Measurement and Verification of Refrigeration Measures in 4 Grocery Stores in Pacific County
-
Upload
slade-hooper -
Category
Documents
-
view
21 -
download
0
description
Transcript of Measurement and Verification of Refrigeration Measures in 4 Grocery Stores in Pacific County
Measurement and Verification of Refrigeration Measures in 4 Grocery Stores in Pacific County
Presented to the Regional Technical ForumAugust 8th, 2006
Introduction
Review Work to Date with NRM Present Results of M&V for 4 stores in
Pacific County Present recommendations for future
grocery store M&V.
February 7th 2005
RTF reviewed and approved NRM measures and calculation methodology on a pilot basis:
Require 3rd-party M&V on first 10 projects.
Revise credit as indicated after completion of first 10 projects.
March 2005
BPA developed M&V plan for pilot.By BPA Two week pre/post installation electrical
power metering. Pre/post installation review of equipment
and operation.By NRM Detailed pre-installation audit and post
installation data collection.
June 2005 – Pacific County Incentive Offer
Location kWh Savings Cost ($) Incentive Owner's Cost SavingsPayback
(yrs)
Riverdale Grocery 28,570 $9,012 $7,714 $1,802 $1,914 0.9
Ilwaco Marketplace 31,523 $13,391 $8,511 $4,879 $2,112 2.3
Okies Food Center #2 68,139 $23,828 $18,398 $5,431 $4,565 1.2
Pioneer Market & Deli 31,955 $10,406 $8,628 $2,081 $2,141 1.0
Okies Select Market 32,333 $12,012 $8,730 $3,282 $2,166 1.5
Pioneer Market 42,572 $17,341 $11,494 $5,846 $2,852 2.0
Total 235,092 85,989 $63,475 $23,322 $15,751 1.5
July–November 2005 - BPA Baseline Metering
5 stores 10 site visits over 5 months Average 32 man-hours per store in
combined travel and in-store time. Labor Intensive Adds months of time
Baseline Compressor-Condenser Unit Duty Cycle & Run-Time kW Load
Observed NRM*Cooler 52% 53%Freezer 68% 53%
Cooler kW 4.3 4.3Freezer kW 4.6 4.3
* NRM assumes 55% Duty Cycle for units during non-winter months (OSA temp > 35 degrees F), otherwise 35%.
Post-Install Compressor – Condenser Unit Duty Cycle
Observed NRM*Cooler 33% ~42%Freezer 64% ~42%
* NRM assumes 55% Duty Cycle for units during non-winter months (OSA temp > 35 degrees F), otherwise 35%.NRM estimates 3% reduction in compressor-condenser unit duty cycle thru direct digital temp controls. Further reductions in duty cycle estimated by reduced refrigeration load due to ECM motor installations, but not directly specified in % basis.
Reduced Compressor Duty Cycle
Observed NRM*Cooler 19% ~11%Freezer 3% ~11%
* NRM estimates reduction in compressor-condenser unit duty cycles due to combination of measures – direct digital control, evaporator fan cycling, and ECM motor installations. Due to ECM motor installations only in coolers, not freezers, NRM estimated % reductions should be slightly higher for cooler compressor-condenser units compared to freezers [NRM calculations do not directly specify % duty cycle reductions for specific measures, only kWh per year.]
Compressor-Condenser Units per Stores Coolers & Freezers
See Spreadsheet
Note large variance in run-time kW, from low of 1.6 to high of 10.3.
Baseline Door Heater Duty Cycle & Average Connected Load (kW)
Observed NRM*Cooler X 100%Freezer X 100%
Cooler Door (kW) 87 95Freezer Door (kW) 170 195* NRM assumes 100% duty cycle pre-installation. Site visits did not conflict with this
assumption, but note difficulty in metering (CT sizes, access, etc.), as well as a difference in temperature felt and measured at several doors.
Post-Installation Average Door Heater Duty Cycle & Annual kWh per Door Savings
Observed NRM*Cooler 4% 21%Freezer 54% 59%
Cooler Door826 644(kWh/yr Savings)
Freezer Door 822 744(kWh/yr Savings)
Door Heater Control Results per Stores, Coolers & Freezers
See Spreadsheet Cooler Door Heater Control with
average B/C ratio = 2.57 Freezer Door Heater Control with
average B/C ratio = 1.40
Sampling of Baseline Evaporator Fan Connected Load (kW) – Metered to NRM Estimates
Observed (kW) NRM (kW)Bev. Cooler (10) 1.25 1.173Produce Cooler (4) 0.36 0.704Bev. Cooler (10) 1.65 1.955Meat Cooler (3) 0.61 0.528
Misc. Freezer (4) 0.37 0.938Meat Freezer (2) 0.27 0.352Misc. Freezer (3) 0.91 0.587
Post-Installation Average Evaporator Fan Duty Cycling
Observed NRM*Cooler 59% 68.78%Freezer 63% 68.78%
Post-Installation Evaporator Fan % Savings and Fan kWh per Year Savings from Control Measure
Observed NRM*Cooler 41% 31.22%Freezer 37% 31.22%
Cooler Fan 583 444(kWh Savings per Year)
Freezer Fan575 485(kWh Savings per Year)
Evaporator Fan Control Measure Results per Store, Coolers and Freezers
Cooler Units with Average B/C Ratio = 2.74
Freezer Units with Average B/C Ratio = 1.40
See Spreadsheet
New Evaporator Fan ECM Motors Connected Load (kW) – Metered to NRM Estimates
Observed (kW) NRM (kW)*Produce Cooler (4) 0.17 0.4224Bev. Cooler (10) 0.93 1.197
* NRM assumes a 40% reduction in motor load.
Vendor Beverage CoolersObserved Percent kWh Savings
Description % Savings
1 - Two (2) Door Pepsi 20%
2 - Two (2) Door RC 40%
3 - Three (3) Door Pepsi 36%
4 - One (1) Door Pepsi 18%
1 - Two (2) Door Coca Cola 47%
2 - Two (2) Door Unit 50%
3 - Three (3) Door Unit 40%
4 - Misc. 48%
1 - Snapple 18%
Average 35%
Vendor Beverage CoolersSummary
Summary Averaged Results
kWh/yr Savings Cost ($) B / C Ratio
1,023 $320 1.34
ObservedNRM*
% Savings 35% 36%
Store Total Results
Location Total Savings
Total Cost ($) to Implement Measures
Benefit to Cost Ratio (using commercial
refrigeration measure/profile)
Oakie's Food Center #2, Ocean Park
Oakie's Mkt., Naselle
Pioneer Mkt., Long Beach
Pioneer Grocery, South Bend
1.44
0.83
1.52
1.57
$31,835.89
$8,083.59
$10,163.43
$17,312.32
109,737
15,971
36,979
64,821
Pacific County Grocery Stores - Monthly Consumption
0
20000
40000
60000
80000
100000
120000
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Mo
ntl
ly C
On
sum
pti
on
(kW
h)
Okies - Ocean Park
Pioneer Grocery - South Bend
Okies - Naselle
Pioneer Mkt - Long Beach