    PROMAC. LEADING THE WAY.

    OPERATOR & MAINTENANCE

    MANUAL

  • 7/28/2019 Manual Operacao Amf25

    2/67

    S80PS

    GENERATING SET

    OPERATOR & MAINTENANCE MANUAL

    Table of Contents

    1. Foreword ..................................................................................................

    2. Safety Information.............................................................................................. 2

    2.1 General Safety Precautions ...................................................................................... 3

    2.2 Safety During Transportation .................................................................................. 3

    2.3 Safety During Installation & Initial Start-up ........................................................... 4

    Edition B B

    Date 2011-06-07

  • 7/28/2019 Manual Operacao Amf25

    3/67

    2.4 Safety During Operation .......................................................................................... 4

    2.5 Safety Around Diesel Engines ................................................................................. 5

    2.6 Safety During Maintenance ..................................................................................... 5

    2.7 Symbols and Their Meanings .................................................................................. 6

    3. Specifications and Parts Introduction ............................................................. 9

    3.1 Specifications ........................................................................................................... 9

    3.1.1 Use ................................................................................................................ 9

    3.1.2 Main Specifications ..................................................................................... 10

    3.1.3 Design Ambient Conditions ........................................................................ 10

    3.2 Generator Specifications ........................................................................................ 11

    3.3 Generator Layout and Major Components ............................................................ 13

    3.4 Control Cabinet and Panel ..................................................................................... 15

    3.4.1 Control Cabinet ........................................................................................... 15

    3.4.2 Control Panel............................................................................................... 18

    3.4.3 AMF 25 Controller....................................................................................... 23

    3.5 Generator Wiring Diagram .................................................................................... 34

    4.1. Noise consideration ............................................................................................... 35

    4.2. Acoustic Material consideration ........................................................................... 35

    4.3 Fire protection ........................................................................................................ 35

    4.4 Mounting Arrangement .......................................................................................... 36

    4.6 Indoor Installation .................................................................................................. 40

    4.7 MECHANICAL CONNECTIONS ........................................................................ 41

    4.7.1 Fuel system ................................................................................................. 414.7.2 Lubrication system ...................................................................................... 43

    4.7.3 Exhaust system ........................................................................................... 45

    4.7.4 Ventilation and cooling system................................................................... 45

    4.8 Load Connections .................................................................................................. 46

    4.8.1 Sizing Load Cables ....................................................................................... 46

    4.8.2 Connecting Load Cable................................................................................ 46

    4.9 Earth Connections .................................................................................................. 47

    4.10 Battery Connections ............................................................................................. 47

    4.11 ATS Connections ................................................................................................. 48

    5. Operation ........................................................................................................... 49

    5.1 General Pre-check Before Starting ........................................................................ 49

    5.2 Checking Engine Oil, Fuel and Coolant Level Before Starting ............................. 50

    5.2.1 Engine oil..................................................................................................... 50

    5.2.2 Fuel.............................................................................................................. 51

    5.2.3 Coolant ........................................................................................................ 51

    5.3 Manual Start-up ..................................................................................................... 52

    5.4 Automatic Start-up ................................................................................................. 52

    5.5 During Operation ................................................................................................... 53

    5.6 Stopping Generator Under Manual Operation Mode ............................................. 54

  • 7/28/2019 Manual Operacao Amf25

    4/67

    5.7 Stopping Generator Under Automatic Operation Mode ........................................ 54

    5.8 Shutting Down Genset ........................................................................................... 54

    5.9 Lifting and Transportation ..................................................................................... 55

    5.10 Overnight Storage ................................................................................................ 55

    5.11 Long-term Storage ............................................................................................... 55

    6. Maintenance...................................................................................................... 55

    6.1 Periodic Maintenance Schedule ............................................................................. 56

    6.2 New Machines ....................................................................................................... 57

    6.3 Air Cleaner ............................................................................................................. 57

    6.3.1 Clean Air Filter Element .............................................................................. 57

    6.3.2 Change Air Filter Element ........................................................................... 57

    6.4 Engine Coolant ....................................................................................................... 57

    6.4 Engine Coolant ....................................................................................................... 58

    6.5 Engine Oil and Oil Filter ........................................................................................ 59

    6.5.1 Change Engine Oil ....................................................................................... 59

    6.5.2 Change Oil Filter.......................................................................................... 59

    6.6 Fuel Filter ............................................................................................................... 60

    6.6.1 Drain Water / Sediment in the Fuel Filter .................................................. 60

    6.6.2 Change Fuel Filter ....................................................................................... 60

    6.7 Troubleshooting ..................................................................................................... 60

    6.7 Troubleshooting ..................................................................................................... 61

  • 7/28/2019 Manual Operacao Amf25

    5/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-1

    1. Foreword

    Thank you for purchasing your new Nugen soundproof diesel generator.

    The Operator and Maintenance Manual must be read and understood prior to operating thegenerator.

    This manual contains information for the correct operation and maintenance of your

    generator and important safety and installation information, including troubleshooting

    guidelines. This manual must be kept with the generator at all times.

    This manual does not cover the diesel engine and alternator maintenance procedures. Please

    consult the engine and the alternator operation and maintenance manuals if necessary.

    This manual is not to be reproduced in any form or by any means without the express writtenapproval of Promac Sales Pty Ltd.

    ENGINE EXHAUST can cause serious injury or even death!

    Use only in open well ventilated areas or vent exhaust outside!

    DISCLAIMER STATEMENT

    Promac Sales Pty Ltd publishes the technical information in this manual as an aid to its

    customers and to the public. The information included in this manual is based on sound

    engineering principles, research, extensive field experience, and technical judgments.

    This mater is subject to change in light of developments in technology and field

    experience. Use or adoption of the information contained in this manual is voluntary.Promac Sales Pty Ltd reserves the right to change any portion of this information without

    notice.

  • 7/28/2019 Manual Operacao Amf25

    6/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-2

    2. Safety Information

    This manual contains important instruction that should be followed during installation and

    maintenance of the generator and batteries

    Before operating the machine, read the operators manual and become familiar with it and

    the equipment. Safe and efficient operation can only be achieved if the equipment is

    correctly operated and maintained. Many accidents are caused by failure to follow

    fundamental rules and precautions.

    This symbol, the industrys Safety Alert Symbol, is used throughout this manual and on

    labels attached to the machine itself. It warns of the potential for personal injury. It is

    essential that you carefully read the instructions and safety regulations before you attempt

    to operate or maintain this machine.

    Indicates potential personal injury hazards

    Indicates a hazardous situation which, if not avoided, will result in

    serious injury or even death

    Indicates a hazardous situation which, if not avoided, could result

    in serious injury or even death

    Indicates a hazardous situation which, if not avoided, could result

    in minor or major injury

    Indicates additional information important to a procedure

  • 7/28/2019 Manual Operacao Amf25

    7/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-3

    2.1 General Safety Precautions

    Check that all necessary or available guards are correctly fitted. DO NOT dismantle or

    disable any safety devices.

    Check the generator is securely mounted.

    Check all mechanical connections are satisfactory.

    Check all electrical connections are correct, safely insulated and suitably earthed.

    Ensure that the earth spike is connected to the earth point in front of the plant.

    All service and maintenance personnel must be competent and adequately trained.

    Always dispose of any rags used to clean up fuel or oil in appropriate bins.

    Always disconnect the main battery before commencing maintenance operations.

    Ensure that the appropriate Personal Protective Equipment (PPE) is worn while

    working on generators.

    Stay clear of any moving parts.

    2.2 Safety During Transportation

    Always shut the engine down before transporting.

    Never transport the generator with any access doors open.

    Ensure the fuel tank cap is securely tightened.

    Drain fuel when transporting the generator over long distances or rough terrain.

    In order to lift and transport the generator, lifting machines of the appropriate

    capacity must be used. All loose and pivoting parts must be securely fixed.

    When relocating the generator only lift from designated lift points.

    Do not use the lifting points located over the engine, alternator or any other

    components.

    If the generator is damaged during transport, repairs should only be carried out by

    an authorised service agent.

    Unpacking must be carried out carefully, avoiding any damage to the goods

    particularly when using levers, saws or any other metallic tools.

  • 7/28/2019 Manual Operacao Amf25

    8/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-4

    2.3 Safety During Installation & Initial Start-up

    All installation and repair procedures must be carried out by competent and

    adequately trained personnel.

    Installation of the generator must be in accordance with Clause 4.

    Ensure all emergency procedures are adhered to.

    Ensure that the appropriate PPE is worn while working on the generator.

    Under no circumstances are any guards, panels or insulating materials to be

    tampered with.

    Do not leave any flammable liquids or materials near the generator or any other part

    of the electrical installation.

    Take extreme caution to avoid risks of electrocution. Ensure that all earthing

    installations have been fitted according to the Electrical Standards and all local

    regulations.

    Ensure all connections and wires are insulated. Do not leave any of the generators

    electrical terminals unprotected.

    Ensure all connection points and their accessories have been correctly earthed.

    Verify and ensure that all electrical power connections and auxiliary service

    connections are correct.

    Check that the phase rotation matches the power supply.

    Ensure the correct ventilation of the premises so that all exhaust gases are released

    to the atmosphere and verify that they are in a safe position away from all doors,

    windows and air intakes.

    Make sure there are no leaks in the oil and fuel pipes.

    Never stand under or close to any object that is being hoisted or lifted into position.

    2.4 Safety During Operation

    Only competent and adequately trained personnel are to access the operating area

    of the generator.

    Always wear ear protection when the generator is in operation.

    Before operating the generator, make sure the earth spike is connected to the earth

    point in front of the plant.

    Before starting the engine, turn off any connected loads and set all circuit breakers

  • 7/28/2019 Manual Operacao Amf25

    9/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-5

    to the OFF position.

    Do not operate the generator in any poorly ventilated areas.

    Do not handle any wires or connections when the generator is operating.

    Do not touch any rotating machinery.

    Do not move the generator when it is operating.

    Do not connect or disconnect loads whilst the generator is operating. High voltage is

    present whenever the engine is running. Loads should be connected correctly before

    starting the engine.

    Do not smoke near the generator or any other fuel sources.

    Do not point the exhaust towards people or buildings.

    Use the emergency stop button only in an actual emergency. Do not restart the

    engine until the problem has been verified and corrected.

    2.5 Safety Around Diesel Engines

    Do not operate the engine when the air cleaner is removed. Engine backfire can

    cause serious burns.

    Do not remove the radiator cap while the engine is running. Allow the coolant to

    sufficiently cool before removing the radiator cap. Coolant that is hot and under

    pressure may cause serious burns.

    Do not add coolant, oil or fuel to a hot engine. Allow the engine to sufficiently cool

    first.

    Do not touch the engine and muffler while the engine is running. Allow the engine to

    sufficiently cool before any maintenance is performed.

    Do not smoke in the vicinity of the generator.

    Consistently monitor the exhaust system for leaks. In the event of a leak, repair

    immediately.

    2.6 Safety During Maintenance

    All checks or maintenance of the generator must be carried out by competent and

    adequately trained personnel.

    Ensure that the engine has fully stopped before performing any maintenance.

    Disconnect the terminals from the battery before operating any components of the

    electrical installation.

  • 7/28/2019 Manual Operacao Amf25

    10/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-6

    Do not remove the radiator cap while the engine is running. Allow the coolant to

    sufficiently cool before removing the radiator cap. Coolant that is hot and under

    pressure may cause serious burns.

    Only correct plugs are to be used in electrical outlets.

    Ensure all naked flames have been extinguished before refuelling.

    Periodically check the clamping and insulation of all electrical connections.

    Ensure that the appropriate PPE is worn while working on the generator.

    2.7 Symbols and Their Meanings

    The following symbols are used on the product and throughout this manual.

    TABLE 1: SAFETY LABELS

    LABEL DESCRIPTION

    1. Read the Operator Manual.

    2. No sparks or naked flames near the machine.

    3. Press the emergency stop switch when an emergency

    occurs.

    4. Do not disassemble the machine.

    Warning

    1. To prevent hearing loss, wear hearing protection.

    2. Avoid spraying water into generator.

    3. Avoid hand injury in rotating belts and pulleys.

    4. Mechanical moving parts can cause severe injury.

    Safety Instructions

    Read the Safety Instructions before operation.

    Warning

    Electric shock will cause serious injury or death.

    Warning

    Escaping steam can cause severe burns.

    Never remove the pressure cap while the engine is warm

    or hot. Always allow the engine to cool before removing

    the pressure cap.

  • 7/28/2019 Manual Operacao Amf25

    11/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-7

    Warning

    Always refuel with the engine stopped and in a

    well-ventilated area. Do not smoke or allow open flames

    or sparks in or near the area where refuelling is

    performed or where fuel is stored.

    Warning

    Do not operate while transporting. Ensure panel latches

    and caps are secure for transporting or relocating.

    Warning

    Read this label before lifting and transporting.

    Only use designated lifting points on generator.

    Warning

    1. Disconnect the battery before servicing.

    2. Read the Operator Manual for instructions.

    Warning

    Do not manipulate the generator with the switch on.

    Warning

    Engine exhaust can cause serious injury or even death.

    Hot surfaces can burn skin.

    Danger

    High voltage.

    Warning

    Do not clean the alternator with water

    Warning

    High temperature.

  • 7/28/2019 Manual Operacao Amf25

    12/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-8

    Caution

    Check the engine oil level before starting the engine.

    Warning

    High voltage

    Note

    1. Check the coolant level in the radiator

    2. Check the coolant level in the overflow bottle

    3. Check the engine oil level

    Warning

    Not a lifting point

    Note

    Lubrication oil inlet

    Note

    Fuel inlet

    Note

    Phase connection points.

    Note

    Earth connection points.

    Note

    Water inlet.

  • 7/28/2019 Manual Operacao Amf25

    13/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-9

    Note

    Forklifting point

    Note

    Bottom drain bund

    Diesel fuelling point

    Coolant refill point and type of coolant

    Main Isolator Switch

    Off On Switch

    Circuit Breaker Type & Size

    3. Specifications and Parts Introduction

    3.1 Specifications

    3.1.1 Use

    The generator can be used as a power supply for two main types of services:

    Continuous service Used for the production of electrical energy for variedpurposes: motion force, lighting, heating, etc.

  • 7/28/2019 Manual Operacao Amf25

    14/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-10

    Emergency service Used to rectify main supply interruptions or to faceconsumption peaks.

    3.1.2 Main Specifications

    Reliable and powerful Perkins engine and Leroy Somer alternator.

    Operation: Using the advanced Intelilite AMF 25 Controller, allows for simpleand convenient fingertip control through the front control panel or by PC

    connection. The Intelilte AMF 25 Controller also monitors the engine and the

    alternator displaying all warning alarms and performing automatic shutdowns on

    fault signals.

    50C designed cooling system.

    The engine and alternator have rubber av mounts installed to reduce vibration.

    High anti-corrosion protection.

    Easy maintenance: Wide doors are designed to allow easy access formaintenance and cleaning.

    Super quiet performance: Acoustic insulation installed inside all of the panelsand doors and an oversized muffler to minimise noise.

    Engine and alternator can resist any direct impact stress.

    Control cabinet can reach IP66 protection. Canopy can reach IP44 protection.

    Double bunded fuel tank protection.

    Leak proof base: All drain points are located on the inside.

    Muffler with spark arrester.3.1.3 Design Ambient Conditions

    Installation: Outdoors and indoors in a well-ventilated area.

    Temperature: -15C to 50C.

    Relative humidity: Less than 80%.

    Altitude: To a maximum of one thousand (1000) metres above sea level.

  • 7/28/2019 Manual Operacao Amf25

    15/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-11

    3.2 Generator Specifications

    TABLE 2: GENERATOR SPECIFICATIONSITEM UNIT DATA

    Model S80PS

    Rated OutputkVA 80

    kW 64

    Rated Voltage V 415 / 240

    Power Factor 0.8

    Rated Frequency Hz 50

    Rated Speed rpm 1500

    Phase / Wire 3-Phase / 5-Wire

    Noise Level dB(A)@7m 69.8

    ENGINE SPECIFICATIONS

    Model Perkins (UK), 1104C-44TAG1

    Number of Cylinders 4 vertical in-line

    Bore mm 105 / 4.13

    Stroke mm 127 / 4.99

    Engine Speed rpm 1500

    Prime Power kW 80

    Standby Power kW 88

    Compression Ratio 18.2:1

    Displacement L 4.4

    Cooling System Water-cooled

    Battery Voltage V 12

    Type of Oil 20W50-CF4 Upgrade

    Type of Fuel 0# or 20# Light Diesel

    Fuel Tank Capacity L 510

    ALTERNATOR SPECIFICATIONS

    Model Leroy Somer LSA43.2 L8

    Exciter Brushless

    Excitation System AREP

    Insulation Type Class H

    DIMENSION

    Length mm 2830

    Width mm 1060

    Height mm 1890

  • 7/28/2019 Manual Operacao Amf25

    16/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-12

    Dry Weight kg 1815

  • 7/28/2019 Manual Operacao Amf25

    17/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-13

    3.3 Generator Layout and Major Components

  • 7/28/2019 Manual Operacao Amf25

    18/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-14

    TABLE 3: CONTROL CABINET

    REF NAME DESCRIPTION

    1 Canopy Size: 2630 x 1060 x 1490mm2 Fire extinguisher bracket Designed for 9kg ABE fire extinguisher

    3 Field wiring cabinet

    4 Base Size: 2830 x 1060 x 400mm

    5 Control cabinet assembly

    6 Spark Arrestor Rating: 8m3/min

    7 Alternator LSA43.2 L8

    8 Diesel engine Perkins 1104C-44TAG1

    9 Radiator 50C

    10 Muffler Rating: 12m3

    /min

  • 7/28/2019 Manual Operacao Amf25

    19/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-15

    3.4 Control Cabinet and Panel

    3.4.1 Control Cabinet

  • 7/28/2019 Manual Operacao Amf25

    20/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-16

    TABLE 4: CONTROL CABINET

    REF NAME DESCRIPTION

    1 Relays DC 12V

    2 Circuit Breaker 6A 1P3 Circuit Breaker 32A 1P

    4 Circuit Breaker 16A 1P

    5 Relays DC 12V (start relay and fuel start relay)

    6 Terminals DC 12V

    7 Battery Charger

    8 DC Regulator Module

    9 Terminals AC 240V

    10 RCD/MCB Combo 10A 2P (Protects the battery charger)

    11 Circuit Breaker 10A 3P

    12AMF/Island Mode

    Selector Switch

    Refer to Note 1

    13Double action RCD

    bypass switch

    Refer to Note 2

    14 Earth Bar

    15 Neutral Bar

    16 Neutral Bar

    17 Earth Bar

    18 MEN Bar19 Terminal Empty

    20 Diode ZP5A

    Note 1: With the switch in AMF mode, the controller will be in Automatic Mains Failure

    function. With the switch in ISLAND mode, the generator can be remotely started by closing

    the remote start terminals.

    Both AMF and Remote Start require the Intelilite AMF 25 Controller to be in AUTO mode.

    NOTE 2: The RCD bypass switch has a protective cap to prevent accidental operation. The

    machines are delivered with the switch in the off position and the cap down. In this

    configuration the adjustable earth leakage relay (16) will monitor any earth leakage current.

    If a leakage current greater than the relay setting is detected the shunt trip will trip the Main

    Circuit Breaker. When the RCD bypass switch is on and the cap is in the up position, the earth

    leakage relay will be bypassed.

    This operation must only be carried out by a licensed electrician.

    NOTE 3: The MEN connection terminals are provided to facilitate simple connection and

    disconnection of the MEN Link. The MEN Link (18) is connected on the alternator side of thetoroids for the earth leakage protection. If the load side has another MEN Link connected,

    the generator side MEN Link must be disconnected. A spare terminal (9), is provided. The

  • 7/28/2019 Manual Operacao Amf25

    21/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-17

    earth leakage relay must also be bypassed (in the control cabinet).

    This operation must only be done by a licensed electrician.

  • 7/28/2019 Manual Operacao Amf25

    22/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-18

    3.4.2 Control Panel

  • 7/28/2019 Manual Operacao Amf25

    23/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-19

    TABLE 5: CONTROL PANEL

    REF NAME DESCRIPTION

    1 Control Cabinet Lamp Switch

    2 Control Cabinet Lamp3 RCD Status Lamp

    4RCD Status Lamp Globe Test

    Button

    5Mains / ATS Battery Charging

    Lamp

    6Mains / ATS Battery Charger

    Selector Switch

    7 Audible Alarm

    8 Master Control Switch

    9 Controller Intelilite AMF 25

    10 Earth leakage relay Schneider Vigirex RH99P; Panel mounted

    11 RCD Test Point 10A ,Test Point

    12 Push Button Mains connected, two pole RCD Test button

    13 Test Point Switch 20A,Lockable

    14 Circuit Breaker 50A 3P,General purpose outlets

    15 Circuit Breaker 2A 2P, Test point

    16 RCD 63A 4P,30mA

    17 Circuit Breaker 20A 3P,General purpose outlets

    18 GPO Switch 150A,Lockable

    19 Main Circuit Breaker 125A 3P

    20 RCD 40A 4P, 30mA

    21 RCD/MCB Combo 20A 2P

    22 RCD/MCB Combo 16A 2P

    23 Door Lock

    1. Control Cabinet Lamp Switch

    The Control Cabinet lamp switch (1) is used to illuminate the control cabinet

    lamp (2).

    2. Control cabinet lamp.

    The control cabinet lamp (2) is located above the controller.

    3. RCD Status Lamp

    The RCD Status Lamp (3) indicates the status of the RCD. When the RCD Status

  • 7/28/2019 Manual Operacao Amf25

    24/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-20

    Lamp is illuminated the earth leakage relay (ELR) is protecting the outlets

    and main field wiring terminals. If the RCD Status Lamp is not illuminated

    the ELR relay is bypassed.

    4. RCD Status Lamp Globe Test Button

    The RCD Status Lamp Globe Test Button (4) is used to test the

    function of the globe of the RCD status lamp (3).

    5. Main/ATS Battery Charging Indicator Lamp

    The indicator (5) will illuminate when the 12V main battery is being

    charged by either the mains inlet power or ATS power.

    6. Mains/ATS Battery Charge Select Switch

    The switch (6) is used to select the source of the battery charging power,

    either Mains Inlet or ATS.

    7. Audible Alarm

    IF the AMF controller senses a fault . The Audible Alarm (7) will sound.

    8. Master Control Switch

    The switch (8) energises the control panel.

    9. Controller (AMF 25)

    The generator controller AMF 25 (9) is a microprocessor-based control

    unit containing all of the necessary functions for the protection and

    control of the generator. It also monitors the three-phase AC voltage &

    current. The unit is equipped with a liquid crystal display, to present all

    values and alarms.

    10. Earth Leakage Relay (ELR)

    The generator is equipped with an earth leakage relay

    (10). There are two different types of relays, the standard

  • 7/28/2019 Manual Operacao Amf25

    25/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-21

    configuration is RH99P, which is panel mounted. The other is RH99M, din rail

    mounted, located in the control cabinet.

    11. RCD Test Point

    The RCD Test Point (11) is used to test the earth leakage protection

    function. When an earth leakage greater than the adjustable ELRs

    setpoint occurs, the main circuit breaker (19) will shunt trip.

    12. Mains RCD Test Pushbutton

    Depressing the Mains RCD Test Pushbutton (12) allows power to the

    RCD Test Point (11).

    13.Test Point Switch

    The test point switch (13) is used to isolate the RCD Test Point (11)

    14.Circuit Breaker (50A 3P)

    The three-phase circuit breaker (50A 3P) (14) is located

    on the control panel. When the electric current in the

    5-pin socket circuit is above 50A, this breaker will turn tothe OFF position automatically and interrupt power

    from the in the load side of RCD to the respective GPO in the field wiring

    cabinet.

    15. RCD Test Point Circuit Breaker (2A,2P)

    The two pole RCD Test Point Circuit Breaker (15) is located on the

    control panel and protects the RCD Test Point (11).

    16.Three Phase Earth leakage Residual Current Device (RCD) (63A,4P,30mA)

    The Three Phase Residual Current Device (16) is located on the control

    panel. When a residual current of greater value than 30mA is detected

    this device will automatically trip to the fault position. This will

    interrupt power from the load side of RCD to the respective GPO in the

    field wiring cabinet.

    Note: If a fault occurs, test accordingly before reinstating RCD.

  • 7/28/2019 Manual Operacao Amf25

    26/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-22

    17. Three Pole Circuit Breaker Protecting 20A Three Phase Outlet

    The Three Phase Circuit Breaker (21) is located on the control panel.

    When the electric current in the three phase outlet circuit is above 20A,

    this breaker will automatically trip to the fault position. This will

    interrupt power from the the load side of RCD to the respective GPO in

    the field wiring cabinet.

    Note: If a fault occurs, test accordingly before reinstating circuit breaker

    18. GPO Switch(150A)

    The GPO switch (18) is used to disconnect the power to all outlets.

    19.Main Circuit Breaker (125A 3P)

    The lockable three-phase circuit breaker (125A 3P) (19) is located on the

    control panel. When the electric current exceeds 125A, it will

    automatically trip to the fault position and interrupt all power from

    the load side of the circuit breaker.When earth leakage fault occurs

    above 30mA, this breaker will turn to the OFF automatically and

    interrupt all power from the load side of breaker. Note: Generator will

    still supply power on the line side of breaker.

    20.Three Phase Earth leakage Residual Current Device (RCD) (40A,4P,30mA)

    The Three Phase Residual Current Device (20) is located on the control

    panel. When a residual current of greater value than 30mA is detected

    this device will automatically trip to the fault position. This will

    interrupt power from the load side of RCD to the respective GPO in the

    field wiring cabinet.

    Note: If a fault occurs, test accordingly before reinstating RCD.

    21. Single Phase RCD/MCB Combo Protecting 20A Single Phase

    Outlet

    The 20A Single Phase RCD/MCB Combo device (21) is

    located on the control panel. When the electric

    current is greater than 20A or a residual current of

  • 7/28/2019 Manual Operacao Amf25

    27/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-23

    greater value than 30ma is detected, this device will automatically trip

    to the Fault position. This will interrupt power from the load side of

    the RCD/MCB to the 20A single phase GPO in the field wiring cabinet.

    RCD capability exists to protect the end user.

    Note: If a fault occurs, test accordingly before reinstating RCD/MCB.

    22. Single Phase RCD/MCB Combo Protecting 16A Single Phase Outlet

    The 16A Single Phase RCD/MCB Combo device (22) is located on the

    control panel. When the electric current is greater than 20A or a

    residual current of greater value than 30ma is detected, this device will

    automatically trip to the Fault position. This will interrupt power from

    the load side of the RCD/MCB to the 16A single phase GPO in the field

    wiring cabinet. RCD capability exists to protect the end user.

    Note: If a fault occurs, test accordingly before reinstating RCD/MCB.

    3.4.3 AMF 25 Controller

    TABLE 5: PUSH BUTTONS

  • 7/28/2019 Manual Operacao Amf25

    28/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-24

    REF NAME DESCRIPTION

    1START button. Works in MAN mode only. Press this button

    to initiate the start sequence of the engine.

    2

    STOP button. Works in MAN mode only. Press this button

    to initiate the stop sequence of the gen-set. Repeatedpressing or holding the button for more than 2s will cancel

    the current phase of stop sequence (ramping the power

    down or cooling) and the next phase will continue.

    3

    FAULT RESET button. Use this button to acknowledge

    alarms and deactivate the horn output. Inactive alarms will

    disappear immediately and status of active alarms will be

    changed to "confirmed" this will allow the alarm to reset

    when the fault condition is alleviated.

    4 HORN RESET button. Use this button to deactivate thehorn output without acknowledging the alarms.

  • 7/28/2019 Manual Operacao Amf25

    29/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-25

    5

    MODE LEFT button. Use this button to change the mode.

    NOTE:

    This button will not work if the controller mode is locked by

    one of the binary inputs: Remote OFF, Remote MAN,

    Remote AUT, Remote TEST.

    6

    MODE RIGHT button. Use this button to change the mode.

    NOTE:

    This button will not work if the controller mode is locked by

    one of the binary inputs: Remote OFF, Remote MAN,

    Remote AUT, Remote TEST.

    7GCB button. Works in MAN mode only. Press this button to

    open or close the GCB manually.

    NOTE:

    Certain conditions must be valid otherwise GCB closing is

    blocked.

    8

    MCB button. Works in MAN mode only. Press this button to

    open or close the MCB manually.

    CAUTION!

    Pressing this button can disconnect the load from the mains

    supply!

    GEN-SET OPERATION INDICATORS

    9

    Gen-Set Failure. If a Gen-set failure fault is detected the Red LED will start

    flashing. After pressing the Fault Reset button the LED will turn off if no alarm is

    active or will become constant if the alarm is still active.

    10

    Gen-Set Volt age OK. If the generator voltage is within the preset limits the GreenLED will be illuminated.NOTE:

    The limits for the generator voltage and frequency are given by set points in theGenerator Protection Parameters.

    11GCB ON. If the Generator Circuit Breaker (GCB) is closed the Green LED will beilluminated.It is driven by the GCB CLOSE/OPEN output (AMF 8/9) or by the GCB feedbacksignal (AMF 20/25).

    12MCB ON. If the Mains Circuit Breaker (MCB) is closed the Green LED will beilluminated.It is driven by the MCB CLOSE/OPEN Output (AMF 8/9) or by MCB feedbacksignal (AMF 20/25).

    13 Mains Voltage OK. If a Mains Voltage is present and within limits the Green LED

    will be illuminated.

    14Mains Failure. If a mains failure is detected the Red LED will start flashing. The

    LED will be constantly illuminated after the gen-set has started and connected to

    the load.

  • 7/28/2019 Manual Operacao Amf25

    30/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-26

    DISPLAY AND CONTROL BUTTONS

    15 Graphic B/W display, 128 x 64 pixels

    16PAGE button. Use this button to switch between display

    pages.See Display Screens and Pages Structure for more details.

    17 UP button. Use this button to move up or increase a value.

    18 DOWN button. Use this button to move down or decrease a

    value.

    19ENTER button. Use this button to finish editing a set point or

    moving right in the history page.

    Display Screens and Pages Structure

    The displayed information is structured into "pages" and "screens". Use the PAGE button to scroll

    through the pages.

    1. The Measurement pagesconsist of screens which display the measured values, ie. voltages,

    current, oil pressure etc. The calculated, values i.e. gen-set power, statistical data & alarm list

    are displayed on the last screen.

    2. The Set Points pagescontain all the set points categorized by their groups and also aseparate page for entering the password.

    3. The History Log pages display the history log in chronological order with the most recent recorddisplayed first.

  • 7/28/2019 Manual Operacao Amf25

    31/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-27

    Alarms

  • 7/28/2019 Manual Operacao Amf25

    32/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-28

    Browsing ECU Alarms

  • 7/28/2019 Manual Operacao Amf25

    33/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-29

  • 7/28/2019 Manual Operacao Amf25

    34/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-30

  • 7/28/2019 Manual Operacao Amf25

    35/67

  • 7/28/2019 Manual Operacao Amf25

    36/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-32

    WARNING:

    ONLY press emergency stop button in the case of an actual emergency.

    Note: Stopping the generator under load may cause mechanical damage!

    1.

    Emergency Stop Switch

    The generator is equipped with two red emergency stop switches. One switch

    (15) is located in the field wiring cabinet, the second is adjacent to the control

    cabinet. The two switches are wired in series. When activated, the emergency

    stop (activated by pushing the red button) will turn off the fuel solenoid,

    resulting in the engine shutting down.

    Rotate button to reset emergency stop.

    Note: The cabinet emergency stop has a protective cover, which has to be lifted to be

    activated.

    2. GPO Manual Switch

    The lockable GPO Manual Switch is used to isolate the respective GPO.

    3. General Purpose Outlet (GPO) (Manually switched 20A 5pin, three-phase)

    The generator is equipped with two 415V three-phase GPO (3) rated at 50A.

    The GPO connects through the main line circuit breaker. It is also protected

    by its own RCD & circuit breaker located in the control cabinet.

    4.General Purpose Outlet (GPO) (Manually switched 20A 5pin, three-phase)

    The generator is equipped with one 240V three-phase GPO (4) rated at 20A.

    The GPO connects through the main line circuit breaker. It is protected by

    TABLE 7 OUTPUT TERMINAL ASSEMBLY

    RE

    F

    NAME DESCRIPTION

    1 Emergency stop switch

    2 GPO manual switch

    3 50A 5-pin GPO Three Phase

    4 20A 5-pin GPO Three Phase

    5 15A 3-pin GPO Single Phase

    6 ATS connector

    7 Tie bar

    8 20A 3-pin GPO Single Phase

    9 10A Male 3 flat pin mains inlet Single Phase

  • 7/28/2019 Manual Operacao Amf25

    37/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-33

    its own RCD/MCB combo breaker located in the control cabinet.

    5.General Purpose Outlet (GPO) (15A, single-phase)

    The generator is equipped with two Auto switched 240V single-phase GPOs (5)

    rated at 15A. Both are connected through the main line circuit breaker. Each

    GPO is protected by its own RCD/MCB combo breakers located in the control

    cabinet.

    6. ATS Connector

    The generator is equipped with an Automatic Transfer Switch (ATS) plug on

    the left side of the control panel. The customer can select an appropriate

    automatic transfer switch (ATS) and connect it to the generator

    7.Tie Bar

    The Tie Bar is used to protect the wiring cables by tied them on it.

    8.Safety Micro Switch

    The generator is equipped with one 240V single-phase GPO (8) rated at 20A.

    The GPO connects through the main line circuit breaker. It is protected by

    its own RCD/MCB combo breaker located in the control cabinet.

    9.Mains Inlet for Battery Charging (10A male 3 flat pin, single phase)

    The generator is equipped with one 240V single phase 3 flat pin inlet, (14)

    rated at 10A. It connects to the battery charger through an RCD/MCB combo

    breaker, which is located in the control box.

    .

    http://void%280%29/http://void%280%29/
  • 7/28/2019 Manual Operacao Amf25

    38/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-34

    3.5 Generator Wiring Diagram

  • 7/28/2019 Manual Operacao Amf25

    39/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-35

    4. Installation

    A diesel generator is a high-speed piece of rotating equipment. To ensure reliability and

    safety the installation must be given thorough attention.

    Before installing the unit, we must consider all environmental factors. Generator installation

    must comply with local building codes, fire regulations and environmental requirements. Usethese instructions as a general guide only, the complete installation must comply with all

    local, state, and federal building codes, fire ordinances, and any other applicable regulations.

    4.1. Noise consideration

    Because noise eafects the surrounding environment, it is important to consider noise factors

    when installing a generator. The generator has been acoustically treated, but if more

    stringent local environmental specifications require additional noise attenuation, please

    consider adding noise barriers or the construction of special rooms, etc.

    4.2. Acoustic Material consideration

    Consider the following when selecting acoustic material:

    Foam is not recommended as an acoustic material, because of its low density it is apoor acoustic insulator. And not all foams are fire retardant.

    A concrete block enclosure is an excellent barrier in regards to noise reduction. The

    blocks may be filled with sand to make the wall denser. However, concrete housingtends to become hot and supplementary cooling methods will be required for

    correct engine performance.

    4.3 Fire protection

    Each country has its own rules and regulations controlling the design of buildings to prevent

    fires. Fire departments are reliable sources of information to determine installation

    compliance. The installation of generators, must comply with the provisions of the local fire

    department. Fire protection systems must be consistent with the requirements of therelevant authorities.

    1. The genset room cannot be used for storage.

    2. Because of the fuel used the genset room must be consdered as a key target area for fire

    prevention.

    3. The generator must be treated as a high-temperature device, exhaust pipe temperatures

    can reach 500C.

  • 7/28/2019 Manual Operacao Amf25

    40/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-36

    4.4 Mounting Arrangement

    The base is used to support the unit and its accessories, its carrying capacity should be 2 to 5

    times the total mass of the generator, but also able to absorb the unbalanced force

    generated by the machine. The generator is specially designed to minimize the vibration of

    the unit. If an installation requires greater noise and vibration attenuation, the generator

    should be installed in a manner that reduces the impact of vibration on buildings.

    The base height is calculated as follows:

    The depth H of base is calculated as the basis:)(mm

    LWD

    GKH

    =

    K: Safety factor, typically value is 2;

    G: Genset weight;

    D: Cement density, typically value is 2400;W: Base width;

    L: Base length;

    The Figure below shows a typical foundation installation.

    TABLE 7 FOUNDATION

    REF DESCRIPTION

    1 Floor slab

    2 Sand or gravel

    3 Foundation

    4 Genset

    5 Sealant material

    6 Grout

    7 Anchor nut

    8 Foundation bolt

  • 7/28/2019 Manual Operacao Amf25

    41/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-37

    When designing the base, we need to pay specific attention to the following:

    The generator base must be isolated from the building foundation.

    Depth and width to meet the basic requirements.

    Foundation must be strong enough to take the impact and running force of the

    machine.

    Ensure that no vibration is transmitted to the building foundation when the unit

    starts.

    Ease of maintenance and servicability operations.

    When calculating the length L and width B of the base allow an additional

    100-300mm on each side.

    The base should be higher than engine room floor by 20-300mm.

    Mounting the Generator

    The generator is mounted on a steel-base tank that provides

    adequate support. Vibration isolators are recommendedbetween the base tank and the foundation to provide stable

    operation and avoid installation damage. Bolting the

    generator directly to the floor or foundation can result in

    excessive noise and vibration, and possible damage to the

    generator and floor foundation.

    Mount the generator on a substantial and level base such as

    a concrete pad. Use 20mm anchored mounting bolts to

    secure the vibration isolators to the base tank using flat or

    bevel washers and a hexagonal nut for each bolt. The isolators should be located as shown

    on the generator outline drawing.

    Incorrect installation or service can result in severe personal injury or death, and/or

    equipment damage. Only qualified service personnel should be allowed to perform electrical

    and mechanical component installation.

    Never install the genset near combustible materials. Locate the genset such that combustible

    material can not accumulate under the machine. The possibility exists of fire or explosion,

    causing damage to the equipment and or severe bodily harm or even death!

  • 7/28/2019 Manual Operacao Amf25

    42/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-38

    CAUTION:Pay close attention to ventilation when operating the generator inside confined spaces and

    enclosed areas. The engine exhaust contains noxious elements. Engine exhaust must be

    routed to a ventilated area.

    4.5 Outdoor InstallationInstall the generator in an area that is free of debris, and overhead obstructions. Make sure

    the generator is on secure level ground so that it cannot slide or shift around. Also install the

    generator in a manner so that the exhaust gases will not be discharged in the direction of

    nearby buildings.

    The installation site must be relatively free from moisture and dust. All electrical equipment

    should be protected from excessive moisture. Failure to do so will result in deterioration of

    the insulation and will result in short circuits. Foreign materials such as dust, sand, lint and

    abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

    The canopy is designed to provide cooling and ventilation for the generator. Several factors

    should be carefully considered when selecting a location for installation.

    For effective cooling and maintenance, the generator should be mounted on a hard,

    flat, non-combustible, level surface. A concrete pad is ideal and provides a secure

    installation.

    The installation area should be well ventilated.

    Drainage must be adequate to ensure the concrete pad is free from standing water. Installation should prevent build-up of leaves, grass, sand, snow etc.

    Serviceable access should be provided to allow the opening or removal of access

    panels/doors for service and maintenance.

    Keep the generator at least one metre away from buildings and other structures.

  • 7/28/2019 Manual Operacao Amf25

    43/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-39

  • 7/28/2019 Manual Operacao Amf25

    44/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-40

    4.6 Indoor Installation

    Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed

    indoor, the exhaust fumes must be vented to the outside. The engine should be installed at

    least 1000mm from any outside wall. Using an exhaust pipe which is too long or too small can

    cause excessive back pressure which will cause the engine to heat excessively and possibly

    burn the valves.

    Room Size

    If the generator is installed indoors, it must be protected from the environment while having

    good ventilation and cooling. Some considerations for planning a room or enclosure are:

    Never use the generator room for storage.

    The room must be large enough to contain the generator and all the accessories.

    1200mm must be allowed on the two sides and 1000mm in front of the engine forservice access. Allow clearance between hot parts of the system (exhaust) and

    structural members of the building (see figure below).

    On the generator end of the engine, allow a space equal to the length of the

    generator.

    The generator installation must comply with all of the current relevant standards

    and local authority requirements.

  • 7/28/2019 Manual Operacao Amf25

    45/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-41

    Room Location

    A separate building located on the site away from the main building is the most

    desirable.

    Maintain the building at a satisfactory temperature

    Ensure the generator is installed in a way that it will not compromise reliability from

    any emergency loads.

    Note

    The generator can be used at temperatures between -15 to 50C, An ambient temperature

    that is outside these temperatures will cause damage to the equipment, when the

    temperature is too low, the metal will become very weak; when the temperature is too high,

    the engine temperature may rise to a point where damage is caused to the engine and other

    components such as piston rings. In order to protect the engine, when the ambient

    temperature is around 50C, or close to -15C, the equipment load must be reduced or

    engine life may be compromised.

    4.7 MECHANICAL CONNECTIONS

    After considering all applicable codes and laws and finding a suitable location for the

    generator set, the installer should consider the mechanical connections that will be

    necessary to make during installation. The four (4) systems that could require mechanical

    connections are the following:

    Fuel system

    Lubrication system

    Exhaust system

    Ventilation and cooling system

    4.7.1 Fuel system

    The fuel system feeds fuel from the fuel tank to the combustion chamber. Its an important

    part of engine.

    The general fuel system of diesel engine is shown in the diagram below:

    WARNING:

    The floor foundation load-carrying capacity must be checked and must not exceed

    the weight of the generator and its associated equipment.

  • 7/28/2019 Manual Operacao Amf25

    46/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-42

    Fuel from the tank flows in the fuel lines and is injected from the nozzle via the fuel injection

    pump. Overflow fuel returns to the tank. The system includes filters to protect it from

    entrance of air, water and dust. While the engine is running, fuel is fed into the pump by the

    fuel feed pump after passing through the fuel filter where any foreign matter is removed.

    The fuel camshaft actuates the injection pump and force feeds fuel to the injection nozzle

    through the injection pipe. Fuel is then sprayed through the nozzle into the combustion

    chamber. The fuel discharged after lubricating and cooling the injection nozzle is returned tothe fuel tank through the over-flow pipe.

    Base Tank

    Base mounted fuel tanks are used to store fuel directly underneath the Genset, eliminating

    the need for a remote main fuel supply tank and/or auxiliary fuel transfer pumps. This

    mounting arrangement offers the convenience of having a fuel supply tank mounted at the

    generator. These tanks are designed to be contained in a rectangular base on which the

    engine-generator set is mounted. Generally, these tanks only increase the height of the

    generator set since the tank base is usually matched to the generator skid dimension.

    Remote tank

    Remote tanks are used when the engine fuel pump does not have the capacity to draw the

    fuel from the base tank; or the base tank is overhead and presents problems of high fuel

    head pressure for the system. In high ambient conditions, the day tank temperature might

    need to be considered. Warm fuel returning from the engine fuel injection pump should not

    be returned to the day tank if possible. As fuel temperature increases, fuel density and

    viscosity decrease, reducing maximum power output and lubrication of fuel handling parts

    such as pumps and injectors. This may be avoided by returning the fuel back to the supply

    tank rather than the day tank.Engines need to maintain some of the oil pump pressure and return oil pressure when the

    engine is working. When using a remote fuel tank, the height difference between the pump

  • 7/28/2019 Manual Operacao Amf25

    47/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-43

    and the fuel tank generates a differential pressure, the differential pressure will affect the

    work of the engine.

    When the fuel tank is above the pump, correct fuel return may become an issue, and the

    tubing will have to be able to withstand a positive pressure. If the differential pressure is too

    large, fuel leaks may become a concern.

    When the fuel tank is below the pump, the fuel supply may become an issue, and the tubingwill have to be able to withstand a negative pressure. If the differential pressure is too large,

    fuel supply may become a concern.

    Fuel Filter and Fuel/Water Separator

    The fuel filter located between the tank and the

    injection pump prevents foreign matter from

    entering the injection pump. A standard filter

    uses a paper element (filtration diameter less

    than 15). Normally filter elements or cartridges

    must be changed every 400 hours. Air trapped in

    the filter is purged by the vent plug.

    Fuel-water separator is a device designed to

    separate gross amounts of fuel and suspended

    solids from the wastewater effluents of fuel

    refineries, petrochemical plants, chemical plants,

    natural gas processing plants and other

    industrial sources.

    Three-way valvesValves used to switch between the base

    tank and a remote tank. Normally, the

    three-way valves are open to the base tank.

    When a remote tank is used simply open

    both of the valves to allow connection to

    the remote tank. The figure shown below

    shows the three-way valves in the default

    location connected to the base tank.

    4.7.2 Lubrication system

    All moving parts of the engine must be lubricated to function correctly. For this purpose, the

    lubricating oil circulating through the engine has a number of functions. In addition to

    reducing friction, the oil cools the engine, controls expansion and dispersion of bearing areas,

    provides a sealing action, prevents rusting, seals out dust, and purifies products generated in

    the cylinders by incomplete combustion.

  • 7/28/2019 Manual Operacao Amf25

    48/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-44

    CLASSIFICATION OF ENGINE OIL

    SAE (Society of Automotive Engineers) Standards are generally used to classify engine oil

    viscosities. Viscosity is a principal property of oil, the higher the viscosity, the thicker the oil

    film formed over the metal surface will be and the lower the viscosity, the thinner the film

    thickness becomes.

    Viscosity varies with temperature. The higher the temperature, the lower the viscosity and

    vice versa. Engine oil should have the appropriate viscosity and have properties which are

    not affected by viscosity changes caused by temperature changes. In other words, engine oil

    must have a high viscosity index. Multi grade oils having relatively low viscosity (For example

    SAE 10W-30) can provide superior lubrication at both low and high temperatures. Such oils

    are available commercially for all-season use.

    Oil viscosity changes in cold temperature as crystallization of the wax element contained in

    oil proceeds, and fluidity is finally lost. Incorrect selection of oil cannot only increase

    resistance for cold starting but also affect lubrication of each part. Oils for low

    temperature, containing additives for lowering the pour point, should be used. The following

    diagram shows how to select lubricants.

    Warning

    Poor quality oil will shorten engine life. Use only the specified lubricating oils. Important

    points regarding lubricating oil are described below.

    NoteThe use of synthetic oil is not recommended.

  • 7/28/2019 Manual Operacao Amf25

    49/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-45

    4.7.3 Exhaust system

    Exhaust system components installed on any genset must be approved and correctly

    installed to meet the codes and regulations required by local government.

    A muffler and spark arrester have been installed in your genset. If a generator is used in a

    forest, on brush or grass covered unimproved land it must be equipped with a Spark

    Arrestor. It is the responsibility of the generator owner or operator to maintain the entireexhaust system in good working condition.

    Engine exhaust must be routed away from building

    intake vents, windows, doorways and other

    openings.

    Because the exhaust discharge is in a vertical

    position it may be possible for raim water to enter

    the muffler. A drain valve has been provided at the

    base of the muffler to remove any unwanted

    water. This process must be completed whilst the

    engine is shut down, as it may cause injury.

    4.7.4 Ventilation and cooling system

    As the generator produces a high volume of

    heat, ventilation and heat dissipation must be

    carefully considered. The generator has been

    specially designed to operate in ambient

    temperatures to 50C.

    If the generator is used outdoors, ensure that no

    objects (such as plastic bags, etc.) are allowed to

    block the air inlet. The engine exhaust

    temperature is extremely high, do not vent

    towards any objects that cannot withstand high

    temperatures.

    The machine is provided with cabinet filters that

    must be cleaned regularly. In dusty

    environments, the cabinet filters must be

    cleaned daily. Remove the cabinet filters as the

    follow steps: Loosen the philips head screw at

    the top of the grille, remove the limit stop, andthen slide the air filter out.

    If the generator is used indoors, make sure that there is adequate ventilation to the air inlets

    and outlets, and that the engine's exhaust is ducted out of room.

  • 7/28/2019 Manual Operacao Amf25

    50/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-46

    4.8 Load Connections

    4.8.1 Sizing Load Cables

    Selecting the load cables, number of cores and diameter, based on its allowable

    amperage and the distance between the generator and the load is critical.

    Correct selection should be carefully calculated. It is recommended that there is a

    maximum 5% marginal drop only for the rated voltage between the load and generator

    via the cables. This should be considered when selecting the cable.

    DANGERIf the load exceeds the allowable amperage overheating may cause damage to cables.

    If the cables are too long, there will be excessive voltage drop. It may result in fire,

    personal injury, reduced performance or damage to machinery.

    4.8.2 Connecting Load Cable

    The generator is ready for field connections. The cables should be connected to the

    Main wiring terminals which are located inside the field wiring cabinet.

    WARNING:

    Before connection, the following precautionary measures must be taken

    Connection must only be carried out by a licensed electrician.

    Battery must be disconnected.

    The control power switch must be set to the OFF position.

  • 7/28/2019 Manual Operacao Amf25

    51/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-47

    4.9 Earth Connections

    The generator and electrical components have their respective earth wires which are all

    connected to the main earth bar in the control cabinet.

    Multiple Earthed Neutral (MEN) is installed on this

    generator.

    4.10 Battery Connections

    The battery cables should be disconnected when the

    generator is required to be transported or be stored for

    long periods. Reconnect the battery cables before running

    the machine.

    Connect the red cable to the positive (+) terminal post.

    Connect the black cable to the negative (-) terminal post.

    WARNING:

    If theterminal is not connected, it may result in injury or death. All the doors must be earthed.

    Main earth and earth spike should be installed and tested by a licensed electrician before

    running the generator.

    WARNING:

    Do not dispose of the battery in a fire. The battery may explode. Battery electrolyte solution

    is caustic and can cause severe burns and blindness. If electrolyte contacts skin or eyes,

    immediately flush the area with water and urgently seek medical attention.

  • 7/28/2019 Manual Operacao Amf25

    52/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-48

    WARNING:

    Do not operate the generator before connection of the ATS.

    4.11 ATS Connections

    The generator is equipped with an Automatic Transfer Switch (ATS) plug on the left side of

    the control panel. The customer can select an appropriate automatic transfer switch (ATS)

    and connect it to the generator.

    Connect the wire between the generator set and ATS plug.

    Connect the wires between the generator main wiring terminals

    and the ATS wiring terminals.

    Connect the wires between the mains supply wiring terminals

    and the ATS wiring terminals.

    Connect the wires between the load wiring terminals and the

    ATS wiring terminals.

    The ATS is controlled by the PLC module which can monitor the incoming AC mains supply. If

    the mains supply is satisfactory the load is run through the ATS and the generator will not

    run. On the contrary the generator will run if the mains power is abnormal.

    THE ATS LOCATION IS IMPORTANT, THE FOLLOWING MUST BE OBSERVED:

    The ATS should be located inside the building near the main switchboard.

    Locate the ATS in a clean, dry, well ventilated location, away from excessive heat.

    When the ambient air is above 40C (104F), fuses and circuit breakers must be

    de-rated. Allow adequate working space around the transfer switch.

    Never install control wires in the same conduit with mains wiring.

    ATS and all equipment must be installed in accordance with relevant local and

    national codes and regulations.

    If the ATS is mounted outside, it must be protected from the environment. Do not mount the ATS on the generator.

    Do not mount the ATS where flammable liquids or vapours are present.

    http://void%280%29/http://void%280%29/
  • 7/28/2019 Manual Operacao Amf25

    53/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-49

    5. Operation

    5.1 General Pre-check Before Starting

    Before starting the generator, check each item below:

    Check engine oil, fuel and coolant.

    Check for leakage at the hose connections.

    Check to make sure there are no obstructions lodged in vents, near the radiator or

    around the cooling fan.

    Ensure that nothing is contacting the muffler or exhaust pipes.

    Check the generator is earthed and the earth spike is installed and tested as per

    local regulations.

    Make correct terminal connections. TEST accordingly.

    Check that all electrical connections were made in compliance with local regulationsand standards.

    Make sure the fan belt and hoses on the engine have no loose connections or are

    fraying. Tighten or replace as required.

    Check the battery cables are firmly secured to the terminals. Tighten the clamps if

    necessary.

    Close and secure side panel access doors.

    Review and follow safety instructions at the front of this manual.

    Warning:

    1. Failure to follow the procedures listed in this manual may cause injury to personnel or

    damage to the generator. Ensure all persons setting up the generator are certified or

    fully trained on the installation of the generator.

    2. Always wear protective gloves, clothes and other P.P.E. as required.

    WARNING:

    Do not use the machine when any leak is found. Repairs are to

    Be carried out by trained personnel and according to regulations.

  • 7/28/2019 Manual Operacao Amf25

    54/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-50

    5.2 Checking Engine Oil, Fuel and Coolant Level Before Starting

    5.2.1 Engine oil

    Ensure that the generator is on level ground before checking

    engine oil level. Install the oil dipstick all the way in.

    The appropriate level should be between the lower limit and

    upper limit on the dipstick.

    Add engine oil if the level is below the lower limit.

    Select the appropriate engine oil.

    Open the access door, remove oil cap.

    Add engine oil to bring oil level NO higher than FULL

    mark on the dipstick.

    Tighten the oil inlet cap and close the access door.

    CAUTION: If the generator is not level when checking the engine oil, you cannot obtain an

    accurate oil level reading.

    Do not overfill the engine oil. The level cannot exceed the upper limit. An excessive

    amount of engine oil may damage the engine.

    Do not smoke and extinguish any naked flames before adding engine oil.

  • 7/28/2019 Manual Operacao Amf25

    55/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-51

    5.2.2 Fuel

    Remove the fuel inlet cap and check the fuel level in the tank.

    Adding Fuel:

    Select the correct fuel.

    Loosen the fuel inlet cap and remove it. Fill the fuel through the inlet until the fuel is slightly

    less than the full-tank level

    Tighten the fuel inlet cap.

    5.2.3 Coolant

    Remove the radiator cap, check coolant level in the tank.

    Adding Coolant:

    Remove the coolant inlet cap.

    Remove the radiator cap.

    Fill coolant up to the radiator inlet top.

    Reinstall and tighten the coolant inlet and radiator

    caps.

    WARNING:

    Avoid injury! The coolant will be hot and can burn skin. Built-up pressure may cause

    explosive release of coolant when the radiator cap is removed. Shut off engine and

    allow it to cool. Do not remove cap unless the radiator and the engine are cool to

    touch with bare hands. Slowly loosen the cap to the first stop to release all pressure,

    then remove cap.

    CAUTION:

    1. Do not smoke while you are refuelling an engine.

    2. Do not refuel an engine near open flames or sparks.

    3. Always stop the engine before refuelling.

  • 7/28/2019 Manual Operacao Amf25

    56/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-52

    DANGER:

    Before turning the Main Circuit Breaker (19) to ON, make sure all loadcircuit breakers and switches are positioned to OFF. Failure to do so may

    cause an electric shock to the operator.

    Do not touch any wires or connections when the generator is running, thismay result in serious injury or death.

    5.3 Manual Start-up

    Carefully read the illustration on the control cabinet and control panel (PLC), then

    proceed according to the following operation steps:

    1. Set every circuit breaker and load switch to the OFF position.

    2. Turn the Main Circuit Breaker (19), Circuit Breaker (14, 15, 17), RCD/MCB (21, 22),

    RCD (16, 20),GPO Switch(18) to the OFF position.

    3. Open the side access door and turn on the engine battery switch, then close the

    door.

    4. Turn the Master Control Switch (8) to the ON position.

    5. Select manual mode.

    6. Press the START button (5), the fuel solenoid is energised and after a one-second

    delay the starter motor will crank the engine for the duration of the crank timer

    (preset on PLC, three attempts).7. After the engine successfully starts, allow allow approximately five minutes for the

    engine to warm.

    8. Turn the Circuit Breakers ON (19, 14, 17 ), turn the GPO Switch(18), RCD/MCB (21,

    22), RCD (16, 20) ON. This will allow power to all of the respective outlets (GPOs &

    main terminals). The external load can now be switched on.

    5.4 Automatic Start-up

    Follow steps 1 to 4 as described above (see 5.3).

    Select AUTO mode.

    Press the START button (5), the module will proceed with its normal auto start

    sequence.

    The module will monitor the incoming AC mains supply. If the mains supply is

    satisfactory, the ATS will carry the mains loads and the generator will not run. On

    the contrary the generator will run the supply power if the mains supply is

    unsatisfactory.

    The generator will operate up to 5 seconds (Warm up Mode).

    PLC will automatically switch (ATS) load circuit breaker to ON, generator will

  • 7/28/2019 Manual Operacao Amf25

    57/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-53

    supply power.

    NOTE: Before operating the automatic start-up mode, connection of ATS is required.

    5.5 During Operation

    Check the LCD reading of voltage, current, frequency by scrolling the Display

    Buttons and .

    Check the LCD reading of engine oil, coolant and fuel levels.

    Check the LCD reading of engine oil pressure and coolant temperature.

    Check for any alarm signal on the LCD or audible alarm.

    Check for any leakage of coolant, oil or fuel.

    Check for any unusual vibration or noise.

    Check for any unusual colour from the exhaust. Under normal conditions the

    exhaust gas has no colour. If the engine cannot run because of low fuel, bleed the air

    from the fuel system.

    Loosen air release bleed bolt on the fuel filter.

    Bleed the air in the fuel system for about 30seconds.

    Tighten the bolt.

    CAUTION:

    1. If a fault is detected, stop and isolate the machine immediately.

    2. Generator to be repaired by certified or fully trained personnel (refer to

    troubleshooting guidelines 6.7).

  • 7/28/2019 Manual Operacao Amf25

    58/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-54

    5.6 Stopping Generator Under Manual Operation Mode

    1. Turn off every RCD/circuit breaker.

    2. Turn the Main Circuit Breaker (19), Circuit Breaker (14, 15, 17), RCD/MCB (16,

    18), RCD (21, 22), GPO Switch( 18)to the OFF position.

    3. Press the Stop button (6).

    4. Allow the engine to remain idle for approximately one minute to cool down.

    5. Turn off the Master Control Switch (8).

    6. Open the side access door and turn off the battery isolator switch, then close

    the door.

    5.7 Stopping Generator Under Automatic Operation Mode

    If the mains supply returns and the generator does not stop running, follow the steps

    listed below:

    Turn every switch and circuit breaker on the load to OFF position.

    Turn off the Master Control Switch (9).

    Open the side access door and turn off the engine battery switch, then close thedoor.

    5.8 Shutting Down Genset

    The generator is equipped with an automatic shutdown feature. The LCD will display

    the fault.

    Warning:

    In the event of a shutdown alarm, turn off the engine. Generator must be repaired by

    certified or fully trained personnel according to the troubleshooting guidelines (see

    6.7).

  • 7/28/2019 Manual Operacao Amf25

    59/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-55

    5.9 Lifting and Transportation

    Lifting: The top of the generator has two lifting lugs and

    the four chassis angles have four holes attached to the

    lifting frame inside the housing. Refer to the technical datafor the weight of the generator. Make sure the lifting

    device has sufficient capacity to lift the unit safely. When

    lifting the generator, attach a hook or sling securely to the

    lifting lug.

    Transportation: When transporting the generator, it should

    be secured correctly with ropes tied to the roping lugs at

    the top of the generator.

    5.10 Overnight Storage

    When storing the generator overnight, make sure all access

    doors are closed and padlocked.

    CAUTION:

    Do not store generator in a low lying area, as large quantities of water canenter the generators electrical / mechanical systems and damage may result.

    5.11 Long-term Storage

    If the generator will not be used for more than two months, the following procedures need

    to be performed.

    Close and padlock all access doors. Remove the start key.

    Avoid storing generator in a dusty, humid environment.

    Refer to and follow the engine manufacturers recommendations for long-term storage.

    These procedures are designed to help minimize engine corrosion.

    6. Maintenance

    Before performing any checks or maintenance, stop the engine and remove the start key.

    For detailed maintenance procedures on the engine, refer to engine operator's manual.

  • 7/28/2019 Manual Operacao Amf25

    60/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-56

    6.1 Periodic Maintenance Schedule

    SERVICE ITEMS

    DAILY

    ORAFTER

    8 HRS

    WEEKLY

    ORAFTER

    50 HRS

    MONTHLY

    ORAFTER

    100 HRS

    SIX

    MONTHS

    OR

    AFTER

    250 HRS

    YEARLY

    OR

    AFTER

    500

    HRS

    TWO

    YEARS

    ORAFTER

    1000

    HRS

    Check various meters and

    alarm lamps

    Check engine oil , fuel and

    coolant level

    Check for leaks (oil, fuel

    and coolant)

    Check air cleaner dust cap Check generator visually

    Check battery charging

    system

    Check drive belt tension

    Drain water/sediment

    from fuel filter

    Drain water/sedimentfrom fuel tank

    Change engine oil and

    replace oil filter

    Change fuel filter element Clean or change air filter

    element

    Change

    Change

    Check cooling system Clean unit inside & outside Change coolant Pressure test cooling

    system

    Clean inside fuel tank

  • 7/28/2019 Manual Operacao Amf25

    61/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-57

    6.2 New Machines

    Run the generator at least 60 100% of continuous load for the first 100 hours.

    Change engine oil and replace oil filter after the first 50 hours.

    6.3 Air Cleaner

    6.3.1 Clean Air Filter Element

    Loosen clips in the air cleaner and remove the dust cap.

    Remove the air filter element which contains a primary filter and a safety filter.

    Loosen the safety filter from the primary filter.

    Use compressed air to flush the safety filter and primary filter from inside.

    Use a clean cloth to wipe the filter sealing surface and the inside of the outlet

    tube.

    Reinstall the air cleaner in the reverse order.

    6.3.2 Change Air Filter Element

    Loosen clips in the air cleaner andremove the dust cap.

    Remove the air filter element.

    Loosen the safety filter from theprimary filter.

    Change the primary filter.

    Reinstall the air cleaner in thereverse order

    Caution:Do not remove the air cleaner while operating the generator or immediately after

    stopping the machine.

    Do not start the engine after the air cleaner is removed. The backfire can cause

    serious burns.

    Change the primary filter every 250 hours or as required; and the safety filter every

    500 hours or as required.

  • 7/28/2019 Manual Operacao Amf25

    62/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-58

    6.4 Engine Coolant

    Changing Coolant:

    Open the radiator drain ball valve, located on the top of the generator base tank,

    and drain coolant.

    After draining, close the drain ball valve.

    Remove the coolant inlet cap.

    Remove the radiator cap.

    Pour new coolant into the radiator up to the

    radiator inlet top.

    Close the radiator cap and coolant inlet cap.

    WARNING:

    Avoid injury! The radiator will be hot and can burn skin. Built-up pressure may cause

    explosive release of coolant when the radiator cap is removed. Shut off engine and

    allow it to cool. Do not remove cap unless the radiator and the engine are cool to

    touch with bare hands. Slowly loosen the cap to the first stop to release all pressure,

    then remove cap.

  • 7/28/2019 Manual Operacao Amf25

    63/67

    OPERATOR & MAINTENANCE MANUAL

    PAGE-59

    6.5 Engine Oil and Oil Filter

    6.5.1 Change Engine Oil

    Open the oil drain ball valve.

    Open the access door.

    Open sump and oil ball valve which is under the oil

    pump.

    Use oil pump to drain engine oil.

    After draining, close the oil drain ball valve and oil

    ball valve.

    Loosen and remove the oil inlet cap; add oil to the oil inlet through an outside oil filter

    until the level is slightly less than the upper limit by checking the oil level on the oil gauge.

    Tighten the oil inlet cap and close the access door.

    6.5.2 Change Oil Filter

    Drain engine oil completely, as described in 6.5.1.

    Loosen and remove the oil filter.

    Add engine oil into a new oil filter.

    Lubricate the new gasket with oil.

    Screw the new filter into place and tighten it until thegasket touches the seal surface. Tighten accordingly.

    Supply engine oil as described in 6.5.1.

    WARNING:

    1. If the generator is not level when checking the engine oil, you cannot obtainaccurate oil level.

    2. Do not overfill the engine oil. The level cannot exceed the upper limit becausethe excessive amount of engine oil may damage the engine.

    3. Do not smoke or be near an open flame when adding engine oil.

  • 7/28/2019 Manual Operacao Amf25

    64/67

    6.6 Fuel Filter

    6.6.1 Drain Water / Sediment in the Fuel Filter

    Loosen the drain plug to drain water and sediment.

    Bleed the air and tighten plug.

    6.6.2 Change Fuel Filter

    Loosen the drain plug and drain fuel and water.

    Loosen and remove fuel filter.

    Add fuel into a new fuel filter.

    Lubricate the new gasket will oil.

    Screw the new filter into place and tightenaccordingly.

    DANGER:

    Do not smoke while you are refuelling an engine. Do not refuel an engine nearopen flames or sparks. Always stop the engine before refuelling.

    Wear protective gloves, goggles and clothing when changing the fuel filter.

  • 7/28/2019 Manual Operacao Amf25

    65/67

    6.7 Troubleshooting

    When performing any troubleshooting, follow the guidelines. If further clarification is

    required please contact our authorised service agent.

    TROUBLE CAUSES SOLUTIONS

    Low engine oil pressure

    1. Lubricant oil is insufficient 1. Add lubricant oil

    2. Oil hose has leak 2. Tighten or change oil hose

    3. Oil filter is clogged 3. Change oil filter

    4. Wrong oil is used 4. Change to correct oil

    High coolant

    temperature

    1. Coolant is insufficient 1. Add coolant

    2. Coolant pipe has leak 2. Tighten or change coolantpipe

    3. Fan belt is loose 3. Tighten the belt

    4. Radiator core is clogged 4. Clean radiator core

    5. Water temp sensor is

    defective5. Repair or change the sensor

    6. Engine thermostat is

    defective

    6. Repair or change the

    thermostat

    Low fuel level

    1. Fuel is insufficient 1. Add fuel2. Fuel hose has a leak 2. Tighten or change fuel hose

    3. Fuel tank has a leak 3. Repair or change fuel tank

    4. Fuel filter is clogged4. Drain water/sediment or

    change fuel filter

    5. Fuel level sensor is defective 5. Repair or change the sensor

    Cannot turn the breaker

    to on

    1. The main breaker position is

    located between on and off

    1. Turn off and on.

    2. Replace breaker if faulty

    2. Short circuit on the load 2. Check and repair the loadcircuit

    Controller not working

    1. The controller cable is

    disconnected from the

    battery

    1. Connect the controller cable

    to the battery

    2. The battery power is

    insufficient

    2. Charge the battery with the

    utility power

    3. The DV fuse is damaged 3. Change the DV fuse

    Voltage drops when

    connecting to the load

    1. Loads total exceeds the

    rated current

    1. Decrease the loads to meet

    the rated output

  • 7/28/2019 Manual Operacao Amf25

    66/67

    2. Battery output is low 2. Charge the battery

    3. Battery is deteriorated 3. Change the battery

    4. Battery terminal is loose 4. Tighten the terminal

    Starter

    motor

    drives, but

    engine

    cannot start

    1. Fuel is insufficient 1. Add fuel

    2. Fuel hose has leak 2. Tighten or change fuel hose

    3. Fuel filter is clogged3. Drain water/sediment or

    change fuel filter

    4. Gauze filter is clogged 4. Clean or change gauze filter

    5. Air is mixed in fuel line 5. Bleed the air

    Engine starts but stalls

    at once

    1. Fuel hose has a leak 1. Tighten or change fuel hose

    2. Fuel filter is clogged 2. Drain water/sediment orChange fuel filter

    3. Gauze filter is clogged 3. Clean or change gauze filter

    4. Lubricant oil is insufficient 4. Add lubricant oil

    5. Air is mixed in fuel line 5. Bleed the air

    6. Air filter element is clogged6. Clean or change air filter

    element

    Muffler releases black

    smoke

    1. Wrong fuel is used 1. Change to correct fuel

    2. Air filter element is clogged 2. Clean or change air filterelement

  • 7/28/2019 Manual Operacao Amf25

    67/67