Measurement Result Analysis at Chiller JW Marriott · PT. Mitra Kreasi Sejati A perfect solution...
Transcript of Measurement Result Analysis at Chiller JW Marriott · PT. Mitra Kreasi Sejati A perfect solution...
PT. Mitra Kreasi SejatiA perfect solution for efficiency
www.mitra-energy.co.id
Measurement Result Analysisat Chiller JW Marriott
December 15, 2017 - December 19, 2017
1
ChillerVoltage Line - Line
Unbalanced
Voltage = 0,49%
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
2
ChillerCurrent
Unbalanced
Current = 3,7%
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
4
ChillerCosphi
Cosphi is pretty good,
above 0.89 and
average about 0.92
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
5
ChillerTHD i (Harmonis Arus)
Harmonious
Reaches 48%
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
6
ChillerDetail Harmonis Arus -Orde
Harmonic Analysis
1. The 5th and 7th Harmonic domains, the
cause is Inverter
2. There is a Harmonic to 3.9, where the
harmonic in this order will flow into Neutral
resulting in a neutral and inefficient heat cable
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
7
ChillerCurrent Waveform
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
8
ChillerArus VS THD i
There is a 25% harmonic
current at 786 A, so it can
be seen real harmonic
current = 196 A
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
10
ChillerVoltage Waveform
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
11
Result
1. There is Unbalanced Load (3.7%) and Unbalanced Voltage is still below the NEMA
level of 0.49 (NEMA Standard Unbalaced Voltage> 1%)
2. Cosphi Still pretty good that is above 0.89
3. Harmonic The current is quite high, which can reach 48%, and the real Harmonic
current reaches 190 Ampere (SPLN: Harmonic Flow <20%)
4. Harmonic voltage reaches 5.1% (SPLN Harmonic Voltage <5%)
5. Dominant Harmonic at the 5th and 7th Order, this is due to Inverter or Rectifier Usage
load, but in addition there is harmonic to 3 and 9, where the current in this order will
flow to neutral cable
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
12
ChillerAnalisa hasil Pengukuran
Problem Chiller
A high Harmonic of 48% will result in:
Harmoniously affects the capacitor, which
can cause the current in the capacitor to rise
high
Resulting In the heat on the cable, vibrating
in the transformer, and interfere with the
Transformer and the load around the
transformer in the chiller
Solution :
1. Adding Reactor to Capacitor
to protect capacitor from
harmonic current
2. Addition of Active Filter
harmonic (AFH) on Chiller
Charge side
The AFQ solution for this chiller capacity is =
Safety Factor x Real Harmonic Current
Safety factor adjusted to harmonic voltage,
where the harmonic voltage is 5%, so the
safety factor = 1.5
Solution :
1. AFQ = 1,5 x 192 = 288 A
2. The addition of this AFQ will
be guaranteed to reduce the
current harmonic at <5%
Phase
R| INCOMING |
Powe
r
Load
| OUTGOING |
Power Meter
(kWH1)
Power Meter
(kWH2)
PLCPLA
PLOCPLGC
ST
Sensing Transforme
r
CTL has the following functions:
PLC : Programmed Logic ControlPLA : Programmed Logic AnalogPLOC : Programmed Logic Oscilloscope ControlPLGC : Programmed Logic Graphic Control
S
T
N
R
S
T
N
ST ST
Efficiency
10% - 25%
POT Proportional Respon
SP RW Volt HzTHD%
PLN
End-user
Installation scheme and how CTL Enery Saver + works
15
PT. Mitra Kreasi Sejati A perfect solution for efficiency
www.mitra-energy.co.id
THANK YOU!UNTUK INFORMASI DAN KETERANGAN LEBIH LANJUT SILAHKAN MENGHUBUNGI KAMI
KEMBALI
Jalan Jalur Sutra 30D NO.10
Alam Sutra – Serpong Utara
Tangerang Selatan - 15324
021 – 22221561
0878-8883-8339 (24 Hours)
http://www.mitra-energy.co.id
Jalan Ki Hajar Dewantara
Golden 8 blok H/29 Gading Serpong
Tangerang selatan - 15810
021 – 22221561
0878-8883-8339 (24 Hours)
http://www.mitra-energy.co.id