Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf ·...

24
Remote Temperature Controller Technical Manual Part 107 917A NORDSON CORPORATION. AMHERST, OHIO. USA

Transcript of Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf ·...

Page 1: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Remote Temperature Controller

Technical Manual

Part 107 917A

NORDSON CORPORATION. AMHERST, OHIO. USA

Page 2: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Nordson Corporation welcomes requests for information, comments and inquiries about its products.

Address all correspondence to

Nordson Corporation 11475 Lakefield Drive

Duluth, GA 30136

Notice

This is a Nordson Corporation publication which is protected by copyright. No part of this document may be photocopied, reproduced, or translated to another language without the prior written consent of Nordson

Corporation. The information contained in this publication is subject to change without notice.

Trademarks

AquaGuard, Blue Box, Control Coat, Equi=Bead, FloMelt, FoamMelt, FoamMix, Helix, Hot Shot, Hot Stitch, Meltex, MicroSet, MultiScan, Nordson, the Nordson logo, OmniScan, Porous Coat, Posi-Stop, RBX, Sure-Bond,

UniScan, UpTime, and Versa-Spray are registered trademarks of Nordson Corporation.

BetterBooksM, CF, Controlled Fiberization, Easy-Screen, Fibermelt, Flo-Tracker, PrintGuard, and Package of Values are trademarks of Nordson Corporation.

Manual 46-69 107 917A Issued 1 l/88

0 198El Nordson Corporation All Rights Reserved

Page 3: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page O-l

Table of Contents

Section 1 i Safety Summary

Introduction ....................................... .1-l Explanation of Terms and Symbols .......................... .1-l Safety During Installation ............................... .l-2

Electrical ..................................... .l-2 Safety During Operation ................................ .l-2 Safety During Servicing ................................ .l-3 Safety When Using Hot Melt Adhesives and Solvents ............... .l-4

Hot Melt Adhesives ............................... .l-4 Heat Solvents .................................. .l-5

Section 2 Equipment Familiarization

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-l Specification Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-l

Section 3 Preparation For Use

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-l Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-l Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-l Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-l

Section 4 Operating Instructions

Description of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-l Setting the Remote Temperature Controller . . . . . . . . . . . . . . . . . . . . . .4-l

Section 5 Maintenance

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-l Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-l Corrective Maintenance . . . . . . . . 5-l

Troubleshooting Chart ’ : : : : : : : : : : : : : : : : : : : : : : . . . . . . . .5-2 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3

Pub. No. 107 917A ONORDSON CORPORATION 1988 All Rights Reserved

Issued 11/88

Page 4: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page O-2

Temperature Controller

Section 6 Illustrated Parts List

Column Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6- 1 Remote Controller Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2

Issued 1 l/88 ONORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 5: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page l-l

SECTION 1 SAFETY SUMMARY

INTRODUCTION

This section of the manual contains safety guidelines for the use of NordsonB equipment. They are repeated throughout the manual where they apply, along with some specific warnings and cautions which are not included here. The guidelines cover instal- lation, operation, and servicing. The safety information contained in this section applies to anyone working with Nordson equip- ment, including operations and service personnel.

A WARNING: Failure to follow these recommendations may result in personal injury from burns or electrocution and/or equipment and property damage.

EXPLANATION OF TERMS AND SYMBOLS

The following safety symbols and signal words are used throughout this publication to alert the reader to personal safety hazards, or to identify conditions that may result in equipment or property damage.

A WARNING: General warning. Failure to observe may result in personal injury or death.

A WARNING: Risk of electrical shock. Failure to ob-

% serve may result in personal injury or death.

A CAUTION: General caution. Failure to observe may result in minor personal injury or damage to property.

NOTE: Important information. Failure to observe may result in equipment damage.

Pub. No. 107 917A BNORDSON CORPORATION 1988 All Rights Reserved

Issued 11/88

Page 6: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page l-2

Temperature Controller

SAFETY DURING INSTALLATION

Electrical

1. A protective electrical ground connection to a reliable earth ground is essential for safe operation. Without one, all acces- sible conductive components (including knobs and controls that appear insulated) can render an electric shock.

2. A disconnect switch with lockout capability must be provided between the power source and the equipment.

3. The power supply wire gauge and insulation must be sufficient to meet the temperature and power requirements.

4. Only fuses of the correct type voltage rating and current rating should be used. Refer to the Nordson equipment parts list for fuse recommendations. Using incorrect or nonrecommended fuses can present a fire hazard.

SAFETY DURING OPERATION

DO NOT operate Nordson equipment under the following condi- tions:

1. At a pressure higher than the rated maximum working pres- sure of any component in the system.

2. Near volatile or otherwise explosive gases or materials.

3. Without the covers, panel and safety guards properly installed.

4. At atmospheric temperatures below 20°F (-6°C) or above 120°F (50°C).

5. With hoses enclosed in any material that interferes with heat dissipation. This includes electrical conduit, insulation of any type or tight metal covers.

6. With large areas of hose in contact with a cold floor, cold sup- ports or other such surfaces. Cold points along the hose restrict the flow of adhesive inside the hose and can create potential problems during operations.

Issued 1 l/88 @NORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 7: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page l-3

7. In drafty areas with the applicator guns unshielded from the draft. Rapid heat dissipation due to air movement across the guns may cause operational problems.

8. (If a handgun is used) with the handgun trigger left unlocked while the gun is unattended.

in addition:

1. Use only the metal base when attempting to lift or move an ap- plicator. DO NOT use equipment covers, doors, panels or hose connectors as braces or grips.

2. NEVER use Nordson equipment as a ladder or stepping stool.

3. Route all hoses to prevent damage from kinking, abrasion and other physical damage. DO NOT allow a hose to be installed with a bend radius of less than 6 inches (150 mm).

4. NEVER point an applicator handgun at yourself or anyone else.

SAFETY DURING SERVICING

1.

2.

3.

4.

5.

6.

DO NOT perform internal service or adjustment on any equip- ment unless another person capable of rendering first aid and resuscitation is present.

Only qualified personnel should service Nordson equipment.

To avoid personal injury, never touch exposed connections and components while power is ON. Dangerous voltages exist at several points in the equipment.

Disconnect, lock out and tag external electrical power before removing protective panels or replacing electrical components.

Remove all jewelry (rings, watches, etc.) before servicing equip- ment.

If possible, stand on a rubber mat when servicing Nordson equipment. DO NOT work on equipment if standing water is present. Avoid working in a high-humidity atmosphere. Cover exposed terminals and work areas with rubber sheeting to avoid accidental contact while the Dower is ON.

Pub. No. 107 917A BNORDSON CORPORATION 1988 All Rights Reserved

Issued 11/88

Page 8: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manua146-69 Page1-4

Temperature Controller

7. Always wear safety glasses, protective gloves (Nordson P/N 902 514) or equivalent and long-sleeved protective clothing to prevent injury from hot applicator parts, splashed hot melt ad- hesive and hot gun surfaces.

8. To prevent serious injury from molten adhesive under pres- sure, always relieve system hydraulic pressure (by triggering the gun, for example) before opening any hydraulic fitting or connection.

9. NEVER use an open torch, drill or broach when cleaning a noz- zle.

10. NEVER operate equipment with a known leak in the system.

SAFETY WHEN USING HOT MELT ADHESIVES AND SOLVENTS

Hot Melt Adhesives

1. Use extreme care when working with molten material. They solidify rapidly at high temperatures and present a hazard. Severe burns can occur if the molten materials come in contact with the skin. Even when first solidified, they are still hot.

2. Always wear protective clothing and eye protection when han- dling molten material or working near equipment containing hot melt adhesives under pressure.

3. IF MOLTEN MATERIAL COMES IN CONTACT WITH THE SKIN.

l DO NOT try to remove molten material from the skin.

l Immediately immerse the affected area in cold, clean water. Keep the affected areas immersed until the material has cooled. DO NOT try to remove the cooled material from the skin.

l Cover the affected area with a clean, wet compress.

l In cases of severe burns, look for signs of shock. If shock is suspected, have patient lie down, use a blanket to preserve body heat and elevate the feet several inches.

l Call a physician immediately.

issued 1 l/88 BNORDSON CORPORATION 1988 All Rights Reserved

Pub.No. 107917A

Page 9: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page l-5

Heat Solvents

1. DO NOT use an open flame or uncontrolled heating device to heat solvents (for example, a small pan on an unregulated hot plate).

2. Avoid fire hazard by using a controlled heating device to heat solvents (for example, a small deep fat fryer or thermo- statically controlled hot plate).

3. DO NOT USE PAINT-TYPE SOLVENTS UNDER ANY CIR- CUMSTANCES! These solvents are volatile and may be a fire and/or toxic-vapor hazard even at room temperature.

4. Always be sure the work area is adequately ventilated. Avoid prolonged or repeated breathing of solvent vapors.

5. Halogenated Hydrocarbon Solvents are dangerous when used to clean aluminum components in a pressurized fluid system. No available stabilizers prevent halogenated hydrocarbon sol- vents from reacting under all conditions with aluminum com- ponents in a pressurized fluid pumping system.

6. NEVER clean any aluminum component or flush any system using halogenated hydrocarbon solvents. Use Type R (P/N 270 755) solvents or contact your solvent or hot melt supplier for a non-halogenated hydrocarbon solvent for cleaning and flush- ing. Halogenated fluids include the following solvents:

Fluorinated Solvents:

l Dichlorofluoromethane

l Trichlorofluoromethane

Chlorinated Solvents:

Carbon Tetrachloride

Chloroform

Dichloromethane

Ethlylene Dichloride

Methylene Chloride

Monochlorobenzene

Monchlorotoluene

Orthodichlorobenzene

Pub. No. 107 917A BNORDSON CORPORATION 1988 All Rights Reserved

Issued 1 l/88

Page 10: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page 1-6

f Temperature Controller

l Perchloroethylene

l Trichloroethylene

Brominated Solvents:

l Ethylene Dibromide

l Methyl Bromide

l Methylene Chlorobromide

Iodinated Solvents:

4 Ethyl Iodide

l Methyl Iodide

l N-butyl Iodide

l Propyl Iodide

Issued 11/88 @f’JORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 11: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page 2-l

SECTION 2 EQUIPMENT FAMILIARIZATION

INTRODUCTION

The NordsonB Remote Temperature Controller is designed for use with Nordson H20 Spray Guns. The Remote Temperature Control- ler monitors and maintains the integral air heater’s temperature through the use of a Resistance Temperature Detector (RTD) in- stalled in the air heater.

SPECIFICATION SUMMAReY

Control Mode

l PID: Proportional with auto reset and rate (integral and derivative).

l Proportional Band, Reset, Rate and Cycle Time are adjusted at the factory for optimum performance.

Operator Interface

l l/2” LEDs displaying process input value and, when setpot knob is depressed, primary set point valve.

l LED indication of output energized (load light).

Input

. RTD input 2 wire, platinum 100 ohms @ 0°C calibrated for curve:

#3850 (DIN): O.O03850LM2/“C

l Sensor break protection de-energizes output to protect system. Display will indicate open sensor.

Upscale: EEE Downscale: - - -

Output Control

Power

l Triac. 15A @ 240 VAC zero-crossed switching 100 mA min load, Resistive ratings only.

. 230 VAC flO%, 50/60 Hz.

. 6 VA power consumption

Pub. No. 107 917A ONORDSON CORPORATION 1988 All Rights Reserved

Issued 1 l/88

Page 12: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page 2-2

Temperature Controller

Operating Environment . 30 to 130”F/O to 55°C

. 0 to 90% RH, non-condensing

Dimensions Height 5.25 inches Width 8.25 inches Depth 7.31 inches

Issued 11/88 ONORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 13: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page 3-l

SECTION 3 PREPARATION FOR USE

INTRODUCTION

The following paragraphs describe procedures for unpacking, in- specting, and installing the NordsonB Remote Temperature Con- troller.

UNPACKING

No special instructions are required to unpack the components. Normal care should be taken not to damage the equipment during unpacking.

INSPECTION

After unpacking, inspect the controller for the conditions listed below.

1. Check for evidence of dents, scratches, corrosion, or other physical damage. Should any component be damaged, contact your Nordson service representative before performing any in- stallation.

2. Check for loose electrical connections, and tighten where re- quired.

3. Check the controller tiower cord for frayed connections and evidence of kinks. Should the power cord be damaged, contact your Nordson service representative before installing the con- troller.

4. Ensure all fasteners are tight, and secure where necessary.

INSTALLATION

A WARNING: Turn the incoming power main circuit

? breaker OFF. Disconnect and lock out external electrical power to the circuit breaker before proceeding.

1. Connect the remote temperature controller power cord to a 230 VAC single phase power source.

Pub. No. 107 917A ONORDSON CORPORATION 1988 All Rights Reserved

Issued 11/88

Page 14: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

4

P

Page 15: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page 4-l

SECTION 4 OPERATING INSTRUCTIONS

DESCRIPTION OF OPERATION

The Single Channel Temperature Controller maintains the in- tegral air heater’s temperature at the desired level by controlling the integral air heater’s power supply. A Resistance Temperature Detector (RTD) installed in the integral air heater provides feed- back to the temperature controller.

The white “power on” light on the front of the cabinet indicates when the unit is energized. The load light on the display panel in- dicates when power is being applied to the integral air heater. Under normal conditions, the load light will glow steadily while the air heater is warming up, and will then blink regularly as the controller maintains the air heater at the set temperature. The “Band” adjustment on the front panel is factory set and should not be changed.

NOTE: Any changes to the factory setting of the ‘Band” will seriously impair the temperature controllers performance.

SETTING THE REMOTE TEMPERATURE CONTROLLER

1. Turn the incoming power main circuit breaker ON. (Figure 4-l)

2. Turn the temperature controller rocker switch ON. The white light on the front panel will come on.

3. Push in and hold the control knob on the front of the control- ler. The digital readout will be the set point for the integral air heater. Turn the knob clockwise to increase and counterclock- wise to decrease the set point.

4. Release the control knob. When the knob is released the ac- tual temperature of the air heater is indicated.

Pub. No. 107 917A ONORDSON CORPORATION 1988 All Rights Reserved

Issued 1 l/88

Page 16: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page 4-2

Load ‘Eight” \

Temperature Controller

Digital Display

I

Power ON Light

\ Power ON Switch

Control Knob

Figure 4-l Remote Temperature Controller

Issued 11/88 ONORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 17: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page 5-1

SECTION 5 MAINTENANCE

INTRODUCTION

The following paragraphs cover both preventive and corrective maintenance. Preventive maintenance covers general maintenance procedures. Corrective maintenance covers Remote Temperature Controller troubleshooting.

PREVENTIVE MAINTENANCE

1. Keep the temperature controller as clean as possible at all times.

2. Ensure all electrical connections are secure. Tighten connec- tions as required.

3. Avoid bending or kinking the air heater cordset.

CORRECTIVE MAINTENANCE

A WARNING: The Remote Temperature Controller con-

* tains electrical potentials that can be fatal. Use ex- treme caution when making adjustments to the controller with the power ON. Only qualified person- nel should make such adjustments.

Refer to the Troubleshooting Chart on Page 5-2 for troubleshoot- ing procedures.

Pub. No. 107 917A ONORDSON CORPORATION 1988 All Rights Reserved

Issued 11/88

Page 18: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page 5-2

Temperature Controller

TROUBLESHOOTING

Problem Possible Cause Possible Solution

The load light display and white (a) The A.C. input is not con- (a) Check the A.C. input connec- “power ON” light will not turn netted or is connected im- tions. ON. properly.

(b) Fuses have failed. (b) Replace fuses located on the front of the controller cabinet. If fuses continue to blow, check for short circuits in the wiring or heater cartridges.

The display indicates EEE. (a) An open RTD. (a) Repair or Replace.

(b) A jumper (51) is not being used between terminals 11 and 16.

(b) Connect per Wiring Diagram (Page 5-3).

A display error. The sensor is connected improper- Check the sensor location, connec- lY* tions, and the sensing element.

Repair or replace the sensor as re- quired. RTD - Place a 100 ohm resistor across the sensor terminals. The indicator is functioning properly if the display indicates ap- proximately O”C/32”F.

The load light will not turn ON. (a) An open RTD. (a) Repair or Replace.

(b) The load circuit is open. (b) Check th e connection to the in- tegral air heater. Check the heater cartridges and over- temperature thermostat. (See Integral Air Heater Troubleshooting Section in your H20 Spray Gun Manual.)

(c) tezu.ilty temperature control- (c) Call your Nordson Service Rep- resentative.

The load light will not turn OFF. A short circuit between terminals With the power OFF, measure the 3 and 4 on the back of the resistance across pins 3 and 4. If temperature controller. short circuited, call your Nordson

Service Representative.

Issued 11/88 ONORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 19: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69 Page 5-3

-

Ll 8 a 8 dc9qF-J 9.

s1 I 16

4 - 7 L I 13 - Jl / \

L2p 6 ,8 0 10 ~odoooo\o

1 5 ’ 1s 0 10111213141616

4- 14 CONTROLLER

- 3 13

-2 12

1 11

16 17

s 12 3 4 t LIGHT 1

Figure 5-1 - Remote Temperature Controller Wiring Diagram

Pub. No. 107 917A ONORDSON CORPORATION 1988 All Rights Reserved

Issued 1 l/88

Page 20: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page 5-4

Temperature Controller

This Page intentionally Left Blank.

Issued 1 l/88 ONORDSON CORPORATION 1988 All Rights Reserved

Pub. No. 107 917A

Page 21: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Temperature Controller Manual 46-69

Page 6-l

SECTION 6 ILLUSTRATED PARTS LIST

COLUMN IDENTIFICATION

The Item No. column indicates the number assigned to the part in associated figure. A dash is used for parts that are not shown.

The Part No. column indicates the Nordson part number. A dash signifies that the item is a nonsaleable part or a nonsaleable sub- assembly of a saleable assembly.

The Description column gives the name of the part together with its dimensions and other physical properties, where appropriate.

The Req’d column indicates the quantity required per unit or as- sembly. When the item is listed for reference only or the quantity is not applicable, the term “Ref’ or a dash, respectively, appears in the column.

Pub. No. 107 917A ONORDSON CORPORATION 1988

All Rights Reserved

Issued 1 l/88

Page 22: Manual, Remote Temperature Controlleremanuals.nordson.com/adhesives/English_Manuals/107917.pdf · 2014-09-26 · Temperature Controller Manual 46-69 Page l-3 7. In drafty areas with

Manual 46-69 Page 6-2

Temperature Controller

One Channel Temperature Controller Parts List

Item Part No. No. Description Req’d

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27

109 093 107 887 101 185 109 250 274 650 274 651

274 653 982 221 983 411 984 700

985 111

937 159 933 477 600 082 984 529 939 257 108 976 815 190 981079 983 111 933 075 933 074 804 655

Cabinet, Gun Control Handle, 6 Inch Mounting Connector, Strain Relief Cord, Power, with Terminals Gasket, Connector, Cordset, Unit Gasket, Connector Connector, Socket, 12 Pin Cover, Connector, Socket, 12 Pin Screw, Pan Hd, M3 x 0.5 x 10 Washer, Flat, Narrow, M3 Nut, Hex, M3 Tag, Warning, Disconnect Power Rivet, Pop, 3132 x .032-.125 Nameplate Switch, DP Strocker Fuse Holder, 5 x 20 mm Nameplate, Nordson Oval Nut, Spring, Push on, .125 Lamp, Indicator, Rect, White Control, Temperature, Gun, Degree F Stand-Off, Terminal Block Screw, Pan Hd, #8-32 x .625 Washer, Lock, Split, #8 Strip, Marker, 8 Station Block, Terminal, 8 Station Kit, Ground Stud Wire Group

939 709 Fuse, 10 AMP, 5 mm x 20 mm, 250 VAC

1 1 4 4 4 1 6 1 1 2 1 2 1 1 2 4 4 1 1 1 1 2

Issued 11/88 ONORDSON CORPORATION 1988 All Rights Resewed

Pub. No. 107 917A