MC61A
-
Upload
alison-foster -
Category
Documents
-
view
219 -
download
0
Transcript of MC61A
-
8/9/2019 MC61A
1/5
THREE PHASE OVER CURRENT +
EARTH FAULT RELAY WITH HIGHSET
TYPE MC61ARelay MC61A is a three phase over current + Earth fault relay with 4 measuring elements.
The relay has built in highest (instantaneous trip) protection, for both over current & earthfault elements. The relay can be used for feeder protection in all low voltage, medium voltage
and high voltage sub-stations. The relay has a front panel 4 digit seven segment LED display
to read various settings, on line values, switch on values, last trip data etc. User has a choice
of 7 trip time characteristics.
TECHNICAL SPECIFICATIONS
1.0 Rated Current In 1A or 5A (Field selectable)
2.0 Rated Frequency 50Hz 2.5 Hz
3.0 Auxiliary Power Supply 24V to 110V AC/DC 15% or
95V to 240V AC/DC 15%4.0 Relay Settings:
Over Current (Is) 0.2 to 2.0 times In, in steps of 0.05In
High set Over Current (Ihs) 0.2 to 40 times In, in steps of 0.2 Inor Disable
Earth Fault (Os) 0.05 to 0.8 times Onin steps of 0.05 On
High set Earth fault (Ohs) 0.1 to 20 times Onin steps of 0.1 Onor Disable
Time Multiplier 0.1 to 1.6 in steps of 0.05 (independent settings for O/C
& E/F modes)
5.0 Operating Characteristics Front panel programmable, using push buttons.
Time /Current Separate characteristics can be selected for O/C &
Characteristics E/F modes.
a) Normal Inverse (NI) 3sb) Normal Inverse (NI) 1.3s
c) Very Inverse (VI)
d) Extremely Inverse (EI)
e) Definite Time (DT) 1s
f) Definite time (DT) 10s
g) Definite time (DT) 100s
..2
-2-
Three Phase Over current
Earth Fault
Highset Over current
Higset earth fault
Inverse & Definite time trip Characteristics4 digit display
CT secondary 1A / 5a field selectable
50 / 51, 50N/ 51N
-
8/9/2019 MC61A
2/5
High set operating time Less than 50 millisecond at 2 Ihs
Accuracy As per Error class 5 of IS: 3231: 1987
Pick up current Same as set current
Reset Current 95% to 90% of pick up current
Reset time 0.1 to 10sec in steps of 0.1 sec or less than 50 ms
6.0 Burden Less than 0.25 VA/ phase at CT inputs
Less than 10 VA at Auxiliary Power supply
7.0 Operation Indicators Separate LED indications for:
Power on
Trip status for R, Y, B & E
(These LEDs blink when input crosses set point and
become steady on when relay has tripped. LEDs
have to be manually reset)
4 digits, seven segment LEDs for parameter display
8.0 Output Relay Contacts 4 contacts for trip signal on feeder faults
(One version with 2N/O + 2 N/C and
Other version with 4 N/O).
1 N/C contact for internal relay fault9.0 Output contact rating
Rated voltage 250 V AC / 30 V DC
Rated current 5A
Rated Breaking Capacity 2000VA / 240 W (Resistive)
10.0 Over Load capacity 2 times rated current continuously
20 times rated current for 1 sec
11.0 Electrical performance Please refer separate document
Specifications General Electrical Characteristics
12.0 Case
Front Bezel 158 x 136 mm
Panel Cutout 142 x 113 mm
Depth 204 mm13.0 Weight 1.5 kG approx.
3
-3-
-
8/9/2019 MC61A
3/5
.4
-
8/9/2019 MC61A
4/5
-4-
.5
-
8/9/2019 MC61A
5/5
-5-
CATALOG NOs.
MC61AAXX000
MC61AAXX001
MC61ABXX000
MC61ABXX001
ORDERING INFORMATION :
1) Auxiliary Power supply Type A or Type B
2) Contact configuration 4 N/O or 2 N/0 + 2 N/C
6 1 A AC X XM 0 0 0
Contact Configuration
0 = 4 N/O
1 = 2 N/O + 2 N/C
Aux. Power supply
A = 24 to 110 V AC/DC 10%
B = 110 to 240 V AC/DC 10%