Medium Voltage Motor Control
Transcript of Medium Voltage Motor Control
Medium Voltage Motor Control
Variable Frequency Drive
14 March 2013 2
Variable Frequency Drive: motors
VFD for use with:• Asynchronous motor (squirrel cage induction
motor)• Synchronous motor
– Additional: control of excitation current
• Slip ring induction motor• Slip ring synchronous motor
14 March 2013 3
VFD: Technology / control method
• Standard VFD– Open loop control (VVVF)– Closed loop control– Fans, pumps, compressors
• Vector control VFD– Open loop vector control (sensor-less vector control)– Closed loop vector control– High starting torque; conveyors, kilns, mills, lifts etc.
• Active front end– Open loop vector control– Closed loop vector control– Regenerative applications; bidirectional flow of energy between mains
and motor; e.g. rolling mills
14 March 2013 4
VFD: Range – voltage and power
• Voltage (kV)– 2.3, 3.3, 4.16, 6, 6.6, 10, 11, 13.8; 50 / 60 Hz– Mains and motor voltage need not be the same!
e.g. 13.8 kV mains, 4.16 kV motor, or6.6 kV mains, 11 kV motor
• Power range
VFDs can be applied to a motor of lower kW rating
• Rated ambient temperature: 45 degree C
Voltage 3.3 kV 4.16 kV 6.6 kV 11 kV 13.8 kVMax kW
(HP)3,600
(4800HP)4,600
(6000HP)7,320
(9800HP)12,200
(16000HP)>15,000(20000HP)
14 March 2013 5
VFD: configuration
V I/P pulses O/P level/steps3.3 18 13 (6-0-6)4.2 24 17 (8-0-8)6.6 36 25 (12-0-12)11 54 37 (18-0-18)
14 March 2013 6
VFD: Output waveform
Each power cell has PWM output (L1-L2)L1-L2 output of each cell is connected in series to get MVSeries arrangement of cells provides Multi-level PWM > good for output waveform and input harmonics
14 March 2013 7
VFD: Performance specifications
Input power factor 0.96 or better– No need for PFC capacitors– Happy electricity provider company– No penalty for poor PF, cash saving, happy accountants!
Harmonics reflected on mains very low (< 5% current)– Comply with IEEE 519– Happy electricity provider company and neighbours– Achieved with 18-24-36-54 pulse configuration
High efficiency: 96% or better, including input transformer– Full energy saving potential realized– Low heat loss in cabinets & electric room > reduced heat load for
air-conditioning equipment (e.g. <40 kW for 1 MW drive)– Low net installation cost
14 March 2013 8
VFD: 18+pulse VFD
Extract from a technical paper by WEG
AuCom VFDs offer a minimum of 18-pulse front-end rectification.24 pulse for 4.2 kV36 pulse for 6.6 kV
14 March 2013 9
VFD: Performance specifications
Harmonics reflected on motor very low, <2.5%– Clean output waveform to motor– No de-rating of motor > motor can be used up to its full capacity– Suitable for standard motors and retrofits– No stress on insulation of motor or cables– No output filter necessary– No vibration or stress on bearings– No resonance of the motor– DC component less than 1% > all torque produced is for useful work– Very long motor cable length possible > good for Oil & Gas applications,
where VFD is in safe area but motor & pump is in hazardous area with long cable run.
– PULSE NUMBER DOES NOT IMPACT MOTOR WAVEFORM
14 March 2013 10
VFD: Output waveform to motor
14 March 2013 11
AuCom VFD offers 17 level (8-0-8) for 4.2 kV and 25 level (12-0-12) for 6.6 kV, together with PWM control.This makes the output waveform to motor very sinusoidal.Extract from a technical article by WEG:
VFD: Performance specifications
Voltage-source inverter technology with multi-level PWM control
– Stable, mature and proven technology– VFD design is independent of motor design parameters (as against
with Current source inverters)– Use IGBT as devices for inverter section
• Fine control to achieve near sine-wave• Output short-circuit proof design
– Reliable VFD operationBuilt-in soft startMTBF > 27500 hoursMTTR < 15 minutes
14 March 2013 12
VFD: Dry-type transformer
– Built in with VFD, saves cabling > lower installation cost
– No oil or other fluids > safe environment– Insulation class H (rugged design)– Fan-cooled design– Protection with embedded RTDs– Multi-pulse operation achieved by phase shifted
secondary windings– Secondary windings electrically isolated from
one another– Only power cabling required is from upstream
breaker to VFD, and from VFD to motor– Designed to suit mains and motor voltage
specifications
14 March 2013 13
VFD: Transformer
14 March 2013 14
VFD: Control configuration
14 March 2013 15
VFD: Product construction features
• Conformal coating on PCBs• Surge arrestors• Space heaters in power cell and
transformer cabinets• Viewing windows for mains and motor
cable termination chambers• Lamps for each viewing window to
facilitate viewing• Start and stop push buttons on panel
door• Indication lamps: MV mains ON, VFD
running, VFD fault• RAL 7032
14 March 2013 16
VFD: Control
• Set via HMI, choice of languages – English, Spanish, Portuguese• External analog signal, 4~20 mA
• Output frequency or• Process variable
• Communications bus• Modbus (built-in)• Profibus DP• DeviceNet• TCP / IP
• Start/stop commands can also be from local or remote, independent of location of frequency setting
14 March 2013 17
VFD: Application features
• Open or closed loop control• Open: frequency as per set point• Closed: frequency determined by process variable, such as pressure,
level, temperature etc.• Ride-through, 35% dip without tripping• Auto restart, on recovery of mains supply. VFD checks motor
speed automatically and catches up.• Motor protections built in: Overvoltage, overcurrent, under-
voltage, phase loss, overload, overheat, earth fault, short circuit.• Minor and serious faults. VFD continues to operate with minor
faults
14 March 2013 18
VFD: Application features, optional
• Mains voltage different from motor voltage• External 3-phase 380 V AC control supply
• With “standard” 1-phase 110/220/240 V AC control supply, when the mains supply is OFF, the fans of VFD are also OFF
• With 3-phase 380 V AC control supply, the fans remain operational even when mains supply is off.
• Rotating start, for fan application• Power cell bypass (for 4.16 kV models and above)• VFD bypass (to run the motor at fixed speed if VFD fails)• Input / mains side switchgear• Multi-motor start, with sync transfer function• Master / slave operation, for 2 or more VFDs in tandem
• Soft coupling or hard coupling• PLC for high-end functionality
14 March 2013 19
Panels with VFD bypass system
14 March 2013 20
VFD: Performance features
• Mains voltage tolerance: +15, -20%• Mains frequency tolerance: +/- 10% (output frequency held steady)• Overload (standard): 120%for 120 s (150% for 3 s)• Acceleration / deceleration time: 0~1600 s, programmable• Output frequency range: 0 ~ 120 Hz• Frequency resolution: 0.01 Hz / 0.002 Hz
14 March 2013 21
VFD: Inspecting filters
• Removing filters for inspection is very easy. Just lift and remove. No tools are needed.
• While the filter is removed, safety of personnel is maintained by the mesh in the panel.
14 March 2013 22
VFD: Cell bypass feature (option)
• Allows the application to continue operation with 1 or 2 failed cells
• Failed cells are bypassed automatically, the user process does not see any interruption
• Corresponding cells in other 2 phases are bypassed, to maintain neutral point.
• Failed cells can be replaced with a spare one within minutes, due to draw-out construction of power cell
• Available for VFDs for 4.16 kV and above
14 March 2013 23
VFD: After sales support structure
• Multi-level• Appropriate level comes in to play• Right level of training
1. User’s electrical staff• Trouble shooting, first-aid, essential spares, accurate problem report
2. Service organization in the country• Main responsibility for installation & service, spares
3. Regional service headquarters• Expert advice, spares for the region
4. AuCom, New Zealand• Train the trainers, product & application expertize, spares for business
14 March 2013 24
VFD: Spares and tools
• No special tools needed for installation and maintenance. Tool list:• Screw driver, cross head, large and small• Screw driver, slotted, large and small• Sharp nose pliers• Diagonal cutting snipers• Wrench, size 8~24 (8 pieces)• Ratchet wrench
• Spares:• Power cells• Electronic PCBs• Fans
14 March 2013 25
VFD: Power cells
Power cell L (mm) W (mm) H (mm) Wt (kg) Use690 V/ 048A 425 200 400 20 for 48 A VFD690 V/ 061A 425 200 400 20 for 61 A VFD690 V/ 096A 478 246 400 30 for 77-96 A VFD690 V/ 130A 478 246 400 30 for 130 A VFD690 V/ 192A 508 285 455 36 for 154-173-192 A VFD690 V/ 250A 508 285 455 40 for 220-243 A VFD690 V/ 320A 600 325 530 77 for 304 A VFD690 V/ 400A 600 325 530 80 for 400 A VFD690 V/ 500A 711 503 581 130 for 500 A VFD690 V/ 600A 711 503 581 130 for 600 A VFD690 V/ 800A 711 550 578 154 for 800 A VFD
• VFDs of different voltages use the same power cells – only the quantity of cells used in series per phase changes from one voltage to another.
• For power cells > 250 A, a lifting trolley, as shown, is provided with the VFD.
14 March 2013 26
VFD: Power cells
• We use 690 V rated IGBTs in power cells• On the other hand, many other manufacturers use high-
voltage IGBTs or IGCTs• 690 V IGBTs are used by many LV VFD manufacturers,
hence are available widely and economically.• Therefore, using 690 V rated IGBTs gives the advantage of
reasonably priced spare-parts, while giving the technical advantages discussed earlier.
• When you use an AuCom VFD, you will not have to stretch your maintenance and spares budget!
14 March 2013 27
VFD: conclusion
• AuCom VFD provides a very balanced solution.• AuCom VFD comes with some unique and exciting features,
aimed at providing:• Good technical design• Good return on your investment• Ease of use and maintenance
• Your local supplier will take care of local pre-sales and after-sales service needs.
• Thank you.
14 March 2013 28