIATIONS THAT MIGHT APPLY TO THIS LIMITED WARRANTYProducts are warranted in conformance with applicable laws. If any part or term of this Limited Warranty is held to be illegal, unenforceable or in conflict with applicable law by any court of competent jurisdiction, the validity of the remaining portions of the Limited Warranty shall not be affected, and all rights and obligations shall be construed and enforced as if this Limited Warranty did not contain the particular part or term held to be invalid. Some geographies, including certain US states, do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Limited Warranty gives the user specific legal rights. The user may also have other rights which vary from state to state or country to country.

LIMITED WARRANTY FOR MESSANA CONTROLS