Medical Gas Pipeline
-
Upload
ankit-sharma -
Category
Documents
-
view
629 -
download
50
description
Transcript of Medical Gas Pipeline
Dr. Ankit SharmaDept. of Anaesthesia & Intensive
CareDr. B. S. A. Hospital, Rohini,
Central Medical Gas System
IntroductionGases and Vacuum are used in hospitals for
therapeutic purposesThe gases used in hospitals are
Medical GasesOxygenNitrous Oxide
Compressed airVacuum
IntroductionCentralized gas and vacuum supply service
is a modern system of piped supply of medical gases from a central storage area called manifold room to all delivery points in hospital
It provides a very efficient, economical and highly dependable life support service
Makes better patient care in all the areas of hospital
Functions
Supply of right medical gases at right pressure
Supply of compressed air at right pressureSupply of clinical vacuum at right pressure
50 55-psig
-(400-600)mmHg
ComponentsSource of supply: Central supply room with
control equipments and panelsDistribution system: piping Point of use delivery connections: Suitable
station outlet valves and pendantsMonitoring and control equipment and
alarms
Manifold RoomConsists of a cylinder manifold and a
control panelManifold can be of 2 banks of 2 cylinders
each or 2 banks of 20 cylinders eachControl panel: primary and secondary
pressure regulators; warning lampPressure gauges
Manifold RoomPrimary supply Secondary supply when primary supply is
exhaustedPrimary and secondary provides normal operating
supplyWhen operating supply fails, a reserve supply takes
over
Manifold RoomIn case of breakdown of control panel of
oxygen and nitrous oxide, an emergency kit ensures supply of gas through the pipes
Emergency kit comprises a regulator and high pressure tubing to a bulk cylinder and the gas is fed directly to the pipeline through a service outlet
In case the vacuum and air supply system fails, a standby motor-cum-pump is used to provide uninterrupted supply
Manifold RoomHalf of the total daily consumption of oxygen
and nitrous oxide is kept in the manifold room as reserve
Oxygen and nitrous oxide should be stored seperately from flammable gases and liquids
Storage location should be free of combustible materials
If exceeding 2,000 cubic feet storage should be outside the building
Must have generator backup, adequate ventilation, lighting and telephone communication
Control panel
Cylinder banks
NRV & TAILPIPES
PipesShould be seamless type, non-ferrous, non-
arsenic, of high quality copper tubingShould be protected against physical
damage and corrosionExposed oxygen pipelines should not be
installed in areas like kitchen, laundry and rooms where combustible materials are stored
Colour coded as per the gas content
42mm 28mm 15mm
PipesBefore pipes are erected, all pipes, tubes and
fittings should be cleaned thoroughly and washed with tetrachloride
Pipes should be blown clear using oil-free air or nitrogen
When whole system is in place, it should be subjected to a test pressure of 150 psi or 1 ½ times the working pressure for 24 hours to check, if it can withstand the pressure as well as leakages
This test, called pressure lock is done section by section
Terminal unitsGas outlets / vacuum inlet unitsConnected to source equipment through
the distribution systemLocated at actual usage pointOutlets should be gas specific and non-
interchangeableFitted with locking system and non-return
valves
Alarm systemAudio-visualMonitoring of pressureMeant to warn maintenance dept
Location and spaceGround floor in rear part Near maintenance areaSeperate enclosure for full cylinders, empty
cylinders, compressed air, vacuum supplyNo fire hazardCompresor unit in sound proof area
Story of our SystemSystem installed 2003………………functional
2009Repaired ( changed automatic control panel of
oxygen) 2013
Why the panel goes berserk repeatedly
New Automatic control panel
Old pipeline systems without alarm systems or
properly assessed
leakages. No pressure test
done.
Repeated faults in control panel in spite of replacement There is an undetctable leakage in the
pipeline downstream of the main control panelPressures were reset to higher side in order to
overcome the low pressure problems at the outlet (user ends)
Microprocessor is at the risk of damage at higher pressure settings
Solution is not possible before proper alarm systems are installed at recommended points.
Leaky valves can confuse the microprocessor to cause frequent tip-offs. And can damage it.
Key problems & there solutions in our system
Installation company: sevice contract. CMC/AMC• Electrical Backup:
Open system vs closed system
our system is open system hence both banks will open in case of power failure. Pro &
cons Alarm systems audio visual with pressure gauge importance in our current situation
Communication intercom connection and CUG phones Staffing trained technical staff attendants housekeeping Procurement of oxygen cylinders preferably from two different sources ensuring properly filled cylinders with leak free valves
Problems : when the leakage is there; it can
cause malfunction of
the control panel.
Key problems & there solutions in our system
Cylinder reserve. to ensure backup of atleast one day
preferabley 2-3 days.
Currently we have total of 76 cylinders onlyOne bank of 11 cylinders run for avg. 5 hours Approx. 55-60 cylinders/day
Recommendation is to have liquid o2 tank if demand more than one D type cylinder/hour
Reserve falls short of at least 40 cylinders.
Key problems & there solutions in our system
Problems & solutions
Leakage/
partial full
Microprocessor/ natually open
alarms
Outlet leakage
Thank You