Meet the DBI Pros” Meet the DBI Pros” Summit Summit October 12, 2007 October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER ‘SUMMIT’ PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT SAN FRANCISCO FIRE DEPARTMENT

Transcript of Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE...

Page 1: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

““Meet the DBI Pros” Meet the DBI Pros” SummitSummit

October 12, 2007October 12, 2007

WELCOME TO THE AUTOMATIC SPRINKLER ‘SUMMIT’ PRESENTED BY THE

SAN FRANCISCO FIRE DEPARTMENTSAN FRANCISCO FIRE DEPARTMENT

Page 2: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

NFPA 13-Installation of Sprinkler NFPA 13-Installation of Sprinkler

Systems: Systems: Transition from 1999 to 2002 Transition from 1999 to 2002

EditionsEditions

By: Gerald Zari and Jon CorbettBy: Gerald Zari and Jon Corbett

“ “MEETMEET THE DBI PROS” THE DBI PROS”

THE SAN FRANCISCO FIRE DEPARTMENT PRESENTS

Page 3: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Reorganization of the NFPA 13 Standard:

• NFPA 13, 2002 Complies with the NFPA Manual of Style:

– First Chapter is “Administration”

– Second Chapter is “Reference Publications” (previously Chapter 13)

– Third Chapter is “Definitions”

– Changes/additions indicated with a vertical bar

Page 4: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

The “Administration” Chapter provides general guidance for the following aspects of Sprinkler Systems:– Scope: Minimal design & installation of systems.– Purpose: Reasonable degree of protection– Application: Water Supplies, sprinklers, piping, fittings

and Materials used– Retroactivity Clause: The AHJ can apply this standard

to existing systems where there is an “unacceptable degree of risk”

– Equivalency: Allows the AHJ to accept alternate approaches, based on engineering judgment, that meets the intent of the standard

– New Technology: Accepts the use of newly developed sprinkler, fittings, etc…within their listings

Page 5: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Referenced Publications:Referenced Publications:– Updated to the most current, applicable Updated to the most current, applicable

StandardsStandards– Directs user to other standards for Directs user to other standards for

design of sprinkler systems not design of sprinkler systems not addressed in NFPA 13addressed in NFPA 13

New Definitions:New Definitions:– Bathrooms in Dwelling unitsBathrooms in Dwelling units– Ceilings: Flat, Horizontal, and SlopedCeilings: Flat, Horizontal, and Sloped– Materials: Non-Combustible and Limited Materials: Non-Combustible and Limited

Combustible; consistent with NFPA 220Combustible; consistent with NFPA 220

Page 6: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 4: Chapter 4: Owners Certificate (4.3)Owners Certificate (4.3)• A new form with information provided by A new form with information provided by

the Owner or an Authorized Agentthe Owner or an Authorized Agent• States intended use of building, materials States intended use of building, materials

within and storage heightswithin and storage heights• Provides a preliminary building plan for Provides a preliminary building plan for

design of the sprinkler systemdesign of the sprinkler system• If applicable, special information about the If applicable, special information about the

water supply and Microbiologically water supply and Microbiologically influenced corrosion (MIC)influenced corrosion (MIC)

• SFFD may require this form on the SFFD may require this form on the approved plansapproved plans

Page 7: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 6 (1999 Chpt.3): Chapter 6 (1999 Chpt.3): System Components and System Components and HardwareHardware• Specially listed products (6.1.1.1)Specially listed products (6.1.1.1)

– Installation must conform to all Installation must conform to all conditions required by the listing, this conditions required by the listing, this information is found in the product information is found in the product literature and installation instructionsliterature and installation instructions

– Examples: WS sprinklers, extended Examples: WS sprinklers, extended coverage, flex heads and residential coverage, flex heads and residential sprinklerssprinklers

Page 8: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 7 (1999 Chpt.4): Chapter 7 (1999 Chpt.4): System requirementsSystem requirements

• Gauges are now required above and Gauges are now required above and below check valves in a Riser, i.e. below check valves in a Riser, i.e. both sidesboth sides

• Freezing conditions: areas where Freezing conditions: areas where Temperatures are below 40 degrees Temperatures are below 40 degrees FahrenheitFahrenheit

Page 9: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 8 (1999 Chpt.5): Chapter 8 (1999 Chpt.5): Installation RequirementsInstallation Requirements• Sprinkler thermal sensitivity (8.3.3)Sprinkler thermal sensitivity (8.3.3)

– Per 8.3.3.3, where Quick Response (QR) Per 8.3.3.3, where Quick Response (QR) sprinklers are installed, all sprinklers in that sprinklers are installed, all sprinklers in that room/compartment are required to be QR room/compartment are required to be QR ordinary temperature-rated (135-170 ordinary temperature-rated (135-170 00F)F)

– The exception is a circumstance that requires a The exception is a circumstance that requires a higher temperature sprinkler, e.g. a heat higher temperature sprinkler, e.g. a heat source like a Fire Place Stove or skylight, then source like a Fire Place Stove or skylight, then use of Standard sprinklers is permitteduse of Standard sprinklers is permitted

– Does Does NOTNOT apply to Residential Sprinklers apply to Residential Sprinklers

Page 10: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 8, continued: Chapter 8, continued: • Sidewall Spray Sprinklers (8.4.2):Sidewall Spray Sprinklers (8.4.2):

– Light Hazard: Allows installation of sidewall Light Hazard: Allows installation of sidewall sprinklers in smooth, horizontal or sloped sprinklers in smooth, horizontal or sloped ceilingsceilings

– Deflector Orientation (8.7.4.2.2):Deflector Orientation (8.7.4.2.2):• In sloped ceilings: locate sprinkler in highest point In sloped ceilings: locate sprinkler in highest point

of slope with deflector parallel to slopeof slope with deflector parallel to slope

– Definitions:Definitions:• Smooth Ceiling: a continuous ceiling free of Smooth Ceiling: a continuous ceiling free of

significant irregularitiessignificant irregularities

• Horizontal Ceiling: 2:12 slope or less (10Horizontal Ceiling: 2:12 slope or less (10oo))

• Sloped Ceiling: Greater than a 2:12 slope (>10Sloped Ceiling: Greater than a 2:12 slope (>10oo))

Page 11: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 8, continued:Chapter 8, continued:• Skylights and Similar (Small) Ceiling Skylights and Similar (Small) Ceiling

Pockets (8.5.7):Pockets (8.5.7):– Omission of Sprinklers allowed in openings Omission of Sprinklers allowed in openings

if:if:

1.1. Opening does not exceed 32 ftOpening does not exceed 32 ft2 2

ANDAND

2.2. Edges of openings are horizontally separated Edges of openings are horizontally separated by 10-feet or more to other openingsby 10-feet or more to other openings

Max 32 ft2

Max 32 ft2

10 feet or more4’-0

8’-0

2’-0

16’-0

Example:

Page 12: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 8, continued:Chapter 8, continued:• Ceiling Pockets (8.6.7)Ceiling Pockets (8.6.7)

– Sprinklers required except where ALL of the Sprinklers required except where ALL of the conditions listed below are met:conditions listed below are met:1.1. Volume (cubic feet) is 1000 ftVolume (cubic feet) is 1000 ft33 or less or less

2.2. Maximum of 36-inch deepMaximum of 36-inch deep

3.3. Entire floor area below has sprinkler coverageEntire floor area below has sprinkler coverage

4.4. Adjacent openings are horizontally located 10-feet Adjacent openings are horizontally located 10-feet or more away from any other pocketsor more away from any other pockets

5.5. Construction is limited/non-combustibleConstruction is limited/non-combustible

6.6. Skylights allowed to be plastic if 32 ftSkylights allowed to be plastic if 32 ft22 or less or less

7.7. Quick Response sprinklers are used in the roomQuick Response sprinklers are used in the room

Page 13: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 9 (1999 Chpt.6): Chapter 9 (1999 Chpt.6): Hangers, Bracing , and Hangers, Bracing , and Restraint of System PipingRestraint of System Piping• Fasteners in Concrete (9.1.3)Fasteners in Concrete (9.1.3)

– Installed in the Horizontal position unless Installed in the Horizontal position unless one of the following conditions is met:one of the following conditions is met:•Used in concrete with gravel/crushed stone Used in concrete with gravel/crushed stone

for supporting up to 4-inch pipefor supporting up to 4-inch pipe•Alternated with hangers connected to Alternated with hangers connected to

structural members or sides of concrete structural members or sides of concrete beams for 5-inch or larger pipebeams for 5-inch or larger pipe

•Spacing is 10-feet or less for 4-inch and larger Spacing is 10-feet or less for 4-inch and larger pipepipe

Page 14: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 9, continued.Chapter 9, continued.• Unsupported Ends of Branch Lines (BL) and Unsupported Ends of Branch Lines (BL) and

Armovers with static/flow pressures exceeding Armovers with static/flow pressures exceeding 100 psi (9.2.3.4.3 and 9.2.3.5.2):100 psi (9.2.3.4.3 and 9.2.3.5.2):

– Steel Pipe requires a hanger and vertical restraint Steel Pipe requires a hanger and vertical restraint within 12-inches of the BL and armover endwithin 12-inches of the BL and armover end

– Copper Tube requires a hanger and vertical Copper Tube requires a hanger and vertical restraint within 6-inches of the BL and armover endrestraint within 6-inches of the BL and armover end

Page 15: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Chapter 9, Continued.Chapter 9, Continued.

• Risers (9.3.5.5)Risers (9.3.5.5)

– 4-way braces required for risers more 4-way braces required for risers more than 3-feet in length. than 3-feet in length.

– 4-way braces not required where riser 4-way braces not required where riser penetrates intermediate floors of a penetrates intermediate floors of a multistory building where clearances multistory building where clearances required by 9.3.4 are not exceeded.required by 9.3.4 are not exceeded.

Page 16: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

A QUICK COMPARISON OF NFPA 13, 13R, AND 13D STANDARDS

Page 17: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

REQUIREMENT NFPA 13 NFPA 13R NFPA 13D

SPRINKLERS THRU-OUT ALL AREAS/ALL OCCUP. X

SPRINKLERS IN ‘R’ OCCUPANCIES UP TO 4 STORIES

X X

SPRINKLERS IN ‘R-3’- 1 & 2 FAMILY DWELLINGS X X X

EXTRA STORY 2007 CBC TBL 503 X NOT ALLOWED NOT ALLOWED

MORE AREA 2007 CBC TBL 503 X NOT ALLOWED NOT ALLOWED

CLOSETS:*

HOTEL/MOTEL CLOSETS 24 sq. ft. or less N/A

HOTEL/MOTEL CLOSETS greater than 24 sq. ft. X X N/A

CLOTHES/LINEN CLOSETS/PANTRIES (non-hotel/motel) 24 sq. ft. or less

X

CLOTHES/LINEN CLOSETS/PANTRIES (non-hotel/motel) Greater than 24 sq. ft.

X X X

BATHROOMS:**

BATHROOMS 55 sq. ft. or less

BATHROOMS greater than 55 sq. ft. X X X

QUICK COMPARISON OF NFPA 13, 13R, AND 13D STANDARDS

Page 18: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

DESIGN: NFPA 13 NFPA 13R NFPA 13D

RESIDENTIAL @ 0.1GPM/sq. ft. (or listed flow >0.1 gpm, res. Sprinkler)

X

RES. OCC. USE QUICK RESP./ CALC. 1500 sq. ft. X

RES. OCC. USE RES. SPRKLRS/ CALC. 4 HEADS X X

RES. OCC. USE RES. SPRKLRS/ CALC. 2 HEADS & 1HEAD CALC.

X

NO HOSE ALLOWANCE REQUIRED (must include domestic use)

X X

RES. OCC. ADD 100 GPM HOSE ALLOWANCE X

MUST USE LISTED RESIDENTIAL SPRINKLERS

QR or RES. X X

MINIMUM DENSITY 0.05GPM/sq. ft. (listed sprinkler flow)

X X

MINIMUM OPERATING PRSS. OF 7 PSI X X X

Page 19: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

MISCELLANEOUS AREAS:NFPA 13 NFPA 13R NFPA 13D

GARAGES (requires 250gpmhosedemand) X Refer to NFPA 13 Refer to NFPA 13

ATTICS/CRAWL SPACES/CONCEALED SPACES-NOT INTENDED FOR STORAGE OR LIVING PURPOSES

X

*The least dimension not exceeding 3’.

**The walls and ceilings must be non or limited-combustible construction.

Page 20: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.02 Fire Department Connection Omission

  • In the past, it was the Fire Department's position to allow the

omission of a Fire Department Connection in buildings with fewer than 20 sprinkler heads per floor. This was allowed by N.F.P.A.  13, as it left the decision up to the Authority Having Jurisdiction. However, due to Standard changes, the 2002 edition of N.F.P.A. 13 (8.16.2.2) no longer allows the omission of an FDC except in the following circumstances: 

• Exception 1.   Buildings located in remote areas that are inaccessible for fire department support.         

• Exception 2.   Large-capacity deluge systems exceeding the pumping capacity of the fire department.         

• Exception 3.   Single-story buildings not exceeding 2,000 sq. ft. in area.   

• Two additional exceptions for the requirement for FDC's are found in the 2001C.B.C.  , Section 904. The first pertains to combination domestic/fire services. When approved by the Fire Department, the FDC may be omitted in these systems. The second exception applies to Group I Occupancies housed in existing single family dwellings under certain conditions (see 2001  C.B.C.  , section 904.1.2, exception 4). 

• It is the Fire Department's position that an FDC will be required except in the instances outlined above.

Page 21: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.04 Color Coding of Existing Standpipes

• Reference: 2007C.B.C.  Section 905.4.2  • It is the Bureau of Fire Prevention's policy that all standpipe systems

with multiple risers be interconnected at their base. However, existing systems that were approved and installed without such interconnection may have their use continued if such standpipe system is provided with an approved color code. Color code markers shall be of a permanent material at least one inch wide surrounding the flange of the standpipe inlet. All outlets supplied by this inlet shall be equipped with similar marking.

• If the standpipe is exposed, the pipe directly above the outlet handle shall be marked with a color band at least one inch wide which is the same color as installed at the inlet which supplies such outlet. If the standpipe is enclosed by construction, such markings shall be located on the wall directly behind the standpipe outlet. This marking may be a 3 inch color disk or 3 inch square area and shall be the same color as the inlet which supplies such outlet.

• The Bureau of Fire Prevention will accept five colors which must be florescent: hospital white, royal blue, canary yellow, fire engine red, and bright orange.

Page 22: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.05 Protection of Standpipe Inlets

• Reference: 2007C.F.C.  Section 912, 2003 NFPA 14

Section 12.9

• THE SAN FRANCISCO FIRE DEPARTMENT'S REQUIREMENTS FOR THE PROTECTION OF STANDPIPE INLET THREADS ARE:

• 1.  Hose connections for standpipes shall be equipped with an approved plastic or metal plug which may be removed and reused.

• 2.  The use of cast iron caps which are not threaded shall not be used.

Page 23: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.06 Design Criteria for Fire Department Connections and Standpipe Outlet Valves

• Reference: 2003 N.F.P.A.  14 

• Fire Department connections shall be located not less than 18 inches nor more than 48 inches above the level of the adjoining ground (NFPA 14 sec. 6.3.6). 

• Each standpipe shall be equipped with approved outlet valves which discharge horizontally. They shall be located not less than three feet nor more than five feet above the floor. NFPA 14 sec. 7.3.1

• The recommended height is 42 inches from the finished floor to the center line of the valve.) It shall be placed to provide a minimum clearance of six inches on all sides of the handle and 12 inches on all sides of the threaded outlet. All measurements are to be taken from the finished surface to the handle or outlet

• Connections and outlets shall be placed so that doors or walls do not interfere with the use of the outlet valve.

• Fire Department connections and outlet valves shall have "3" inch National Standard hose threads.

Page 24: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.08 Design Criteria for Installation of Underground Piping for Fire Sprinkler Service

Reference: 2007 C.B.C.  Sec. 903  NFPA  24, 2002 edition, section 10.4.3, requires that the depth of cover for fire service main pipe be not less than 30 inches or one foot below the frost line for the locality. Where frost is not a factor, the 30 inch depth of cover is required to protect the pipe from mechanical damage.  The San Francisco Water Department supplies domestic water meters for all fire services of two-inch and smaller, including combination fire/domestic services. These meters require that the pipe be installed less than the 30 inches required by N.F.P.A.  24.  Due to the practical difficulty of compliance with this standard, all two-inch and smaller fire services, including combination services, shall be allowed to be installed following the criteria listed below which will prevent mechanical damage:1.   All installation of piping shall comply with San Francisco Plumbing Code  section 609.1 which requires a minimum depth of cover of 12 inches below finished grade.  2.   A minimum four inches of concrete shall cover the area above the pipe. The four inch concrete installation shall extend a minimum of 12 inches horizontally on both sides of the pipe.3.   A minimum of three inches of earth shall be maintained between the pipe and concrete. Exception: Pipe and joints that have been coated and wrapped do not have to comply with requirement number 3.

Page 25: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.09 Removal of Class II Standpipe Hose Cabinets in Sprinkler-Retrofitted Buildings

Section 901.8 of the 2007 C.F.C. requires written Fire Marshal approval in order to remove existing fire appliances. In order to speed the permit process, buildings subject to the San Francisco High-rise Sprinkler Ordinance will be permitted to remove Class II Standpipe hose cabinets on individual floors after they have been fully sprinklered. The applicant shall state his or her intention to remove the hose cabinets on the approved sprinkler plans. 

• Buildings not subject to the ordinance will continue to require written Fire Marshal approval in order to remove any fire appliance. These written requests will be considered on a case-by-case basis.

Page 26: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.10 Testing of Fixed Extinguishing Systems

(Standpipes and PRV's)

• Reference: C.A.C.  Title 19, Chapter 5 

• Title 19, California Administrative Code  , includes regulations for Automatic Extinguishing Systems. Chapter 5 contains the criteria and time frames for maintenance and service inspections for all fixed automatic extinguishing systems. 

• Sections 904.2(i) and (j) permit the local Fire Department to require notification prior to any service inspection and also to be sent a report of the results.

• The San Francisco Fire Department shall be notified at least twenty-four (24) hours prior to any servicing of a system. Also, a report of the results of any service inspection shall be forwarded to the San Francisco Fire Department at:

• San Francisco Fire DepartmentBureau of Fire Prevention698 Second StreetSan Francisco, California 94107

Page 27: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.10 Testing of Fixed Extinguishing Systems (Standpipes and PRV's) - continued

• Pressure Reducing Valves-Certification Of• Section 904.4(c)(3) and (d)(3)-Service Regulations for Class III and

Combined Standpipe Hose Outlets state that "Each Hose Valve Outlet shall be inspected in a manner that will indicate the valves are fully operable."

• The primary function of a PRV type hose outlet is to reduce pressures under both flow and no-flow conditions. The only way this pressure reducing feature can be tested and certified as operational is to flow test the valve.

• All PRV type hose outlets shall be flow tested for certification. The following test results and information shall be submitted to the Fire Department for review: valve type or model, valve pressure setting, reduced static pressure, outlet residual pressure flowing 500 g.p.m. for the first standpipe and 250 for each additional standpipe with the pump running at its rated capacity.

• PRV hose valves shall be certified as per the design criteria at the time of their installation.

• Hose valve design criteria for new installations require outlet pressures of 100 to 125 psi residual pressure flowing 250 g.p.m. and 75-100 psi residual pressure when flowing 500 g.p.m. from the roof manifold of the hydraulically remote standpipe and 250 g.p.m. for each additional standpipe. Maximum static pressure must not exceed 150 psi.

• All test results will be reviewed by the San Francisco Fire Department.

Page 28: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

4.20 Design of Fire Pump Suction Piping and Fire

Pump Location• Reference: NFPA  20-2003, Section 5.2.4 

• Design of the fire pump suction pipe must be approved by the Fire Department. As required by NFPA  20, fire pump suction piping from the city main and fire water storage tank to the fire pump suction flange shall be designed and installed to avoid air pockets. For this reason, the location of the fire pump will also be reviewed and approved by the Fire Department before the Site Permit is approved and issued. 

• For new building installations, air pockets in the fire pump suction piping is not allowed. Providing an automatic release valve for the air pockets instead of avoiding air pockets is not acceptable.

• For existing buildings, design of the fire pump suction piping must avoid air pockets. If it is impossible to do so, the Fire Department will review these installations on a case-by-case-basis.

Page 29: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

• 4.23 Combination Fire Services4.23 Combination Fire Services• Reference: 2007C.B.C.  , Sections 903.3.1.5.2,  NFPA  13-

2002,  NFPA  13R-2002  • A.   Combination fire service will be permitted only when the A.   Combination fire service will be permitted only when the

combined sprinkler system and domestic water demand combined sprinkler system and domestic water demand through the meter will not exceed the manufacturers' listed through the meter will not exceed the manufacturers' listed maximum, intermittent delivery rate. The following guidelines maximum, intermittent delivery rate. The following guidelines will be used to comply with this policy:will be used to comply with this policy:

• SPRINKLER SYSTEM DESIGN CRITERIA• Sprinkler systems supplied by the combination fire service Sprinkler systems supplied by the combination fire service

must be hydraulically designed in accordance with must be hydraulically designed in accordance with NFPANFPA  13D,   13D, 13R and/or 13 as required by the  13R and/or 13 as required by the  C.B.C.C.B.C.  , the Department of   , the Department of Building Inspection, and the Fire Department.  Building Inspection, and the Fire Department. 

• The domestic water demand must be included in the sprinkler The domestic water demand must be included in the sprinkler flow at the domestic water system point of connection to the flow at the domestic water system point of connection to the combination fire service line. Domestic water demand shall be combination fire service line. Domestic water demand shall be at least 5 gpm per unit for two dwelling units or less. For three at least 5 gpm per unit for two dwelling units or less. For three or more dwelling units, the domestic demand shall be as or more dwelling units, the domestic demand shall be as estimated using the Tables in estimated using the Tables in NFPANFPA  13R.    13R. 

– The maximum delivery rates for combination fire service The maximum delivery rates for combination fire service are:are:

1 inch service = 50 gpm1 1/2-inch service = 100 gpm2 inch service = 160 gpm

Page 30: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

The meter friction losses to be used in the hydraulic calculations are:

– B.   Combination Fire Service Pipe    – For all sizes, the service line must be copper

(Type K with brazed joints) from the meter to the sprinkler connection to minimize problems of tuberculation.

Service size\flow

25 gpm 50 gpm 75 gpm 100 gpm 150 gpm 160 gpm

1 inch 5 psi 9 psi

1.5 inch 1 psi 3 psi 7 psi 12 psi

2 inch 1 psi 1 psi 3 psi 5 psi 8 psi 12 psi

Page 31: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

•4.24 FDC Requirement for Low-Rise Buildings4.24 FDC Requirement for Low-Rise Buildings

•Reference: NFPA  13   NFPA  14  

•The San Francisco Fire Department may require The San Francisco Fire Department may require more than one FDC in a low-rise building when:more than one FDC in a low-rise building when:

•1)   The building fronts on more than one public 1)   The building fronts on more than one public way.way.

•2)   It has significant floor area where firefighter 2)   It has significant floor area where firefighter response to the seat of the fire may be delayed.response to the seat of the fire may be delayed.

•3)   The adjacent streets or public way 3)   The adjacent streets or public way characteristics may hinder firefighting operations.characteristics may hinder firefighting operations.

– 4)   Deemed necessary for any other reason 4)   Deemed necessary for any other reason by the Fire Department.by the Fire Department.

– FDC locations to be approved by Fire Department.

Page 32: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

Some 2007 CBC new Some 2007 CBC new requirements:requirements:• 1. All buildings with a R-1 (hotels) and R-2 1. All buildings with a R-1 (hotels) and R-2

(apartments) fire area must be sprinklered (apartments) fire area must be sprinklered throughout. Sec. 903.2.7throughout. Sec. 903.2.7

• 2. All valves controlling the water supply 2. All valves controlling the water supply for automatic sprinkler system must be for automatic sprinkler system must be electrically supervised. Sec. 903.4electrically supervised. Sec. 903.4

• 3. Alarm, supervisory, and trouble 3. Alarm, supervisory, and trouble signals……signals……

and automatically transmitted to an and automatically transmitted to an approved central station, remote approved central station, remote supervising or proprietary supervising supervising or proprietary supervising station as defined in NFPA 72. Sec. 903.4.1station as defined in NFPA 72. Sec. 903.4.1

Page 33: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

• 4. Systems with 20 or more sprinklers 4. Systems with 20 or more sprinklers must be must be supervised and monitored by a supervised and monitored by a central central station or equivalent. Sec. 903.4station or equivalent. Sec. 903.4

• 5. All Group ‘A’ occupancies shall be 5. All Group ‘A’ occupancies shall be sprinklered throughout and all the floors sprinklered throughout and all the floors

between the ‘A’ occupancy and the between the ‘A’ occupancy and the level of level of exit discharge. Sec. 903.2.1exit discharge. Sec. 903.2.1

Page 34: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.

SEISMIC BRACING REQUIREMENTSCBC 2007 and NFPA 13-2007SEISMIC BRACING REQUIREMENTSCBC 2007 and NFPA 13-2007

CBC Sec. 1613.1CBC Sec. 1613.1• Design of sprinkler supports and attachments shall be in Design of sprinkler supports and attachments shall be in

accordance with ASCE-7 (American Society of Civil Engineers).accordance with ASCE-7 (American Society of Civil Engineers).• Some exceptions are allowed based on specific criteria.Some exceptions are allowed based on specific criteria.• ASCE Sec. 11.4ASCE Sec. 11.4

Seismic Ground Motion Values (SSeismic Ground Motion Values (SDS or DS or SSD1D1), Occupancy Category ), Occupancy Category values determined by a California registered Engineer.values determined by a California registered Engineer.

• ASCE Sec. 13.6.8.2 and 13.6.8.3ASCE Sec. 13.6.8.2 and 13.6.8.3

Seismic design requirements based on Occupancy CategorySeismic design requirements based on Occupancy Category

Occupancy Category ‘C’ is based on NFPA 13-2007Occupancy Category ‘C’ is based on NFPA 13-2007

Occupancy Category ‘D’, ‘E’, and ‘F’ are required to comply with ASCE 7Occupancy Category ‘D’, ‘E’, and ‘F’ are required to comply with ASCE 7

• Most buildings in San Francisco appear to fall into the D to F Occupancy Most buildings in San Francisco appear to fall into the D to F Occupancy Categories.Categories.

• Categories D to F: ASCE Section 13.6.8.3Categories D to F: ASCE Section 13.6.8.3

Hangers and Bracing designed in accordance with NFPA 13Hangers and Bracing designed in accordance with NFPA 13

Design strength, Force and Displacement calcs. by a Calif. Registered EngineerDesign strength, Force and Displacement calcs. by a Calif. Registered Engineer

• The SFFD will issue an Administrative Bulletin concerning the specific The SFFD will issue an Administrative Bulletin concerning the specific submittal requirements for Fire Sprinkler Seismic Bracingsubmittal requirements for Fire Sprinkler Seismic Bracing

Page 35: Meet the DBI Pros Summit October 12, 2007 WELCOME TO THE AUTOMATIC SPRINKLER SUMMIT PRESENTED BY THE SAN FRANCISCO FIRE DEPARTMENT.