MCset 2009

84
MCset 17.5 kV Medium Voltage Distribution Air insulated switchboard Withdrawable switchgear SF6 or vacuum technology Catalogue 2009

description

Catalogue

Transcript of MCset 2009

  • MCset 17.5 kV Medium Voltage Distribution

    Air insulated switchboardWithdrawable switchgear SF6 or vacuum technology

    Catalogue2009

  • A new path for achieving your electrical installations

    A comprehensive offer

    The MCset range is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements. All of these products have been designed to work together: electrical, mechanical and communication compatibility.The electrical installation is thus both optimised and has improved performance:@ better service continuity,@ increased personnel and equipment safety,@ guaranteed upgradeability,@ effi cient monitoring and control.You therefore have all the advantages at hand in terms of know-how and creativity for achieving optimised, safe, upgradeable and compliant installations.

    Tools for facilitating the design and installation

    With Schneider Electric, you have a complete range of tools to help you get to know and install the products whilst complying with current standards and good working practices. These tools, technical sheets and guides, design software, training courses, etc are regularly updated.

    For a real partnership with you

    A universal solution doesnt exist because each electrical installation is specifi c. The variety of combinations on offer allows you to truly customise the technical solutions.You are able to express your creativity and put your know-how to best advantage when designing, manufacturing and exploiting an electrical installation.

    Schneider Electric is associating itself with your know-how and your creativity to produce optimised, safe, upgradeable and compliant installations

  • 3DEAI02EN.indd

    MCset 17.5 kV General contents

    Presentation 5

    General 13

    Cubicle description 25

    Protection, monitoring and control 33

    Switchgear 43

    Installation 73

    Appendices 79

    Note: this catalogue replaces the previous version DEAI02EN - 10-2007

  • 4 DEAI02EN.indd

  • 5DEAI02EN.indd

    MCset 17.5 kV Presentation

    MCset, the strength of experience 6The ranges advantages 7MCset, continuity of service and complete safety 8MCset, a comprehensive solution 9Quality - Environment - Maintenance 11A few references 12

  • 6 DEAI02EN.indd

    PE

    5684

    PE

    5745

    0P

    E56

    579

    PE

    5746

    1

    MCset adapts to all electrical power distribution requirements from 1 to 17.5 kV

    MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations.

    MCset offers you:pre-engineered and adaptable solutions tailored to your specific

    requirements,SF6 and vacuum switching technologies,significantly reduced maintenance,local support centres throughout the world.

    MCset gives you the advantages of:continuity of service for your networks,enhanced safety for your staff and operations,optimized investment throughout the life of your installation,the possibility of integrating your medium voltage switchboard

    in a monitoring and control system.

    MCset is present on all power distribution marketsEnergy

    Electric power stations (thermal, nuclear),Auxiliary substations,Source substations.

    IndustryOil & gas,Chemical industry,Paper mills, Metallurgy,Car industry,Mining,Cement plants,

    InfrastructureAirports,Ports,Hospitals,Water treatment,

    Marine and Navy applicationsCruisers,Container ships,Tankers,Offshore platforms, fixed and mobile, LNG (Liquid Natural Gas),Navy,

    b

    v

    v

    v

    v

    b

    v

    v

    v

    v

    bbb

    bbbbbbbb

    bbbbb

    bbbbbbb

    Presentation MCset, the strength of experienceP

    E57

    462

  • 7DEAI02EN.indd

    Presentation The ranges advantagesP

    E56

    386

    MCset is solidly based on extensive experience acquired throughout the world and provides your electrical network with a high level of dependability and safety.MCset integrates a host of innovative solutions designed around proven techniques: high performance switchgear, digital protection, monitoring and control systems, enclosures capable of withstanding internal arcing.MCsets design and experience allow you to benefit from its experience and ensure, now and in the future:

    SafetyOperations are all performed from the front, including access to

    connections and busbars.Racking in and out is only possible with the door closed.The power-on indicator is situated on the front of the functional unit.A earthing switch with making capacity.One single anti-reflex handle is used for all MCset operations.Internal arc withstand developed for all functional units.

    Reduced maintenance and fewer failuresThermal monitoring and temperature rise location.

    ReliabilityType testing was carried out for each performance level in the MCset

    range.The design, manufacturing and testing of MCset was carried out

    according to ISO 9001quality standard.Three-dimensional computer modeling techniques were used to study

    the electrical fields.

    Simplicity A user interface which is easily understood by everybody.Interlocks and padlocks preventing operator errors.Sepam-type protection units enabling on-site information retrieval

    without any additional devices.Maintenance limited to simple, routine operating checks and cleaning

    and greasing every 5 to 10 years.Easy installation due to identical civil engineering dimensions for

    all cubicles and installation being possible against a wall.

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    PE

    5658

    1P

    E90

    006

    PE

    5658

    2

  • 8 DEAI02EN.indd

    PE

    5702

    1P

    E57

    123

    MCset provides the most efficient means to control and protect a wide range of applications.Due to the devices it comprises, MCset can be easily integrated into a monitoring and control system.

    Sepam protection and control unitsSepam series 20, series 40 and series 80 digital protection relays take full advantage of Merlin Gerin experience in electrical network protection.Sepam series 20, series 40 and series 80 provides all the necessary functions:

    effective protection of people and property,accurate measurements and detailed diagnosis,integral equipment control,local or remote indication and operation.

    Easy evolutionAddition of communication, digital I/Os, analog output, or temperature acquisition are possible due to its modular design.

    PowerMeter and Circuit Monitor metering unitsThe PowerLogic PowerMeter replaces a full complement of basic analog meters. This cost effective, high performance meter provides a full complement of accurate true-rms metering values.The PowerLogic series 3000/4000 Circuit Monitor is designed for critical power users and large energy consumers, to provide the information needed to confidently enter the evolving world of deregulation.It can be adapted to meter almost any time-of-use or real-time rate.

    Monitoring and controlMCset can be easily:

    integrated into an existing monitoring and control system:communication between Sepam digital relays and PowerMeter/Circuit Monitor metering devices via a standard protocol (Modbus),

    integrated into a SMS PowerLogic electrical installation monitoring system.

    Thermal diagnosis systemSpecially designed for Schneider Electric MV equipment,this system continuously monitors the temperature rise, using optical fibres and sensors installed at the heart of the sensitive areas.Thermal diagnosis system reduces the probability of failure and reduces maintenance time.

    bbbb

    b

    b

    MT2

    0062

    PE

    5747

    0Presentation MCset, continuity of service

    and complete safety

  • 9DEAI02EN.indd

    PE

    5513

    7

    Sepam

    Sepam

    CM/PM

    TCP/IP over Ethernet

    Front socketHub

    EGX400

    DE

    5749

    2EN

    MCset switchboard

    MCset Transparent Ready optionMCset switchboards integrate Web technologies so that you can find out information about your electrical installation as easy as opening a Web page.All you need is a standard Web browser and a PC connected to your local area network.

    Simple choiceA simple choice between TRe-1 and TRe-2 service levels allows you to easily order your Transparent Ready MCset switchboard.A customized level is also available.Your Transparent Ready MCset switchboard comes equipped with a Web server including Web pages dedicated to power equipment data.

    Easy commissioningTransparent Ready equipment is delivered ready to connect and commission. A Quick Start guide, packaged with your switchboard, provides three easy-to-follow steps.

    Functionalities providedTRe-1 TRe-2

    Instantaneous readingsDisplays automatically updated meter values

    b b

    Circuit summary Displays the RMS current 3-phase average (A),the real power (kW), the power factor, the circuit breaker status (if applicable), etc.

    b b

    Load current summaryDisplays the current RMS value for each phase (A), for all circuits

    b b

    Demand current summaryDisplays the average demand current value for each phase (A), for all circuits

    b b

    Power summaryDisplays the present demand (kW), the peak demand (kW) and the times and dates of the records

    b b

    Energy summary Displays the energy (kWh) the reactive energy (kvarh), and the times and dates of the records

    b b

    Instantaneous readings, all devices Basic historical data logging, energy and trendingDisplays automatically updated meter values for all the communicating devices in the equipment

    b

    Log displaysDisplays data as time curves, or tables

    b

    Export of data tablesAllows data tables to be exported in a standard Windows format

    b

    PE

    5747

    1P

    E57

    472

    PE

    5747

    3

    Presentation MCset, a comprehensive solution

  • 10 DEAI02EN.indd

    Presentation MCset, a comprehensive solution (cont.)

    MT2

    0064

    MT2

    0065

    EN

    Schneider Electric Services, by your sidethroughout the life of your installation

    SpecifyingWe help you to define your solutions: selection guide, technical assistance, advice

    ImplementingWe oversee the completion and commissioning of your installation: design, cost optimization, guaranteed performances and dependability, commissioning tests, etc.

    OperatingWe help run your daily operations in real time: maintenance contract, technical assistance, supply of replacement parts, corrective and preventive maintenance, operation and maintenance training, etc.

    ModernizingWe can bring the performance of your installation up to date:installation audit, switchgear diagnosis, adaptation and modification, end of life recycling, etc.

    Examples of services providedWarranty extensionA warranty extension is proposed if your installation is checked by ourselves before being commissioned.

    Circuit breaker-contactor diagnosisThroughout the life of the equipment, it is possible to carry out routine measurement of its characteristics in order to optimize maintenance. This service may be part of a global installation maintenance contract.

    Help with preventive maintenanceA MCset 1 2 3 Maintenance & Services guide is available and gives the most important general instructions for:

    reducing equipment wear and tear (and/or failure)ensuring that the equipment is safe during all installation, repair and

    servicing operations.In the pages of this guide, all the information needed for:

    operations on: control mechanisms, insulating materials and vents, power circuits, auxiliary circuits.

    recommended frequency according to operating conditions: normal, in a corrosive atmosphere, for naval use.

    End-of-life recyclingSchneider Electric Services has an operational subsidiary allowing you to recycle your medium voltage switchgear.

    bb

    b

    b

    PE

    5745

    1EN

    Modernizing Operating

    Specifying Implementing

  • 11DEAI02EN.indd

    Presentation Quality - Environment - Maintenance

    PE

    5673

    3

    Certi ed quality: ISO 9001 and ISO 9002A major assetIn each of its units, Schneider Electric integrates a functional organization whose main role is to check quality and monitor compliance with standards. This procedure is:

    uniform throughout all departments,recognized by many customers and approved organizations.

    But above all, it is its strict application that has allowed us to obtain the recognition of an independent organization: The French Quality Assurance Association (AFAQ).The quality system for the design and manufacture of MCset is certified to be in conformity with the requirements of ISO 9001 quality assurance standard.

    Strict and systematic checksDuring manufacture, each MCset functional unit is subject to systematic routine testing with the aim of checking the quality and conformity of the following features:

    measuring of opening and closing speeds,measuring of operating torque,dielectric test,testing of safety systems and interlocks,testing of low voltage components,conformity with drawings and diagrams.

    The results obtained are recorded and approved by the quality control department on each devices test certificate.This therefore guarantees product traceability.

    Checking SF6 switchgearsealing test,filling pressure test.Checking vacuum switchgear

    Each vacuum interrupter, sealed and airtight, is checked for the quality of the vacuum obtained. This pressure measurement is based on the proven magnetron discharge method. Using this sophisticated procedure, measurement is very precise and does not require access to the inside of the bulb, thus not affecting the airtight seal.

    Protected environmentSchneider Electric is committed to a long-term environmental approach.All the necessary measures have been taken in conjunction with our services, suppliers and subcontractors to ensure that the materials used in the composition of the MCset equipment do not contain any substances prohibited by the regulations and directives.In order to help you protect the environment and to relieve you of any concerns in terms of stock or dismantling, Schneider Electric Services offers to take back your equipment at the end of its life. MCset has been designed with environmental protection in mind:

    the materials used, insulators and conductors are identified, easily separable and recyclable,

    the SF6 can be recovered at the end of the equipments life and reused after treatment,

    The environmental management system adopted by Schneider Electrics production sites for the manufacture of MCset has been assessed and recognised as conforming to the requirements of the ISO 14001 standard.

    b

    b

    b

    b

    b

    b

    b

    b

    b

    v

    v

    b

    b

    b

    b

    MT5

    5054

    MT5

    5055

    ISO 14001

    MT5

    5145

    10%

    25%

    3%

    62%

    DE

    5746

    0 Copper

    Aluminium

    Plastic

    Steel

  • 12 DEAI02EN.indd

    PE

    5658

    6

    PE

    9000

    9M

    T200

    72P

    E57

    459

    PE

    5746

    0P

    E57

    463

    Presentation A few referencesMCset, a product for all your electrical distribution applications

    Energy and InfrastructureOil and Gasb

    Occidental Mukhaizna LLC OmanQatargas Technip QatarTengiz Chevroil JV KazakhstanAbu Dhabi Oil Refining Company United Arab EmiratesQatar Petroleum QatarONAL GabonSyrian Gas Company SyriaYemen LNG Company YemenTurkmengaz TurkmenistanYemgas Technip YemenAlya Co KazakhstanPazflor (*) Angola

    InfrastructurebItalian Railways Italy

    MarinebFREMM FranceSubsea NorwayZhen Hua Port Machinery ChinaSTX Shipyard KoreaSovcomflot RussiaM.O.L. JapanCPOC MalayaNorvegian Cruise Lines USAConti Rederei GermanyPetropod NorwayTMT TaiwanBritish gas United KingdomMSC ItalyJan de Nul BelgiumNikki Shipping Greece

    Power generationbMoranbah Generation Facility AustraliaSonelgaz AlgeriaEnertherm FranceErgon Energy AustraliaChina Nuclear Power programmes ChinaMount Isa Clark Energy AustraliaLa Termica ItalyAl Fanar Electrical System KSA

    IndustryMining, Minerals & Miningb

    Croesus Mining AustraliaRollestone Coal Pty LTD AustraliaCiment Karadag AzerbaijanArab Union Contracting Company LibyaCiment Lafarge Equator - TurkeyArcelor LuxemburgBHP Billiton AustraliaFord Motor BelgiumOpel RussiaCyristal Chemical Ind. Co. Saudi ArabiaCiment Bastas Turkey

    WaterbIrak Traitement des eaux IrakAlgrienne des eaux Algeria

    BuildingsHotelsb

    Hamilton Island AustraliaAl Bustan Palace Hotel Oman

    Industrial buildings - OfficesbCentral Park Mall of Jeddah KSAEmta Adana Irak

    PE

    9001

    0

  • 13DEAI02EN.indd

    MCset 17.5 kV General

    Description 14Technical characteristics 16Operating conditions 17Protection of people 18Specific applications 19Marine applications 20A range for all functions 22Choice of functional units

  • 14 DEAI02EN.indd

    General Description

    PE

    5746

    7

    Sepam

    Busbars

    Withdrawable part

    Current transformers

    Cablesconnection

    LV control cabinet

    Voltagetransformerscompartment

  • 15DEAI02EN.indd

    General Description (cont.)

    LSC2B (Loss of Service Continuity IEC 62271-200):this category defines the possibility of keeping other compartments energised (in service) when opening a main circuit compartment.

    Make up of an MCset switchboardMCset switchboards are made up of several interconnected functional units.Power connections are made between functional units within a switchboard via a single busbar.The electrical continuity of all metal frames is provided by the connection of each functional units earthing busbar to the switchboards main earthing circuit.Low voltage wiring trays are provided in the switchboard above the low voltage control cabinets.LV cables can enter the switchboard through the top or bottom of each functional unit.

    Description of a functional unitA functional unit comprises all equipment in the main and auxiliary circuits which together provide a protection function. Each functional unit combines all the components which are required to fulfil this function:

    the cubicle,the protection, monitoring and control system,the withdrawable part.

    The cubicleThe cubicle is of LSC2B (Loss of Service Continuity Category) type as defined by IEC standard 62271-200, in other words the medium voltage parts are compartmented using metal partitions (PM class) which are connected to earth and which separate:

    the busbars,the withdrawable part (circuit-breaker, fuse-contactor, disconnector truck or

    earthing truck),MV connections, earthing switch, current sensors and voltage transformers

    as required.MCset guarantees a high level of protection of people; when a compartment containing a main circuit is open, the other compartments and/or functional units may remain energised.The low voltage auxiliaries and monitoring unit are in a control cabinet separated from the medium voltage section.Five basic cubicle layouts are offered:

    incomer or feeder ADline up bussection CL - GLbusbar metering and earthing TTswitch-fuse feeder DI

    AD and CL cubicles have withdrawable vacuum type circuit-breaker and contactor switchgear.

    The protection, monitoring and control systemThis includes:

    Sepam, protection, monitoring and control unit,current sensors, which may be of 3 types,conventional current transformers,low voltage toroid type current transformers,LPCT type current transformers.CSP type broad-range current transformers,voltage transformers,zero sequence core balance current transformers (CSH type).

    The withdrawable partThis includes:

    the circuit-breaker, contactor or the earthing truck with its closing and opening mechanism, or the disconnector truck,

    the lever-type propulsion mechanism for racking in-out,interlocks to fix the withdrawable part on the fixed part either in service position

    or disconnected.

    bbb

    bb

    b

    bbbb

    bbvvvvbb

    b

    bb

  • 16 DEAI02EN.indd

    General Technical characteristicsP

    E57

    468

    IAC (internal arc classification):The metal enclosed switchgear may have different types of accessibility on the various sides of its enclosure. For identify purpose of different sides of the enclosure, the following code shall be used (according to IEC 62271-200 standard):A: restricted access to authorized personnel onlyF: access to the front sideL: access to the lateral sideR: access to the rear side.

    The values below are given for normal operating conditions as defined in IEC 62271-200 and 60694.

    Rated voltage (kV)7.2 12 17.5 (6)

    Rated insulation levelPower frequency withstand voltage 50 Hz - 1 min (r ms kV) 20 28 38Lightning impulse withstand voltage 1.2/50 s (kV peak) 60 75 95Nominal current and maximum short time withstand current (1)Functional unit with circuit breaker

    Short time withstand current

    Ith max. (kA/3 s) 25 25 2531.5 31.5 31.540 40 40

    (kA/3 s) (7) 50 50 50 (6)

    Rated current In max. busbar (A) 4000 4000 4000Rated current In CB (A) 1250 1250 1250

    2500 2500 25003150 3150 31504000 (2) 4000 (2) 4000 (2)

    Functional unit with fuse-contactor (3)

    Short time withstand current

    Ith max. (kA) 50 (4) 50 (4) (5)

    Rated current In max. (A) 250 200 (5)

    Functional unit with switch-fuse (DI cubicle)Short time withstand current

    Ith max. (kA) 50 (4) 50 (4) 31.5 (4)

    Rated current In max. y (A) 200 200 200Internal arc withstand (maximum value)

    (kA/1 s) 50 50 50

    (1) For functional units equipped with circuit breakers or fuse-contactors,the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (2) With fan. (3) Lightning impulse dielectric withstand voltage = 60 kV peak.(4) Limited by fuses.(5) With Rollarc contactor.(6) Limited to 15 kV - 50 kA with Evolis HP circuit breaker. Limited to 17.5 kV - 40 kA with LF circuit breaker.(7) Limited to 1 s for In circuit breaker: 1250 A.

  • 17DEAI02EN.indd

    General Operating conditionsP

    E57

    464 Operating conditions

    Normal operating conditions, according to the IEC International Standards listed below, for indoor switchgear.

    Ambient air temperature:less than or equal to 40C,less than or equal to 35C on average over 24 hours,greater than or equal to 5C.Altitude:less than or equal to 1000 m,above 1000 m, a derating coefficient is applied (please consult us).Atmosphere:no dust, smoke or corrosive or inflammable gas and vapor, or salt

    (clean industrial air).Humidity:average relative humidity over a 24 hour period 95%,average relative humidity over a 1 month period 90%,average vapor pressure over a 24 hour period 2.2 kPa,average vapor pressure over a 1 month period 1.8 kPa.

    Specific operating conditions (please consult us)MCset has been developed to meet the following specific conditions:

    temperature (possible derating),corrosive atmospheres, vibrations, (possible adaptation).

    Storage conditionsIn order to retain all of the functional units qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between 25C and + 55C.

    StandardsThe MCset range meets the following international standards:

    62271-1 : clauses common to high voltage switchgear62271-200 : metal-enclosed switchgear for alternating current at rated voltages

    of between 1 and 52 kVIEC 62271-100 : high voltage alternating current circuit breakersIEC 60470 : high voltage alternating current contactorsIEC 60265-1 : high voltage switchesIEC 60282-2 : high voltage fusesIEC 60271-102 : alternating current disconnectors and earthing switchesIEC 60255 : measurement relay and protection unit for the applicable partsIEC 60044-1 : current transformersIEC 60044-2 : voltage transformersIEC 60044-8 : electronic current transformers (for LPCT).

    bvvvbvvbv

    bvvvv

    bb

    bb

    bbbbbbbbb

  • 18 DEAI02EN.indd

    General Protection of peopleM

    T200

    76

    MCset switchboard with tunnel

    MT2

    0077

    MCset internal arcBasic version (gas exhaust) MCset is designed to eliminate the effects of internal arcing in total safety, due to:

    metal flaps positioned above the enclosure, which in the case of internal fault, limit overpressure in the compartments.

    nonflammable materials used for the cubicle.Internal arc versionMCset is designed to withstand and protect operators in the case of failure due to an internal arc. MCset has been successfully tested using type tests.Protection against internal arcing is available on 25 kA, 31.5 kA, 40 kA and 50 kA ratings.MCset proposes several options to install an internal arc switchboard.

    3-sided internal arc protection For an MCset switchboard fitted against a wall, access to the rear of the cubicle is impossible. Internal arc protection on 3 sides is sufficient.

    4-sided internal arc protectionIn the case of an MCset switchboard installed in the middle of a room, internal arc protection on 4 sides is necessary in order to protect an operator who goes behind the cubicle.

    Installation in a room with limited ceiling height:height exceeding 2.8 m, potential for installing a tunnel above the switchboard to

    prevent reflection of hot gases on the ceiling.Ceiling height Tunnel2.8 m < h < 4 m Mandatoryh > 4 m Not mandatory

    Internal arcing detector MCset has 2 systems that can detect internal arcing and switch off the power supply so as to limit the fault duration.

    electromechanical detectorThis system employs a positive security electromechanical tripping circuit, positioned on the cubicles flap valves. This set transmits the information to the Sepam to give the opening order to the circuit breaker located upstream of the fault.

    optic detector (VAMP system)Internal arcing is detected by optical sensors which will measure the light caused by the initiation of arcing. Based on this information, an electronic module, after processing the information, will give the opening order to the circuit breaker located upstream of the fault.

    Dependable mechanical control devicesAll operations are carried out from the front face, including access to connections and busbars.The user is guided through icon-diagrams on each front panel making it easy to understand the operating sequence and device status.Interlocks and padlocks prevent operator errors.Several additional levels of security also protect operators:

    racking in and out is only possible with the door closed.locking of the MV door open if the LV plug of the circuit breaker is not plug-in.the very extensive set of mechanical and electrical interlocks do not allow operator

    error. These can be added to by key locks or padlocks according to specific operating procedures. Each selector can be fitted with one to three padlocks.

    all operations are carried out from the front face including access to connections and busbars.

    the voltage present indicator is located on the front face of the functional unit, in the immediate vicinity of the earthing switch control.

    disarming of circuit breaker when racking out. This function enables the circuit breaker control springs to be disarmed during the extraction operation.

    locking of withdrawable part/cable compartment. This function disables the possibility of racking the withdrawable part in if the front panel (cable compartment) is not installed.

    b

    b

    b

    b

    bv

    b

    v

    v

    bbb

    b

    b

    b

    b

  • 19DEAI02EN.indd

    General Speci c applicationsP

    E56

    575 Nuclear

    The medium voltage electrical distribution switchgear in a nuclear power station must meet the most stringent requirements. Schneider Electrics experience in this area over more than 30 years is proposed to you via the MCset range. Certified by the chief nuclear standards (IEC, RCCE), MCset provides you with:

    Optimized personal safety,Solidity of electrical and mechanical solutions,Switchgear subjected to various tests:seismic,electrodynamic,switch-off.Panel of compact cubicles.

    Seismic areasMCset meets international seismic specifications. Test procedures follow IEC 60068-3-3 standard.MCset is qualified following the standards:

    UBC 97,IBC 2000,MSK 64,ENDESAEDF HN.20.E53.

    DEP ShellMCset switchboards are certified by Shell n compliance with DEP 33.67.51.31 Gen (July 1998 - updated November 2006) for MV equipments.

    GOST certification (Russia)The GOST certification system applies to most of the products sold and used in Russia.As far as electrical equipment is concerned, this certificate applies when the equipment is used under the following conditions:

    electrical equipment designed for use in an explosive environment and in mines,equipment related to the oil and gas industries: prospecting, exploration, refining,

    transportation, storage,equipment used in the chemical and petrochemical industries and considered

    to be potentially hazardous because it operates in a toxic, explosive and aggressive environment,

    electrical heating equipment used to produce ferrous and non-ferrous metal casting.This certification is drawn up by an organisation external to Schneider Electric from all the product technical documents and must conform to the following Russian standards:

    GOST 2.601-95PB 03-576-03PB 03-584-03.

    The entire MCset range meets the GOST certification requirements.

    bbbvvvb

    bbbbb

    bb

    b

    b

    bbb

  • 20 DEAI02EN.indd

    General Marine applications

    Derived from standard MCset, a Marine version has been developed to meet specific conditions when used on ships or offshore platforms (vibrations/impacts, slant, etc.).This version carries over the electrical and dimensional characteristics of the standard range, adapted to marine requirements:

    metalclad compartmented cubicle (LSC2B type),front access,withdrawable circuit breaker,Sepam protection and control chain,internal arc withstand,thermal diagnosis (optional).

    Environmental conditionsAmbient temperature 5 to +45CHumidity On 24 h 95%

    On 1 month 90%Vibrations(IEC 60068-2-6)

    Frequency range2 to 13.2 Hz 1 mm13.2 to 100 Hz 0.7 g

    MCset Marine certificationsSF6 circuit breaker and contactor Vacuum circuit breakerAmerican Bureau of Shipping (ABS) Bureau VERITAS (BV)Bureau VERITAS (BV) DNV (*)DNV Germanischer LloydGermanischer Lloyd Lloyds RegisterLloyds Register Nippon Kaiji Kyokai (NKK)RINA(*) Consult us.

    bbbbbb

    PE

    9000

    7P

    E57

    453

    PE

    5745

    2

  • 21DEAI02EN.indd

    General Marine applications (cont.)

    Suitable for Naval requirements Internal arcing withstand is ensured by the use of a tunnel specifically designed

    for marine applications. Located above the cubicle, it can evacuate gases due to arcing effects.

    A low voltage control cabinet has also been designed to meet the need for using numerous control and monitoring systems and LV components.

    The cubicles are provided with switchgear employing SF6 or vacuum technology (please consult us).

    The incoming/outgoing feeder cubicles are connected by cables through the bottom. Skids are available on option to group together several cubicles on a platform

    for improved rigidity and to absorb vibrations by means of dampers. They also facilitate handling and installation of the switchboard.

    Motor starter applications: see Motorpact catalogue.MCset is the solution to the specific needs and requirements of a Naval environment:

    Performancesfrom 25 to 50 kA (consult us) Internal arc withstand 1 sCompactness: to meet space constraints (clearance under ceiling) that are

    sometimes indispensable, a specific version is proposed.

    Rated voltage (kV)7.2 12 17.5

    Rated insulation levelPower frequency withstand voltage 50 Hz - 1 min (r ms kV) 20 28 38Lightning impulse withstand voltage 1.2/50 s (kV peak) 60 75 95Nominal current and maximum short time withstand current (1)Functional unit with circuit breaker

    Short time withstand current

    Ith max. (kA/3 s) 25 25 25

    Rated current In max. busbar (A) 3150 3150 3150Rated current In CB (A) 1250 1250 1250

    2500 2500 25003150 3150 3150

    Functional unit with Rollarc fuse-contactor (2)

    Short time withstand current

    Ith max. (kA) 50 (3) 50 (3)

    Rated current In max. (A) 250 200

    Internal arc withstand (maximum value) AFLR(kA/1 s) 25 25 25

    (1) For functional units equipped with circuit breakers or fuse-contactors,the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (2) Lightning impulse dielectric withstand voltage = 60 kV peak.(3) Limited by fuses.

    b

    b

    b

    bb

    b

    bvvb

    2530

    1200

    85

    DE

    5679

    2 Tunnel for internal arcing gasesAuxiliary cable duct

    Higher low voltage control cabinet (640 mm)

    Anti-rolling handle

    Skid (option)

    PE

    5745

    3P

    E57

    458

    PE

    5745

    5

    PE

    5745

    7

  • 22 DEAI02EN.indd

    General A range for all functions Choice of functional units

    Function Incomer (1) Feeder

    Line Transformer Generator Line Transformer Transformer

    Functional unit LI-B TI-B GI-B LF-B TF-B TF-S

    Cubicle AD1-2-3 AD1-2-3 AD1-2-3 AD1-2-3 AD1-2-3 DI 2

    Device Circuit breaker Circuit breaker Circuit breaker Circuit breaker Circuit breaker Fuse-switch

    Sepam protection relayApplications Substation Transformer Generator Substation Transformer TransformerSingle line diagrams

    MT2

    0080

    Sepam

    MT2

    0081

    Sepam

    MT2

    0082

    The MCset range comprises 13 functional applications.The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit.Selection guide:You want to supply power to a transformer.The chosen solution is a transformer feeder/breaker.The corresponding functional unit will therefore be a TF-B, comprising a AD cubicle equipped with a withdrawable circuit breaker, and transformer application Sepam.

    (1) The direct incomer (functional unit without circuit breaker, equipped with a fixed busbar bridge) is produced using cubicles AD1-2-3.(2) Transition cubicle for MCC application (Motorpact).

  • 23DEAI02EN.indd

    General A range for all functions Choice of functional units (cont.)

    Feeder Bussectioning Metering and busbar earthing

    Motorpact transition (2)

    Motor Motor Capacitor Capacitor Switchboard Substation Motor control

    MF-B MF-C CB-B CB-C BS-B SS-B BB-V

    AD1-2-3 AD1C AD1-2-3 AD1C CL1-2-3 and GL1-2-3

    AD1-2-3 TT1-2

    Circuit breaker Fuse contactor Circuit breaker Fuse contactor Circuit breaker Circuit breaker

    Motor Motor Capacitor Capacitor Busbar Substation

    MT2

    0081

    Sepam

    MT2

    0083

    Sepam

    MT2

    0081

    Sepam

    MT2

    0083

    Sepam

    MT2

    0084

    DE

    5507

    6

    MT2

    0078

    DE

    6016

    7

  • 24 DEAI02EN.indd

  • 25DEAI02EN.indd

    MCset 17.5 kV Cubicle description

    AD type cubicles 26Incomer and feeder

    CL - GL type cubicles 27Line-up bussectioning

    TT type cubicles 28Metering Busbar earthing

    DI type cubicles 29Fuse switch feeder

    Motorpact 30Motorpact transition cubicle (MTP)Motor protection and control

  • 26 DEAI02EN.indd

    Cubicle description AD type cubicles Incomer and feeder

    DE

    5677

    5

    DE

    5508

    2

    AD1, AD2, AD3

    Characteristics (for more details, see the pages on the switchgear in question)AD1 AD2 AD3

    Rated voltage (kV) 7.2 12 7.2 12 17.5 7.2 12 17.5Breaking capacity (kA) 25 31.5 50

    (1)25 31.5 50

    (1)40 50 40 25 31.5 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50

    Rated current (A)Evolis circuit breaker

    630 b b b b b b b b1250 b b b b b b b b b2500 b b b b b b b b b

    Evolis HP circuit breaker

    1250 b b (5)

    2500 b b b (5)

    3150 b b b b b b b b b (5) b (5) b (5) b (5)

    4000 (3) b b b (5)

    CTV1 contactor 200 bLF circuit breaker 630 b b b b b b b b b

    1250 b b b b b b b b b b b2500 b b b b b b b b b b b3150 b b b b b b b b b4000 (6) b b b

    Rollarc contactor 200 b b250 b

    Short-circuit making current Ip (kA peak)

    50 Hz 63 79 63 79 100 125 100 63 79 63 79 100 125 63 79 100 125 63 79 100 12560 Hz 65 82 65 82 104 130 104 65 82 65 82 104 130 65 82 104 130 65 82 104 130

    Dimensions (mm) H 2300 2300 2300W 570 700 900D (2) 1550 1550 1550

    Weight (kg) (4) 850 1000 1300

    (1) Limited by fuses.(2) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, for 4000 A or 2 sets of CTs.(3) With fan (consult us).(4) Approximate weight fully equipped cubicle.(5) Limited at 15 kV.(6) With fan.

    1

    7

    2

    54

    6

    3

    MT2

    0080

    Sepam

    MT2

    0081

    D

    H

    W

    MV compartments1 Busbars for cubicle interconnection2 Withdrawable part3 MV connections by cables accessible from the front face4 Earthing switch5 Current sensors6 Voltage transformers (optionally equipped with withdrawable fuses).LV control cabinet7 Low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separated from the medium voltage part.

    DEAI02EN.indd 26DEAI02EN.indd 26 30/04/09 14:50:4530/04/09 14:50:45

  • 27DEAI02EN.indd

    Cubicle description CL - GL type cubicles Line-up bussectioning

    DE

    5748

    9

    DE

    5677

    6

    DE

    5677

    7

    MT2

    0084

    The bussectioning functional unit comprises 2 cubicles mounted side by side (one cubicle equipped with a circuit breaker, the other with a busbar return). CL1, CL2, CL3 GL1, GL2, GL3

    CL1-2-3 or GL1-2-3

    1

    2

    5

    1

    53

    4

    D

    H

    W W D

    Characteristics (for more details, see the pages on the switchgear in question)CL1-GL1 CL2-GL2 CL3-GL3

    Rated voltage (kV) 7.2 12 7.2 12 17.5 7.2 12 17.5Breaking capacity (kA) 25 31.5 25 31.5 40 50 40 25 31.5 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50Rated current (A)Evolis circuit breaker

    630 b b b b b b b b1250 b b b b b b b b b2500 b b b b b b b b b

    Evolis HP circuit breaker

    1250 b b (5)

    2500 b b b (5)

    3150 b b b b b b b b b (5) b (5) b (5) b (5)

    4000 (3) b b b (5)

    LF circuit breaker 630 b b b b b b b b b1250 b b b b b b b b b b b2500 b b b b b b b b b b b3150 b b b b b b b b b4000 (6) b b b

    Short-circuit making current Ip (kA peak)

    50 Hz 63 79 63 79 100 125 100 63 79 63 79 100 125 63 79 100 125 63 79 100 12560 Hz 65 82 65 82 104 130 104 65 82 65 82 104 130 65 82 104 130 65 82 104 130

    Dimensions (mm) H 2300 2300 2300W 570 (x 2) 700 (x 2) 900 (x 2)D (2) 1550 1550 1550

    Weight (kg) (4) 1300 (CL1 + GL1) 1500 (CL2 + GL2) 1700 (CL3 + GL3)

    (2) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, for 4000 A or 2 sets of CTs.(3) With fan (consult us).(4) Approximate weight fully equipped cubicle.(5) Limited at 15 kV.(6) With fan

    MV compartments1 Busbars to connect the bussectioning functional unit with other switchboard functional units2 Withdrawable part3 Current sensors4 Voltage transformers (optionally equipped with withdrawable fuses).LV control cabinet5 Low voltage auxiliaries and protection, monitoring and control unit are in one control cabinet, separated from the medium voltage part.

  • 28 DEAI02EN.indd

    Cubicle description TT type cubiclesMetering Busbar earthing

    DE

    5509

    3

    DE

    5677

    8

    MT2

    0078

    CharacteristicsTT1 TT2

    Rated voltage kV 7.2 12 7.2 12 17.5 (*)Insulation voltage kV r ms 50 Hz - 1 min 20 28 20 28 38

    kV impulse 1.2/50 s 60 75 60 75 95Rated current A 630 b b b b b b(busbar intensity)) 1250 b b b b b b

    2500 b b b b b b3150 b b b b b b4000 (2) b b b b b b

    Short time withstand current kA r ms 3 s 31.5 31.5 50 50 31.5 40Dimensions (mm) H 2300 2300

    W 570 700D (1) 1550 1550

    Weight (kg) 500 550

    (1) Overall + 175 mm for 4-sided internal arcing protected switchboards.(2) With LF circuit breaker only.

    (*) Note: rated voltage 15 kV available for the Evolis HP circuit breaker and for a short-time withstand current of 50 kA rms 3 s.

    TT1-2

    1

    4

    2

    3

    D

    H

    W

    MV compartments1 Busbars to connect the TT functional unit with other switchboard cubicles2 Earthing switch3 Voltage transformers (optionally equipped with withdrawable fuses).LV control cabinet4 Low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separated from the medium voltage part.

  • 29DEAI02EN.indd

    4

    1

    2

    3

    Cubicle description DI type cubicles Fuse switch feeder

    DE

    5509

    8

    DE

    5677

    9

    MT2

    0082

    CharacteristicsDI2

    Rated voltage kV 7.2 12 17.5Insulation voltage kV r ms 50 Hz - 1 min 20 28 38

    kV impulse 1.2/50 s 60 75 95Rated current A 200 b b bShort time withstand current kA r ms 1 s (2) 25 25 25Dimensions (mm) H 2300

    W 700D (1) 1550

    Weight (kg) 750

    (1) Overall + 175 mm for switchboard internal arcing 4 sides.(2) Limited by fuses.

    DI cubicles including a fuse switch are used to supply power and protect low power transformers.E.g.: auxiliary service transformers in primary substations.All operations are carried out from the front face, including access to connections and busbars. All functional interlocks meet recommendations in IEC 62271-200:

    the switch is only possible to close if the earthing switch is open and the connection access panel is in place,

    closing of the earthing switch is only possible if the switch is open, opening of the access panel to medium voltage connections and fuses is only

    possible of the earthing switches upstream and downstream of the fuses are closed,the switch is locked in the open position when the access panel is taken off.

    The voltage presence indicator is situated on the front face of the functional unit, integrated in the switchs control panel.

    b

    bb

    b

    DI2

    D

    H

    W

    MV compartments1 Busbars to connect the DI functional unit with other switchboard cubicles2 Switch - earthing switch3 MV fusesLV control cabinet4 Low voltage auxiliaries and protection, monitoring and control unit are in one control cabinet, separated from the medium voltage part.

  • 30 DEAI02EN.indd

    Cubicle description MotorpactMotor protection and control (MTP)

    DE

    5679

    0

    DE

    5679

    1

    DE

    6016

    7

    Characteristics

    Maximum rated voltage 7.2 kVInsulation voltage

    Power frequency withstand (1 min) 20 kVLightning impulse withstand (1.2/50 s, peak value) 60 kV

    Busbars rating 630 A1250 A2500 A3150 A

    Dimensions H 2300 mmW 375 mmD 1550 mm

    Approximate weight 1250 A 240 kg2500 A 275 kg3150 A 310 kg

    D

    H

    W

    CompositionBasic equipment

    1 enclosure (standard IP3X),1 set of busbars in separate compartment,1 removable front panel.

    OptionsInternal arc withstand,IP4X or IPX1 enclosure,Encapsulated busbars.

    bbb

    bbb

  • 31DEAI02EN.indd

    Cubicle description MotorpactMotor protection and control (cont.)

    PE

    5514

    1P

    E57

    469

    MCset lined up with Motorpact

    Motorpact, an innovative range of motor starters, with vacuum technology contactor Motorpact is a motor monitoring and control switchboard that can be combined with an MCset switchboard by means of a transition cubicle.Main characteristics:

    rated voltage 7.2 kV,maximum busbars rating: 3150 A,rated short time withstand current: 40 kA 3 s,internal arc withstand: 25 kA 1 s

    40 kA 0.5 s 50 kA 0.25 s,

    rated operational current: 400 A,maximum fuse rating: 2 x 250 A.

    Note: for details, see Motorpact catalogue no. AMTED302059.

    Motorpact motor starters provide a wide range of applications including reduced voltage starting:

    FVNR: direct on line motor starter,RVAT: reduced voltage autotransformer motor starter,RVSS: reduced voltage SoftStart motor starter.

    They are suitable for all MV motor applications in markets such as: oil & gas, mining, water, pulp and paper, for starting:

    pumps,fans,compressors,crushers,conveyors, etc.

    CompactnessCompact dimensions thanks to a 375 mm width.Softarter and Autotransfo built into the switchboard.

    SafetyFull cubicle protection for internal arc withstand (AFLR 4 sides).Electrical and mechanical interlocking, closed door operation.Visible insulation by means of portholes.

    ReliabilityFewer components and fasteners.

    Less maintenanceCorrosive atmosphere withstand.Maintenance free disconnector (capacity: 5000 operations).Front access to compartments.

    Characteristics

    Installation Indoor typeMaximum rated voltage 7.2 kV Insulation voltage

    Power frequency withstand (1 min) 20 kV Impulse withstand voltage (1.2/50 s, peak value) 60 kV

    Maximum rated short time withstand current (busbars) 40 kA 3 s 50 kA 2 s*

    Rated frequency 50/60 HzMaximum busbars rating 2500 A

    3150 A*Degree of protection

    Enclosure IP3X, IP4X, IPX1, IPX2Between compartments IP2XC

    * for stand-alone applications or when lined up with LF circuit breaker MCset switchgear

    bbbb

    bb

    bbb

    bbbbb

    bb

    bbb

    b

    bbb

  • 32 DEAI02EN.indd

    Cubicle description MotorpactMotor protection and control (cont.)

    FVNRFull voltage non reversing asynchronous motor starter

    DE

    5708

    6

    SepamM20

    M

    LPCT

    DE

    5679

    3

    DE

    5679

    4

    7

    5

    1

    4

    6

    2

    3

    MV compartment1 Line disconnector 2 Busbars3 Fuses 4 Contactor 5 Earthing switch6 Current sensors LPCT,current transformer and earth fault sensor

    LV control cabinet7 LV protection, measurement and control devices

    RVATAuto-transformer asynchronous motor starter

    DE

    5708

    8

    SepamM41

    M

    LPCT

    DE

    5679

    5

    DE

    5679

    6

    1

    3

    2

    1 Run and start vacuum contactor 2 Busbars3 Auto-transformer

    RVSSSoftstart asynchronous motor starter

    DE

    5709

    0EN

    Sepam

    LPCT

    M

    SoftStartprotectionrelay

    DE

    5679

    7

    DE

    5679

    8

    1

    3

    2

    1 By-pass vacuum contactor 2 Busbars3 SoftStart power stack

    The Motorpact range includes 3 types of motor starter

  • 33DEAI02EN.indd

    MCset 17.5 kV Protection, monitoring and control

    Thermal diagnosis 34Protection system Sepam range 35Sepam series 20, series 40, series 80, Sepam 100 36Sepam series 20, series 40, series 80 37Selection guide

    Instrument transformers 38

  • 34 DEAI02EN.indd

    Protection, monitoring and control

    Thermal diagnosisP

    E90

    039

    DE

    5678

    0

    Thermal diagnosis systemUseTo reduce maintenance costs in MV substations.It continuously monitors temperature rise using optical fibres and sensors installed at the heart of the sensitive areas.The sensors are located on cable connections and on top MV fuse holders.

    PresentationThermal diagnosis is based on the principle of temperature measurement of energized circuits. By using optical fibres, the system doesnt introduce any risks in terms of insulation.It provides:

    permanent monitoring of the temperature rise in power circuits at the connections,tripping of a pre-alarm, then an alarm by activating dry contact outputs,indication of the zone and circuit involved.

    The standard solution is composed of the MDT module and two probes as described hereunder.

    Probes CFO733The optical fibre probes are factory-built assemblies comprising:

    3 sensors attached to the power circuit,the optical connections,a connector linked to the module.

    This connector incorporates the opto-electrical conversion unit thus eliminating any optical connections when assembling.

    MDT106 moduleThe MDT106 electronic module is mounted in the low voltage compartment of the cubicle. It provides the following functions:

    monitoring of temperature rise in 2 zones,triggering of the pre-alarm,triggering of the alarm,self-monitoring of the module,self monitoring of the temperature probes.

    Technical characteristics

    Optical fibre probes CF0733Maximum equipment voltage 17.5 kVRated power frequency voltage 38 kV 1 min - 42 kV 1 minImpulse voltage 95 kVMaximum fibre/sensor temperature 120C

    MDT106 moduleTemperature rise adjustment To be definedPossibility of adjusting the ambient temperature correctionMaximum absolute threshold value Pre-alarm = 115C

    Alarm = 120CMulti9 profile width 10.5 cmModule power 24/250 Vdc, 110/240 VacDry contact Voltage 24, 48, 127, 220 Vdc

    110 to 240 VacCurrent 5 A permanent (pre-alarm)

    8 A permanent (alarm)Consumption (standby-max.) Vdc < 1.2 W (standby) - < 3.4 W (max.)

    Vac < 4.4 VA (standby) - < 6.6 VA (max.)Note:Inspection and test tools and accessories have been developed and approved by Schneider Electric entities and their suppliers. Example: thermal diagnosis test kit. For further information, contact your usual Schneider Electric representative.

    bbb

    bbb

    bbbbb

    Continuity of service is of prime importance for electrical power supplies, particularly.for heavy industries.By using the new thermal diagnosis system developed for MCset, we offer you the possibility of monitoring on an on-going basis, thus reducing the probability of failure and reducing maintenance time.

  • 35DEAI02EN.indd

    Protection, monitoring and control

    Protection system Sepam rangeP

    E57

    021

    DE

    5678

    1Each MCset functional unit can be equipped with a comprehensive protection, monitoring and control system comprising:b instrument transformers (*) to measure the necessary electrical values (phase current, residual current, voltages, etc.)b protection relays, providing functions adapted to the part of the network to be protectedb metering equipment, to inform operatorsb low voltage relaying, i.e. to provide control of the breaking device (contactor and circuit breaker) of the withdrawable partb various auxiliaries: secondary circuit test units, etc.

    (*) Please check in the Sepam catalogue the sensor to use.

    Protection relaysmetering equipment

    Switchgear (circuit breaker and contactor)

    Instrument transformers

    Sepam: protection digital relaysSepam, is a range of digital monitoring protection and control units.Sepam is at the centre of the protection, monitoring and control system for MCset functional units: all the necessary protection, metering, control, monitoring and signalling functions are carried out by Sepam.

    Like the MCset range, the Sepam range is a range of units defined to provide an optimal solution for each application, and includes (eg):

    Sepam S, substation incomer and feeder,Sepam B, bussectioning,Sepam T, transformer feeder,Sepam M, motor feeder,Sepam G, generator feeder,Sepam C, capacitor feeder.

    The Sepam range consists of Sepam series 20, series 40 and series 80, a range of modular protection relays to adapt precisely to your need.

    bbbbbb

    Sepam advantagesReliability

    Over 20 years of experience in multi-function digital protection relays.Over 150,000 Sepam units in service in more than 90 countries.

    QualityQuality design based on dependability studies and strict definition of

    environmental constraints: temperature, pollution, EMC, dielectric strengthQuality manufacturing based on procurement agreements with suppliers

    and inspection throughout all manufacturing phases.Simplicity of use

    Local operation facilitated by the ergonomic User Machine Interface informing the operator fully and clearly in his own language.

    Ease of setup thanks to the flexibility and user-friendliness of the parameters setup software.

    bb

    b

    b

    b

    b

  • 36 DEAI02EN.indd

    PE

    5658

    7

    Sepam 100 MI Sepam 100 LD Sepam 100 LA

    PE

    6011

    6

    PE

    5712

    5

    PE

    5712

    6

    The Sepam range of protection relays is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations at all levels of voltage.It includes 3 families: b Sepam series 20, for usual applications.b Sepam series 40,for demanding applications.b Sepam series 80, for custom applications.To cover all needs, from the simplest to the most complete. Sepam is compliant with IEC 61850 (series 20, 40, 80).

    Protection, monitoring and control

    Sepam series 20, series 40, series 80, Sepam 100

    Sepam multifunction protection relaysA range of solutions adapted to your application

    Substation protection (incomers, feeders, busbars),Transformer protection,Motor and generator protection.

    All of the necessary functions for your application Effective protection of people and property,Accurate measurements and detailed diagnosis,Integral equipment control,Local or remote indication and operation.

    Flexibility and upgrading capabilityTo adapt to as many situations as possible, and allow for future installation upgrading, optional modules may be added to Sepam at any time for new functions.

    bbb

    bbbb

    Sepam series 80 modular architecture1- Base unit, with integrated or remote advanced User Machine Interface.2- Parameter and protection settings saved on removable memory cartridge.3- 42 logic inputs and 23 outputs relays with 3 optional modules providing 14 inputs and 6 outputs.4- 2 independent Modbus communication ports.b Direct connection to 2-wire RS 485, 4-wire RS 485 and fiber optic networks.b Connection to Ethernet TCP/IP network via PowerLogicSystem webserver (Transparent Ready).5- Processing of data from 16 temperature sensors.6- 1 low level analog output, 0-10 mA, 4-20 mA or 0-20 mA.7- Synchro-check module.8- Software tools:b Sepam parameter and protection setting and control logic customization,b local or remote installation operation,b retrieval and display of disturbance recording data.

    Sepam 100 additional unitsSepam 100 units round off the Sepam range and can be installed either separately or combined with either Sepam series 20, series 40 and series 80.Sepam 100 has several variants:

    Sepam 100 MI, local breaking device control and signalling modules (many different line diagram types are available):

    Sepam 100 LD, high impedance differential protection Sepam 100 LA, self-powering protection (back-up protection without auxiliary

    power supply).

    b

    bb

  • 37DEAI02EN.indd

    Protection, monitoring and control

    Sepam series 20, series 40, series 80Selection guide

    Sepam Protections ApplicationsBasic Specific Substation Transformer Motor Generator Busbar Capacitor

    Sepam series 2010 logic inputs8 relay outputs1 communication port8 temperature sensor

    inputs

    bbbb

    DE

    5749

    3 Current protection

    S20 T20 M20

    Breakerfailer

    S23 T23

    DE

    5749

    4 Voltage and frequency protection

    B21

    Loss of mains (ROCOF)

    B22

    Sepam series 4010 logic inputs8 relay outputsLogic equation editor1 communication port 16 temperature sensor

    inputs

    bbbbb

    DE

    5749

    5 Current,voltage and frequency protection

    S40 T40 G40

    Directional earth fault

    S41 M41

    Directional earth fault and phase overcurrent

    S42 T42

    Sepam series 8042 logic inputs23 relay outputsLogic equation editor2 communication ports,

    for multi-master or redundant architecture

    16 temperature sensor inputs

    Removable memory cartridge with parameters and settings for quick commissioning after replacement

    Battery to save disturbance recording and event logging data

    Mimic-based User Machine Interface for safe local equipment control

    Logipam programming software (optional), to program specific functions

    bbbb

    b

    b

    b

    b

    b

    DE

    5749

    6 Current,voltage and frequency protection

    S80 B80

    Directional earth fault

    S81 T81 M81

    Directional earth fault and phase overcurrent

    S82 T82 G82

    Loss of mains (ROCOF)

    S84

    DE

    5749

    7 Transformer or machine transformer- differential

    T87 M88 G88

    Machine differential

    M87 G87

    DE

    5749

    8 Voltage and frequency protection for two sets of busbars

    B83

    DE

    5749

    9 Capacitor bank unbalance

    C86

  • 38 DEAI02EN.indd

    E28

    676

    E74

    399

    E74

    400

    ARJP1, 2 or 3

    ARJA1

    ARO1

    Protection, monitoring and control

    Instrument transformers

    Conventional current transformers Conventional current transformers are used to provide power to metering, measuring or control devices. They measure the value of primary current from 10 A to 3150 A. Schneider Electric has drawn up a list of current transformers which are appropriate for use with digital protection devices in order to make it easier to determine accuracy characteristics. This list is available in the selection guide on page 81.

    For contactor cubicle AD1Transformer ARJP1/N2J

    Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

    bbI1n (A) 10 20 30 50 75 100 150 200 250Ith (kA) 1.2 2.4 3.6 6 10 10 10 10 10t (s) 1 1 1 1 1 1 1 1 1Measuring* Protection*

    cl.0.5 15 VA5P20 2.5 VA

    For cubicles AD1-CL1-GL1-AD2-CL2-GL2Transformer ARJP2/N2J

    Double primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

    bbI1n (A) 50-100 75-150 100-200 150-300 200-400 250-500 600 750Ith (kA) 40 40 31.5-40 40 40 40 50 50t (s) 1 1 1 1 1 1 1 1Measuring* Protection*

    cl.0.5 5-10VA 10-20 VA 7.5-15VA 10-20 VA 20VA 20VA5P20 2.5-5VA 2.5-5VA 2.5-5VA 2.5-5VA 5-10VA 5-10VA 7.5VA 7.5VA

    For cubicles AD1-CL1-GL1-AD2-CL2-GL2Transformer ARJP3/N2J

    Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

    bbI1n (A) 1000 1250Ith (kA) 50 50t (s) 1 1Measuring* Protection*

    cl.0.5 30 VA 30 VA5P20 10 VA 10 VA

    For cubicles AD3-CL3-GL3Transformer ARJA1/N2J

    Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

    bbI1n (A) 1500 2000 2500Ith (kA) 50 50 50t (s) 1 1 1measuring* protection*

    cl.0.5 30 VA 30 VA 30 VA5P20 15 VA 15 VA 15 VA

    For cubicles AD3-CL3-GL3Transformer ARO1a/N3

    Single primary current, triple secondary current for measurement or protectionFrequency 50-60 Hz

    bbI1n (A) 3150Ith (kA) 50t (s) 1Measuring* Protection*

    cl.0.5 30 VA5P20 7.5 VA

    * The secondary current for measuring and protection can be of 1 A or 5 A.

  • 39DEAI02EN.indd

    Protection, monitoring and control

    Instrument transformers (cont.)

    LPCT in cubicle

    LPCTs (Low Power Current Transformers) meet IEC standard IEC 60044-8.These are CTs with a direct voltage output which has the advantage of having a very wide range of applications, simplifying selection.

    LCPT low power current transformers LPCTs are specific current sensors with a direct voltage output of the Low Power Current Transformers type, in conformity with standard IEC 60044-8.LPCTs provide metering and protection functions.They are defined by:

    the rated primary currentthe extended primary currentthe accuracy limit primary current or the accuracy limit factor.

    These have a linear response over a large current range and do not start to saturate until beyond the currents to be broken.

    PE

    5656

    1

    PE

    5656

    3

    CLP1 CLP3

    AD1 - AD1C 630/1250 A b

    AD2 630 A b

    AD3 1250 A b

    2500 A b

    bbb

    Type Primary current Secondary voltage

    Accuracy class

    Accuracy limit factor

    Thermal resistance

    Rated insulation Frequency Secondary connectorrated extended

    (A) (A) (mV)FLP

    (kA - 1 s)Ur(kV)

    Ud(kV - 1 min)

    Up(kV peak) (Hz)

    CLP1 100 1250 22.5 0.5 - 5P 500 50 17.5 38 95 50/60 RJ45 - 8 ptsCLP3 2500 400 40

    PE

    5656

    4

  • 40 DEAI02EN.indd

    Protection, monitoring and control

    Instrument transformers (cont.)E

    7296

    5E

    2867

    8

    Low voltage toroid type current transformersFor cubicles AD1-AD2 with one single-pole cableTransformer ARC2

    Single primary current, single secondary current for protectionFrequency 50-60 Hz

    I1n (A) 75 100 150 200 250 300 400Ith (kA) 50 50 50 50 50 50 50t (s) 1 1 1 1 1 1 1Protection 5P20 2.5 VA 2.5 VA 5 VA 5 VA 5 VA 5 VA 5 VA

    Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

    I1n (A) 200 250 300 400 600Ith (kA) 50 50 50 50 50t (s) 1MeasuringProtection

    5 VA cl.1 10 VA cl.0.5 10 VA cl.0.5 15 VA cl.0.5 15 VA cl.0.55P20 2.5 VA 5 VA 5 VA 5 VA 5 VA

    For cubicles AD1-AD2 with two single-pole cablesTransformer ARC3

    Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

    I1n (A) 750 1000 1250Ith (kA) 50 50 50t (s) 1MeasuringProtection

    cl.0.5 20 VA 30 VA 30 VA5P20 7.5 VA 10 VA 10 VA

    Zero sequence core balance current transformers (CSH type)CSH 120 and CSH 200 core balance CTs, provide more sensitive protection by direct measurement of earth fault currents.Specifically designed for the Sepam range, they can be directly connected to the Sepam residual current input.They are only different in terms of their diameter:

    CSH 120 - 120 mm internal diameter,CSH 200 - 200 mm internal diameter.

    bb

    bb

    bb

    bb

    Zero sequence core balance CT (CSH type)

  • 41DEAI02EN.indd

    Protection, monitoring and control

    Instrument transformers (cont.)E

    2868

    0E

    2867

    9

    VRQ3

    VRC1/S1F

    MT2

    0104

    VRCR

    Voltage transformersThese supply power to:

    measuring, metering and monitoring devices,relays or protective devices,auxiliary LV sources for various types of switchgear; all these devices are protected

    and insulated from the MV section.They are installed at the bottom of the functional unit. In the withdrawable fuse version, the voltage transformers are attached to a side wall. The energized part is entirely encapsulated in an epoxy resin, which provides both electrical insulation and excellent mechanical strength.They include the following models:

    with one insulated MV terminal, for connection between neutral and phase conductors in three-phase systems with withdrawable MV fuses,

    with two insulated MV terminals, for connection between phase conductors.

    For cubicles AD1-CL1-GL1-TT1-AD2-CL2-GL2-AD3-CL3-GL3Transformer VRQ3n/S2

    Phase-earthFrequency 50-60 Hz

    Primary voltage (kV)

    3/3 3.3/3 5.5/3 6/3 6.6/3 10/3 11/3 13.8/3 15/3

    1st secondary voltage (V)

    100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3

    2nd secondary voltage (V)

    100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3

    1st secondary accuracy class (VA)

    30-50 VA cl.0.5

    2nd secondary accuracy class (VA)

    50 VA cl.0.5

    For cubicles AD2-CL2-GL2-TT2-AD3-CL3-GL3Transformer VRC1/S1F

    Phase-phaseFrequency 50-60 Hz

    Primary voltage (kV) 3.3 5.5 6,6 11 13.8 15Secondary voltage (V) 110 110 110 110 110 100Accuracy class (VA) 75 VA cl.0.5

    For cubicle AD1 contactorThis transformer provides power to the coil in order to keep the magnetic circuit of the contactor closed.Transformer VRCR/S1

    Phase-phaseFrequency 50-60 Hz

    Primary voltage (kV) 3.3 5.5 6.6Secondary voltage (V) 110 110 110Accuracy class (VA) 50 VA cl.0.5

    bbb

    b

    b

    bb

    bb

    bb

  • 42 DEAI02EN.indd

  • 43DEAI02EN.indd

    MCset 17.5 kV Switchgear

    Safety and protection of persons and property 44

    Vacuum type switchgearEvolis 17.5 kV circuit breaker 46PresentationCharacteristicsP2 stored energy operating mechanism

    Evolis HP circuit breaker 53PresentationCharacteristicsRI stored energy operating mechanism

    CTV1 contactor 59Presentation Characteristics

    SF6 type switchgearLF circuit breaker 61PresentationCharacteristicsRI stored energy operating mechanism

    Rollarc contactor 67PresentationCharacteristics

    DI switch cubicle 70PresentationCharacteristicsFuses

  • 44 DEAI02EN.indd

    PE

    5746

    5Switchgear Safety and protection of persons

    and property

    Extraction table

    Withdrawable part

  • 45DEAI02EN.indd

    The devices used to equip the MCset range of functional units have outstanding features:

    long service life,maintenance-free live parts,high electrical endurance,operating safety,insensitivity to the environment.

    The withdrawable parts:the circuit breaker or contactor, the disconnector truck or the earthing truck,the lever-type propulsion mechanism for racking in-out,interlocks to fix the withdrawable parts onto the fixed part.

    The live parts are housed in an insulating enclosure in the sealed pressure system in compliance with IEC 62271-100.

    bbbbb

    bbb

    Switchgear Safety and protection of persons and property (cont.)

    6105

    8N Circuit breakerA circuit breaker is a safety device enabling switching and protection of electrical distribution networks. Installed in the MCset cubicle, it protects all components situated downstream during a short-circuit.

    Vacuum breakingEvolisEvolis HPBreaking in SF6LF.

    bvvbv

    6101

    1N ContactorThe contactor is a motor control and protection device.

    Vacuum breakingCTV1Breaking in SF6Rollarc.

    All accidental overpressure would be limited by the safety disk opening.

    bvbv

    DE

    5678

    4 Earthing truck The earthing truck is a safety feature which allows the cubicle busbar to be earthed. It is installed instead of the circuit breaker and has the same interlock possibilities.

    DE

    5678

    5 Disconnector truck The disconnector truck enables the upper and lower part of the cubicle to be short-circuited. It is installed instead of the circuit breaker and has the same interlock possibilities.

  • 46 DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerPresentation

    PE

    5656

    5 PresentationThe Evolis circuit breaker is used to equip AD1-2-3 and CL1-2-3 cubicles for rated values of 7.2kV to 17.5kV.

    High electrical enduranceA magnetic field is applied in the axis of the interrupter contacts.This process maintains the arc in diffuse mode, even at high current values. It ensures optimal distribution of energy over the contact surface and avoids localized temperature rise.The advantages of this technique are:

    a very compact interrupter unit,low dissipation of arc energy in the interrupters.

    Evolis is in conformity with the highest electrical endurance class (IEC 62271-100: class E2).

    High mechanical enduranceThis magnetic field is generated by a patented outside coil which surrounds the contact area. This solution has many advantages:

    a simplified and therefore reliable interrupter unit,heavy duty contacts which do not distort during repeated switching operations.

    For the first time the control mechanism in a low voltage device is being integrated in a medium voltage circuit breaker. The Masterpact control unit used on Evolis gives us the benefit of a system that has proved its value over more than ten years in hundreds of thousands of installations.Evolis is in conformity with the most demanding mechanical endurance class (IEC 62271-100: class M2).

    bb

    bb

  • 47DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerCharacteristics

    Electrical characteristics according to IEC 62271-100Evolis/MCset 1 Evolis/MCset 2

    Phase to phase mm 145 185Rated voltage Ur kV 50/60 Hz 7.2 12 7.2 12 17.5Insulation level- power frequency withstand Ud kV 50 Hz 1 min (*) 20 28 20 28 38- lightning impulse withstand Up kV peak 60 75 60 75 95Rated current Ir A 630 b b b b b b b b b b

    1250 b b b b b b b b b bShort circuit current Isc kA 25 31.5 25 31.5 31.5 40 31.5 40 25 31.5Short time withstand current Ik/tk kA/3 s 25 31.5 25 31.5 31.5 40 31.5 40 25 31.5Short-circuit making current Ip kA peak 50 Hz 63 79 63 79 79 100 79 100 63 79

    60 Hz 65 82 65 82 82 104 82 104 65 82

    Evolis/MCset 3Phase to phase mm 240Rated voltage Ur kV 50/60 Hz 7.2 12 17.5Insulation level- power frequency withstand Ud kV 50 Hz 1 min (*) 20 28 38- lightning impulse withstand Up kV peak 60 75 95Rated current Ir A 630 b b

    1250 b b b2500 b b b b b b b b b

    Short circuit current Isc kA 25 31.5 40 25 31.5 40 25 31.5 40Short time withstand current Ik/tk kA/3 s 25 31.5 40 25 31.5 40 25 31.5 40Short-circuit making current Ip kA peak 50 Hz 63 79 100 63 79 100 63 79 100

    60 Hz 65 82 104 65 82 104 65 82 104

    Characterisitics of Evolis circuit breakers in MCset cubiclesThe electrical characteristics are given on the circuit breaker designation (rating plate).

    Common characteristics according to IEC 62271-100Rated switching sequence O-3 min-CO-3 min-CO b

    O-0.3 s-CO-3 min-CO bO-0.3 s-CO-15 s-CO b

    Operating times Opening < 50 msBreaking < 60 msClosing < 71 ms

    Service temperature T C 25 to + 40Mechanical endurance Class M2

    Number of switching operations

    10 000

    Electrical endurance Class E2Number of switching operations at full Isc value

    25 kA 10031.5 kA 5040 kA 30

    Capacitive current breaking capacity Class C1Average relative humidity Over 24 h < 95%

    Over 1 month < 90%

    (*) Circuit breaker tested at Ud 42 kV 50 Hz, 1 minb Available Not available.

  • 48 DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismPresentation

    PE

    5660

    0 Operation of the P2 stored energy operating mechanismThis mechanism guarantees the device an opening and closing speed unaffected by the operator, for both electric and manual orders. It carries out the O and CO cycles and is automatically recharged by a gear motor after closing. It consists of:

    the stored energy operating mechanism which stores in springs the energy required to open and close the device

    a gear motor electrical charging device with manual charging by lever(useful on loss of auxiliary supply)

    manual order devices by push buttons on the front panel of the device an electrical remote closing device containing a release with an antipumping relayan electrical opening device containing one or more releases, for example:shunt openingUndervoltageMitop, a low consumption release, used only with the Sepam 100 LA

    protection relay.an operation counter a position indication device by mechanical indicator

    and 3 modules of 4 auxiliary contacts whose availability varies according to the diagram used

    a device for indicating charged operating mechanism status by mechanical indicator and electrical contact.

    Wiring diagram (principle)

    b

    b

    bbbvvv

    bb

    b

    DE

    5752

    5EN

    Fault Ready to close

    Auxiliary contacts

    Circuit breaker openOperating mechanism loaded

    Remote control

    OF24OF23OF22OF21OF14OF13OF12OF11OF4OF3OF2OF1

    SDE

    or

    PF

    XF

    MX1

    MX2

    MN

    Mitop Reset

    Charged

    MCH

  • 49DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismOpening circuit

    DE

    5752

    6D

    E57

    527

    Circuit breaker equipped with a shunt opening release (MX)

    Shunt opening release (MX1 and MX2)

    CompositionThe opening circuit is produced using the following components:

    a shunt opening release (MX1)a second shunt opening release (MX2)undervoltage release (MN)time delayed undervoltage release (MNR: MN + time delay).

    The time delay, placed outside the circuit breaker, can be disabled by an emergency stop button to give instant circuit breaker opening.

    low energy release (Mitop).Note: see the table of the releases combinations on the following page.

    Shunt opening release (MX1 and MX2)Energizing this release causes instant opening of the circuit breaker.Permanent power supply to the MX unit locks the circuit breaker in the open position.

    CharacteristicsPower supply V AC 24, 48, 100130, 200250

    V DC 2430, 4860, 100130, 200250Threshold 0.7 to 1.1 UrConsumption (VA or W) Triggering 200 (for 200 ms)

    Latched 4.5

    bbbb

    b

  • 50 DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismOpening circuit (cont.)

    DE

    5752

    7D

    E57

    528

    DE

    5752

    9

    Undervoltage release (MN)

    Undervoltage release (MN)This release unit causes the systematic opening of the circuit breaker when itssupply voltage drops below a value less than 35% of the rated voltage, even if thisdrop is slow and gradual. It can open the circuit breaker between 35% and 70% ofits rated voltage. If the release unit is not supplied power, manual or electrical closingof the circuit breaker is impossible. Closing of the circuit breaker is possible whenthe supply voltage of the release unit reaches 85% of its rated voltage.

    CharacteristicsPower supply V AC 24, 48, 100130, 200250

    V DC 2430, 48 60, 100130, 200250Threshold Opening 0.35 to 0.7 Ur

    Closing 0.85 UrConsumption (VA or W) Triggering 200 (for 200 ms)

    Latched 4.5

    Time delay for MNTo eliminate spurious tripping of the circuit breaker when there are brief voltage drops, the MN action is controlled with a time delay. This function is achieved by adding a time delay unit outside of the undervoltage release (MN) circuit (adjustable time delay).This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening.

    CharacteristicsPower supply V AC 4860, 100130, 200250

    V DC 100130, 200250Threshold Opening 0.35 to 0.7 Ur

    Closing 0.85 UrConsumption (VA or W) Triggering 200 (for 200 ms)

    Latched 4.5Temporisation 0.5 s - 0.9 s - 1.5 s - 3 s

    Low energy release (Mitop)This release includes a low consumption unit and is specifically used with the Sepam 100LA self-powered unit (REFLEX MODULE), or the VIP relay.

    CharacteristicsPower supply Direct currentThreshold 0.6 A < I < 3 A

    Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact, provided with the Mitop. This release also includes a coil (reset) enabling remote SDE contact reset.Comment:Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45-50 ms.

    Releases combinations tableShunt opening MX1 1 1 1 1 1 1Shunt opening MX2 1 1Undervoltage MN 1 1Mitop 1 1 1

    Time delay for undervoltage release (MN)

    Low energy release (Mitop)

  • 51DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismRemote control

    DE

    5752

    7D

    E57

    530

    DE

    5753

    1

    FunctionRemote control enables the remote opening and closing of the circuit breaker. The opening order always takes priority over the closing order.In the event of simultaneous opening and closing orders, the mechanism discharges under no load, without moving the main contacts. The circuit breaker remains in the open position.In the event of latched opening and closing orders, the mechanism carries out anti-pumping function as standard, by blocking the circuit breaker in the open position. Anti-pumping function: after opening on a fault or deliberate opening via the manual or electrical mechanism, the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker.

    CompositionThe remote control comprises:

    an electrical motor (MCH) equipped with a spring armed CH limit switcha shunt closing release (XF).

    Electrical motor (MCH)The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes. This allows instant reclosing of the device after opening. The arming lever is only used as a backup control in the case of the absence of the auxiliary power supply. An electrical motor (MCH) equipped with a spring armed CH limit switch.This contact indicates the armed position of the mechanism (springs armed).

    CharacteristicsPower supply V AC 4860, 100130, 200240

    V DC 24, 2430, 48, 4860 , 100130, 200250Threshold 0.85 to 1.1 UrConsumption (VA or W) 180 Motor overcurrent 2 ot 3 In for 0.1 sArming time 6 s maximumOperating rate 3 cycles maximum per minuteCH contact 10 A/240 V

    Shunt closing release (XF)This release allows remote closing of the circuit breaker when the control mechanism is armed. It can be permanently or briefly supplied power.

    Characteristics XFPower supply V AC 100130, 200250

    V DC 2430, 4860, 100130, 200250Threshold XF 0.85 to 1.1 UrConsumption (VA or W) Triggering 200 (for 200 ms)

    Latched 4.5

    bb

    Shunt closing release (XF)

    Circuit breaker equipped with remote control

    Electrical motor MCH

  • 52 DEAI02EN.indd

    Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismIndication

    DE

    5753

    2D

    E57

    533

    DE

    5753

    4

    Open/closed auxiliary position contacts (OF)These auxiliary contacts indicate the open or closed position of the circuit breaker.

    Rotary type changeover contacts directly controlled by the circuit breaker mechanism.

    Indicator contacts are proposed:for standard relaying applicationsfor low level control applications with plcs or electronic circuits.

    This version is compatible with Sepam series 20-40-80 units.CharacteristicsStandard delivery 4Maximum quantity 12Breaking capacity (A) Standard Min. load: 100 mA/24 VCos : 0.3 V AC 240/380 10/6 *CA12/DC12 480 10/6 *

    690 6V DC 24/48 10/6 *

    125 10/6 *250 3

    Low level Min. load: 2 mA/15 V DCV AC 24/48 6

    240 6380 3

    V DC 24/48 6125 6250 3

    * Standard contacts: 10 A; optional contacts: 6 A (temperature derating)

    Ready to close PF contactThe circuit breaker is ready to close when shown by a mechanical indicator and a PF contact. This information simultaneously indicates that:

    the circuit breaker is openthe storage energy springs are armedthere is no permanent closing orderthere is no permanent opening order caused by:a safety opening order (2nd MX or MN)keylocking of the device in the open position.

    CharacteristicsStandard delivery 0Maximum quantity 1Breaking capacity (A) Standard Min. load: 100 mA/24 VCos : 0.3 V AC 240/380 5CA12/DC12 480 5

    690 3V DC 24/48 3

    125 0.3250 0.15

    Low level Min. load: 2 mA/15 V DCV AC 24/48 3

    240 3380 3

    V DC 24/48 3125 0.3250 0.15

    Operation counter (CDM)The operation counter is visible on the front panel. It totalizes the number of switching cycles (CO) that the device has carried out.

    b

    bvv

    bbbbvv

    Rotary type contacts (OC)

    Ready to close PF contact

    Operation counter (CDM)

  • 53DEAI02EN.indd

    PE

    5657

    0

    Vacuum type switchgear Evolis HP circuit breakerPresentation

    Evolis HP circuit breakers withdrawable version

    Description of the deviceThe basic withdrawable version of the Evolis HP circuit breaker comprises:

    the circuit breaker unit with its operating mechanism:three poles equipped with a vacuum interrupter unit an RI stored energy electrical operating mechanism.

    This gives the device an opening and closing speed that is independent of the operator, for both electrical and manual orders. It enables reclosing cycles to be carried out

    a front panel housing the manual operating mechanism and status indicators.the components enabling it to be withdrawable:the circuit breaker is equipped with racking arms and contact fingers and mounted

    on a racking in/out drive device with a threaded shaft activated by a handle, including all of the safety interlock systems.

    a Harting type male LV connector allows connection of the external auxiliary circuits.Each device can optionally be fitted with:

    locking of the circuit breaker in the following positions:open, by a key lock installed on the control panelracked out, by a key lock installed on the drive device.

    bvv

    vbv

    v

    bvv

  • 54 DEAI02EN.indd

    Vacuum type switchgear Evolis HP circuit breakerCharacteristics

    Electrical characteristics according to IEC 62271-100Evolis HP/MCset 3

    Phase to phase 240Rated voltage Ur kV 50/60 Hz 7.2 12 15Insulation level- power frequency withstand Ud kV 50 Hz 1 min 20 28 38- lightning impulse withstand Up kV peak 60 75 95Rated current Ir A 1250 b (1) b (1)

    2500 b b b3150 b b b b b b b b b b b b4000 (3) b b b

    Short circuit current Isc kA 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50Short time withstand current Ik/tk kA/3 s 25 31.5 40 50 25 31.5 40 50 (1) 25 31.5 40 50 (1)

    Short-circuit making current Ip kA peak 50 Hz 63 79 100 125 63 79 100 125 v60 Hz 65 82 104 130 65 82 104 130 v

    Common characteristics according to IEC 62271-100Rated switching sequence O-3 min-CO-3 min-CO b

    O-0.3 s-CO-3 min-CO bO-0.3 s-CO-15 s-CO b

    Operating times Opening 48Breaking 70Closing 65

    Service temperature T C 5 to + 40 (2)

    Mechanical endurance Class M2Number of switching operations

    10 000

    Electrical endurance Class E2Number of switching operations at full Isc value

    25 kA 10031.5 kA 5040 kA 3050 kA 30

    Capacitive current breaking capacity Class C1Average relative humidity Over 24 h < 95%

    Over 1 month < 90%

    (1) For In 1250 A, the rated short-circuit breaking duration (tk) = 1 s(2) For temperatures lower than - 5 C, consult us(3) With fan.b Available Not available

    Characterisitics of Evolis HP circuit breakers in MCset cubiclesThe electrical characteristics are given on the circuit breaker designation (rating plate).

  • 55DEAI02EN.indd

    PE

    5716

    4

    Vacuum type switchgear Evolis HP circuit breakerRI stored energy operating mechanismPresentation

    Operation of the RI stored energy operating mechanismThis gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual.The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing. It consists of:

    the stored energy operating mechanism which stores in springs the energy required to open and close the device

    a manual lever-operated spring arming devicea geared electrical arming device which automatically re-arms the control

    mechanism as soon as the circuit breaker is closed (optional)manual order devices by push buttons on the front panel of the device an electrical remote closing device containing a release with an antipumping relayan electrical opening order device comprising one or several release units which

    can be of the following type:shunt openingundervoltageMitop, a low consumption release, used only with the Sepam 100 LA

    protection relay.an operation counteran open/closed position indicator device with a mechanical indicator a device for indicating charged operating mechanism status by mechanical

    indicator and electrical contact (optional)a module of 14 auxiliary contacts whose availability varies according

    to the diagram used.

    Wiring diagram (principle)

    b

    bb

    bbb

    vvv

    bbb

    b

    M

    YF +anti-pumping

    Motor Shunt closingrelease+ anti-pumpingsystem

    Remote control

    Shunt openingrelease

    Under-voltagerelease

    Low energyrelease(Mitop)

    NO contacts

    Changeovercontact

    NC contacts

    Close CB

    Open CB

    YM

    M3

    Mitop

    Control mechanism armed indicator contact

    YO1 YO2

    DE

    5761

    1EN

  • 56 DEAI02EN.indd

    DE

    5312

    0D

    E53

    121

    DE

    5312

    2Vacuum type switchgear Evolis HP circuit breaker

    RI stored energy operating mechanismOpening circuit

    DE

    5761

    2EN

    (1) or (3)(2)

    Operating mechanism

    CompositionThe opening circuit can be produced using the following components:

    shunt opening release (on energizing) (YO1)second shunt opening release (on energizing) (YO2)undervoltage release (YM)low energy release (Mitop).

    Note: see the table of the releases combinations page 58.

    Shunt opening release (YO1 and YO2)Energizing this release causes instant opening of the circuit breaker.

    CharacteristicsPower supply V AC (50 Hz) 110, 220

    V AC (60 Hz) 120V DC 24, 48, 110, 125, 220

    Threshold V AC 0.85 to 1.1 UrV DC 0.7 to 1.1 Ur

    Consumption V AC 160 VAV DC 50 W

    Undervoltage release (YM)This release unit causes the systematic opening of the circuit breaker when itssupply voltage drops below a value less than 35% of the rated voltage, even if thisdrop is slow and gradual. It can open the circuit breaker between 35% and 70% ofits rated voltage. If the release unit is not supplied power, manual or electrical closingof the circuit breaker is impossible. Closing of the circuit breaker is possible whenthe supply voltage of the release unit reaches 85% of its rated voltage.

    CharacteristicsPower supply V AC (50 Hz) 110, 220

    V AC (60 Hz) 120V DC 24, 48, 110, 125, 220

    Threshold Opening 0.35 to 0.7 UrClosing 0.85 Ur

    Consumption Triggering V AC 400 VAV DC 100 W

    Latched V AC 100 VAV DC 10 W

    Low energy release (Mitop)This specific release unit comprises a low consumption unit and is specifically used for Sepam 100LA self-powered relays.

    CharacteristicsPower supply Direct current Threshold 0.6 A < I < 3 A

    Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact (option).

    bbbb

    Shunt opening release (1)

    Undervoltage release (2)

    Low energy release (3)

  • 57DEAI02EN.indd

    DE

    5312

    4D

    E53

    125

    DE

    5312

    0

    Vacuum type switchgear Evolis HP circuit breakerRI stored energy operating mechanismRemote control

    DE

    5760

    4

    Operating mechanism

    Electrical motor and gearing (4)

    Shunt closing release (5)

    Operation counter (6)

    FunctionRemote control enables the remote opening and closing of the circuit breaker.

    CompositionThe remote control mechanism comprises:

    an electrical motor with gearing a shunt closing release (YF) combined with an anti-pumping devicean operation counter.

    Electrical motor with gearing (M)The electrical motor carries out the automatic rearming of the stored energy unit as soon as the circuit breaker is closed. This allows the instant reclosing of the