MECHANICAL ASPECTS OF MICHIGAN UNIFORM ENERGY CODE MIAM DOHERTY INN 09-5-2011 CLAIRE, MICHIGAN MARK...

26
MECHANICAL ASPECTS OF MECHANICAL ASPECTS OF MICHIGAN UNIFORM MICHIGAN UNIFORM ENERGY CODE ENERGY CODE MIAM DOHERTY INN 09-5-2011 CLAIRE, MICHIGAN MARK RILEY

Transcript of MECHANICAL ASPECTS OF MICHIGAN UNIFORM ENERGY CODE MIAM DOHERTY INN 09-5-2011 CLAIRE, MICHIGAN MARK...

MECHANICAL ASPECTS OF MECHANICAL ASPECTS OF MICHIGAN UNIFORM MICHIGAN UNIFORM ENERGY CODEENERGY CODE

MIAM DOHERTY INN 09-5-2011CLAIRE, MICHIGAN MARK RILEY

PRESENTATION DIVIDED INTO PRESENTATION DIVIDED INTO TWO PARTSTWO PARTS

RESIDENTIAL R-2, R3, R4, Less than 4 stories.

COMMERCIAL – except low rise residential

RESIDENTIAL CODE RESIDENTIAL CODE

Based on chapter 4 0f 2009 International Energy code modified to Michigan Uniform Energy code

MUEC is 36 pages while is 79 pages

Structure of the IECCStructure of the IECC

Chapter 1 AdministrativeChapter 2 DefinitionsChapter 3 Climate ZonesChapter 4 Residential Energy

EfficiencyChapter 5 Commercial Energy

EfficiencyChapter 6 Referenced Standards

401.3 CERTIFICATE401.3 CERTIFICATE

POSTED ON ELECTRICAL PANEL

CAN’T COVER REQUIRED LABELS ON PANEL

LISTS TYPES EFFICIENCIES OF HVAC & HOT WATER HEATER

Table 402.4.2 Table 402.4.2 concernsconcerns

Shafts, Penetrations duct shafts, B Vent must be sealed.

HVAC register boots outside walls and floors over unconitioned areas.

Fireplace walls – Air barrier required.

THIS CODE IS MESSED UPTHIS CODE IS MESSED UP

HOMEWORK WAS NOT DONE ON THIS CODE!

CONFLICT 403.2 – 1601.4.5 item 4

2009 MRC 403.7 REFERENCES

503 -504 DOES NOT EXIST

SECTION 403.4 CIRCULATING HOT WATER SERVICE SYSTEM REFERENCES HVAC EQUIPMENT!

MANDATORY VS. MANDATORY VS. PRESCRIPTIVE SECTION 403 PRESCRIPTIVE SECTION 403

2 METHODS COMPLIANCE

SECTION 403 ONLY REFERENCES 403.2.1 FOR PRESCRIPTIVE

DUCT INSULATION SEE SECTION 405.2

PRESCRIPTIVE CAN ALSO USE TOTAL U/A ALTERNATIVE RESCHECK.

CONTROLS 403.3CONTROLS 403.3

PROGRAMMABLE THERMOSTAT

INITIALLY PROGRAMED

HEAT PUMP SUPPLEMENTARY

Ducts 403.2 – Ducts 403.2 – INSULATION & INSULATION &

SEALINGSEALING

R-8 SUPPLY IN ATTIC ALL OTHER R-6 (CONFLICTS) WITH 2009 MRC)

DUCT SEALING PER MRC M1601.4.1

AIR DUCT TESTING DELETED

PIPE INSULATION 403.3PIPE INSULATION 403.3

403.3 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F or below 55°F shall be insulated to a minimum of R-3.

Exceptions – HVAC equipment & run out piping 4 feet from valve.

PIPE INSULATION 403.4PIPE INSULATION 403.4

Circulating hot water systems (Mandatory). All circulating service hot water piping shall be insulated to at least R-2. Circulating hot water systems shall include an automatic or readily accessible manual switch that can turn off the hot water circulating pump when the system is not in use.

Exception does not make sense.

EXHAUST FAN DAMPERS 403.5 EXHAUST FAN DAMPERS 403.5

EXHAUST FANS EXHAUST FANS REQUIRE REQUIRE BACKDRAFT BACKDRAFT DAMPERSDAMPERS

MOTORIZED OR GRAVITY ALLOWED

EQUIPMENT SIZING 403.6EQUIPMENT SIZING 403.6

Additional requirements for equipment sizing are included by an inspection for compliance with the Michigan Residential Code. M1401.3

SYSTEMS SERVING MULTIPLE SYSTEMS SERVING MULTIPLE RESIDENCES 403.7RESIDENCES 403.7 For systems serving multiple dwelling units

documentation has been submitted demonstrating compliance with 2009 IECC Commercial

Building Mechanical and/or Service Water Heating (Sections 503 and 504).

No code sections in the book!

Swimming Pools:403.9 Heated swimming pools have an

on/off heater switch. Pool heaters operating on natural gas or LPG have an electronic pilot light. Timer switches on pool heaters and pumps are present.

Exceptions: Where public health standards

require continuous pump operation. Where pumps operate within solar- and/or waste-heat-recovery systems.

Heated swimming pools have a cover on or at the water surface. For pools heated over 90 degrees F the cover has a minimum insulation value of R-12.

SIMULATED PERFORMANCE ALTERNATIVE SECTION 405

Mandatory requirements. Compliance with this section

requires that the mandatory provisions identified in Section 401.2 be met.

All supply and return ducts not completelyinside the building thermal envelope shall be insulated to a minimum of R-6.

EnergyPlus Energy Simulation Software

COMMERCIAL ENERGY CODECOMMERCIAL ENERGY CODE

Rule 1087. Rules governing the energy efficiency for the design and construction of buildings and structures, not including residential buildings, shall be those contained in the international energy conservation code, 2009 edition, section 501.1 and the ASHRAE energy standard for buildings except low-rise residential buildings, ANSI/ASHRAE/IESNA standard 90.1-2007 (hereafter the standard), including appendices A, B, C, and D.

ECONOMIZERSECONOMIZERS