Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and...

36
Monitoring, Control and Alarm System m2 Manual Refrigeration and Air Conditioning Controls REFRIGERATION AND AIR CONDITIONING

Transcript of Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and...

Page 1: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

Monitoring, Control and Alarm Systemm2

Manual

Refrigeration and Air Conditioning Controls

R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G

Page 2: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

� Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

ContentsIntroduction 3

Safety 3

System Overview 4

Alarms 4Security 4Battery Backup 4External Connections 4

Technical data 5

Key Operation 5

Operation via the Key Pad 8

Point Overview 8Point Detail 8Inhibiting a Point 9Point Offset 9Single Point Log Printout 9Graphics 10Pulsed Input 10Alarm Mode 11Muting and Clearing an Alarm 11Main Menu 11Scan Mode 11No Scan 11Point Overview Scan 11Point Detail Scan 1�Alarm History 1�Point Alarm List 1�Event History 1�Print Menu 1�Alarm History 1�Software Version 13Setting the System Time and Date 13Daylight Saving 14Setup Information 14

Configuring the System via the Key Pad 15

Entering Characters in Edit Fields 15Numeric Only Fields 15Diacritic Entry 15Setup Menu 15Entering the Passcode 15Setting Installation Name 15Setting Temperature Units 16Setting Date Format 16Selecting a Point Number 17Name 16Setting the Point Type 16Setting the Units of Measurement 17Defrost Interlock Point 17Setting the Alarm Settings 17Setting the Alarm Action 17Setting the Log Action 18Setting the Graph Action 18Point Setup (Screen �) 18Input Source 18Remote Addr 18Input Type 19Input Number 19Y Axis 19Y Base 19

4 - �0mA Inputs 19Pulsed Input Setup 19Mode 19Pls/kWh 19Export �0Pulsed Input Installation Notes �0Resolution �0Defrost Synchronisation �0Password Setup �1Point Offset Passcode Protection �1Setting the Log/Chart Frequency �1Alarm Action Setup ��Output Name ��Action n ��Delay �3Duration �3Clear On �3Modem Dialout Options �3Dialout �4Call Type �4Number �4Pager Info �5Defining the Probe Curves �5Setting up a Curve Table �64-�0mA Set-up �6

Modem Configuration 27Baud Rate �7Dial �7Answer �7Language Selection �7'AKM' Call Type �8

Maintenance 29

Cleaning �9Service �9

Full Character Set 29

Alphanumeric Character Set 29

Remote Controller Parameters 30

Configuring The m2+ Via The Key Pad 30

Type 30Input Source 30Remote Addr 30Input Type 30Input Number 30

EKC 31

Alarm action setup 34

Page 3: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 3

Introduction

The m� has been developed to provide a comprehensive, yet simple-to-use means of monitoring, recording and control refrigeration temperatures and other aspects of refrigeration plant operation. It is intended for use in small to medium food storage operations (for example a small supermarket) where compliance with the Food Hygiene Regulations is to be demonstrated. A variety of ancillary control equipment may be in use in such installations, each with its own specific requirements in terms of interfacing and monitoring, and m� can be configured to work in such an environment.

Designed for operational simplicity, the system once configured can display the status of each input point in turn with the occurrence of any fault condition indicated immediately by means of audible and visual alarms. Further details on any aspect of the operation of the installation are available via the key pad. In addition there is the ability for authorised personnel to make adjustments to the control and/or monitoring settings. Historical data is stored within the system and may be viewed or printed on a regular basis. The data is accessible both on and off-site via the external modem connection and alarm calls can also be generated if required.

The following sections provide a description of m�, and the remainder of the manual provides further detail on the configuration, operation, and maintenance of the system. It is recommended that the appropriate part(s) are studied before any attempt is made to use the system.

ValidityThis manual was made in 10 - �007 and applies to m� - Dual Comms with software version 3.11.

Safety

To prevent accidents arising from improper handling, installation or operation, please read this manual carefully.

Page 4: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

4 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

System Overview The m� consists of a central monitoring unit which can monitor up to 16 local sensors or inputs which are usually located adjacent to the equipment in question for example specific refrigerated areas (chiller cabinets, freezers, cold rooms), plant rooms or gas detectors, up to 99 EKC - controllers and 3� standard RS485 connections (1�8 1/4 loads) via the third party bus. The precise layout and configuration of these sensors and controllers is specific to each installation, and it is not necessary for a typical operator to be familiar with the operation of the sensors.

The m� provides audio and visual alarms whenever an input exceeds its pre-set alarm levels. For night operation, the system can be pre-set to dial-out using a digital dialler or via a modem whenever an alarm occurs.

Security is provided by having passcode access to the protected settings. In the case of mains failure, an alarm is triggered after a delay. The system can be pre-set to dial-out to an external telephone number if required. The m� will always FAIL SAFE (except for modem dailout).

The unit is provided with battery backup to continue historical logging during a power failure. In this case, the display backlight will switch off but the display will keep running. When an alarm occurs, the alarm siren and the red flashing backlight will still operate. The backlight will flash red, once every 5 seconds until the alarm is muted.

Note: When a mains failure lasts longer than 1 hour, the unit will cease historical logging and stop alarm checking. However, all existing historical readings remain in memory and are not lost.

The m� can monitor up to a maximum of 99 points, including up to 99 EKC - controllers, and or an additional 3� standard RS485 connections (1�8 1/4 loads) via the third party protocol.

If hard copy details of the monitor readings is required, a parallel printer port is provided which can be connected to an Epson compatible parallel printer.

An RS�3� serial interface via a 9-way ‘D’ type connector is provided which allows either a directly connected IBM compatible Personal Computer (PC) or a Minitel to be connected for operational and configuration purposes or to allow connection to a modem.

If a PC is connected either directly or via the modem, the alarms and monitor readings can be read and the set-up details can be changed remotely, using Danfoss Central Station software (refer to manual RS.8C.G for more information).

This manual will simply cover the configuration and use of the m� in monitoring and controlling a refrigeration installation.

Alarms

Security

Battery Backup

External Connections

Page 5: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 5

egatlovylppuSzH06-05.c.a%51-/01+V511zH06-05.c.a%51-/01+V032

yalpsiD 46x042,DCLcihparG

noitarepO lenaptnorfnosnottubhsuP

stupnilangiS

rosneserutarepmet0001TProCTN 1 ,,langisFFO/NO

133/103/102CKE,Am02-4.stupniytrapdriht&srellortnoc

ycaruccagnirusaeMrosnesDTRhtiw

ot08-egnarehtniC°1-/+nahtretteBC°08+

noitcellocataD.xaMbM8

yticapaC 2

yalermralA A1.c.av42:daoL-2

noitcennocretnirP )elbitapmocnospE(lellaraP

pukcabyrettaB ruoh1 3

noitacinummocataD232SR

suB'NOL'584SR'ytraPdrihT'

segaugnaL 4

,hctuD,hcnerF,namreG,hsilgnEeseugutroP,nailatI

,hsinaD,naigewroN,hsinapS,hsiloP,nairagnuH,hsinniF,cidnalecI

hsidewS,hcezC

erutarepmettneibmAC°07+ot02-:tropsnarTC°05+ot0:noitarepO

HR%08-02:ytidimuH

erusolcnE 02PI

thgieW gk56.1

1. Only NTC's or PT1000's can be used at a time.

�. The data collection capacity depends on the amount of memory installed in the m� unit.

3. If a power failure lasts longer than one hour, the monitoring unit will stop the collection of data and the alarm monitoring. Already collected data will remain intact.

The functions of the keys on the front panel of the m� are described in the following sections.

Main Functions

Use this key to acknowledge or reset the alarm and mute the siren. The red ‘ALARM’ backlight will stop flashing and remain steady. Any ‘HIGH’ or ‘LOW’ alarm indication will also stop scrolling and remain steady.

Secondary Function

Operates as a shift key to give extended functions with other keys.

Main Functions

Use this key to select the main or previous menu from any other screen.

Secondary Functions

Cancels input data without storing in edit fields ('ESC' key).

Technical data

m2

Key Operation

Alarm Mute Key

Menu Key

Page 6: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

6 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Print Key

Up Arrow Key

Down Arrow Key

Left Arrow Key

Right Arrow Key

Main Functions

Use this key to select the Print Menu, except when in Alarm/Event history where it will directly print out a list.

Secondary Functions

Changes the Case/Sign in edit fields.

Main Functions

Use this key to scroll the highlight upwards on a menu screen. If the highlight is positioned on the first line of a menu, pressing this key will force the highlight to the bottom of the menu. In addition, when a character entry field has been selected, this key is used to increment the displayed value in the entry field.

Secondary Functions

Moves through the Point Detail screens, moves the cursor on the Overview screen and zooms in on the Graph screen.

Main Functions

Use this key to scroll the highlight downwards on a menu screen. If the highlight is positioned on the last line of a menu, pressing this key will force the highlight to the top of the menu. In addition, when a character entry field has been selected, this key is used to decrement the displayed value in the entry field.

Secondary Functions

Moves through the Point Detail screens, moves the cursor on the Overview screen and zooms out on the Graph screen.

Main Functions

Use this key to move the cursor to the left when a character entry field has been selected. In addition when an option has more than one screen associated with it (e.g. Point Detail), use this key to display the previous screen.

Secondary Functions

Moves the cursor on the Overview screen and moves the Graph Cursor.

Main Functions

Use this key to move the cursor to the right when a character entry field has been selected. In addition when an option has more than one screen associated with it (e.g. Point Detail), use this key to display the next screen.

Secondary Functions

Moves the cursor on the Overview screen and moves the Graph cursor.

Main Functions

Use this key to select an item from a menu or to enter a value and move the cursor to the next entry field ('↵' key).

Secondary Functions

Inhibits points, adds the Graph cursor to the Graph screen and selects points on the Overview screen.

Enter Key

Page 7: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 7

Multiple Key Functions

Operator/Equipment Safety

+

+

OR

+

+

Backspace in edit fields.

Adjusts Screen Contrast.

Starts or Stops the Scanning Mode on the Point Detail or Overview screen.

Diacritics (accented characters editing mode). or Sort and display alarms by point when in Point Detail Screen.

This equipment is safe to operate as long as the instructions in this manual are followed. High voltages are present inside the m� and the front access panel should not be opened while power is applied to the system.Ensure that mains power is disconnected before any maintenance is carried out. It is assumed that operators of the system will have adequate training on its use. Danfoss accept no liability for loss or damage caused by misuse of the equipment.

Page 8: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

8 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Operation via the Key Pad

Point Overview To view the status of all the points at the same time, select the Point Overview option from the Main Menu. The Point Overview screen is displayed. This screen shows each activated point as one of the following icons, depending on the point condition.

- active point in normal condition - an inhibited point

- active point in an alarm condition - a point in defrost

- a point in defrost pulldown

Note: If there are more than �0 points in the system extra lines of points will be displayed underneath the first �0 points (up to a maximum of 99 points).

To select a point, the cursor box can be positioned around a point symbol by using the ‘ ‘ or ‘ ‘ keys. As each point is selected the point number and its current status/temperature is displayed in the window on the right hand side of the screen.When the Overview Scan mode is selected, the cursor will cycle round all the activated points in turn, pausing for 3 seconds on each one so that the current status may be read.

To display more details of a particular point, position the cursor box around the point required and press ‘↵’. The Point Detail screen will be displayed.

Note: If a point has a local offset applied to it, this will be indicated by the

presence of the offset icon at the left of the Point Readout window.

To continuously view the status of a single point, either select the Point Detail option from the Main Menu or select a point on the Point Overview and press ‘↵’. The Point Detail screen is displayed.Use the ‘ ’ key to select the next point or the ‘ ’ key to select the previous point. The point number is displayed in the upper left-hand corner of the screen and the current status is displayed in large text in the centre of the screen. The text and symbols displayed in the window on the right hand side of the screen are as follows:

Indicates the upper alarm limit setting. When the of the symbol is scrolling, it indicates that the upper alarm limit has been exceeded.

Indicates the alarm delay in minutes. When the hand of the clock rotates, it indicates that the point is in the alarm condition and the delay has not yet expired.

Indicates the lower alarm limit setting. When the part of the symbol is scrolling, it indicates that the lower alarm limit has been exceeded.

Indicates the input point type.

this indicates whether the point has been setup for 'Local' or 'Remote' alarms.

- Local - alarms are raised based on m� alarm settings.

- Remote - alarms are raised based on controller alarm settings.

Point Detail

Page 9: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 9

Inhibiting a Point

Point Offset

This area also displays 'inhibit', 'defrost' and 'pulldown' icons, if the point has been setup for 'Local'.

- an inhibited point.

- a point in inhibit pulldown.

- a point in defrost.

- a point in defrost pulldown.

Note: If a point has a local offset applied to it, this will be indicated by the

presence of the offset icon located under the units indicator.When the Detail Scan mode is selected, the display will cycle through all the activated points in turn pausing for 3 seconds on each one so that the current status may be read.Press either the ‘ ’ key or the ‘ ’ key to return to the Main Menu or the ‘ ’ key to display the historical graph data.

To inhibit a point so that it cannot create an alarm, select the required point and press ‘↵’. The Confirm Inhibit Yes/No message is displayed. Use the ‘ ’ or ‘ ’ key to toggle the answer and press ‘↵’. When a point is inhibited a symbol is displayed alongside the point type. To uninhibit a point repeat the operation.

If the alarm condition is exceeded on an inhibited point (i.e. Pull-down), then the animated pull-down arrows will be displayed next to the inhibit symbol .The inhibit function can be password protected. This can be configured by accessing the 'Passcode Setup' screen.

Any points on the m� can have an offset applied to the displayed readings to compensate for cable runs loss etc. These offsets are point specific and may only be defined from the m� keypad, although their value is readable when accessing the unit remotely. Under normal circumstances these offsets (if required) will be entered at installation and should only be modified by Danfoss

personnel. Any point which has an offset active will display the offset icon on both the Point Detail and Point Overview screens.

In the Point Detail screen, pressing the ‘ ’ key displays the Print Range option box. Use the ‘ ’, ‘ , ‘ ’ and ‘ ’ keys to enter the required value and the ‘↵’ key

to move through each field. Press the ‘ ’ key and the Printing in Operation screen is displayed and the data is sent to the printer.

Single Point Log Printout

Page 10: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

10 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

The format of the printout will be as shown:

To display an instant graph of the currently selected point, from the Point Detail screen, press the ‘ ’ key. The chart is then displayed.The default time scale for the data displayed depends on the sample rate set. For example, a sample rate of 15 minutes will give a default time scale of 1 day.

To view historic data, press the ‘ ’ or ‘ ’ keys to page the graphic screens (with no overlap). Pressing the ‘ ’ or ' ' keys scroll through each of the points displaying the data graphs. Press the ‘↵’ to bring up the cursor, this can then be moved along left or right displaying the reading and time for the cursor position in the top right hand corner of the screen. In addition the screen will page left or right when the cursor reaches the end of the display. To zoom in or out press the ' ' or ' ' keys, this will display the following time spans:

45 mins 1� hours 4 weeks 1.5 hours 1 day 1� weeks 3 hours 3.5 days 11 months 6 hours 1 week

To exit the zoom facility, remove the graph cursor by pressing '↵' again. Pressing the ' ' key will then take you back to the Point Detail screen.

When a graph is displayed on the screen, pressing the ' ' key dumps the graph to a directly connected printer (cursor must be removed first).

A pulsed input function is available for accepting pulses from a power meter. The pulsed input is displayed as shown which includes two values. The large value is the ‘Rate’ and indicates either current kW usage (Const) once per minute or the ‘Peak’ kW usage within the current sample period.If the ‘Rate’ current usage is displayed, this value will vary with the actual energy consumed within the last minute. If the ‘Peak’ usage is displayed, this will only change if the usage in the last minute was greater than any other minute in the sample period - hence it will show the highest or ‘Peak’ value. The ‘Rate’ value is stored by the m� and will be displayed in the graph associated with this point.

The second smaller value will show the accumulated kWh used within the current sample period. This value will increase over the sample period then reset to zero at the end.

The ‘Pulsed Icon’ to the left of the display will change from to each time a pulse is being received.

Graphics

Pulsed Input

Page 11: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 11

In normal operation if no scan mode is selected, the m� will revert to the Point Overview screen.When one or more alarms have been raised, the built-in siren will sound, the backlight will flash red and the point(s) in alarm will pulse. If a parallel printer is connected, the time, status and point details of the alarm will be printed.If the ‘ ’ key is not pressed within the programmed time setting, the dial-out relay can be programmed to automatically activate, sending a signal to the dial-out equipment/security system if it is connected.

To stop the siren sounding and the red backlight flashing, press the ‘ ’ key. Check what the problem is by selecting the Point Detail screen for the point in alarm and noting its present status and alarm settings. The fault will need to be found and rectified before the alarm can be successfully cleared.If there appears to be no problem, it could be that the fault has ‘cleared itself’ (e.g. the temperature has since returned to an acceptable level). In this case, the point will stop pulsing. If there are no further faults on other points, the alarm status will be cleared.

To display the Main Menu, press the ‘ ’ key (repeat if necessary). To select an option from the Main Menu, use the ‘ ’ or ‘ ’ key to position the highlight over the required option and press ‘↵’ or ‘ ’. At the bottom of the menu there are two ‘ ’ symbols which indicate more options. To display these options, press the ‘ ’ key. When the highlight reaches the bottom of the screen, the menu will be scrolled upwards to reveal the extra options. Similarly, to re-display the first two options, press the ‘ ’ key. The first two options were described previously while the remaining options are described in the following sections.

Note:Options which have a symbol alongside them are password protected.

To select a scan mode, select the Scan Mode from the Main Menu. The Scan Menu is displayed.

Use this menu to select a scan mode which will cycle the display through all the active points. To select an option from the Scan Menu, use the ‘ ’ or ‘ ’ key to position the highlight over the required option and press ‘↵’. Once an option has been selected, the Main Menu will be re-displayed. You can then select the Point Overview or Point Detail option as appropriate.

The Point Overview or Point Detail screen can also be set to the appropriate scan mode by displaying the relevant screen and pressing the ‘ ’ and ‘ ’ keys together. Pressing them together again deactivates the scan mode.

Use this option to switch off the scan mode. Once this option is selected, no scanning will be performed on either the Point Overview or Point Detail screens. The default screen will become the Point Overview screen.

Use this option to select the scanning mode for the Point Overview screen. When this mode is selected, the cursor on the Point Overview screen will cycle round all the activated points in turn, pausing for 3 seconds on each one so that the current status may be read.

Alarm Mode

Muting and Clearing an Alarm

Scan Mode

Main Menu

No Scan

Point Overview Scan

Page 12: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

1� Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Use this option to select the scanning mode for the Point Detail screen. When this mode is selected, the display on the Point Detail screen will cycle through all the activated points in turn pausing for 3 seconds on each one so that the current status may be read.

To display the alarm history, select the Alarm History option from the Main Menu. The Alarm List screen is displayed with the most recent alarm heading the list.

Up to 999 latest alarms can be viewed.

Each alarm is given a number from 1 to 999 (restarting at 1 after the 999th) and is time and date stamped. The description shows the information relevant to each point. The two ‘ ’ symbols at the bottom of the screen indicate that the list continues. The list can be scrolled up and down using the ‘ ’ or ‘ ’ keys. Press ‘↵’ to display events with the alarms.

To display the alarm history for a point, select the point detail screen, then press

the and keys together. The Alarm List screen is displayed listing all alarms for the selected point only.

To display the event history, select the Event History option from the Main Menu. The Event List screen is displayed with the most recent event heading the list.

The latest 100 events stored are viewed. The list can be scrolled up and down using the ‘ ’ or ‘ ’ keys.

If a parallel printer is connected, a series of printouts can be initiated in condensed mode. To perform a print operation, select the Print Menu option

from either the Main Menu or by pressing the‘ ’ ‘key on all screens except the Alarm/Event List screens. In either case, the Print Menu screen is displayed.

Use this option to print the current status of all points.

Note: Only those points which have their log action set to ON will be printed.

Use this option to print an individual graph of each of the points in turn. From the Print Menu, select the Graph of All Points option. The Select Period screen will then appear. Use the ' ', ' ', ' ' and ' ' keys to enter the required value and the '↵' key to move through each field. The Printing in Operation screen is displayed and the data is sent to the printer.

Note: Only those points which have their graph action set to ON will be printed.

Use this option to print a list of all the alarms and events. The Alarm/Event List is printed showing the Alarm List followed by the Event List.

From the Print Menu, select the Alarm List option. The Select Period screen will then appear. Use the ' ', ' ', ' ' and ' ' keys to enter the required value and the '↵' key to move through each field. The Printing In Operation screen is then displayed and the data is sent to the printer.

Each alarm is given a number from 1 to 999 (restarting at 1 after the 999th) and is time and date stamped. The description shows the information relevant to each point.Similarly, each event is time and date stamped and the description shows the information relevant to each event.

Note: This operation may take considerable time and paper.

Point Detail Scan

Print Menu

Event History

Point Alarm List

Log of All Points

Graph of Selected Points

Alarm History

Alarm History

Page 13: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 13

The various codes printed in the status (St) column are defined as follows:ok No fault presentAlm Equipment faultdEF Defrost dEP Defrost pulldown - (only shown on display)dFP Defrost pulldown - (only shown on printouts)E Equipment (status ok) Err Equipment (status alarm) Flt Comms faultHi High alarmInh Inhibit Low Low alarmOff The input is off OVR Defrost overrun alarmOC Signal over range SC Signal under range The various codes displayed in the printout Reason column are defined as follows:Aft.Def Alarm after defrostFault probe fault> High value alarm greater than high alarm limit< Low value alarm less than low alarm limit.

Use this option to display the units software and hardware details for reference. To return to the Main Menu, either wait 1 minute or press any key.

To set the system time and date, select the Time / Date option from the Main Menu. The Password request is displayed. Enter your User passcode (the default passcode is WOODLEY or the Local passcode).

Use ‘ ’ or ‘ ’ keys to cycle through the character list to the required value and the ‘ ‘ or ‘ ‘ key to move the cursor left or right respectively. Then press ‘↵’ to move onto the next field.

The system time and date are read from the internal clock. If these are incorrect amend them as appropriate.

The Start Day and End Day settings are used to indicate the start and end of trading. This allows the system to perform different operations depending on the time of day.

For example, the system could be set up so that during the day only an audible alarm is activated, whereas the system would dial-out at night.Select each of the days in turn and type in or amend the times as required.

· Use the ‘ ’ or ‘ ’ keys to cycle through the day of the week and the special days.

· Set the Start and End day values.

· Set the date of any Special Days (dd/mm) (5 Special Days maximum).

The Special Days are used to override the normal weekday start and end times.

Note: The Special Days will occur every year if they are not changed.

Software Version

Setting the System Time and Date

Page 14: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

14 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Setup Information

This facility is to set the automatic clock change for winter/summer time.

From the System Times Setup menu, use the ‘↵’ key to highlight the Daylight Saving ‘ ’ symbol, then press the ‘ ’ key.

The Daylight Saving setup menu is then displayed. Use the ‘ ’ or ‘ ’ keys to scroll through the following options:

Mode - Off - Daylight saving switched off. Auto-US - American daylight saving time settings. Auto-EU - European daylight saving time settings. Manual - Times and offset can be manually set.

Time - The hour at which the change will take place.

Offset - The amount in hours the clock will change.

Use this option to print out all setup information. From the Print Menu, select the Setup Information option. The Printing in Operation screen is displayed and the data is sent to the printer.

Daylight Saving

Page 15: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 15

Configuring the System via the Key Pad

Entering Characters in Edit Fields There are two types of character sets that are used in the m� depending on which edit field has been selected:

Full Character Set This is used in most of the edit fields. When the edit field has been selected, the characters within the set can be cycled through using the ‘ ’ or ‘ ’ keys. If the ‘ ’ key is pressed first, it will start at ‘A’ and go forward through the character set. If the ‘ ’ key is pressed first, it will start at ‘z’ and go backwards through the character set.

When a character has been selected, press either ‘ ’ to move to the next space or ‘↵’ to move to the next edit field.

Alphanumeric Character Set If the ‘ ’ key is pressed first, it will start at ‘0’ and go forward through the character set. If the ‘ key is pressed first, it will start at ‘z’ and go backwards through the character set.

By pressing the ‘ ’ or ‘ ’ keys, the field is incremented or decremented. By pressing the ‘ ’ or ‘ ’ keys you can skip across the unit fields to make entering larger numbers easier.

If your language uses Diacritics (accented characters), the m� provides the facility to enter these both from the local keypad and remotely via PC. This facility is language sensitive such that only Diacritics which are relevant to the language active on the unit are available. The method of entry is to select a base character as normal and then add the required accent, e.g. in French if an ‘é’ is required the procedure is to first select ‘e’ as described above, then enter Diacritic mode and select the acute accent ´. To enter a Diacritic mode on a

suitable character, hold down the ‘ ’ like a shift key and press the ‘ ’ key once. This will add the first available accent to your character, any more which are available can then be selected by pressing the ‘ and ‘ ’ keys together. When the required accent is displayed, simply moving on to the next character stores this and cancels the Diacritic mode. If you move the cursor onto an already accented character, the unit will automatically enter Diacritic mode allowing you to change the accent. Diacritic mode may be manually cancelled by pressing the

‘ ’ and ‘ ’ once more.

To configure the system via the key pad, select the Setup Menu option from the Main Menu.

To change any of the configuration information via the keypad, you must first enter the correct password. The default passcode is �91. However, this may have been changed to a passcode which is site specific.

Enter in the password using the ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively. When the password is complete, press ‘↵’.

The installation name is displayed on the Point Overview screen, the Alarm History screen, the Event History screen and on the various printouts.

To set the installation name, select the Installation Name option from the Setup Menu.

Numeric Only Fields

Diacritic Entry

Setup Menu

Entering the Passcode

Setting Installation Name

Page 16: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

16 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Setting the Point Details

Selecting a Point Number

Name

Setting the Point Type

Setting Temperature Units

Setting Date Format

Enter the installation name using the ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively. You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the cursor. When the installation name is complete, press ‘↵’, then ' ' to return to the Setup Menu. Next time you display the Point Overview screen the installation name will appear at the top of the screen.

The m�'s temperature unit of measurement can be set to either fahrenheit or centigrade. To select the temperature unit, press the '↵' key to move the active field box around the 'temperature units' field, then use the ‘ ’ or ‘ ’ key to toggle between fahrenheit and centigrade.

The date format of the m� unit can be set to either 'DD/MM' or 'MM/DD'. To select the date format required, press the '↵' key to move the active field box around the 'temperature units' field, then use the ‘ ’ or ‘ ’ key to toggle between 'DD/MM' and 'MM/DD'.

To set up the details of an individual point, select the Point Setup option from the Setup Menu. The Point Setup screen is displayed with the point number displayed in the top left hand field.

To select a different point number, use the ‘ ’ or ‘ ’ key. As each number is selected, the settings for the selected point are displayed.

To set the name of an individual point, ensure that the cursor is on the correct point number and press ‘↵’. The cursor will move to the Name field. Enter the installation name using the ‘ ’or ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively. A maximum of 18 characters can be entered into this field.You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and ‘ ‘ to change case. When the installation name is complete, press ‘↵’. The edit box will move onto the next field.

To set the point type, repeatedly press ‘↵’ to cycle through the fields until the Type field is highlighted. The input type code refers to the input connected to that point. This can be altered by using the ‘ ’ or ‘ ’ keys to scroll through the list of available types, which are defined as follows.

Off No input connectedRTD PT1000 temperature probe (-100 to +100°C) PT1000VersionOnly

PT1 Low temp. thermistor probe (-80 to 0°C) ThermistorVersionOnly

PT2 Standard thermistor probe (-40 to +40°C) ThermistorVersionOnly

PT3 High temp. thermistor probe (0 to +100°C) ThermistorVersionOnly EKS EKS111 probe (-35 to +85°) PT1000VersionOnly

Low Not applicableEno Equipment (normally-open)Enc Equipment (normally-closed)Dno Defrost interlock (normally-open)Dnc Defrost interlock (normally-closed)420 4-�0 mA input*Cf1 Programmable curve No.1 - input is cross-referenced to a table held in memory.Cf2 Programmable curve No.� - input is cross-referenced to a table held in memory.Cf3 Programmable curve No.3 - input is cross-referenced to a table held in memory.Cf4 Programmable curve No.4 - input is cross-referenced to a table held in memory.

Page 17: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 17

Setting the Units of Measurement

Defrost Interlock Point

Setting the Alarm Settings

Ana Remote analogue input and m�+ units.EKC EKC - ControllersCTL Third Party Controllers

* The 4-�0 mA input is passive. It requires an external 1�-�4 V isolated power supply. Default settings are 0 to 100% (0=4mA and 100=�0 mA). Zero and full scale can be modified via the second Point Setup screen. Values can be between -99 and 999. Applications of 4-�0 mA can be for pressure tranducers, temp, flow, humidity, level, etc.

To set the units of measurement, repeatedly press ‘↵’ to cycle through the fields until the Units field is highlighted.

Enter the units required using the ‘ ’ or ‘ ’ keys to cycle through the character list and the’ ' or ‘ ’ key to move the cursor left or right respectively.

Note:This is a text field only and does not effect the operation of the system. It will not be available if DNO, DNC, ENO or ENC is selected. You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and ‘ ‘ to change case. When the units have been set, press ‘↵’. The edit box will move onto the next field.

Select the point to be used for defrost as previously described. Use the ‘ ’ or ‘ ’ keys to alter the point type code, if necessary, to “Dno” (defrost interlock, normally-open relay) or “Dnc” (defrost interlock, normally-closed relay). Select the point to be interlocked to the defrost and repeatedly press ‘↵’ to cycle through the fields until the Def Int Pt field is highlighted. Use the ‘ ’ or ‘

’ keys to alter the point number to the defrost input.

For example, if probe 1 is a temperature probe and point 16 is a defrost input contact, set 16 as the defrost interlock in probe 1’s settings.

Select the point as previously described. Repeatedly press ‘↵’ to cycle through the fields until the High field is highlighted. Set this field to set the value at or above which an alarm will occur by using the ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively. When the high temperature alarm point has been set, press ‘↵’. The edit box will move onto the next field.Repeat the operation for the Low field, to set the value at or below which an alarm will occur. Press ‘↵’ to move the edit box onto the next field. Repeat the operation for the Delay field. Set the length of time (in minutes) that the fault must be present before an alarm is raised.

Select the point as previously described, then repeatedly press ‘↵’ to cycle through the fields until the Action field is highlighted. The status display shows the alarm action number. Use the ‘ ’ or ‘ ’ keys to set the required alarm actions. These alarm actions can then be set to carry out the desired functions.

For example, point number 3 could be set to have alarm action 1 which sets the siren and dials out to a modem. Whereas, point number 4 could be set to alarm action � which sets the siren, dials out to a pager as well as the modem, etc.The alarm actions are as follows:

0 Turns the alarm off.

1 - 8 Sets alarm actions 1 to 8.

Setting the Alarm Action

Page 18: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

18 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Setting the Log Action

Setting the Graph Action

Log printouts are available for selected points on a timed or demand basis via the print menu. When a log is printed only points with the log action field appropriately set will be output. The available settings are:

Off Set this point to OFF if you do not want this point to be shown on any log printouts.

Timed The point will be automatically logged after a specified time delay.

Manual The point will be logged on demand only.

On Set this option to ON if you require this point to be shown on the timed log printouts and also on log on demand printouts.

Repeatedly press ‘↵’ to cycle through the fields until the Log field is highlighted. Use the ' ' or ' ' keys to set the required log action and press ‘↵’ to move the cursor onto the next field.

Graph printouts are available for selected points on a timed or demand basis via the print menu. When a graph is printed only points with the graph action field appropriately set will be output. The available settings are:

Off Set this option to OFF if you do not want this point graph to be shown on any graph printouts.

Timed The graph for this point will be automatically printed after a the time specified in the Log/Graph Setup screen.

Manual The graph for the point will be printed on demand only.

On Set this option to ON if you require a graph for this point to be printed after the time specified in the Log/Graph Setup screen and also on ‘graph on demand’ printouts.

Repeatedly press ‘↵‘ to cycle through the fields until the Graph field is highlighted. Use the ' ' or ' ' keys to set the required graph action.

With the Graph field highlighted, press and hold down the ‘↵’ key until the second Point Setup screen is displayed or press the ' ' in the point type field.

The point number and name are the same as those described in first Point Setup screen and cannot be edited here.

Use this field to specify whether the input is connected directly to the m� master unit (Local), via a m�+ or third party controller (T-Party) or (Remote) via a EKC controller (Echelon). The input source can be set by pressing the ‘ ’ or ‘

’ keys to the required option. By default the first 16 points are programmed to use the 16 local inputs. This configuration is not fixed and may be changed. Press the ‘↵’ key to move onto the next field.

If ‘T-Party’ has been specified for the Input Source, then this field is used to specify the remote address (refer to relavent controller manual or the m� Instructions RI.8B.M for the m�+ units). If 'Echelon' has been specified for the Input Source, then this field is not accessible as it is set from the EKC controller.

Input Source

Point Setup (Screen 2)

Remote Addr

Page 19: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 19

Input Type

Input Number

Y Axis

Y Base

4 - 20 mA Inputs

Use the ‘ ’ or ‘ ’ keys to cycle through the character list to the required value and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively. Press the ‘↵’ key to move onto the next field.

Use the ‘ ’and ‘ ’ keys to cycle through the valid options as follows: · RESISTOR Resistor input.· CURRENT 4 - �0 mA input. · DIGITAL Normally open or normally closed contacts (Contact).· PT1000 PT1000

This field is to specify the input number of the (Remote) third party controller or m�+ unit.

Use the ‘ ’ or ‘ ’ keys to cycle through the character list to the required value and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively. Press the ‘↵’ key to move onto the next field.

This field refers to the overall size of the graph temperature range. Entering zero selects the auto-scale option. Alternatively, enter the required range. The range goes from the lowest graph point (Y Base value) to the highest graph point. Use the ‘ ’, ‘ ’, ‘ ’ or '‘ ’ keys to enter the required value.

This field refers to the lowest value the graph will show. This value should be slightly lower than you expect the temperature to drop to. If auto scale in the Y axis is selected this value is not used. Use the ‘ ’, ‘ ’, ‘ ’ or '‘ ’ keys to enter the required value.

These values are used exclusively in conjunction with a standard 4-�0 mA input which can represent pressure, humidity, level, flow rate, or any other variable which can produce a 4-�0 mA output.

The value for the upper and lower limits can therefore represent % (RH), PPM, bar or psi etc., depending on the medium being measured. A numerical value for 4 mA (lower limit) and �0 mA (higher limit) is entered, and the m� automatically scales the input for a figure proportional to the measurement. Use the ‘ ’, ‘ ’, ‘ ’ and ‘ ’ keys to enter the required value.

Finally, press ‘ ’ to return to the Setup Menu.

To setup the pulsed input, from the Point Setup menu select ‘PLS’ in the Point Type field. All the remaining fields in ‘Screen 1’ of the Point Setup are the same as normal.

In ‘Screen �’ of the Point Setup there are a couple of extra fields added. These are as explained below:

This field is to set either the ‘Constant’ or ‘Peak’ value to be used as explained previously.

This field is to set the amount of pulses that is to be recieved from the power meter per kWh.

Pulsed Input Setup

Mode

Pls/kWh

Page 20: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

�0 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

If the Pulsed Input is being setup via Danfoss Central Station software, there is an extra field named ‘Export’ that can be used.This field is set if the points data is to be exported to AKM format for analysis by Power Focus or similar software.

The m� Pulsed Input requires a volt free contact or an open collector and the pusle width must be a minimum of 80 mS.

The Pulsed Input will operate with either PT1000 or Thermistor m� input boards.

The resolution of the pulse data depends on the sample rate of the m� – the longer the sample rate, the greater the resolution, as well as the resolution of the power meter being used.

For example: If the power meter outputs five pulses for every Kilo Watt Hour (KWh) and with a current usage of 6 KW.

With an m� sample rate of 3 minutes:

1or2pulsesreceivedper3minuteinterval((5pulsesx6KWh)/60minutes)x3minutes=1.51pulsex0.2KWx20(for1hour)=4KW2pulsesx0.2KWx20(for1hour)=8KW

Resolutionis4.Valuescouldeitherbe0,4,8,12etc.With an m� sample rate of 15 minutes:

7or8pulsesreceivedper15minuteinterval((5pulsesx6KWh)/60minutes)x15minutes=7.57pulsex0.2KWx4(for1hour)=5.6KW8pulsesx0.2KWx4(for1hour)=6.4KW

Resolutionis0.8.Valuescouldbe0,0.8,1.6,2.4,3.2,4.0,4.8,5.6,6.4etc.

With the Peak option, the sample rate is 1 minute (though the storage rate is whatever the m� is set for) which gives a very poor graph resolution, this makes the Peak value very inaccurate unless the power meter outputs many pulses per KWh.

This option allows the coordinated defrost setup of a network of EKC controllers. From the Setup Menu, select the Defrost Schedule option.

Use the ‘↵’ to highlight the field to be modified. Use the ‘ ’ and ‘ ’ keys to scroll through the character or options list and the ‘ ’ and ‘ ’ keys to move the cursor left or right respectively.

Set the values as follows:

Number Set this to the point number required for the defrost schedule.

Name Enter the name required for this defrost schedule (this is the point name).

Mode Select either ‘Master’ or ‘Follows’ depending on whether the controller being setup is a ‘Main’ or ‘Secondary’ controller. If ‘Master’ has been set, then the next field becomes active in which the controllers address needs to be entered.Coordinate This field only becomes active if ‘Master’ is selected in the previous field. Select either ‘Yes’ or ‘No’ depending on if the ‘Secondary’ controllers information is to be used for end of defrost control.

Export

Pulsed Input Installation Notes

Resolution

Defrost Synchronisation

Page 21: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 �1

Defrosts per This field only becomes active if ‘Master’ is selected in the Day previous field. Enter the amount of defrosts per day required, then whether the times are to be set ‘Manually’ or ‘Auotmatically’.

Manual - all defrost times entered manually.

Auto - select the number of defrosts per day, enter the first defrost time, then the remaining times will be calculated for a �4 hour period.

Day Night Select either ‘Yes’ or ‘No’ depending on whether the Day/ Control Night Control on the controller is to be activated of not.

This option allows you to change the three different levels of passcodes – Main, Local and User, also the Inhibit Protection can be activated. The Main and Local Passcode provides access to all the setup screens. The User Passcode only provides access to the Time/Date setup.

From the Setup Menu, select the Password Setup option.

Use the ‘↵’ to highlight the passcode to be modified. Type in the passcode using the ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘

’ key to move the cursor left or right respectively. N.B. Local passcode is numeric only. You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and ‘ ‘ to change case. When the passcode has been set, press ‘↵’ then ‘’ to return to the Setup Menu.

To set the Inhibit Protection, use the ‘↵’ key to highlight the 'Inhibit Protected' field, then using the ‘ ’ or ‘ ’ keys to select either 'Yes' or 'No'.

To set the Point Offset Passcode Disable, use the ‘↵’ key to highlight the ‘Pt Offset Disable’ field in the Passcode Setup menu, then using the ‘ ’ or ‘ ’ keys select either ‘Yes’ or ‘No’.

To set the print frequencies, select the Log/Chart Frequency option from the Setup Menu.

Use the ‘↵’ to highlight the field to be modified. Type in the time required using the ‘ ’and ‘ ’ keys to cycle through the character list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively.

Set the values as follows:

Log Print Interval Set this value to determine the interval between log prints (hours : minutes). Start Print at Enter the time in the day in which you require the printing of the automatic log readings to start. (Only points that have been set as Timed or ON will be printed). Graph Print Interval Set this value to determine the interval between graph prints. Start Print at Enter the time in the day that you require the automatic graph to be printed. (Only points that have been set as Timed or ON will be printed.)Sampling Rate Set this field to the frequency of sampling required for the graphs.

Setting the Log/Chart Frequency

Password Setup

Point Offset Passcode Protection

Page 22: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

�� Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

The sample frequency affects the amount of data that will be stored in the units memory.

TDays = Total number of days stored in memory

Freq = Graph sample frequency

Pt = Highest point number used

Total = Total memory available - �Mb = �09715� - 4Mb = 4194304 - 6Mb = 6�91456 - 8Mb = 8388608

TDays = Freq x (Total - 464000) 1440x(6+(2xPt))

Freq = 1440 x TDays x ((� x Pt)+6) Total - 464000

Example table for days using 40 points. Freq Days 1 47 � 94 5 �35 10 471 15 706

Example table for frequency using 40 points. Days Freq (in minutes) 100 � �00 4 300 6 500 11 700 15These calculations can alter if a large amount of alarms are stored.

Use this option to define the action to take place when an alarm occurs. From the Setup Menu, select the Alarm Action Setup option.Use the ‘ ’ or ‘ ’ keys to cycle through the devices and complete the fields for each device as described below.

RELAY 1 MODEM � RELAY � MODEM 3 SIREN MODEM 4 LAMP MODEM 5 FLASH PRINT MODEM 1

Type in up to 8 characters as an appropriate name for the output device. Use ‘’ or ‘ ’ keys to cycle through the character list and the ‘ ‘ or ‘ ‘ key to move

the cursor left or right respectively.You can use the ‘ ‘ and ‘ ‘ keys together to delete the character before the

cursor and ‘ ‘ to change case. Press ‘↵’ to move onto the next field.

Use this field to specify when the device is to be used. Set the trigger as follows for each of the Alarm Actions:

0 Always OFF (Never trigger)

1 Always ON (day and night) (Always trigger)

D ON during the day (Trigger during the day only)

N ON during the night (Trigger during the night only)

Output Name

Action n

Alarm Action Setup

Page 23: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 �3

For example, on the Alarm Action Setup screen illustrated, Alarm Actions 1, � and 7 will always trigger Relay 1.Note: The alarm action number is set for each point in turn so that pre-determined actions occur when that point is in alarm.

Use this field to specify the delay time in seconds before the device is activated by an alarm. For example, if the site is manned, a delay of say 10 minutes could be entered giving the staff time to respond to the alarm before the dial-out operation occurs. Use ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ‘ or ‘ ‘ key to move the cursor left or right respectively.

For RelaysUse this field to specify the time in seconds that the relay will be activated.

Note:-Entering “999” will activate the relay until the ‘clear on’ condition occurs.

For ModemsUse this field to specify the time in seconds between an unsuccessful call and the next attempt.

Use this field to specify the clear alarm operation as follows:

NoACK Clears the alarm condition when no new or no acknowledged alarms are present.

Mute Clear the alarm when the Mute key is pressed.

Time Clear the alarm when the time specified under Duration has expired.

MuteR When in alarm, if the 'Mute' key is pressed then the relay will open. If after the 'Duration Time' the alarm is still present, then the relay will close again. If the 'Mute' key is not pressed, then the relay will open after the 'Duration Time' for 10 seconds. This will continue until the input triggering the alarm has been reset.

ClrR Same as above except for pressing the 'Mute' key will not open the relay.

Note: It is not recommended that ‘999’ is specified with ‘Time’ as the system would have to be switched off to clear the alarm.

Finally, press ‘ ’ to return to the Setup Menu.

Use this option to set the modem dialout settings. From the Setup Menu, select Modem Dialout Options.

When connected to a modem, the m� is able to make telephone calls to up to five pre-programmed numbers whenever an alarm is detected. Alternatively, individual alarms detected for a particular point can be routed to a particular telephone number. It can also call a radio pager to alert a duty engineer. Three types of pager can be supported - Tone only, Numeric and Alphanumeric. The message that is sent can also be defined.

Note: Support for the TAP pager protocol is available in UK, France, Switzerland and Scandinavia.

Modem Dialout Options

Duration

Clear On

Delay

Page 24: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

�4 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Use the ‘ ’ or ‘ ’ keys to cycle through the dialout numbers and complete the fields for each device as described below:

Use this field to specify the type of device which is connected to the specified telephone number. The options are as follows:

NO DIAL Inhibits the output.

GSM SMS Indicates that a RS�3�/GSM modem device is connected. Sends text messages to a GSM mobile phone and receives messages. For information on this feature refer to document Functional Description RC.8A.M.

DOWNLOAD Indicates that a computer is connected (directly or remotely). Sends the alarm message using Woodley Xmodem Alarm protocol. If the line is busy, the telephone number will be dialled up to four times (8 bit, No Parity, 1 Stop Bit).

AKM Same as above, except that dialout attempts will continue; after every 10 attempts will reset the alarm relay. Note:Modem must be wired in conjunction with the alarm relay (refer to appendix A). BEEPER Indicates that a beeper type pager is connected. The system dials the appropriate telephone number and then disconnects. As there is no security associated with this option, the telephone number is always dialled twice unless the busy tone is received. MESSAGE7 Indicates that a 7 bit modem is connected with a printer attached. (7 bit, Even Parity, 1 Stop Bit) (normally used in France). MESSAGE8 Indicates that an 8 bit modem is connected with a printer attached. (8 bit, No Parity, 1 Stop Bit) (normally used in UK). PAGER7S Indicates that a TAP 7 bit protocol pager is connected which can display a message. The message sent is defined on the Pager Info line (7 bit, Even Parity, 1 Stop Bit).

PAGER7M Identical to PAGER7S but sends message up to 4 times.

PAGER8S Indicates that a TAP 8 bit protocol pager is connected which can display a message. The message sent is defined on the Pager Info line (8 bit, No Parity, 1 Stop Bit).

PAGER8M Identical to PAGER8S but sends message multiple times.

Enter the appropriate telephone numbers for each of the devices used. If a comma ‘,’ is inserted before the number, a delay of between � and 4 seconds will be inserted between the modem picking up the line and dialling. If a ‘w’ is inserted before the number, the modem will wait for the secondary tone before dialling.

For a message to be sent to a pager, two items of information must be supplied in addition to the Tap Pager server telephone number.1. The pager I/D, this is normally marked on the pager.

�. The text message to be sent to the pager.

Dialout

Call Type

Number

Page 25: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 �5

Text codes can be added that add other information into the message. These codes are as follows:

\S Sends the Store Name. \A Sends the Last Alarm Message \C Sends a count of alarms and muted alarms in the format �/4. \R Sends the Carriage Return (CR) character. \L Sends the Line Feed (LF) character. \\ Sends the \ character. // Sends the / character. \N Sends output name.An typical text string will take the form:

123456\RAlarmat \S = \A\RThis page info string would cause pager '1�3456' to receive a message in the form"Alarm at Danfoss Superstore = 24 Fresh Fish 6.4 Hi>6.0"The pager info field is limited to a maximum of 30 characters

Finally, press ‘ ’ to return to the Setup Menu.

Probe curves can be used to define the relationship between input Resistance or Current values and engineering units (e.g. Temperature, Pressure etc.). For example, probe curves could be used for a gas detection sensor.

This option allows you to define such a relationship for 4 separate curve types using information about Resistance/Current to Output Value transfer characteristic of a given probe, supplied by probe manufacturers. From the Set-up Menu, select the Define Probe Curves option. The Curve Table Set-up screen is displayed. There are 4 curve tables available - Cf1, Cf�, Cf3 and Cf4. Use the ‘ ’ or ‘ ’ keys to cycle through the curves until the correct type is displayed.

The table can have up to 1� break points to define the Curve Table relationship. Each of these break points will have a corresponding Input and Output value which must be entered by the user. The Output value will be the reading which should be displayed on the Point Detail /Overview Screen for a given Resistance/Current value. The Input Value will be an Internally Scaled version of that Resistance/Current Input value.

Below are explanations of each fields displayed for defining the curve tables:

Con 1 as This field is for selecting either 'RESISTOR' or 'CURRENT' depending on the type of probe being used.

To use = This field displays the Internally Scaled version of a Resistance/Current connected across the unit's Input 1 and COM terminals. This value will be in the range of 0 to 9999. This readout is used to determine what to put in the Input field when setting up the Curve Table.

Converted = This field displays the result of applying the selected Curve table function to the 'To use =' value being displayed. Thus when no Break Input & Output values have been entered, this will give an out of range reading (SC/OC). As a Curve Table is built up, however, it will start to show the Output value corresponding to whatever the Resistance/Current connected across Input 1.

Defining the Probe Curves

Pager Info

Page 26: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

�6 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Curve This field is used to select 1 of the 4 curve tables (Cf1 - Cf4).

Break This field is used to select the break point being set up on the curve (1 - 1�).

Input This field is for the Internally Scaled input value to be used at the break point selected. The 'To use =' value can be copied into this field by pressing ' ' and ' ' together. This field has a range of between 0 and 9999.

Output This field is for the Output value at the Break Point/ Input value selected. This has a range of between -999.9 and 999.9.

The table should be completed so that the Input readings increase in value. Any reading below the first value or above the last value will return out of range Output Values (OC/SC).In order to set up a Table you will require either a Resistance box (for resistance probes) or a Current Source (for Current Probes) plus the manufacturer's data defining the Input/Output relationship of the probe. The method is described for a Resistance probe, but it is the same for the Current case except that it is necessary to put the Input 1 link in the 4-�0 mA position before starting.

1. Select (up to) 1� Output (Resistance) values from the manufacturer's data sheet which correspond to Input (e.g. Temperature) values in the range you wish to measure. For maximum accuracy these points should be distributed evenly across the required range.

�. Connect the Resistance Box across the Input No. 1 and C terminals of the unit and set it to the lowest of your selected Output values. When you do this you should see a value appear in the 'To use =' field. This is the Internally Scaled version of the resistance you have connected. Set the Break field to 1 and then go to the Input field.

3. Next either manually enter the value displayed in the 'To use =' field, or press the ‘ ‘ and ‘ ‘ keys together to copy it to the Input field.

4. Move to the Output field and enter the Output (e.g. Temperature) value from your probe data corresponding to the Resistance value you set.

5. Move the Edit Box to the Break field again and increase its value by 1, which will clear the Input and Output fields.

6. Set your next chosen Resistance value from the probe data and, when the 'To use =' value has stabilised, repeat from step 3 until all your points have been entered.

Once all points have been entered, you can vary the resistance connected to Input 1 and observe the effect in the Converted field. For a given resistance, this value should now be the same as that shown in the manufacturer's probe data.

For 4-�0 mA inputs the 'Input type' must be set to 'CURRENT', then the Input/Output fields will change to 4 mA/�0 mA. The curve table can now be set up. For example, if a pressure sensor was being used which produced 4 mA at 0.1 bar and �0 mA at 30 bar, then simply add 0.1 to the 4 mA field and 30 to the �0 mA filed. Ensure the point set-up and jumper link on the input terminal is set to 4-�0 mA.

When you have finished or to abandon the operation, press ‘ ’ to return to the Setup Menu.

Setting up a Curve Table

4-20 mA Set-up

Page 27: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 �7

Language Selection

Answer

Baud Rate

Dial

Modem Configuration When connected to a modem, use this option to configure the modem settings. From the Setup Menu, select the Modem Configuration option.

Use the ‘ ’ or ‘ ’ keys to cycle through the valid baud rates to the required value and press ‘↵’ to move onto the next field.

Enter the dial code you require. Use the ‘ ’and ‘ ’ keys to cycle through the character list and the ‘‘and ‘‘ keys to move the cursor left or right respectively.

Enter the answer code you require. Use ‘ ’ or ‘ ’ keys to cycle through the character list and the ‘ ‘ or ‘ ‘ key to move the cursor left or right respectively.

Note: Refer to your modem handbook for details of the valid modem commands and answer codes.

When you have finished or to abandon the operation, press ‘ ’ once to return to the Setup Menu and again to return to the Main Menu.

The m� supports several languages, as listed below:

English Swedish HungarianFrench Norwegian PolishGerman Danish CzechDutch Icelandic FinnishItalian Spanish

Selecting Change Language from the Setup Menu will present you with the appropriate list of languages for your unit. Selection of the required language will refresh the screen to display the Main Menu in the new language and will automatically adjust the range of Diacritics (accented characters) available in Edit Fields.

Page 28: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

�8 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

'AKM' Call Type

Background The Danfoss AKM has been updated to allow it to receive alarms from m� units. However the m� alarm dialout procedure differs from the Danfoss Gateway in that it is not as tolerant of faulty telecommunication equipment. The m� would make repeated calls to try to transmit the alarm message up to a maximum of 8. This conformed to the current telecommunication regulations when the procedure as defined.AKM will continue to try to transmit the alarm indefinitely. It can also control the power to the modem using one of it relays. It does this after ten failed attempts to dial-out and every 6 hours.The 'AKM' call type has been created to mimmic the same dialout as the AKM.

The m� has two relays that are normally used for alarm indication. The Relay � (REP ALARM) can be used to control the modem power. The Relay is rated at �4V 1A max, so the low voltage power after the mains transformer must be switched. Mains voltage MUST NOT be connected to this relay.

Modem to m2 Wiring

Dial Out Settings

Alarm Action Setup:eciveD sgnitteS noitpircseD

:2yaleR 000000000:reggirT lortnocrewopmedomselbanE

nmedoM :reggirT deriuqersAceS0:yaleDceS0:noitaruD

emiT:nOraelC

.thgindnayadNOmedomspeek,111111111yllausU.tuolaidtsrifdnamralaneewtebyaleD

.llactaeperhcaeneewtebyaleD.sseccuslitnutuolaideunitnoC

Modem Dial Out Setup:tuolaiD sgnitteS noitpircseD

:5-1 MKA:epyTllaC:rebmuN deriuqersA

:ofnIregaP

.stpmettaseunitnoctpecxe'daolnwoD'saemaS.rebmunenohpeletMKAehT

.deriuqertoN

Page 29: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 �9

Maintenance

Cleaning To keep the m� free from dust, periodically wipe the outside surface with a soft dry cloth. DO NOT use any abrasive cleaners, wax or solvents. Stubborn marks may be removed by using a soft cloth dampened with a mild detergent.

This m� unit should be serviced only by a qualified service personnel and should ensure that replacement parts match the original safety characteristics.

CAUTION: This unit is fitted with rechargeable batteries, use only manufacturers replacements.

Service

Full Character Set Alphanumeric Character Set

A a )ecaps(

B b !

C c "

D d #

E e $

F f %

G g &

H h '

I i (

J j )

K k *

L l +

M m ,

N n -

O o .

P p /

Q q 0

R r 1

S s 2

T t 3

U u 4

V v 5

W w 6

X x 7

Y y 8

Z z 9

[ { ;

\ | <

] } =

^ ~ >

` º

0 V

1 W

2 X

3 Y

4 X

5 a

6 b

7 c

8 d

9 e

A f

B g

C h

D i

E j

F k

G l

H m

I n

J o

K p

L q

M r

N s

O t

P u

Q v

R w

S x

T y

U z

Page 30: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

30 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Configuring The m2+ Via The Key Pad

The controller's parameters can also be modified using a PC connected to the m� running Danfoss Central Station software. Refer to manual RS.8C.G for more information.

To configure a point to a m�+, select the Point Setup option from the Setup menu and then select a point number to be used.

The standard point setup screen is then displayed with the standard fields as previously described. Use all the fields as previously described except for the following:

Set this field to either 'RTD' (for temperature monitoring) or '4�0' (for 4-�0mA inputs).

With the 'Type' field highlighted, press the ' ' key to display the second point setup screen.

Set this field to 'T-PARTY'.

Set this field to the same address that has been set on the m�+.

Set this field to the type of input being used by the m�+ unit.Use the ‘ ’and ‘ ’ keys to cycle through the valid options as follows: · RESISTOR Resistor input.· CURRENT 4 - �0 mA input. · DIGITAL Normally open or normally closed contacts (Contact).· PT1000 PT1000

Set this field to the input number being used on the m�+ unit for monitoring.

Type

Input Source

Remote Addr

Input Type

Input Number

Remote Controller Parameters

Page 31: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 31

EKC measurements and setup

ConceptThe m� display can display data from individual controllers. Data is uploaded to m� via data com-munication.The following can be displayed, depending on the type of controller and what is being regulated:

The point number w

ill corre

spond to

a controlle

r address

Supplementary text that can be added to the point number

Indicates the upper alarm limit setting. When the of the symbol is scrolling, it indicates that the upper alarm limit has been exceeded.

A waveIndicates the set point for the EKC controller

Indicates the lower alarm limit setting. When the part of the symbol is scrolling, it indicates that the lower alarm limit has been exceeded.

Primary meas-urement from the controller. This shows the air temperature.

For a pack con-trol it could be: P0bar

- Remote - alarms are based on controller settings. Alarm limits will be determined by the external controller.

Some alarm limits are set as absolute values, others as a difference to the set point. See controller data.

Regulation status is shown by means of icons, e.g.:

- cooling

- defrost

- fans on

- compressors on

Secondary measure-ment from the controller. This shows the de-frost temperature.

For a pack control it could be: Pcbar

Page 32: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

3� Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Each controller must have an address set using the controller’s menu system.

Network address o03 1-99

Service-pin message o04 ON

Setup EKC controllersm� can receive signals from up to 99 EKC controllers. (Although max. 99 measurements in all to one m�.)The data communication cable on RS485 (LON) must fulfil the requirements described in the separate document: RC8AC.

AddressesEach EKC controller must have an address set in its menu system. This address must then be sent via data communication to the m� unit. This is done us-ing a setting in the EKC controller. When m� receives the address, it will first use the address number as a point number, so that the two numbers are the same. BUT this is only the case if the point has not already been defined for the other side (another EKC controller or a direct point). If it has already been used, the existing setting will be retained and the last one entered will not be used.

The following controllers can be connected to an m� unit:EKC �01, �01C, �01 dbl. thermostat, EKC 301EKC �0� version A, B, C, DEKC 331EKC 331TEKC 531D1 version 1.36 application 1 (1.361)AK-PC 530 version 1.36 application 1 (1.361)

Do not use the same address for several EKC controllers and do not use an address number that has already been used as a point number.

Sequence:1. Connect m� and the EKC controllers using a data communication cable�. Switch on m�3. Switch on the first EKC controller

a. Set the menu “o03” b. Set the menu “o04”

4. Repeat point 3 for all controllers on the data communication5. Continue setup in m�. See page 33.

Shown in the table below is the operation for logging a EKC controller onto a m� system.

The symbols for pushing of buttons have the following meanings:

Push the upper button Push the lower button

Push both buttons simultaneously

When a EKC controller is logged on to a m� system, whatever the controllers address is parameter (o03) will automatically be assigned as the point number on the m�. This will include overwriting any previous settings set to that point number.Ensure before logging a EKC controller onto a m� system, that the address set is available in the m�. If not available then change the address on the controller.

AEKCcontrollerisloggedontoam2systemfromthecontrolleronly.

Page 33: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 33

Choice of measurements to be displayed as pri-mary and secondary:

Select the menu: Setup Menu \ Point Setup

Number: Select the point number (i.e. address number of EKC)

Type: Select “EKC”Alarms: Will always be “Remote”. The alarm limits

for the controller will be used.

Other settings are those normally used for m�.

Next menu

Press and hold down the ‘Enter’ key until the second Point Setup screen is displayed or press the ' ' in the point type field.

Input Source: Select “ECHELON” (= data communication)Primary Temp: Used to select the parameter to be displayed as primary Secndary Temp: Used to select the parameter to be displayed as secondary

Other settings are those normally used for m�.

Page 34: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

34 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Alarm Action Setup

When an alarm occurs, a number of settings will determine which func-tions are to be activated. The definition of each point includes assigning an action number from 1 to 15.The latter menu display is used to determine which functions will be activated by the action number in question.

Action-number

Pressing “Mute” results in alarm reset 1 2 3 4 5 6 7 8

Pressing “Mute” results in alarm reset and alarm reset for AKM 9 10 11

As above, but also transmits alarm status 0 to AKM, if the alarm turns itself off

12 13 14 15

Action number for use in setting the trigger 1 � 3 4 5 6 7 8

Function

Relay 1

Trig

ger s

ettin

gs

1 1 1

Relay �

Siren 1 1 1 1 1 1 1 1

Lamp 1 1 1 1 1 1 1 1

Flash 1 1 1 1 1 1 1 1

Dial O. 1 1 D

Dial O. � 1 D

Dial O. 3 1 D

Dial O. 4 1 D

Dial O. 5 1 D

Print 1 1 1 1 1 1 1 1

The trigger settings shown are factory settings, but these can be changed as required.Settings have the following function:0: No action1: ActionD: Action, but only for the day periodN: Action, but only for the night periodThe day and night definition is set using the display “SYSTEM TIME SETUP”.

The lines Dial Out 1 to 5 will only be visible if “Modem” is selected in the menu “AK Com-munication Setup”.

Modem Dial Out Settings

Device: Settings Description

Relay �: Trigger: 000000000 Enables modem power control

Page 35: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

m� Version 3.11 Manual RS.8A.N5.0� © Danfoss 10-�007 35

Example

The siren is ON, when action 1, �, 9 or 10 occurs

Relay 1 is ON, when action �, 7, 10 or 15 occurs

A call is made to the following number, when action 1, �, 3, 8, 9, 10 or 11 occurs.(However, 3 and 11 only apply during the daytime)

Page 36: Manual - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/rs8an502.pdf · Manual Refrigeration and ... Icelandic, Finnish, Hungarian, Polish, Czech, ... Use this key to move the cursor

36 Manual RS.8A.N5.0� © Danfoss 10-�007 m� Version 3.11

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

List of Literature

Manual RS.8A.N Provides full instructions on how to operate the m� unit.

Manual RS.8C.G Provides full instructions on how to operate the m� unit via a PC using Danfoss Central Station software.

Instructions RI.8B.M Provides full instructions on how mount the m� unit and connection to EKC controllers and third party units.

Installation RI.8B.N Provides full instructions on EKC-LONWORKS®

data comms with the m�.

Functional RC.8A.M Provides full instructions of the m�'s GSM-SMS comms functions.