MANICA BOARDS and DOORS Tawanda Report on Boiler Final
-
Upload
robin-bushu -
Category
Documents
-
view
42 -
download
2
Transcript of MANICA BOARDS and DOORS Tawanda Report on Boiler Final
1
MANICA BOARDS AND DOORS (MBD) Pvt Ltd
To: Mr. G. T. Zindove
Cc: Mr. S Mukwamba, Mr. Saungweme, Mr. C Nyamugure
From: Mr. Tawanda Bushu (Chemical and Processing System Engineering Attaché).
Date: 7 February 2012
REF: REPORT ON THE BOILER
1.0 INTRODUCTION
A boiler is a heat exchanger that converts chemical energy in fuel to heat energy under
controlled conditions, for the purpose of generating steam. The boiler section is one of the
sections of critical importance in the fiber board production as its operations affect the
whole process of fibreboard manufacture. The main objective of the boiler section is to
provide a steady and constant supply of steam at all times. All this has to happen within the
statutes and parameters that govern the operation of boilers.
2.0 THE BOILER AND ITS SUPPORTIVE ANCILLARY SYSTEMS.
Fig1.1 boiler and its ancillary systems.
2
Fig 1.1 shows what goes into the boiler and what comes out and it is imperative that each
aspect of that system is working in order.
2.1 BOILER.
The type of boiler used at MBD is a Composite Boiler. It consists of a fire-tube boiler and a
John Thompson Chaingrate Stoker (Stoker). A fire-tube boiler is a type of boiler in which
hot gases from a fire pass through one or more tubes running through a sealed container of
water. The heat of the gases is transferred through the walls of the tubes by thermal
conduction, heating the water and ultimately creating steam. The heat source is inside a
furnace or in this case it is the John Thompson Chaingrate Stoker that has to be kept
permanently surrounded by the water in order to maintain the temperature of the heating
surface just below boiling point. (Specifications of boiler found in appendix)
2.2 AIR SUPPLY
Air is drawn in by forced draft fans (FD) which blow onto the feed stocker which will be
carrying burning coal. The volume of feed air is controlled by (FD) dampers but the speed
of the inlet air is constant. Secondary (FD) fans also blow onto the stocker to assist in the
combustion of coal. The heated air is then drawn by a large Induced fan (ID) into fire tubes
on the second section of the boiler. The hot air which in this case is now called flue gas is
further drawn into a grit arrester which in practice is a centrifugal separator to separate grit
from the flue gases. The grit is then collected at the bottom section and the lighter gases
then goes into the chimney where they are discharged into the atmosphere.
2.3 BOILER WATER SUPPLY AND PURIFICATION SYSTEM.
2.3.1 INTRODUCTION
The water supply system must achieve the following.
� Constant supply of safe make up water for the boiler.
� Prevention of corrosion from taking place at all cost or at list keeping it at the lowest
possible level.
� Prevention of formation of scale and scum in the boiler.
3
The system is represented by the flow chart shown below. The water used in the Boiler at
MBD is sourced from the Mutare City Council. The water is first stored in reservoir tanks
then pumped to storage tanks through pipes with strainers to remove suspended solids in
the water. This is the first operation of boiler water treatment. From the storage tanks water
is pumped to the water softeners. From the softeners, water is pumped to 2 treated water
storage tanks. Water from these treated water tanks is fed to the de aerator were it is
scrubbed off the dissolved oxygen in water. Water from the de-aerator is the again treated
with dosing chemicals from the dosing plant en-route to the boiler where steam is
generated in a composite boiler.
Key: A main reservoir
B storage tanks (2)
C, D softeners
E, F storage tanks
G dosing tank
H, I de-aerator water pumps (2)
J de-aerator
4
K, L feed water pumps (2)
M boiler
Fig 1.2 flow chart showing feed water system.
2.3.2 WATER TREATMENT
At (MBD) the chemical laboratory department is the one responsible for caring out all the tests and
analysis of the boiler water. The water is supposed to be tested on two hour intervals .In the event
that there is a large deviation from the normal average then tests are carried out on hourly interval
and a corrective measure is taken in each case until the anomaly is rectified. Boiler water has
certain specifications that it should meet for it to be used in the boiler.
Table 1.1 boiler water specifications
BOILER WATER SPECIFICATIONS
TOTAL
HARDNESS(TH)
NIL
TOTAL DISOLVED
SUBSTANCES(TDS)
2000-3000ppm
Ph More than 10.5
PHOSPATE 30-90ppm
SULPHATE 30-90ppm
CHLORIDE 800ppm
OH 250-600ppm
IRON 0-5ppm
These measurements are critical for the operations of a boiler. Below the different aspects that are
found in water are defined and how they might affect our boiler.
2.3.2.1 DISSOLVED SOLIDS
These are substances that will dissolve in water. The principal ones are the carbonates and sulphates
of calcium and magnesium, Effects:
1. Scale-forming when heated which reducing heat transfer and the effectiveness of the boiler it can
also causing over heating of pipes and eventually the pipes end up bursting.
5
2. Forming and scum formation which can lead to carry overs, damaging of the steam pipes by water
hammers and lowering the steam quality by producing wet steam.
2.3.2.2 SUSPENDED SOLIDS
These are substances that exist in water as suspended particles. They are usually mineral, or organic
in origin. These substances are not generally a problem as they can be filtered out. In the case of
(MDB) strainers are inserted along the pipe lines to trap all suspended solids before the feed water
goes into the boiler. Effects:
1. The effects of suspended solids are the same to those of dissolved solid with the addition that they
damage control valves and heat exchange systems
2.3.2.3 DISSOLVED GASES
Oxygen and carbon dioxide can be readily dissolved by water. Effects:
1. These gases are aggressive instigators of corrosion. According to the design at (MBD) the amount
of oxygen going into the boiler is supposed to be substantially reduced by the de-aerator.
2.3.2.4 SCUM FORMING SUBSTANCES
These are mineral impurities that foam or scum. One example is soda in the form of a carbonate,
chloride, or sulphate. Effects:
1. Scum can cause carry-over of suspended solids which has the same negative effects as those of
suspended solids.
2.3.2.5 HARDNESS
Water is referred to as being either 'hard' or 'soft'. Hard water contains scale-forming impurities
while soft water contains little or none. Hardness is caused by the presence of the mineral salts of
calcium and magnesium and it is these same minerals that encourage the formation of scale. There
are two common classifications of hardness:
1. Alkaline hardness (also known as temporary hardness) - Calcium and magnesium bicarbonates are
responsible for alkaline hardness. The salts dissolve in water to form an alkaline solution. When
heat is applied, they decompose to release carbon dioxide and soft scale or sludge. Alkaline or
temporary hardness.
6
2. Non-alkaline hardness and carbonates (also known as permanent hardness) - This is also due to the
presence of the salts of calcium and magnesium but in the form of sulphates and chlorides. These
precipitate out of solution, due to their reduced solubility as the temperature rises, and form hard
scale, which is difficult to remove. The purpose of the softener is to remove this hardness. In
addition, the presence of silica in boiler water can also lead to hard scale, which can react with
calcium and magnesium salts to form silicates which can severely inhibit heat transfer across the
fire tubes and cause them to overheat.
2.3.2.6 TOTAL HARDNESS
Total hardness is not to be classified as a type of hardness, but as the sum of concentrations of
calcium and magnesium ions present when these are both expressed as CaCO3. If the water is
alkaline, a proportion of this hardness, equal in magnitude to the total alkalinity and also expressed
as CaCO3, is considered as alkaline hardness, and the remainder as non-alkaline hardness
\
2.3.2.7 NON-SCALE FORMING SALTS
Non-hardness salts, such as sodium salts are also present, and are far more soluble than the salts of
calcium or magnesium and will not generally form scale on the surfaces of a boiler
7
2.3.2.8 pH VALUE
This is a numerical value representing the potential hydrogen content of water - which is a measure
of the acidic or alkaline nature of the water. Acids and alkalis have the effect of increasing the
conductivity of water above that of a neutral sample. For example, a sample of water with a pH
value of 12 will have a higher conductivity than a sample that has a pH value of 7.Effects:
1. If the pH value is low then the feed water will be highly corrosive and can not be tolerated.
2. If pH is high say its 13 then it cause corrosion again in the form of crack corrosion.
It is therefore very crucial to make sure that the water is treated so as to avoid the above mentioned
problems. To achieve the above specifications water from the city council goes through a number
of stages so as to meet the above stages. The water is suppose to firstly pass through softeners to
reduce its hardness but currently the water softeners are not working, this is then followed by de-
aeration by a de-aerator which is functioning and lastly trough chemical treatment.
2.4 WATER SOFTENING
At MBD water softening was achieved by using resin softeners to remove hardness of water.
Hard water has high concentrations of Ca2+ and Mg2+ ions in form of salts that encourage
the formation of scale (fouling). Technical specifications of softeners found in
appendix.Water flows into the softener from the top making a fine spray on top of the
resins. The magnesium and calcium ions in the water are adsorbed on the surface of the
resin and sodium ions are released into the water. In principal this is basically the softening
process. The softening action continues until the ion exchange material contains no more
sodium which can be exchanged for calcium and magnesium.
8
After 24 hours the resins becomes saturated with impurities and needs to be regenerated.
The regeneration takes place in four stages that are given below. The whole regeneration
process takes an average of 1 hour 30 minutes.
� Backwash stage
This is the first stage in the regeneration process. Water enters the softener in a
reverse direction all the impurities that are trapped in the softener are washed
out buy this reverse flow into the drain
� Sodium injection
Brine which is sodium chloride solution is pumped into the softener. Sodium
ions are adsorbed on the surface of the resin at the same time magnesium and
calcium ions are discharged into solution the solution. This is preferential
adsorption. During this stage no water enters the softener.
� Fast rinse
Water enters the softener in the normal way and the calcium and magnesium
ions in the solution are then washed out into the drain.
� Slow rinse.
This time water enter into the softener with a very slow rate all the calcium and
magnesium ions are then washed away and the softener is now ready for use
.MBD had two softeners so that during the regeneration of one softener the
other softener will be working but at present none is functioning.
From the softeners the water goes to the water storage tanks. The storage tanks have a glass
water level indicator and must be kept full at all times. In the storage tank EDITA is added
as an ant-scelent. From the storage tanks water goes into the de- aerator.
2.5 THE DE-AERATOR
De-aeration is based on two scientific principles. The first principle can be described by
Henry's Law. Henry's Law asserts that gas solubility in a solution decreases as the gas
partial pressure above the solution decreases. The second scientific principle that governs
de-aeration is the relationship between gas solubility and temperature. Easily explained, gas
9
solubility in a solution decreases as the temperature of the solution rises and approaches
saturation temperature. A de-aerator utilizes both of these natural processes to remove
dissolved oxygen, carbon dioxide, and other non-condensable gases from boiler feedwater.
This process can be classified as a unit operation called scrubbing. The feedwater is
sprayed in thin films into a steam atmosphere allowing it to become quickly heated to
saturation. Spraying feedwater in thin films increases the surface area of the liquid in
contact with the steam, which, in turn, provides more rapid oxygen removal and lower gas
concentrations. This process reduces the solubility of all dissolved gases and removes it
from the feedwater. The liberated gases are then vented from the de-aerator. The de-aerator
saves two purposes
1. To remove dissolved gases in the boiler feed water.
2. To raise the temperature of the feed water to a temperature of about 750 C
Reasons:
� Dissolved gases lead to corrosion of the boiler.
� Dissolve gasses can accumulate in the steam section of the boiler forming
bubbles.
� To avoid heat stress in the boiler so as to avoid thermal stress failure in the
boiler.
� To increases solubility of dosing chemicals.
� To save energy during steam production since the water will be at elevated
temperatures already.
The de-aerator that is being used uses scrubbing mechanism. The diagram below shows
how this process works
10
Water from the storage tanks is pumped into the de-aerator. The de-aerator has a control
valve and a pressure gauge to regulate the rate at which the water goes into the de-aerator
so that flooding or wiping will not take place in the boiler. The feed water enters the de-
aerator in the form a fine spray on top of the tray and flows down onto the trays where it
comes in contact with the steam which will be rising through the perforated trays. The
steam will strip the water of dissolved gases as it rises. Heat exchange also takes place
between the steam and the water resulting in an increase in the temperature of the water as
a result the solubility of dissolved gases decrees and the water gives up the dissolved gases.
The water then accumulates in the water storage section where a further heating occurs to a
temperature of about 80oC. From the de-aerator the water is then pumped in the boiler by
boiler feed pumps. Before it is pumped dosing chemicals are introduced between the de-
aerator and the feed pumps.This conditioning the water is then feed into boiler
2.6 DOSING CHEMICALS
Three chemicals are dosed online into the feed water. One is for scale and deposit control,
the other one for oxygen corrosion control and the last one is a pH booster.
� scale and deposit control
To control this, a phosphate based treatment (chematron 155) is used. Chematron
155 is synergistic blend of organic and inorganic scale inhibitors.
11
� Oxygen corrosion control
The oxygen scavenger used has sulphite as the active component.
� pH buster
Caustic Soda is used as the pH buster
These chemicals are feed into the feed water stream by an adjustable pump which regulates
the rate at which these chemicals are feed into the feed water.
2.7 CONTROL SYSTEM
2.6.1 BOILER CONTROL SYSTEM
The boiler has a control system that regulates it operations. The system has gauges that self
regulate according to set points. (Copy of boiler control system attached)
� Water level
The boiler has a self regulating system that controls the amount of water in the boiler as
per set range of set points set by the operator. It also has a gauge known as the mobri
switch that gives an alarm when the water level reaches a critical low level. It also
operates within a range of set points set by the designer. If it reaches the lower set point
it automatically shuts the boiler off. The main feed water modulating control valve is an
electro pneumatic control valve which actuates level into pneumatics. It opens when the
level is below the lower value set point and closes when the level goes above the upper
set parameter. The system has a bypass in case of failer of modulating valve which can
be used during repairs to the valve
� Pressure control
The boiler has a valve that regulates the pressure within design set points. This gauge
shuts off the ID fans when pressure reaches the upper set point. The pressure release
valves are design feature for failure of the pressure control valves. It also controls the
amount of heart that goes through to the shells reducing the amount of steam generated
and thus controlling pressure.
� Flow control
12
The boiler has a valve that controls flow rate as per designed parameters. The feeder
pipe has a designed capacity of nominal flow 16.5t.h and a maximum flow of 20.0t.h.
� Combined control system
The above control systems are connected altogether in controlling the boiler. The main
objective of a combined control system is to for them to complement one another in
case one fails the other can regulate the system.
2.6.2 DE-AERATOR CONTROL SYSTEM
The de-aerator has a control system that regulates its operations. The system has gauges that
self regulate according to set points. (Copy of boiler control system attached)
� Water control.
It has an electro pneumatic control valve which controls the level of water in the de-
aerator within two set points. It opens when the level goes below the lower limit and
closes when it passes the upper limit. There is also a bypass system which is used in
case the valve malfunctions.
It also has an over flow valve that opens when the water level surpasses the upper set
value of level and closes when it reaches the lower limit. It compliments the level
control valve.
� Steam control
The de-aerator has a pressure electro pneumatic pressure control valve which maintains
the pressure in the de-aerator within given set. There is also a bypass system which is
used in case the valve malfunctions.
2.8 STEAM GENERATION
13
Hot gases from a fire pass through one or more tubes first running through a sealed container
of water. The heat of the gases is transferred through the walls of the tubes by thermal
conduction, heating the water and ultimately creating steam. The heat source is inside a furnace
or in this case it is the John Thompson Triumph Chaingrate Stoker that has to be kept
permanently surrounded by the water in order to maintain the temperature of the heating
surface just below boiling point. With the aid of the ID fan the flue gas moves to the shell side
of the boiler where it travels through 2 tube passes transferring heat by convection to the
surrounding water creating steam
2.9 STEAM USES
1. Pre-heating the de-aerator
2. Source of energy during pressing
3. Pre-treatment of the chips before defibration process
4. Source of energy during defibration process
5. Heat water at the accumulator
.
2.10 HEAT GENERATION
Coal is used as source of fuel in the stoker and it is washed pear size currently sourced
from Hwange. Washed peas coal is used and an average consumption of
1200tonnes/month. From the stoker hopper coal is laid onto the Chaingrate which is
rotating at a preselected speed. The Chaingrate then transfers the cola into the boiler via the
guillotine door which regulates the fuel bed thickness. After passing under the guillotine
door the coal is heated by radiation from the hot refractory ignition arc. Release of
volatile’s constituents of coal commences at about 1500C. The volatiles mix with the air
supplied by the FD fans and burn above the fuel bed. The burning volatiles heat the ignition
arc and radiate directly onto the oncoming fuel and supplement the effect of the arc. A step
in the arc increases turbulence in the ignition zone. This promotes mixing of the volatiles
and the air, increasing flame temperature and so improving the overall effect of the system.
The coke formed in the ignition arc the move s into the furnace arc where burns through a
14
high temperature oxidizing atmosphere leaving a layer of ash on the chain grate. The coal
burns according to the following equation
C + O2 → CO2 + heat
The heat produced is of importance and is quantified by equation
Q=UAdT
Where
Q is the heat transferred per unit time,
A the area available for the flow of heat,
dT the difference in temperature between the flame and the boiling water, and
U is known as the overall heat transfer coefficient (W/m2 K).
Heat is either transferred by conduction to the water tubes surrounding the stoker or by
convection and radiation to the fire tubes of the boiler
For conduction:
Q= kA(T1-T2)/x [3]
Where:
k is the thermal conductivity of the material.
x wall of thickness
T1 and T2 Temperatures of stoker inside and outside walls respectively
For convection (forced convection):
Q= hA(T1-T2) [4]
Where:
k is the thermal conductivity of the material.
x wall of thickness
T1 and T2 Temperatures of stoker inside and outside walls respectively
The heated water will then produce steam and the amount of heat can be quantified by:
15
Q = mCpdT [5]
Where:
m mass flow rate of top up water (Kg/s)
Cp specific heat capacity of water
dT temperature rise of top up water
The following energy balance equation will then apply assuming that there are no further
energy losses.
Ms hfg = Q¯ = m Cp dT [6]
Where:
Ms = mean steam consumption rate (Kg/s)
hfg = specific enthalpy of evaporation of steam (kJ/Kg)
Q¯ = mean heat transfer rate (kW)
Heat is also lost in a number of ways and these have effects on thermal efficiency of the
boiler.Boiler efficiency simply relates energy output to energy input, usually in percentage
terms:
Boiler efficiency, in the simplest terms, represents the difference between the energy input
and energy output. The following design issues should be considered during a boiler
efficiency evaluation.
1. Number of boiler passes.
The number of boiler passes simply represents the number of times the hot
combustion gas travels across the boiler (heat exchanger). A boiler with two passes
provides two opportunities for the hot gasses to exchange heat to the water in the
boiler. A 4-pass unit provides four opportunities for heat transfer. The stack
temperature of a 4-pass boiler will be lower than the stack temperature of a similar
size 2- or 3-pass boiler operating under similar conditions.
2. Repeatable air/ fuel control
16
The efficiency of the boiler depends on the ability of the burner to provide the
proper air to fuel mixture throughout the firing rate, day in and day out, without the
need for complex set-up or adjustments. Many burner designs can deliver the
required air-to-fuel mix with enough time provided to adjust the burner or for a
single test period.
3. Combustion Efficiency
Combustion efficiency is an indication of the burner’s ability to burn fuel. The
amount of unburned fuel and excess air in the exhaust are used to assess a burner’s
combustion efficiency. Burners resulting in low levels of unburned fuel while
operating at low excess air levels are considered efficient.
4. Thermal Efficiency
Thermal efficiency is a measure of the effectiveness of the heat exchanger of the
boiler. It measures the ability of the exchanger to transfer heat from the combustion
process to the water or steam in the boiler. Because thermal efficiency is solely a
measurement of the effectiveness of the heat exchanger of the boiler, it does not
account for radiation and convection losses due to the boiler’s shell, water column,
or other components. Since thermal efficiency does not account for radiation and
convection losses, it is not a true indication of the boilers fuel usage and should not
be used in economic evaluations.
5. Fuel-To-Steam Efficiency
Fuel-to-steam efficiency is a measure of the overall efficiency of the boiler. It
accounts for the effectiveness of the heat exchanger as well as the radiation and
convection losses. It is an indication of the true boiler efficiency and should be the
efficiency used in economic evaluations. when dealing with fuel to steam efficiency
2.11 HEAT LOSSES
� Heat losses due to unburned carbon
� Size of the coal, fired in boiler should be controlled. For example for
sticker fired coal, it should not be more than 20 mm.
� Proper amount of excess air should be supplied to the boiler. Boiler
should not be overloaded.
17
� Homogenous mixing of air and fuel should be maintained.
� Heat losses due to formation of carbon monoxide
� Excess air should not be less than 60%.
� Air should be entered with higher turbulence so that each carbon atom
comes in contact with oxygen atoms.
� Ratio of Actual air to theoretical air should be more than 1.3.
� Heat losses due to moisture in the fired coal
� Proper storage of coal should be done. (Especially in rainy season). Coal
preheating
2.12 HEALTH AND SAFETY
The boiler is both the source of energy for most unit operations in fibreboard production as
well as a source of indirect and direct risk. The operations of the boiler are guided by the law
• The Factories and Works Act 14:08/1996
• Regulations that include
1. RGN 279 of 1976 (Boilers).
2. RGN 303/1976 (Pressure vessels).
It is the best interest of the company that these regulations are followed for the safety of the
operator and the boiler itself.
2.13 FINDINGS
� Water analysis
The primary objective of the boiler is to supply steam to the production line, this supply
if primarily affected by things such as boiler efficiency and the efficiency is affected a
number of things and boiler water is one of them. Boiler water samples were taken for a
number of days to analyze the effect of the boiler water to the boiler.
MONDAY TUESDAY
property FW SW ST BW DW FW SW ST BW DW
pH 6.4 6.2 6.6 9.2 7.0 6.8 6.6 6.7 9.9 8.1
conductivity 26 14 24 700 22 20 20 22 84 89
18
TDS 18 22 16 540 14 14 14 18 580 62
TH 17 11 20 ND ND 20 9 23 ND ND
Ca H 6 NA 11 10 4 NA
CL 84 70
Sulphite 11 9
PH 30 20
WENESDAY THURDAY
FW SW ST BW DW FW SW ST BW DW
pH 7.73 7.90 6.69 10.65 9.15
conductivity 20 20 20 900 34 20 20 20 920 26
TDS 18 20 20 540 14 14 14 18 580 62
TH 9 9 9 6 7 7 10
Ca H 6 2 5 7 5 7 6 4
CL 84 67
Sulphite 35 40
OH 31 34
A close analysis of these results will help us appreciate the effects of the water top the
boiler. The main are of concern is hardness, as the softeners are not working. The
results of the city council water show that it is not hard water as total hardness is fairly
low, lucky for us. Analysis of the feed water and the softeners water produces relatively
the same results.
The pH is generally within the parameters playing around alkalinity which is good for
the boiler. The next other thing very important is the sulphite concentration in the boiler
water; a low concentration would mean that little oxygen was removed from the boiler
water resulting in the corrosion of the shells. The results show that this was happening
on monday and tuesday with a corrective measure being taken the day after. The major
issue that was highlighted was the boiler operators were conducting blow downs before
the chemicals added to counter this effect had worked.
19
It can be said that the dosing chemicals are achieving their desired objective and it can
be highlighted by the results above
� Boiler operations
Boiler operations have deviated from their designed operations. Control mechanisms
that were put in pace to make boiler operations safe and within desirable parameters are
no longer functional. The majority of the valves on the boiler and the de-aerator are not
functioning properly. Shear pins that seem to be so little to the running of the boiler and
which by design must be made of brass were changed and steel ones were put in place.
They have caused a lot of damage in the running of the chain grate.
The boiler and steam flow should be almost closed a closed system with a little of make
up water but currently make up water is now the major source of water being used. This
shows us that the piping system is now in bad shape as it is loosing a lot of stem and
water which in turn increase the operational costs.
� Redundant equipment
It was observed that the redundant equipment is no longer in the designed specifications
resulting in unnecessary stoppages due to failer of some of the equipment. Below is a
list of the design specification of the equipment.
Boiler Design current
1 Storage tank pumps 1running, 1 standby 1running, no
standby
2 De-aerator feed water
pumps
1running, 1 standby I running, 1
standby
3 Feed water pumps 1running, 1 standby I running, no
standby
4 softeners 1running, 1 standby No running
5 Dosing pumps 1running, 1 standby I running, no
stand by
20
� Analysis of coal used at MBD
Coal used at MBD comes from a different places and an analysis of the coal used
for the past two years was done. Analysis of the results was done (see copy of the
results attached). It can be said that the ideal coal for use in the burner should have
low sulpher contents which are good for the boiler and the atmosphere, high volatile
content which release sufficient heat energy to ignite the coal, and an average
moisture content as it helps to limit segregation. It can be seen that at times the
buying of the coal is done not paying much attention to the previous records of
which coal is best for boiler.
� Soot blowing.
Soot blowing was condemned, as the boiler is not producing dry steam which is a cause
of concern. Removing of soot is now done during plant shut downs.
2.14 RECOMMENDATION
� Control system repair needs to be restored. It is imperative that the boiler and de-
aerator control systems be functional. This not only reduces pressure on the
operator but also on the system as a whole. All valves on the boiler and de-aerator
need to be repaired.
� Redundant equipment need to maintain as per designed specifications so as to
reduce dead time.
� New softeners need to be bought and installed to further reduce the effects of
hardness on the boiler.
� Finding the perfect coal with the right constituents is a bit difficult but blending two
typical coals is recommended for example Hwange coal and sengwa coal. Hwange
coal is typical low moisture, high sulphur, high volatile content coal and low ash
fusion temperature, with sengwa being a low sulphur, moderately to high moisture
content, high volatile content but high ash fusion temperature. Blending the two
colas produces excellent results as the shortfalls of the other are complimented by
21
the other. Blending enables Hwange coal to burn to ash reducing clinkage and
significantly reducing costs.
� Proper maintenance of the boiler needs to be done as this can reduce future
operational costs which at times can even result in the whole boiler being replaced.
� It needs to be investigated why the boiler is producing wet steam.
2.15 APPENDIX
� Boiler specifications
Type Water tube and Fire tube
Manufacturers Cochrane engineering
Working pressure 32 bars
Design efficiency 75%
Size Capacity output 20 tones per hour
Type of fuel Coal (washed peas)
Firing methods chain grate stroker
Draught plant ID and FD draughts
� De-aerator specifications
Model Chematron T.6
Storage volume 3700 kg normal operation
Outlet capacity 1 800-2 150 kg/hr
Operating pressure 410 kPa
Design pressure 600 kPa
Outlet temperature 152 0C
Heating steam volume 1 200 kg/hr
Heating steam pressure 2 900 kPa
Heating steam temperature 233 0C
� Softeners specifications
MODEL AC 300 Aquamatic
22
Maximum working pressure 550 kPa
Minimum working pressure 250 kPa
Maximum softening flow 12 m3/hr
Minimum softening flow 1.5 m3/hr
Resins Ambelite IR12 sodium cations
softening resins
� Blow down Blow down is the removal of water in the boiler. Feed water impurities, oxygen scavengers,
caustic soda and other chemicals that are injected in the boiler form sludge in the boiler. If
uncontrolled the sludge will cause “foaming” and “carryover” which is a threat to the
piping system. Blow down is necessary to avoid total dissolved solids from exceeding 3500
mg/ l.