MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
Transcript of MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 1/19
A 30-01-2012 Issue for Approval B.M.SHIM D.W.SHIN S.H.HYUN
REV. DATE DESCRIPTION DSGN CHKD APPD
PROJECT :
TWO(2) x 500 MW MONG DUONG 1 THERMAL POWER PLANT
EMPLOYER :
CONSULTANT :
CONTRACTOR :
DESIGNED BY DATE TITLE :
B.M.SHIM 30-01-2012CALCULATION
FORGENERATOR TRANSFORMER SIZING
CHECKED BY DATE
D.W.SHIN 30-01-2012
APPROVED BY DATE PROJECT NUMBER DOCUMENT NUMBER REV.
S.H.HYUN 30-01-2012 ADB/MD1-TPIP/EPC150911 MD1-0-E-505-06-00001 A
FOR APPROVAL
APPROVED A
Approved without exception
APPROVED WITH COMMENTS AC
Approved Subject to Incorporation of comments
RETURNED FOR CORRECTION RT
Insufficient Information/ Detail
Resubmit for Approval
REJECTED RJ
Complete redesign required
RECEIVED FOR INFORMATION I
Returned without comments
RECEIVED FOR INFORMATION IC
Returned with comments
any obligations covered under contract
Engineer:
Discipline:
Date:
Note: Approval or comments does not relieve the Contractor of
Pöyry Energy
TWO(2) X 500MW
MONG DUONG 1 THERMAL POWER PLANT
Mark Brooks
Elec
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 2/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA i 30-01-2012
CONTENTS
1.0 PURPOSE ............................................................................................................................... 1
2.0 CODE & STANDARD .......................................................................................................... 1
3.0 SITE CONDITIONS .............................................................................................................. 1
4.0 CALCULATION CRITERIA ............................................................................................... 1
5.0 GIVEN DATA FOR GENERATOR TRANSFORMER SIZING ..................................... 2
6.0 CALCULATION FOR GENERATOR TRANSFORMER SIZING ................................ 2
7.0 DECISION OF GENERATOR TRANSFORMER SIZING ............................................. 3
<ATTACHMENTS>
ATTACHMENT#1 HEAT BALANCE DIAGRAM PRELIMINARY
ATTACHMENT#2 TRANSFORM SIZING CALCULATION
ATTACHMENT#3 LOADING GUIDE FOR OIL IMMERSED POWER TRANSFORMER
ATTACHMENTS:
1. Attachment#1 is the basis for maximum
output however this is still a preliminary
document. This value can only be considered
once the diagrams have been approved.
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 3/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA 1 30-01-2012
1.0 PURPOSE
This calculation is prepared to determine and verify the capacity of generator transformer
(525kV/21kV) for Mong Duong Thermal Power Plant Phase 1 Project in Vietnam .
2.0 CODE & STANDARD
IEC 60076: Power Transformers
3.0 SITE CONDITIONS
The site climatic conditions and the site design conditions are as follows :
a) Absolute minimum air temperature : -0.2℃
b) Absolute maximum air temperature : 39.5 ℃
c) Ambient design temperature : 39.5 ℃
d) Humidity range : 18-92%
4.0 CALCULATION CRITERIA
To calculate transformers sizing, the following points are considered.
a) The load for the Unit Auxiliary Transformer will not be considered.
b) The capacity of generator transformer will be capable for the operating power factor
range of 0.85 lagging to 0.9 leading at the generator terminals.
c) The maximum generator output based on the maximum turbine output(VWO condition)
is considered as follows ;
- Output : 552.955 MW (Refer to Attachment #1)
- Voltage : 21 kV ± 5% , 50 Hz
- Current : 15,202.3 Amperes
- Power Factor : 0.85 Lagging
d) Generator transformer voltage ratings are as follows ;
- High voltage : 525.0 kV WYE with grounded neutral
- Low voltage : 21.0 kV DELTA
e) Generator transformer will be operated at its ODAF rating under most condition.
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 4/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA 2 30-01-2012
5.0 GIVEN DATA FOR GENERATOR TRANSFORMER SIZING
a) The generator will be operated with max. continuous rating 650.535 MVA (552.955
MW at power factor 0.85 lagging).
DescriptionOperating Condition
(Case : VWO) Remark
Ambient Air Temperature 34.5 °C
Refer to Heat
Balance Diagrams
(Attachment #1)
Cooling Water Temperature 30.5 °C
Relative Humidity 85.0 %
Power Factor 0.85 lagging
Power at the Generator Terminal 552.955 MW
b) The generator will be operated in any of the following power factor ranges ;
- Case I : 0.90 P.F Leading
- Case II : 1.0 P.F
- Case III : 0.85 P.F Lagging
6.0 CALCULATION FOR GENERATOR TRANSFORMER SIZING
The generator output based on the maximum turbine output(VWO condition) is calculated asfollows ;
- Power factor 0.90 Leading :
MVA = 552.955 / 0.9 = 614.394 MVA at 39. 5°C amb. temp.
- Power factor 1.0 :
MVA = 552.955 / 1.0 = 552.955 MVA at 39. 5°C amb. temp.
- Power factor 0.85 Lagging :
MVA = 552.955 / 0.85 = 650.535 MVA at 39. 5°C amb. temp.
The capacity of generator transformer will be sized to cover the generator output at the power
factor ranges of 0.85 lagging to 0.9 leading as calculated above and therefore, generator
transformer capacity at 39. 5°C amb. temp should be :
620.538 MVA or above @ 0.90P.F. Leading
558.485 MVA or above @ 1.0P.F.
657.041 MVA or above @ 0.85P.F. Lagging
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 5/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA 3 30-01-2012
The rated capacity of transformer has been selected as 660MVA(based on ODAF) at the
ambient temperature 39.5°C, which has the output capabilities by ambient temperature as
listed below. Also, this capacity will satisfy to have minimum 1% margine for generator
output for all ambient temperature condition as shown in Attachment #2.
Ambient Temperature -0.2°C 34.5°C 39.5°C
Transformer Capacity
[MVA]842.1 682.8 660
* Note) The transformer capacity is calculated as per the loading factor at the different
ambient temperatures. (Refer to the attachment #3, IEC 60354 Loading Guide for Oil-
immersed Power Transformers, 3.3 Normal continuous Loading – Table 6. Acceptable load
factor for continuous duty K24 at different ambient temperatures (ON, OF and OD cooling)).
7.0 DECISION OF GENERATOR TRANSFORMER SIZING
Because the capacity of transformer means a value of input power to transformer, the capacity
of generator transformer should be equal or larger than the output of generator.
Based on the calculation results given above, the capacity of the generator transformer is
selected as below;
660MVA(220MVA x 3), ODAF, 525/21 kV
Z=14.5% @660MVA
On load HV tap changer ±17 x 1.3% taps
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 6/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA 4 30-01-2012
Attachment #1 Heat Balance Diagram preliminary
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 7/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 8/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 9/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 10/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 11/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 12/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 13/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 14/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 15/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA 5 30-01-2012
Attachment #2 Transformer Sizing Calculation
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 16/19
GENERATOR TRANSFORMER SIZING CALCULATION
1. GENERATOR RATING BASED ON 34.5Deg.C 2.TRANSFORMER IMPEDANCE DATA BAS
GEN MVA PF MW %z 14.50%
650.5353 0.85 552.955 X/R RATIO
552.9550 1 552.955 TOLERANCE 7.5%614.3944 0.9 552.955 MARGIN 101%
3.CALCULATION
MW MVAR MVA
GOUT(P) GOUT(Q) TIN(M) TIN(M)*1.01
0.85 552.955 342.7 650.535 657.0406
1 552.955 0.0 552.955 558.4846
0.9 552.955 -267.8 614.394 620.5384
0.85 552.955 342.7 650.535 657.0406
1 552.955 0.0 552.955 558.48460.9 552.955 -267.8 614.394 620.5384
0.85 552.955 342.7 650.535 657.0406
1 552.955 0.0 552.955 558.4846
0.9 552.955 -267.8 614.394 620.5384
34.5 552.955
39.5 552.955
-0.2 552.955
Temp Deg. ℃
Generator Output
MW
GOUT(P)
PF
TR Input(TIN(M)) Considering Margin
(MVA)
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 17/19
MONG DUONG POWER STATION PH.1
Calculation for Generator Transformer Sizing Rev. A
MD1-0-E-505-06-0001_GEN. TR Size_RA 6 30-01-2012
Attachment #3
Loading Guide for Oil-Immersed Power Transformers (IEC 60354)
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 18/19
8/12/2019 MD1-0-E-505!06!00001 Generator Transformer Sizing Calculation
http://slidepdf.com/reader/full/md1-0-e-5050600001-generator-transformer-sizing-calculation 19/19