GE Oil & Gas Masoneilan * SVI * FF Digital Positioner Quick Start Guide (Rev. D) GE Data Classification: Public

Transcript of Masoneilan* SVI* FF Digital Positioner - Baker Hughes...The SVI FF digital valve positioner is...

  • GE Oil & Gas

    Masoneilan* SVI* FF Digital PositionerQuick Start Guide(Rev. D)

    GE Data Classification: Public

  • About this GuideThis instruction manual applies to the following instruments and approved software:SVI FF

    with Firmware version 1.0.0.1 or higher

    with ValVue* version 3.0

    with handheld communicator with DD published for SVI FF

    All information contained herein is believed to be accurate at the time of publication and is subject to change without notice. The information contained in this manual, in whole or part, shall not be transcribed or copied without GE Oil & Gas’ written permission.In no case does this manual guarantee the merchantability of the positioner or the software or its adapt-ability to a specific client needs.Please report any errors or questions about the information in this manual to your local supplier or visit www.geoilandgas.com/valves.

    DISCLAIMERTHESE INSTRUCTIONS PROVIDE THE CUSTOMER/OPERATOR WITH IMPORTANT PROJECT-SPECIFIC REF-ERENCE INFORMATION IN ADDITION TO THE CUSTOMER/OPERATOR’S NORMAL OPERATION AND MAIN-TENANCE PROCEDURES. SINCE OPERATION AND MAINTENANCE PHILOSOPHIES VARY, GE (GENERAL ELECTRIC COMPANY AND ITS SUBSIDIARIES AND AFFILIATES) DOES NOT ATTEMPT TO DICTATE SPECIFIC PROCEDURES, BUT TO PROVIDE BASIC LIMITATIONS AND REQUIREMENTS CREATED BY THE TYPE OF EQUIPMENT PROVIDED.THESE INSTRUCTIONS ASSUME THAT OPERATORS ALREADY HAVE A GENERAL UNDERSTANDING OF THE REQUIREMENTS FOR SAFE OPERATION OF MECHANICAL AND ELECTRICAL EQUIPMENT IN POTENTIALLY HAZARDOUS ENVIRONMENTS. THEREFORE, THESE INSTRUCTIONS SHOULD BE INTERPRETED AND APPLIED IN CONJUNCTION WITH THE SAFETY RULES AND REGULATIONS APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE.THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERA-TION OR MAINTENANCE. SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROB-LEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE CUSTOMER/OPERATOR'S PURPOSES THE MATTER SHOULD BE REFERRED TO GE.THE RIGHTS, OBLIGATIONS AND LIABILITIES OF GE AND THE CUSTOMER/OPERATOR ARE STRICTLY LIM-ITED TO THOSE EXPRESSLY PROVIDED IN THE CONTRACT RELATING TO THE SUPPLY OF THE EQUIPMENT. NO ADDITIONAL REPRESENTATIONS OR WARRANTIES BY GE REGARDING THE EQUIPMENT OR ITS USE ARE GIVEN OR IMPLIED BY THE ISSUE OF THESE INSTRUCTIONS.THESE INSTRUCTIONS CONTAIN PROPRIETARY INFORMATION OF GE, AND ARE FURNISHED TO THE CUS-TOMER/OPERATOR SOLELY TO ASSIST IN THE INSTALLATION, TESTING, OPERATION, AND/OR MAINTE-NANCE OF THE EQUIPMENT DESCRIBED. THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART NOR SHALL ITS CONTENTS BE DISCLOSED TO ANY THIRD PARTY WITHOUT THE WRITTEN APPROVAL OF GE.

    CopyrightCopyright 2017 by GE Oil & Gas. All rights reserved. PN 720023977-888-0000 Rev. D.

    © 2017 General Electric Company. All rights reserved.2 | =GE Oil & Gas

  • Document Changes

    Version/Date Changes

    B/12-14 Updated headers and footers.Made a few changes to Quick Start sectionChanged ES-776 to Rev J.

    C/02-15 Changed ES-776 to Rev. K and to Declaration of Conformity

    D/03-17 Changed ES-776 to Rev. L.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 3

  • This page intentionally left blank.

  • 1. SVI FF Quick Start

    Safety Information

    Safety Symbols

    Indicates a potentially hazardous situation, which if not avoided could result in serious injury or death.

    Indicates a potentially hazardous situation, which if not avoided could result in instrument or property damage, or data loss.

    Indicates important facts and conditions.

    WARNING

    CAUTION

    NOTE

    Masoneilan SVI FF Positioner Quick Start Guide =| 5© 2017 General Electric Company. All rights reserved.

  • SVI FF Product Safety

    The SVI FF digital valve positioner is intended for use with industrial compressed air or, natural gas systems only.

    Ensure that an adequate pressure relief provision is installed when the application of system supply pressure could cause peripheral equipment to malfunction. Installation must be in accor-dance with local and national compressed air and instrumentation codes.

    General installation, maintenance or replacement

    Products must be installed in compliance with all local and national codes and standards by qualified personnel using safe site work practices. Personal Protective Equipment (PPE) must be used per safe site work practices.

    Ensure proper use of fall protection when working at heights, per safe site work practices. Use appropriate safety equipment and practices to prevent the dropping of tools or equipment during installation.

    Under normal operation, compressed supply gas is vented from the SVI FF to the surrounding area, and may require additional precautions or specialized installations.

    Intrinsically Safe Installation

    Products certified as explosion proof or flame proof equipment or for use in intrinsically safe in-stallations MUST BE:

    Installed, put into service, used and maintained in compliance with national and local regulations and in accordance with the recommendations contained in the relevant standards concerning potentially explosive atmospheres.

    Used only in situations that comply with the certification conditions shown in this document and after verification of their compatibility with the zone of intended use and the permitted maximum ambient temperature.

    Installed, put into service and maintained by qualified and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmospheres.

    Installations using natural gas are Zone 0 or Div 1 installations.

    NOTE

    © 2017 General Electric Company. All rights reserved.6 | =GE Oil & Gas

  • WARNING Before using these products with fluids/compressed gases other than air or for non-industrial applications, consult the factory. This product is not intended for use in life support systems.

    WARNING Under certain operating conditions, the use of damaged instruments could cause a degradation of the performance of the system which may lead to personal injury or death.

    Installation in poorly ventilated confined areas, with any potential of gases other than oxygen being present, can lead to a risk of personnel asphyxiation.

    Use only genuine replacement parts which are provided by the manufacturer, to guarantee that the products comply with the essential safety requirements of the European Directives.

    Changes to specifications, structure, and components used may not lead to the revision of this manual unless such changes affect the function and performance of the product.

    Product Numbering

    See the ES document in “ES-776 and Declaration of Conformity” on page 17.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 7

  • Installation and Set UpThe steps necessary to complete the SVI FF installation and software setup are outlined in Table 1.

    Table 1: SVI FF Installation Steps

    Step No. Procedure

    1 Attach mounting bracket to the actuator.

    2 Install the SVI FF magnetic assembly (rotary valves only).

    3 Assemble the SVI FF on the bracket that is mounted to the valve actuator.

    4 Connect the pneumatic tubing to the SVI FF.

    5 Connect the air supply to the SVI FF.

    6 Connect the positioner to the H1 segment by installing the SVI FF wiring.

    7 Configure/calibrate using ValVue, the SVI FF DTM or a handheld using the DD. See“Example Configuration” on page 13 for a general example.

    WARNING Failure to adhere to the requirements listed may cause loss of life and property.

    Before installing, using, or carrying out any maintenance tasks associated with this instrument, READ ALL THE INSTRUCTIONS CAREFULLY.

    © 2017 General Electric Company. All rights reserved.8 | =GE Oil & Gas

  • Pushbuttons and Local Display

    Pushbuttons

    The local pushbuttons are located behind a hinged cover, directly below the display window. To open the cover loosen the screw and swing the cover down. Always re-fasten the cover after use to protect the pushbuttons from environmental contamination.

    The three pushbuttons perform the following functions:

    Left Button - Marked with *, permits you to select or accept the value or parameter option currently displayed.

    Middle Button - Marked –, permits you to move back through the menu structure to the previous item in the menu or decrement the value currently shown in the digital display. When used to decrease a displayed value, holding the button down causes the value to decrease at a faster rate.

    Right Button - Marked +, permits you to move forward through the menu structure to the next item in the menu, or to increment the value currently shown in the digital display. When used to increase a displayed value, holding this button down causes the value to increase at a faster rate.

    CAUTION The display is limited to values between 0 and 100. Therefore, the display may show a value for the actual setpoint that is not valid if the setpoint is above 100 or below 0.

    NOTE When an exclamation point (!) appears in the SVI FF display window, it indicates that there is instrument status available.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 9

  • Mounting the SVI FF on Rotary Valves

    Travel Sensor Alignment

    Table 2 shows the general guidelines for travel sensor alignment. Review the table prior to in-stalling the SVI FF on a rotary valve actuator for proper alignment of the magnet. Alignment is required for proper Hall sensor operation.

    Table 2: Travel Sensor Alignment

    Rotary Mounting

    System

    Stroke Direction Magnet Orientation

    Valve Position

    Sensor Counts (TB: RAW_POSITION)

    Rotary 60° RotationClockwise with increas-ing setpoint

    (-45°)

    Full Open or Full Closed

    -8000 +/- 1500 or+8000 +/- 1500

    >60° RotationCounter Clockwise rota-tion with increasing set-point

    (+45°)

    Full Open or Full Closed

    -8000 +/- 1500 or+8000 +/- 1500

    General Rule for other configura-tions

    Any amount of rotation Clockwise or counter-clockwise

    (0°)

    50% Travel(Mid-Stroke)

    0 +/- 1000

    © 2017 General Electric Company. All rights reserved.10 | =GE Oil & Gas

  • Mounting the SVI FF on Reciprocating Valves

    Table 3: Reciprocating Valve Mounting Hole and Turnbuckle Length

    Actuator SizeMasoneilan

    Stroke Mounting Hole

    Lever Hole Turnbuckle Length

    6 and 10 0.5 - 0.8" (12.7 - 20.32 mm)

    A A 1.25" (31.75 mm)

    10 0.5 - 0.8"(12.7 - 20.32 mm)

    A A 1.25" (31.75 mm)

    10 >0.8 – 1.5" (20.32 - 41.5 mm)

    B B 1.25" (31.75 mm)

    16 0.5 - 0.8" (12.7 - 20.32 mm)

    B A 2.90" (73.66 mm)

    16 >0.8 – 1.5" (20.32 - 41.5 mm)

    C B 2.90" (73.66 mm)

    16 >1.5 – 2.5" (41.5 - 63.5 mm)

    D C 2.90" (73.66 mm)

    23 0.5 - 0.8" (12.7 - 20.32 mm)

    B A 5.25" (133.35 mm)

    23 >0.8 – 1.5" (20.32 - 41.5 mm)

    C B 5.25" (133.35 mm)

    23 >1.5 – 2.5" (41.5 - 63.5 mm)

    D C 5.25" (133.35 mm)

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 11

  • Wiring the SVI FF

    Figure 1 Connections to Electronics Module (via Terminal Board)

    Display

    Remote

    I/P Connector

    PositionSensor

    Configuration LockJumper

    9 - 32 V Foundation*

    Discrete Out

    Input

    Discrete

    Shield(on FF unit

    Input Signal(polarity independent)

    Input

    Fieldbus

    housing)

    AI PV 1-5 VDC(Not used in this release)

    © 2017 General Electric Company. All rights reserved.12 | =GE Oil & Gas

  • FF Environment Minimum SettingsThe general steps necessary to complete the SVI FF configuration and software setup are out-lined in Figure 2.

    Step 4: Enter a Device Address and Device Tag.

    Step 2: Set Control Tuning by choosing Single or Double Acting and setting tuning type. Autotune is recommended, Custom requires entering your values.

    Step 1: Set Air Action.

    Step 3: Set Characterization Type. Custom requires entering your values.

    Step 5: Run Find Stops and then run Autotune.

    Figure 2 Quick Start Configuration

    Example Configuration

    Step 1: Install the Positioner on the Valve

    See “Installation and Set Up” on page 8.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 13

  • Step 2: Set Tag and Address

    Using NI Configurator:

    1. Import DD/CFF files.

    2. Right-click on the device, select Set Tag, follow the prompts to enter a Tag.

    3. Click Set .

    4. Right-click on the device, select Set Address, follow the prompts to enter an Address.

    5. Click Set .

    Do not navigate to the NI DD folder and copy the DD file onto itself.

    Do not deactivate the Set to OOS mode checkbox. The block must be in OOS to change the Tag.

    If the device is at the temporary address range (248 (0xF8)- 251 (OxFB)), you must set the address outside of that range.

    Do not deactivate the Set to OOS mode checkbox. The block must be in OOS to change the Address.

    CAUTION

    CAUTION

    CAUTION

    CAUTION

    © 2017 General Electric Company. All rights reserved.14 | =GE Oil & Gas

  • Step 3: Basic Configuration

    This section serves as an example where the AO block and TB block are configured. However, there are a number of combinations that can be configured. This discussion is valid if the posi-tioner is controlled by the AO block.

    1. For the Transducer block set:

    ACTUATOR_3.ACT_FAIL_ACTION_1 = either 1. Valve Closed (most common) or 2. Valve Open

    ACCESSORY.REMOTE_SENSOR = 0, if remote sensor is not in use (internal Hall sensor is used)

    ACTIVATE_CONTROL_SET to one of:

    0: Activate Custom Control Set (required for Auto-tune as well - most common)

    1: Activate Control Set 1 (Slowest)

    2: Activate Control Set 2

    3: Activate Control Set 3

    4: Activate Control Set 4

    5: Activate Control Set 5 (Fastest)

    6: Activate Control Set 6 (Double Acting - Slow)

    7: Activate Control Set 7 (Double Acting- Fast)

    CHAR_SELECTION.TYPE to one of:

    0. Linear (most common)

    1. Equal Percent-age (30:1)

    2. Equal Percent-age (50:1)

    3. Quick Open (reversal from Equal Percentage (50:1))

    4. Custom 5. Camflex Percentage

    See Transducer Block Parameters in the SVI FF instruction manual for further settings.

    2. For the AO block review/set as below:

    PV_SCALE.UNIT INDEX = %

    XD_SCALE.UNIT INDEX = %

    CHANNEL = Position

    SHED_OPT = NORMAL SHED NORMAL RETURN

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 15

  • Step 4: Run Find Stops METHOD

    Use a configuration tool (DD, SVI FF local pushbuttons or software) to run METHOD.

    Step 5: Run Auto Tune METHOD

    Use a configuration tool (DD, SVI FF local pushbuttons or software) to run METHOD.

    DownloadsTo download the complete user manual, DD, SVI FF Advanced DTM and the ValVue Suite trial pro-gram, visit: https://www.geoilandgas.com/file-download-search.

    © 2017 General Electric Company. All rights reserved.16 | =GE Oil & Gas

  • 2. ES-776

    Rev Description Date Written by L. Lu Jun. 10, 2013 A Initial Release

    ECO-14740 Jun. 10, 2013 Approved

    by R. Belmarsh Jun. 10, 2013

    B ECO-15557 Aug. 23, 2013 C ADR-003891 Sept, 24, 2013 ES-776 Rev K D ADR-003896 Oct. 1, 2013 E ADR-003908 Nov 6, 2013 F ADR-003913 Jan 8, 2014 G ADR-003926 Feb 24, 2014 H ADR-003933 May 6, 2014 J ADR-003987 Dec 16, 2014 K ADR-004000 Jan 16, 2014 L PDR ECO-

    0026891 Oct 28, 2016

    Page 1 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    ES-776

    SPECIAL INSTRUCTIONS FOR INSTALLING Masoneilan SVI FF POSITIONER IN AREAS WHERE THERE IS A POTENTIAL FOR

    EXPLOSIVE GAS ATMOSPHERE OR FLAMMABLE DUST

    Masoneilan SVI FF Positioner Quick Start Guide =| 17© 2017 General Electric Company. All rights reserved.

  • GE Oil & Gas

    ES-776 Rev L Page 2 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    Contents 1 INTRODUCTION ........................................................................................................ 3 2 GENERAL REQUIREMENTS ......................................................................................... 4 3 MODEL NUMBER DESCRIPTION OF SVI FF POSITIONER .............................................. 5 4 FLAMEPROOF AND DUST IGNITION PROOF REQUIREMENTS ...................................... 6

    General .............................................................................................................. 6 4.1 Cable Glands ..................................................................................................... 6 4.2 Natural gas ......................................................................................................... 6 4.3 Bolting ................................................................................................................ 6 4.4 Carbon Disulphide Exclusion ............................................................................. 6 4.5 Label Cleaning ................................................................................................... 6 4.6 Dust Environment ............................................................................................... 6 4.7

    5 INTRINSICALLY SAFE REQUIREMENTS ........................................................................ 7 Div 2 ................................................................................................................... 7 5.1 Category II 1 (Zone 0) ........................................................................................ 7 5.2 Category II 1 (Zone 0) ........................................................................................ 7 5.3 Internal pollution degree 2 and overvoltage category III ..................................... 7 5.4

    6 DESCRIPTION OF FLAMEPROOF AND INTRINSICALLY SAFE MARKINGS ....................... 8 7 INTRINSICALLY SAFE INSTALLATION WIRING REQUIREMENTS ................................. 10 8 NOTES FOR INTRINSICALLY SAFE INSTALLATION ..................................................... 11

    HAZARDOUS LOCATION ............................................................................... 11 8.1 FIELD WIRING ................................................................................................. 11 8.2 Foundation Fieldbus IN (+) and (-) Terminals .................................................. 11 8.3 PV 1-5VDC (+) and (-) Terminals ..................................................................... 12 8.4 SW (+) and (-) Terminals .................................................................................. 12 8.5 REMOTE (1) and (2) and (3) Terminals ........................................................... 12 8.6 Digital In Terminals .......................................................................................... 12 8.7 Entity Requirement ........................................................................................... 13 8.8 Use in dust atmosphere ................................................................................... 13 8.9

    9 REPAIR .................................................................................................................... 13 Main Cover ....................................................................................................... 14 9.1 I/P ..................................................................................................................... 14 9.2 Relay ................................................................................................................ 14 9.3 Electronics........................................................................................................ 14 9.4 Pneumatic Cover .............................................................................................. 14 9.5

    © 2017 General Electric Company. All rights reserved.18 | =GE Oil & Gas

  • GE Oil & Gas

    ES-776 Rev L Page 3 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    1 INTRODUCTION This manual covers the requirements for safe installation, repair, and operation of the SVI FF positioner as it relates to operation in areas where there is a potential for explosive atmosphere or flammable dust. Adherence to these requirements assures that the SVI FF positioner will not cause ignition of the surrounding atmosphere. Hazards related to control of the process are beyond the scope of this manual. For mounting instructions on specific valves refer to the mounting instructions supplied with the mounting kit. Mounting does not affect the suitability of the SVI FF positioner for use in a potentially hazardous environment. For language translation assistance contact your local representative or email [email protected]. Pour la langue de traduction aide, contactez votre représentant local ou envoyez un e-mail [email protected]. The SVI FF positioner is manufactured by:

    Dresser Inc. 12970 Normandy Blvd.

    Jacksonville FL – 32221 – USA

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 19

  • GE Oil & Gas

    ES-776 Rev L Page 4 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    2 GENERAL REQUIREMENTS

    Installation and maintenance must be performed only by qualified personnel. Area Classification, Protection Type, Temperature Class, Gas Group, and Ingress protection must conform to the data indicated on the label. Wiring and conduit must conform to all local and national codes governing the installation. Wiring must be rated for at least 10ºC above the highest expected ambient temperature. Approved wire seals against ingress of water and dust are required and the NPT fittings must be sealed with tape or thread sealant in order to meet the highest level of ingress protection. Where the protection type depends on wiring glands, the glands must be certified for the type of protection required. The metal housing is a die-casting alloy which is predominately aluminum. “X” Marking is on label. Before powering the SVI FF positioner:

    Verify that the pneumatic and electronic cover screws are tightened. This is important to maintain the ingress protection level and the integrity of the flameproof enclosure.

    If the Installation is Intrinsically safe, then check that the proper barriers are installed and the field wiring meets local and national codes for an IS installation. Never install a device, which was previously installed without an intrinsically safe barrier, in an intrinsically safe system.

    If the pneumatic system is powered by a combustible gas then the installation must be treated as Zone 0 or DIV I.

    In non-incendive installation, check to ensure all electrical connections are made to approved circuits which meet local and jurisdictional installation codes.

    Verify that the markings on the label are consistent with the application.

    Verify that the air supply pressure can not exceed the marking on the respective label.

    !WARNING! Failure to adhere to the requirements listed in this manual may cause loss

    of life and property.

    © 2017 General Electric Company. All rights reserved.20 | =GE Oil & Gas

  • GE Oil & Gas

    ES-776 Rev L Page 5 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    3 Model Number Description of SVI FF positioner SVI-abcdefgh Not all combinations are available.

    SVI- A Style (2,3,4) B

    Pneumatic Train (1,2)

    C Pneumatics

    (1,2)

    D Display / housing Material (1,2,3,4)

    E Communications

    (F,P)

    F Options

    (1)

    G Agency

    Approvals (2)

    H Other Agency

    Approvals (1,2,3,4,5,6)

    1 Single Acting Standard

    Flow

    No Display No Buttons Aluminum

    F= Foundation Fieldbus

    None

    North American

    Zone (FM, FMc)

    2 Standard Diagnostics Double Acting

    High Capacity

    Display Buttons

    Aluminum

    P=Profibus

    Unilabeled (ATEX,

    IEC,FMc, FM)

    GOST

    3 Advanced Diagnostics No Display No Buttons

    Stainless Steel

    KOSHA

    4 Display Buttons Stainless

    Steel

    NEPSI

    5 INMETRO 6 JIS

    7 CCOE

    MODEL CODES COVERED BY THIS DOCUMENT: SVI-abcdefgh, where “a” thru “h” can take on the following values:

    a= 1..X. Indicates internal firmware style. (NOT RELEVANT TO PROTECTION TYPES) b= 1, 2. Indicates pneumatic train type. (1 = SINGLE ACTING, 2 = DOUBLE ACTING) c= 1, 2. Indicates pneumatic flow. (1 = STANDARD FLOW, 2 = HIGH FLOW) d= 1, 2, 3, 4. Indicates display type and housing material.

    (1 = NO DISPLAY; NO BUTTONS; ALUMINUM) (2 = DISPLAY; BUTTONS; ALUMINUM) (3 = NO DISPLAY; NO BUTTONS; STAINLESS STEEL) (4 = DISPLAY; BUTTONS; STAINLESS STEEL)

    e= F, P. Indicates communication protocol. (F = FOUNDATION FIELDBUS. P = PROFIBUS) f= 1..X. Indicates options turned on by firmware. (NOT RELEVANT TO PROTECTION TYPES) g= 2. Indicates agency approvals. (UNI-LABEL; ATEX, IEC, FM, FMc) h= 1. Indicates North American Zone Approvals

    2...X. Indicates additional region specific approvals.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 21

  • GE Oil & Gas

    ES-776 Rev L Page 6 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    (NOT RELEVANT TO PROTECTION TYPES) 4 FLAMEPROOF and DUST IGNITION PROOF REQUIREMENTS

    General 4.1

    The 1/2 inch NPT fittings must enter the housing at least five full turns. The cover flange must be clean and free of corrosion products.

    Cable Glands 4.2

    Certified cable glands are required based on the hazardous area the device is installed in. That is, the particular cable gland used must have the same certification as the tick-box checked off on the label.

    Natural gas 4.3

    Use of a pressurized gas which is ignitable in the presence of air (for example natural gas) is not allowed as the SVI FF positioner supply pressure in a flameproof (protection type “d”) installation.

    Bolting 4.4

    “X” Marking on label- M8 X 1.25-6g cover screws must be supplied by GE. No substitution allowed. Minimum yield stress to be 296 N/mm^2 (43,000 psi).

    Carbon Disulphide Exclusion 4.5Carbon Disulphide is excluded. (IEC 60079-1, Clause 15.4.3.2.2., carbon disulphide is excluded for enclosures with a volume greater than 100cm3)

    Label Cleaning 4.6

    ”X” marking on label-Potential Electrostatic Charge Hazard – Use only damp cloth when cleaning or wiping. Do not use solvent.

    Dust Environment 4.7

    ”X” marking on label-Instruments Installed in dusty hazardous areas. Must be cleaned regularly to prevent the buildup of dust layers on any surface. To avoid the risk from electrostatic discharge follow the guidance as detailed in EN TR50404.

    © 2017 General Electric Company. All rights reserved.22 | =GE Oil & Gas

  • GE Oil & Gas

    ES-776 Rev L Page 7 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    For safe operation, use only wet cloth when cleaning or wiping the device. Cleaning must only be done when local conditions around the device are free of potentially explosive atmospheres. Do not use dry cloth or any solvents.

    5 INTRINSICALLY SAFE REQUIREMENTS Div 2 5.1

    WARNING: EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOW TO BE NON-HAZARDOUS.

    Category II 1 (Zone 0) 5.2

    For operation in hazardous area category II 1, over-voltage protection of the electrical connections need to be installed according to EN 60079-14. For operation in hazardous area category II 1 the ambient temperature needs to be lowered according to the requirements of EN 1127-1 (reduction factor of 80%). The max. allowed ambient temperature for category 1 inclusive the requirement of EN1127-1 is:

    T6 : Ta = -40°C to +60°C T5 : Ta = -40°C to +75°C T4 : Ta = -40°C to +85°C

    Category II 1 (Zone 0) 5.3

    “X” Marking on label - Since the SVI-abcdefgh (“SVI FF positioner”) contain greater than 10% aluminum, care must be taken during installation to avoid impacts or friction that could create an ignition source.

    Internal pollution degree 2 and overvoltage category III 5.4 Ensure all covers and seals are correctly installed before putting device into service.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 23

  • GE Oil & Gas

    ES-776 Rev L Page 8 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    6 Description of Flameproof and Intrinsically Safe Markings Applicable models numbers can be found in Section 3.

    IN GROUP A INSTALLATIONS CONDUIT SEAL REQUIRED WITHIN 18 INCHES OF ENCLOSURE

    Summary of Agency Markings Factory Mutual Approvals

    Intrinsically Safe & FISCO Class I Division 1 Groups A,B,C,D T6…T4 Class II,III Division 1 Groups E,F,G T6…T4 Class I, Zone 0, AEx ia IIC T6…T4 Ga Class I, Zone 2, AEx ic IIC T6…T4 Gc Zone 20, AEx ia IIIC T96°C Da

    Explosion Proof Class I, Division 1, Groups A,B,C,D T6…T4 Class I, Zone 1, AEx d mb IIC T6…T4 Class I, Zone 1, IIC T6…T4

    Temperature Classification T4 Ta = -40°C to 85°C T5 Ta = -40°C to 75°C T6 Ta = -40°C to 60°C

    Type n Protection Class I Division 2 Groups A,B,C,D T6…T4 Class II Division 2 Groups F,G T6…T4 Class III Division 1,2 T6...T4 Class I, Zone 2, IIC T6...T4

    Dust Ignition Proof Class II,III Division 1 Groups E,F,G T6...T4 Zone 21, AEx tb IIIC T96°C Db Zone 22, AEx tc IIIC T96°C Dc

    Ingress Protection IP66; NEMA Type 4X

    Canada Approvals (FM Canada Approved)

    Intrinsically Safe & FISCO Class I, Division 1, Groups A,B,C,D T6…T4 Class II,III Division 1 Groups E,F,G Class I, Zone 0, Ex ia IIC T6…T4 Ga Class I, Zone 2, Ex n IIC T6…T4 Gc Zone 20, Ex ia IIIC T96°C Da

    Explosion Proof Class I Division 1 Groups B,C,D T6…T4 Class I, Zone 1, Ex d m IIB+H2 T6…T4 Class I, Zone 1, IIB+H2 T6…T4

    Temperature Classification T4 Ta = -40°C to 85°C T5 Ta = -40°C to 75°C T6 Ta = -40°C to 60°C

    Type n Protection Class I Division 2 Groups A,B,C,D T6…T4 Class II Division 2 Groups F,G Class III Division 1,2

    Dust Ignition Proof Class II, Division 1 Groups E,F,G Class III, Division 1,2

    Ingress Protection IP66, Type 4X

    © 2017 General Electric Company. All rights reserved.24 | =GE Oil & Gas

  • GE Oil & Gas

    ES-776 Rev L Page 9 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    ATEX Approvals FM14ATEX0014X FM14ATEX0015X

    Intrinsically Safe II 1G Ex ia IIC T6…T4 Ga II 1D Ex ia IIIC T96°C Da II 3G Ex ic IIC T6…T4 Gc

    Flame Proof II 2G Ex d mb IIC T6…T4 Gb

    Temperature Classification T4 Ta = -40°C to 85°C T5 Ta = -40°C to 75°C T6 Ta = -40°C to 60°C

    Dust Ignitionproof II 2D Ex tb IIIC T96°C Db II 3D Ex tc IIIC T96°C Dc

    Ingress Protection IP66

    IECEx Approvals IECEx FMG 14.0007X

    Intrinsically Safe Ex ia IIC T6…T4 Ga Ex ia IIIC T96°C Da Ex ic IIC T6…T4 Gc

    Flame Proof Ex d mb IIC T6…T4 Gb

    Temperature Classification T4 Ta = -40°C to 85°C T5 Ta = -40°C to 75°C T6 Ta = -40°C to 60°C

    Dust Ignitionproof Ex tb IIIC T96°C Db Ex tc IIIC T96°C Dc

    Ingress Protection IP66

    Operating Ranges Temp: -40°C ≤ Ta ≤ 85°C Voltage: 9 to 32V DC Pressure: 150 psig (1.03MPa) Current: 18.3 mA (Max)

    Notes Related to Explosionproof Rating

    1) “DO NOT OPEN EVEN WHEN ISOLATED WHEN EXPLOSIVE ATMOSPHERES ARE PRESENT”

    Notes Related to Intrinsic Safety

    1) “INSTALL Per ES-776” 2) “Supply Connection Wiring Rated for 10ºC Above Max Ambient” 3) “PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED”

    Model Code:

    “SVI-abcdefgh” (see section 3 above for explanation)

    Serial Number: “SN-nnyywwnnnn”

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 25

  • GE Oil & Gas

    ES-776 Rev L Page 10 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    7 Intrinsically Safe Installation Wiring Requirements

    OptionalIntrinsically SafeProcess VariableTrnsmitter

    NON- HAZARDOUS LOCATION- UNSPECIFIED EXCEPTTHAT BARRIERS MUST NOT BE SUPPLIED FROM NORCONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS ASOURCE OF POTENTIAL WITH RESPECT TO EARTH INEXCESS OF250 VOLTS RMS OR250 VOLTS DC

    HAZARDOUS LOCATIONSEE8.1 , 8.2

    1

    24

    3

    SVIF

    FPo

    sitio

    ner

    SW

    1(D

    O)

    -+

    Equi- Potential

    Optional FieldLoad

    Shunt Zener Diode Safety BarrierController Output Type (See 8.3)

    24 VDC from DCS

    To DCS DI

    Shunt Zener Diode SafetyBarrier Switch Type Barrier (See 8.5)

    Cable Shield

    SVI FF RemoteMount

    - - -

    - - -

    Remote

    1

    2 1 to 5 Volts tocontrol system

    4

    3

    AI_P

    V1-

    5VD

    C

    -

    +

    Shunt Zener Diode SafetyBarrier Switch Type Barrier

    ( See8.4)

    1

    24

    3

    Shunt Zener Diode Safety Barrier-Controller Output Type (See 8.4)

    -

    +

    Transmitter

    24 VDC fromControl System

    See Note8.6

    DI

    +

    -

    Simple PassiveApparatus

    (Switch, relay)

    +

    -

    Foun

    datio

    nFi

    ebu

    sdl

    4

    3 1

    2

    ( See8. )

    Optional Hand Held

    8Communicator

    Foundation Field busSet Point fromControl system

    Optional Hand HeldCommunicator

    Each intrinsically safe cable must include a grounded shield or be run in a separate metal conduit.

    © 2017 General Electric Company. All rights reserved.26 | =GE Oil & Gas

  • GE Oil & Gas

    ES-776 Rev L Page 11 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    8 Notes for Intrinsically Safe Installation

    HAZARDOUS LOCATION 8.1

    Refer to the device label for the description of the environment in which the device may be installed.

    FIELD WIRING 8.2

    Intrinsically Safe wiring must be made with grounded shielded cable or installed in grounded metal conduit. The electrical circuit in the hazardous area must be capable of withstanding an A.C. test voltage of 500 volts R.M.S. to earth or frame of the apparatus for 1 minute. Installation must be in accordance with GE guidelines. The installation including the barrier earthing requirements must comply with the installation requirements of the country of use. For Division 1/Zone 0 installations, the configuration of associated apparutus shall be FM Approved under Entity/FISCO Concept.

    FM Approvals requirements (USA): ANSI/ISA RP12.6 (Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations) and the National Electrical Code, ANSI/NFPA 70. Division 2 installations must be installed per the National Electrical Code, ANSI/NFPA 70.

    FMc requirements (Canada): Canadian Electrical Code Part 1. Division 2 installations must be installed per the Canadian Electrical Code Division 2 Wiring Methods.

    ATEX requirements (EU): Intrinsically safe installations must be installed per EN60079-10 and EN60079-14 as they apply to the specific category.

    Foundation Fieldbus IN (+) and (-) Terminals 8.3

    These terminals power the SVI FF positioner, and are not polarity sensitive. The FF interface shall conform to the physical layer reqiurements of IEC60079-11, IEC61158-2, and FF-816.

    FISCO I.S. Model Parameters

    Entity Model Parameters

    Max. Input Voltage Ui 17.5V 24V Max. Input Current Ii 380mA 250mA Max. Input Power Pi 5.32W 1.2W

    Max. Internal Capacitance Ci 1nF 1nF Max. Internal Inductivity Li 1μH 1μH

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 27

  • GE Oil & Gas

    ES-776 Rev L Page 12 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    PV 1-5VDC (+) and (-) Terminals 8.4

    The Process Transmitter and the SVI FF positioner’s PV Input are both barrier protected. The transmitter 4 to 20 mA signal is converted to 1 to 5 Volts at the Transmitter barrier. The 1 to 5 volt signal is monitored by the DCS and used by the SVI FF positioner for the embedded process controller. The sense resistor may be in the barrier or in the Digital Control System. The Process Transmitter must be approved for use with the Process Transmitter Barrier. An example of a suitable barrier is MTL 788 or 788R An example of the PV INPUT barrier is MTL 728. Entity Parameters of the PV terminals:

    Vmax = 30 Vdc; Imax = 125 mA; Ci = 1 nF; Li = 0 uH; Pmax = 900 mW

    SW (+) and (-) Terminals 8.5

    There is one solid state switch contact output on the SVI FF positioner. It is labeled SW. The switch is polarity sensitive – that is, conventional current flows INTO the plus terminal. Entity parameters are: Vmax = 30 Vdc Imax = 125 mA Ci = 4 nF Li = 10 uH Pmax = 500 mW

    REMOTE (1) and (2) and (3) Terminals 8.6

    The REMOTE terminals deliver reference Voltage to an optional remote position sensing potentiometer. Current, Voltage, and Power are limited by the SVI FF positioner. The REMOTE terminals entity parameters are the parameters of the 4 to 20 mA INPUT barrier. The SVI-II REMOTE MOUNT is approved for use as a remote position sensing device with the SVI FF positioner. Entity parameters of the Remote Terminals are:

    Uo/Voc = 6.5 Volts Io/Isc = 9.6 mA Ca = 22 uF La = 300 mH Connect only to suitable potentiometer.

    Digital In Terminals 8.7

    The Digital In terminal is suitable for direct connection to a passive switch. Entity Parameters are: Uo/Voc = 5.35 Volts Io/Isc = 50.6 mA Ca = 1.25 uF La = 2 mH Connect only to passive dry contact simple apparatus.

    © 2017 General Electric Company. All rights reserved.28 | =GE Oil & Gas

  • GE Oil & Gas

    ES-776 Rev L Page 13 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    Entity Requirement 8.8

    Cable capacitance and inductance plus the I.S. apparatus unprotected capacitance (Ci) and inductance (Li) must not exceed the allowed capacitance (Ca) and inductance (La) indicated on the associated apparatus. If the optional Hand Held Communicator is used on the Hazardous Area side of the barrier, then the capacity and inductance of the communicator must be added and the communicator must be agency approved for use in the hazardous area. Also, the current output of the Hand Held Communicator must be included in the current output of the associated equipment. For North American installations, the barriers may be active or passive and from any FM Approved manufacturer as long as the barriers comply with the listed entity parameters. For European installations, the barriers may be active or passive and from any certified manufacturer as long as the barriers comply with the listed entity parameters and are installed per the guidelines of EN60079-14. For other international installations, the barriers may be active or passive and from any certified manufacturer as long as the barriers comply with the listed entity parameters and are installed per the guidelines of IEC60079-14. If the electrical parameters of the cable used are unknown, the following values may be used: Capacitance – 197pF/m (60 pF/ft), Inductance – 0.66 μH/m (0.20 μH/ft).

    Use in dust atmosphere 8.9

    Dust-tight conduit seal must be used when installed in dust hazard environments.

    9 REPAIR WARNING: EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN A HAZARDOUS LOCATION. Only qualified service personnel are permitted to make repairs on the SVI FF positioner. Replace ONLY with genuine GE parts. Use only cover bolts of Autenitic Grade A2 Class 70 or Grade A4 Class 70, supplied by the manufacturer. Consult the manufacturer for dimensional information on the flameproof joints for repair. Only parts supplied by GE are permitted. This includes not only the major assemblies but also mounting screws and “O” rings. No substitutions with non-GE parts are permitted.

    © 2017 General Electric Company. All rights reserved. Masoneilan SVI FF Positioner Quick Start Guide =| 29

  • GE Oil & Gas

    ES-776 Rev L Page 14 of 14

    Copyright 2016. This document and all information herein is the property of Dresser Inc.

    Detailed replacement procedures are described in the SVI FF Quick Start Guide. The following summary assures the safe operation of the SVI FF positioner. For assistance, contact the nearest sales office, your local representative or email [email protected]. Visit our web page at www.ge-energy.com/valves

    Main Cover 9.1

    Make sure that: The gasket is seated in the groove in the housing flange. No wires or retaining cable can be trapped under the cover flange. The flange area is not corroded and the surface is not scarred. The four cover bolts are securely tightened. Secure the four cover bolts by applying a torque of 55±5 in-lbs.

    I/P 9.2

    Make sure that: The wire is not damaged when feeding it through the housing. A single “O” ring is in place on the wire-sleeve and is not damaged. The four retaining screws are snug. Inserting the wire sleeve through the housing does not require force.

    Relay 9.3

    Make sure that: The five “O” rings are seated in the base of the relay and are not damaged. Note that the five “O” rings may be 5 individual parts, or 5 “O”rings ganged together as 1 part. The mounting screws are snug.

    Electronics 9.4

    Make sure that: The 4 “O” rings are seated on the base of the electronics assembly and are not damaged. The four retaining screws are snug,

    Pneumatic Cover 9.5

    Make sure that: The gasket is seated in the groove. The retaining screws are snug.

    © 2017 General Electric Company. All rights reserved.30 | =GE Oil & Gas

  • DIRECT SALES OFFICE LOCATIONS

    AUSTRALIA BrisbanePhone: +61-7-3001-4319Fax: 88+61-7-3001-4399

    ITALY

    Phone: +39-081-7892-111Fax: 88+39-081-7892-208

    SOUTH AFRICA

    Phone: +27-11-452-1550Fax: 88+27-11-452-6542

    Perth

    Phone: +61-8-6595-7018Fax: 88+61-8-6595-7299

    JAPAN Tokyo Phone: +81-03-6871-9008Fax: ==+81-03-6890-4620

    SOUTH and CENTRAL AMERICA AND THE CARIBBEAN Phone: +55-12-2134-1201Fax: 88+55-12-2134-1238

    MelbournePhone: +61-3-8807-6002Fax: 88+61-3-8807-6577

    KOREAPhone: +82-2-2274-0748Fax: 88+82-2-2274-0794

    SPAINPhone: +34-93-652-6430Fax: 88+34-93-652-6444

    BELGIUMPhone: +32-2-344-0970Fax: 88+32-2-344-1123

    MALAYSIAPhone: +60-3-2161-0322Fax: 88+60-3-2163-6312

    UNITED ARAB EMIRATESPhone: +971-4-8991-777Fax: 88+971-4-8991-778

    BRAZIL

    Phone: +55-19-2104-6900

    MEXICO

    Phone: +52-55-3640-5060

    UNITED KINGDOM BracknellPhone: +44-1344-460-500Fax: 88+44-1344-460-537

    CHINAPhone: +86-10-5689-3600Fax: 88+86-10-5689-3800

    THE NETHERLANDSPhone: +31-15-3808666Fax: 88+31-18-1641438

    SkelmersdalePhone: +44-1695-526-00Fax: 88+44-1695-526-01

    FRANCE CourbevoiePhone: +33-1-4904-9000Fax: 88+33-1-4904-9010

    RUSSIAVeliky NovgorodPhone: +7-8162-55-7898Fax: 88+7-8162-55-7921

    UNITED STATES Jacksonville, FloridaPhone: +1-904-570-3409

    GERMANY RatingenPhone: +49-2102-108-0Fax: 88+49-2102-108-111

    Moscow

    Phone: +7 495-585-1276Fax: 88+7 495-585-1279

    Corpus Christi, Texas

    Phone: +1-361-881-8182Fax: 88+1-361-881-8246

    INDIA MumbaiPhone: +91-22-8354790Fax: 88+91-22-8354791

    SAUDI ARABIA

    Phone: +966-3-341-0278Fax: 88+966-3-341-7624

    Deer Park, Texas

    Phone: +1-281-884-1000Fax: 88+1-281-884-1010

    New DelhiPhone: +91-11-2-6164175Fax: 88+91-11-5-1659635

    SINGAPOREPhone: +65-6861-6100Fax: 88+65-6861-7172

    Houston, TexasPhone: +1-281-671-1640Fax: 88+1-281-671-1735

    Visit us online at: www.geoilandgas.com/valves

    Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners.

    © 2017 General Electric Company. All rights reserved.