MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN...

107
MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 C O N T E N T S Section Name of Section Page Nos. No. From To Notes (i) (iii) 1 PM Pumps 1 10 2 VA Valve Actuators 11 12 3 PW Pipe Work and Vessels 13 16 4 LF Lifting Equipments 17 19 5 SS H.T. Sub-station Equipments 21 29 6 TR Transformer and Voltage Stabilizer 31 38 7 LT L.T. Panel 39 50 8 CP Capacitor 51 51 9 LG LT Switchgear and Protection 53 57 10 HG HT Switchgear and Protection 59 62 11 CB Cable 63 76 12 MO Motors 77 82 13 LB Removing, Dismantling, Assembling & Re-erection 83 84 14 TL Tools 85 86 15 EC Electro Chlorination System 87 88 16 GC Fully Automatic Gas Chlorination System 89 89 17 WM Water Meter 91 113 18 Cable Selection Chart 115 118

Transcript of MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN...

Page 1: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MAHARASHTRA JEEVAN PRADHIKARAN

ELECTRICAL & MECHANICAL CSR 2012-13

C O N T E N T S

Section Name of Section Page Nos.

No. From To

Notes (i) (iii)

1 PM Pumps 1 10

2 VA Valve Actuators 11 12

3 PW Pipe Work and Vessels 13 16

4 LF Lifting Equipments 17 19

5 SS H.T. Sub-station Equipments 21 29

6 TR Transformer and Voltage Stabilizer 31 38

7 LT L.T. Panel 39 50

8 CP Capacitor 51 51

9 LG LT Switchgear and Protection 53 57

10 HG HT Switchgear and Protection 59 62

11 CB Cable 63 76

12 MO Motors 77 82

13 LB Removing, Dismantling, Assembling & Re-erection 83 84

14 TL Tools 85 86

15 EC Electro Chlorination System 87 88

16 GC Fully Automatic Gas Chlorination System 89 89

17 WM Water Meter 91 113

18 Cable Selection Chart 115 118

Page 2: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MAHARASHTRA JEEVAN PRADHIKARAN

MJP ELECT. / MECH. CSR 2012-13

NOTES

1. The rates in this CSR are applicable for Electrical and Mechanical Works in Maharashtra Jeevan Pradhikaran.

2. The rates in this schedule are inclusive of all taxes, duties and insurance but exclusive of

octroi. 3. In case of work, which are in the octroi limit of Municipal Corporation, the provision of

this amount shall be made while preparing the working estimate and got sanctioned by competent authority.

4. The rates in the schedule are inclusive of routine tests at manufacturer’s works, packing,

forwarding, loading, transportation including head load carting upto 0.5 km., unloading, storing and insurance and overhead charges wherever applicable.

5. The rates in this schedule do not include charges payable to MSEDCo. for power supply. 6. Following increase on rates in this CSR is admissible on account of the following-

Admissible increase on Rates for Supply Part Erection Part

a) Notified hilly and inaccessible area / tribal area as detailed in Civil CSR of MJP for respective regions (except Matheran)

2% 20%

b) For additional lead for head load carting above 0.5 km (except Matheran)

2% 10%

c) Matheran and its pumping stations 5% 20%

d) Test and Inspections

i) Manufacturer’s inspecting agency’s charges for routine and performance test of pump, motor, transformer and other equipments at manufacturer’s works to be witnessed by M.J.P

As per MJP circular

ii) Inspection charges of third party agency approved by MJP for any or all test at manufacturer’s work.

Page 3: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

7. The rates of items not included in this schedule shall be adopted as follows -

i) The rates if included in CSR of civil works of MJP. ii) If not included in the Civil CSR of MJP, the rates as per CSR of Electrical wing of

Public Works Department of Govt. of Maharashtra. iii) If not included in both (i) and (ii) above the rates as per CSR of MIDC (E & M). iv) If not included in both (i), (ii) and (iii) above, the same shall be worked out on the

basis of budgetary offer / price lists of manufacturers as given below.

For Equipments manufactured out

of Maharashtra

For Equipments manufactured in

Maharashtra

1) Budgetary offer / price list

2) Add for Excise Duty if not included in (1) above

As rate applicable As rate applicable

3) Add for Central Sales Tax for equipments manufactured in States where VAT is not applicable

3%

Nil

4) Add for Value Added Tax (VAT) As rate applicable As rate applicable

5) Add for packing, forwarding, transit insurance, loading, unloading, transportation, insurance upto completion of work

5%

5%

8. Supply rates mentioned in the CAR are derived as per procedure mentioned in Note 7-iv

above, and the same are inclusive of excise duty at the rate applicable. The items for which the third party inspection is made mandatory vide circular no.

MJP/MS (Tech.) TS1 / 350 / 4161 / dt. 10.12.98 will come under extraction of excise duty. For extracting the Excise Duty made payable from supply rate mentioned in CSR, following multiplying factor shall be applied.

Equipments Multiplying Factor

a) Pumps 0.0365

b) Other items excluding (a) 0.073

c) While extracting excise duty, the supply rate of Submersible Pump shall be taken as (Supply rate as per CSR minus Rs. 1,200/-)

Page 4: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

9. Rate of valves shall be as per Civil CSR of MJP and makes of valves shall be as per Elect. / Mech. approved list of MJP.

10. Erection rate mentioned in this CSR shall not be applicable for left over works for which

separate analysis covering actual expenses shall be prepared. 11. While preparing the Estimate, factor for economy of scale shall be used as below -

1) For individual items costing total amount Rs. 5 lakhs to 25 lakh, 5% less shall be adopted on the CSR rate of that individual item.

2) For individual items costing total amount beyond Rs. 25 lakh, 10% less shall be

adopted on the CSR rates. 3) For bulk procurement of Submersible Pumps, Valves, Cable, the CSR rate shall

be reduced by 5%. For Example : The individual item in an estimate is of 5 nos. of motors each costing Rs. 4.00 lakh, totaling to Rs. 20 lakh, rate shall be reduced by 5%.

Page 5: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Code No Description Unit Supply Rate Rs.

Erection Rate Rs.

Total Amount

Rs.

SECTION 1 - PM [ PUMPS ]

PM1 Providing, erecting and giving test of submersible pumpset conforming to IS 8034 and motor conforming to IS9283, with water proof winding. Pump shall be suitablefor various delivery head and discharge with stainlesssteel shaft. Motor suitable for working on 415 V ± 10%,3 Ph, 50 Hz A.C. Supply, with cable guard, thrustcarbon/fiber bearing to withstand entire hydraulic thrust.The pump set shall be suitable for direct coupling, withsuitable suction strainer. Pump should have suitabledischarge out let as per manufacturer's design.Antithrust stream lined non return valve shall beprovided with the pump. 3 m submersible copperconductor cable in single / double run and 2 pairs ofsuitable size erection clamp 10 mm thick shall beprovided with each pump.

PM 1-1 Submersible Pump set 100 mm dia (withPolypropylene / Noryl Impeller) up to 20 stages

PM 1-1-1 1.5 HP Each 18139 2710 20849

PM 1-1-2 2 HP Each 18924 2710 21634

PM 1-1-3 2.5 HP Each 20237 2710 22947

PM 1-1-4 3.0 HP Each 23344 2710 26054

PM 1-1-5 4.0 HP Each 26995 2710 29705

PM 1-1-6 5.0 HP Each 28712 2710 31422

Note 1 Supply rate should be increased by Rs. 200/- per stagefor pump with more than 20 stages

PM 1-2 Submersible Pump 150 mm dia (with BronzeImpeller) up to 8 stages

PM 1-2-1 1.5 HP Each 22155 2710 24865

PM 1-2-2 2.0 HP Each 23320 2710 26030

PM 1-2-3 3.0 HP Each 25613 2710 28323

PM 1-2-4 4.0 HP Each 27105 2710 29815

PM 1-2-5 5.0 HP Each 28343 2710 31053

Page 6: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PM 1-2-6 6.0 HP Each 30039 3529 33568

PM 1-2-7 7.5 HP Each 35404 3529 38933

Note 2 Supply rate should be increased by Rs. 600/- per stagefor pump with more than 8 stages

PM 1-2 Submersible Pump 150 mm dia (with BronzeImpeller) up to 12 stages

PM 1-2-8 8.0 HP Each 37683 3925 41608

PM 1-2-9 9.0 HP Each 38021 3925 41946

PM 1-2-10 10.0 HP Each 40426 3925 44351

PM 1-2-11 11.0 HP Each 44006 3925 47931

PM 1-2-12 12.5 HP Each 47233 4540 51773

PM 1-2-13 15.0 HP Each 51056 4540 55596

Note 3 Supply rate should be increased by Rs. 600/- per stagefor pump with more than 12 stages

PM 1-2 Submersible Pump 150 mm dia (with BronzeImpeller) up to 15 stages

PM 1-2-14 17.5 HP Each 54973 5154 60127

PM 1-2-15 20.0 HP Each 61419 5154 66573

PM 1-2-16 22.5 HP Each 69704 5154 74858

Note 4 Supply rate should be increased by Rs. 600/- per stagefor pump with more than 15 stages for Borewell only.

For other use 200 mm dia pump shall be preferred over150 mm dia with more than 15 stage pump.

2) For 150 mm dia energy efficient pumps add as below

a. upto 8 stages 3% of supply rates

a. upto 12 stages 4% of supply rates

a. upto 15 stages 5% of supply rates

PM 1-3 Submersible Pump 200 mm dia (with BronzeImpeller) up to 5 stages of category A & B

Page 7: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PM 1-3-1 7.5 HP Each 41740 3529 45269

PM 1-3-2 10.0 HP Each 45701 3925 49626

PM 1-3-3 12.5 HP Each 48078 4540 52618

Note 5 Supply rate should be increased by Rs. 1900/- perstage for pump with more than 5 stages

PM 1-3 Submersible Pump 200 mm dia (with BronzeImpeller) up to 8 stages of category A & B

PM 1-3-4 15.0 HP Each 58663 5154 63817

PM 1-3-5 17.5 HP Each 63415 5154 68569

PM 1-3-6 20.0 HP Each 68331 5154 73485

PM 1-3-7 22.5 HP Each 72064 5154 77218

PM 1-3-8 25.0 HP Each 75794 5154 80948

PM 1-3-9 27.5 HP Each 79202 5154 84356

Note 6 Supply rate should be increased by Rs. 1900/- perstage for pump with more than 8 stages

PM 1-4 Submersible Pump 250 mm dia (with BronzeImpeller) up to 8 stages of category A & B

PM 1-4-1 15.0 HP Each 58663 5154 63817

PM 1-4-2 20.0 HP Each 68331 5154 73485

PM 1-4-3 22.5 HP Each 76584 5154 81738

PM 1-4-4 25.0 HP Each 78724 5154 83878

PM 1-4-5 30.0 HP Each 80159 5154 85313

PM 1-5 Submersible monoblock Pump set (with BronzeImpeller) Horizontal / Vertical - up to 3 stages

(Motor with water lubricated bearing to accept entirehydraulic thrust)

Page 8: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PM 1-5-1 3.0 HP Each 20271 2710 22981

PM 1-5-2 5.0 HP Each 24118 3119 27237

PM 1-5-3 7.5 HP Each 29107 3529 32636

PM 1-5-4 10.0 HP Each 35278 3529 38807

Note 7 Erection rates for submersible pump set areconsidering drop pipe length up to 15 m. The erectionrates shall be increased for additional length of droppipe by 50% of the rate of erection of respective dia ofGI pipe for more than 15 m drop pipe. Refer Civil CSRfor the rates of erection of GI pipes.

Note 8 For turbid water use of submersible pump shall beavoided, however for emergency situation mechanicalseal of TCTC construction shall be provided with themotor and adequate screen to prevent floating materialshall also be provided for which Rs. 7500/- shall beadded in additional to supply rate.

PM 2 Centrifugal Monoblock Pump set

Providing, erecting and giving test of CentrifugalMonoblock pump set conforming to IS 9079 operatingat 2900 RPM with CI impeller, priming funnel, cock,suitable flanges at suction and delivery side. Pump shallhave common shaft for pump and motor. Motor shall besuitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C.Supply. Motor shall be TEFC type. Pump set shall besuitable for working at various discharge and headrequirements. Pump shall be erected on Provided C.C.foundation block with suitable foundation bolts groutedin C.C. foundation block.

PM 2-1 Centrifugal Monoblock Pump set (Single Stage)

PM 2-1-1 2.0 HP Each 11774 1905 13679

PM 2-1-2 3.0 HP Each 14272 1905 16177

PM 2-1-3 5.0 HP Each 17446 2504 19950

Page 9: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PM 2-1-4 7.5 HP Each 21255 2504 23759

PM 2-1-5 10.0 HP Each 28155 2504 30659

PM 2-1-6 12.5 HP Each 34315 3119 37434

PM 2-1-7 15.0 HP Each 37450 3119 40569

PM 2-1-8 20.0 HP Each 53994 3119 57113

PM 2-1-9 25.0 HP Each 71022 3119 74141

PM 2-1-10 30.0 HP Each 87935 3119 91054

PM 2 -2 Centrifugal Monoblock Pump set ( Two Stage )

PM 2-2-1 5.0 HP Each 19770 2504 22274

PM 2-2-2 7.5 HP Each 24017 2504 26521

PM 2-2-3 10.0 HP Each 31840 2504 34344

PM 2-2-4 12.5 HP Each 39305 3119 42424

PM 2-2-5 15.0 HP Each 46754 3119 49873

PM 2-2-6 20.0 HP Each 62127 3119 65246

PM 3 Centrifugal Coupled Pump set

C.S.R. for centrifugal coupled set is not prepared due towide variation in rates per horse power as per dutyconditions and type of material. The rates required shallbe worked out on basis of quotations, offers frommanufacturer, distributors, dealers in individual case.

PM 4 Centrifugal Coupled Pump set -- Erection charges

Erecting and giving test of centrifugal coupled pump setwith foot mounted motor excluding base plate couplingand foundation bolts, etc. on provided concretefoundation / RSJ with accurate levelling with shims andproper alignment.

Page 10: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PM 4-1 15 TO 30 HP Each 0 3573 3573

PM 4-2 31 TO 50 HP Each 0 4276 4276

PM 4-3 51 TO 100 HP Each 0 5097 5097

PM 4-4 101 TO 150 HP Each 0 6107 6107

PM 4-5 151 TO 200 HP Each 0 7117 7117

PM 4-6 201 TO 250 HP Each 0 8142 8142

PM 4-7 251 TO 300 HP Each 0 9767 9767

PM 4-8 More than 300 HP HP 0 44 44

PM 5 Vacuum Pump set (Monoblock)

Providing, erecting Kirloskar make or other approvedmake Mono block Vacuum pump set with base plateexcluding C.C. foundation / cross channels / RSJ frameand foundation bolts etc complete.

PM 5-1 1 HP, single Ph (Type kV 20) Each 21633 1905 23538

PM 5-2 3 HP, three Ph (Type kV 30) Each 40563 1905 42468

PM 6 Vacuum Pump set (Coupled)

Providing, erecting Coupled Vacuum pump set withhorizontal foot mounted TEFC squirrel cage motorworking on three phase 50 Hz, 415 Volts +/- 10% withbase plate including cost of flexible couplings, couplingguard etc complete.

PM 6-1 5 HP (Type DV 40) Each 75541 2754 78295

PM 6-2 10 HP (Type DV 50) Each 93671 2754 96425

Note 10 Cost of starters, cable, switches, suitable GI Pipe withcoupling and specials, valves etc shall be added as perCSR.

PM 7 V.T. Pumps, Water / Oil lubricated

Page 11: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

C.S.R. for Vertical Turbine Pump set is not prepareddue to wide variation in rates per horse power as perduty conditions, number of stages, column pipe sizeand length required and type of material. The ratesrequired shall be worked out on basis of quotations,offers from manufacturer, distributors, dealers inindividual case.

PM 8 V.T. Pump erection charges (For column length upto 6 m)

Erecting, commissioning and giving test of VerticalTurbine Pump (Water Lubricated) including bowlassembly and discharge head etc on provided channel /RSJ / RCC beam including erecting on provided soleplate with blue matching.

PM 8-1 Up to 30 HP Each 0 4437 4437

PM 8-2 31 HP to 100 HP Each 0 6618 6618

PM 8-3 101 HP to 200 HP Each 0 9152 9152

PM 8-4 201 HP to 300 HP Each 0 12212 12212

PM 8-5 above 300 HP HP 0 44 44

Note 11 For column length more than 6m additional rate percolumn joint

100 mm dia column pipe Joint 0 132 132

150 mm dia column pipe Joint 0 250 250

200 mm dia column pipe Joint 0 279 279

300 mm dia column pipe Joint 0 382 382

350 mm dia column pipe Joint 0 499 499

400 mm dia column pipe Joint 0 615 615

450 mm dia column pipe Joint 0 762 762

500 mm dia column pipe Joint 0 821 821

600 mm dia column pipe and above Joint 0 983 983

Note 12 Add 5 % for erection of oil lubricated pumps

Page 12: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Note 13 Generally self water lubricated VT pumps shall bepreferred. In exceptional cases, oil lubricated VT pumpsshall be selected with prior approval fromSuperintending Engineer (Mech).

Note 14 Above rates shall not be applicable where supply part isover and erection part is left. In such cases erectionand testing charges shall be worked out separately.

PM 9 Sewage Pump

C.S.R. for Sewage pump set is not prepared due towide variation in rates per H.P. as per duty conditions,speed, length of transmission shaft, type etc. The ratesrequired shall be worked out on the basis on quotations/ offers from manufacturers / authorised distributors ineach individual case.

PM 10 Sewage Pump, Erection charges

Erection and giving test and trial for directly coupledsewage pump set on provided foundation.

PM 10-1 Up to 30 HP Each 0 3573 3573

PM 10-2 31 HP to 100 HP Each 0 4686 4686

PM 10-3 101 HP to 200 HP Each 0 6618 6618

PM 10-4 201 HP to 300 HP Each 0 8947 8947

PM 10-5 Above 300 HP HP 0 44 44

Note 15 Add 25 % to above rates in case of submersiblesewage pump set including guide rail etc or extendedshaft of sewage pump.

PM 11 Pressure gauges

Providing, erecting Pressure gauge of required rangecomplete with syphon tube, isolating cock suitable for12 mm dia G.I. Pipe. Pressure gauge shall be installedas directed, with tapping on rising main.

PM 11-1 Pressure gauge (100 mm dia) Each 737 51 788

PM 11-2 Pressure gauge (150 mm dia) Each 848 51 899

Page 13: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Glyscerine Filled Pressure gauge Bourdon's type as IS3624:1987 Mounting - direct bottom, stainless steel body,toughened glass window

PM 11-3 Pressure gauge 100 mm dia (black & red marking) Each 1175 51 1226PM 11-4 Pressure gauge 150 mm dia Each 1737 51 1788

PM 12 Vacuum / Combination gauge

Providing, erecting Vacuum Gauge / Combinationgauge of required range complete with syphon tube,isolating cock suitable for 12 mm dia G.I. Pipe. Vacuum/ Combination gauge shall be installed as directed, withtapping on main lines.

PM 12-1 Vacuum / Combination gauge - 100 mm dia Each 816 51 867

PM 12-2 Vacuum / Combination gauge - 150 mm dia Each 927 51 978

PM 13 Foot Valve

Providing, erecting C.I. foot valve having single leatherflap and gunmetal seating. Valve shall be fixed onsuction side of pump as per requirement includingjointing material and hardware.

Screwed Type

PM 13-1 50 mm Each 404 97 501

PM 13-2 65 mm Each 538 97 635

PM 13-3 80 mm Each 689 97 786

PM 13-4 100 mm Each 1060 186 1246

PM 13-5 125 mm Each 1632 186 1818

PM 13-6 150 mm Each 2373 186 2559

Flanged Type

PM 13-7 50 mm Each 1143 351 1494

PM 13-8 65 mm Each 1346 351 1697

PM 13-9 80 mm Each 1531 351 1882

PM 13-10 100 mm Each 2103 457 2560

PM 13-11 125 mm Each 3515 457 3972

PM 13-12 150 mm Each 5129 457 5586

Page 14: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 2 - VA [ VALVE ACTUATORS ]

VA Valve Actuator

Page 15: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing, erecting electric Valve actuators totallyenclosed, weather-proof and dust proof constructionwith IP-67, protection class suitable for installation inany position without lubrication, leakage or otheroperational difficulty with special grease filled gear boxand hand wheel for emergency manual operation whichwill automatically dis-engage on restoration of power tomotor and with 10 watt single phase space heater andcontinuous local mechanical position indicator andindividually replaceable counter gear assembly and withtwo torque and four limit switches with S.S. flap andoperated with gear driven cams and of rating 250 Volt,5 Amp, AC/DC, torque switch dial and with TEFCsquirrel cage induction motor working on 440 Volts +/-10%, 3 phase, 50 Hz AC of intermittent duty rating S-2,insulation class "F" and temp rise restricted to class "B"with IP - 67 protection class suitable for DOL startingand with three thermostat and 30% over load margin.The torque rating of reduction gear box shall be atleast1.5 times max. torque required for opening and closing o

VA -1 Electric Valve Actuator for non rising spindle typesluice valve, PN 1 & PN 1.6 ratingFor Valve Size (Without integral starter)

VA 1-1 50 mm dia Each 71000 2423 73423

VA 1-2 65 mm dia Each 71000 2423 73423

VA 1-3 80 mm dia Each 72000 2423 74423

VA 1-4 100 mm dia Each 75500 2423 77923

VA 1-5 125 mm dia Each 78500 2423 80923

VA 1-6 150 mm dia Each 80500 2423 82923

VA 1-7 200 mm dia Each 83800 2423 86223

VA 1-8 250 mm dia Each 89300 2423 91723

VA 1-9 300 mm dia Each 97500 2423 99923

VA 1-10 350 mm dia Each 105019 2423 107442

VA 1-11 400 mm dia Each 105019 2423 107442

VA 1-12 450 mm dia Each 105019 2423 107442

VA 1-13 500 mm dia Each 114566 2423 116989

VA 1-14 600 mm dia Each 128887 2423 131310

VA 1-15 700 mm dia Each 167076 2423 169499

Page 16: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

VA 1-16 750 mm dia Each 167076 2423 169499

VA 1-17 800 mm dia Each 167076 2423 169499

VA 1-18 900 mm dia Each 167076 2423 169499

VA 1-19 1000 mm dia Each 167076 2423 169499

SECTION 3 - PW [ PIPE WORK AND VESSELS ]

PW 1 G.I. Bend "B" Class

Supplying and erecting "B" class G.I. Bend in positionwith necessary material

PW 1-1 15 mm dia Each 51 16 67

PW 1-2 25 mm dia Each 75 16 91

Page 17: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PW 1-3 40 mm dia Each 98 16 114

PW 1-4 50 mm dia Each 149 25 174

PW 1-5 65 mm dia Each 218 25 243

PW 1-6 75 mm dia Each 351 25 376

PW 1-7 100 mm dia Each 703 39 742

PW 2 G.I. Tee "B" Class

Supplying and erecting "B" class G.I. Tee in positionwith necessary material

PW 2-1 15 mm dia Each 31 16 47

PW 2-2 25 mm dia Each 67 16 83

PW 2-3 40 mm dia Each 133 16 149

PW 2-4 50 mm dia Each 212 25 237

PW 2-5 65 mm dia Each 393 25 418

PW 2-6 75 mm dia Each 562 25 587

PW 2-7 100 mm dia Each 921 39 960

PW 2-8 150 mm dia Each 1001 39 1040

PW 3 G.I. Coupling / Nipple "B" Class

Supplying and erecting "B" class G.I. Coupling / Nipplein position with necessary material

PW 3-1 15 mm dia Each 18 5 23

PW 3-2 25 mm dia Each 35 5 40

PW 3-3 40 mm dia Each 67 13 80

PW 3-4 50 mm dia Each 113 13 126

PW 3-5 65 mm dia Each 185 13 198

Page 18: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PW 3-6 75 mm dia Each 279 13 292

PW 3-7 100 mm dia Each 451 16 467

PW 3-8 150 mm dia Each 552 16 568

PW 4 G.I. Union (Heavy Duty)

Supplying and erecting Heavy Duty G.I. Union inposition with necessary material

PW4-1 15 mm dia Each 54 5 59

PW 4-2 25 mm dia Each 98 5 103

PW 4-3 40 mm dia Each 189 13 202

PW 4-4 50 mm dia Each 290 13 303

PW 5 G.I. Elbow (Heavy Duty)

Supplying and erecting Heavy Duty G.I. Elbow inposition with necessary material

PW 5-1 15 mm dia Each 18 9 27

PW 5-2 25 mm dia Each 54 13 67

PW 5-3 40 mm dia Each 113 13 126

PW 5-4 50 mm dia Each 175 13 188

PW 6 Dismantling Joints

Providing, erecting and commissioning M.S.Dismantling joint as per requirement and Department'sapproved drawing and specifications, includingmachining and rubber rings and suitable for 16 kg/cm2working pressure with required flanges of suitable sizewith nut bolts etc complete. The joint should havethrough long bolts so that during normal workingpressure there should be no sliding movement ofsliding flanges. L.O.F. ( length over flange ) should notbe less than 75% of dia.

PW 6-1 200 mm dia Joint Joint 13258 583 13841

Page 19: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PW 6-2 250 mm dia Joint Joint 15695 746 16441

PW 6-3 300 mm dia Joint Joint 17093 785 17878

PW 6-4 350 mm dia Joint Joint 20227 1027 21254

PW 6-5 400 mm dia Joint Joint 24067 1278 25345

PW 6-6 450 mm dia Joint Joint 27207 1580 28787

PW 6-7 500 mm dia Joint Joint 33134 1725 34859

PW 6-8 600 mm dia Joint Joint 44501 2053 46554

PW 6-9 700 mm dia Joint Joint 64174 2226 66400

PW 6-10 750 mm dia Joint Joint 76725 2441 79166

PW 7 Surge/ Air Vessels

Providing, fabricating, erecting, testing andcommissioning as per IS 2825 (code for unfiredpressure vessels) Surge vessel / Air Vessel fabricatedin boiler quality plate conforming to grade I of IS 2002with radiography testing on provided foundationincluding epoxy painting.

PW 7-1 Boiler quality Plate kg 259 0 259

PW 8 Pressure Vessels

Providing, fabricating, erecting, testing andcommissioning pressure vessel fabricated in M.S. plateon provided foundation including epoxy paint.

PW 8-1 M.S. Plate kg 187 0 187

PW 9 Sole Plate

Providing, fabricating, erecting, Sole Plate of requiredsize and thickness with both side machined to matchthe surface area not less than 60%.

PW 9-1 Sole Plate kg 127 0 127

Page 20: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

PW 10 M.S. Flanges

Providing, fabricating, erecting, M.S. Flanges sleep ontype (all tables) of required size and thickness with bothside machined.

PW 10-1 Up to 300 NB kg 141 0 141

PW 10-2 Above 300 NB kg 132 0 132

SECTION 4 - LF [ LIFTING EQUIPMENT ]

LF 1 Chain Pulley Block

Providing, erecting triple spur gear type Chain PulleyBlock suitable for capacity as below with 6 m liftcomplete with load chain and hand chain suitable forabove lift, tested to 50% over load as per IS 3832carrying ISI mark.

LF 1-1 1 Tonne Capacity Each 12809 157 12966

LF 1-2 2 Tonne Capacity Each 17609 194 17803

LF 1-3 3 Tonne Capacity Each 21841 291 22132

LF 2 Travelling Trolley

Providing, erecting Travelling Trolley of capacity asbelow with 6 m lift, tested to 50% over load

Page 21: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LF 2 -1 1 Tonne Capacity Each 8316 117 8433

LF 2 -2 2 Tonne Capacity Each 11806 157 11963

LF 2 -3 3 Tonne Capacity Each 16669 194 16863

Note 1 Add Rs. 356/- per m for extra handling chain for allcapacity geared trolley

Note 2 Add for Additional 1 m load chain for all capacity chainpulley block

For 1 Tonne -- Rs. 586/- per m

For 2 Tonne -- Rs. 1190/- per m

For 3 Tonne -- Rs. 1540/- per m

LF 3 Hand Operated Circular or Rectangular TravellingCrane ( Single Girder)

Providing , erecting and commissioning Single GirderHand Operated Circular / Rectangular Travelling Cranewith 6 m lift complete with chain pulley block ISI markedand travelling trolley both tested for 50 % overloadincluding arrangement for longitudinal travel / circulartravel and cross travel with wheel, hand chain, etccomplete.

LF 3-1 3 Tonne Capacity

LF 3 -1-1 Up to 5 m span Each 147600 12856 160456

LF 3 -1-2 Above 5 m upto 6 m span Each 159640 13380 173020

LF 3 -1-3 Above 6 m upto 8 m span Each 186700 14600 201300

LF 3-2 5 Tonne Capacity

LF 3 -2-1 Up to 5 m span Each 189330 12856 202186

Page 22: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LF 3 -2-2 Above 5 m upto 6 m span Each 203170 13380 216550

LF 3 -2-3 Above 6 m upto 8 m span Each 234580 14600 249180

LF 3 -2-4 Above 8 m upto 10 m span Each 284060 15975 300035

Note 3 The rates are exclusive of corbel / rail / square bar andtrack girders for supporting rails.

LF 4 Electric Operated Circular or Rectangular TravellingCrane ( Single Girder)

Providing, erecting and commissioning single girderElectrically Operated Rectangular Over head TravellingCrane with 6 m lift complete with wire rope hoist, classII duty, all three motions electrically operated by suitablerating motor IP 54, control panel and down pendantcontrol block.

LF 4-1 5 Tonne Capacity

LF 4-1-1 Above 6 m upto 8 m span Each 739746 16456 756202

LF 4-1-2 Above 8 m upto 10 m span Each 786960 18395 805355

LF 4-2 7.5 Tonne Capacity

LF 4-2-1 Above 6 m upto 8 m span Each 894906 18395 913301

LF 4-2-2 Above 8 m upto 10 m span Each 952641 20331 972972

LF 4-3 10 Tonne Capacity

LF 4-3-1 Above 6 m upto 8 m span Each 985032 20331 1005363

LF 4-3-2 Above 8m upto 10 m span Each 1047906 22268 1070174

Note 4 The rates are exclusive of corbel / rail / square bar andtrack girders for supporting rails.

Note 5 For D.S.L. (Down Shop Lead) system for above craneAdd Rs. 2500/- per m length of longitudinal travel.

Note 6 Rate for Additional Load Chain /Handling Chain.

Load Chain

For 1 Tonne m 770 0 770

For 2 Tonne m 1540 0 1540

Page 23: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

For 3 Tonne m 2714 0 2714

Handling Chain m 357 0 357

LF 5 Square Bar / Rail

Providing, erecting and fixing square bar of EN 8 as railfor over head crane on provided track, girder /continuous corbel beam, including supporting plate and"J" bolts.

LF 5 -1 50 X 50 mm ( EN 8) m 1544 19 1563

LF 5 -2 40 X 40 mm ( EN 8 ) m 984 19 1003

SECTION 5 - SS [ H.T. SUB STATION EQUIPMENTS ]

SS1 RSJ pole

Supplying, erecting Rolled Steel Joist (Girder) polecomplete erected duly painted with two coats of redoxide paint and one coat of bituminous paint for thelength to be embedded in ground and plinth and twocoats of aluminium paint for the remaining portioncomplete with base plate of size 30 X 30 X 0.6 cmswelded at the bottom complete erected in provided C.C.foundation and plinth.

SS 1-1 ISMB 175 - 8.5 mtr Long As Per PWD CSR

Note 1 Add / subtract Rs. 1170/- per meter for addition orreduction in length

SS 1-2 ISHB I50 -11 mtr long As Per PWD CSR

Note 2 Add / subtract Rs. 1660/- per meter for addition orreduction in length

SS 2 Pole Foundation

Page 24: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing C.C. foundation including excavation for thepoles with 60 X 60 cm and 180 cm deep in 1:3:6cement concrete (20 to 25 mm stone metal) and 45 X45 X 45 cm plinth duly plastered and with necessarycuring and finishing in an approved manner

As Per PWD CSR

SS 3 GI Stay

Supplying, erecting G.I. Stay set for poles, includingloop insulators at in accessible height complete withanchor plate 300 X 300 X 6 mm, straining screws, G.I.Stay rod 20 mm X 1.8m length and pole clamps erectedin provided C.C. foundation.

SS 3-1 Size 7/10 SWG/ Size7/8 SWG As Per PWD CSR

SS 3-2 GI Stay Foundation

Providing CC foundation Each including excavation forstay 60 cms x 60 cms x 1.5 mtr. Deep in 1:3:6 cementconcrete (20 to 25 mm stone metal) with necessarycuring and finishing in an approved manner.

As Per PWD CSR

SS 4 Cross Arm, ISMC 100 ( 2.4 m long )

Supplying erecting 100 X 50 mm with 4.7 mm thick weband 7.5 mm flange channel iron cross arm of suitablelength fabricated for H.T. insulator mounting anderected on two pole structure, 2.4m apart provided withtwo clamps of 50 X 6 mm M.S. flat and 15 mm nuts andbolts for each cross arm, duly painted with one coat ofred lead and two coats of silver paint.

As Per PWD CSR

Note 3 Add / subtract Rs. 490/- per m for addition or reductionin length.

SS 5 Lightening Arrestor

Supplying, erecting approved make thyrite typeLightening Arrestor suitable for H.T. supply withnecessary ancillary material complete on providedcross arm and connected to overhead line.

Page 25: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SS 5-1 Suitable for 11 kV Supply, Distribution class Set 2889 421 3310

SS 5-2 Suitable for 22 kV Supply, Distribution class Set 5261 421 5682

SS 5-3 Suitable for 33 kV Supply, Station class Set 30897 583 31480

SS 6 Disc Insulator

Supplying, erecting porcelain Disc Type Insulators withhardware fittings suitable for H.T. overhead linecomplete erected with nuts and bolts on provided crossarm.

SS 6-1 Suitable for 11 kV line Each 851 141 992

SS 6-2 Suitable for 22 kV line Each 1738 164 1902

SS 6-3 Suitable for 33 kV line Each 2448 194 2642

SS 7 Pin Insulator

Supplying, erecting porcelain Pin Type Insulators withhard ware fittings suitable for H.T. overhead linecomplete erected with nuts and bolts on provided crossarm.

SS 7-1 Suitable for 11 kV line Each 308 55 363

SS 7-2 Suitable for 22 kV line Each 777 71 848

SS 7-3 Suitable for 33 kV line Each 1074 79 1153

SS 8 Air Break Switch Without Earth Switch

Supplying, erecting approved make H.T. out door typegang operated air break, triple pole switch of requiredcapacity with 3 post / pin type insulator per phase,mounted in horizontal or vertical position on providedcross arm with adequate length of G.I. pipe foroperating handle erected on extended square shaft.The operating handle provided with lock and key atsuitable height from ground with necessary clamps.

SS 8-1 Suitable for 11 kV line

SS 8-1-1 Rocking / Tilting Type Set 19598 466 20064

SS 8-1-2 Rotating Type Set 26255 466 26721

SS 8-2 Suitable for 22 kV line

SS 8-2-1 Rocking / Tilting Type Set 29465 484 29949

Page 26: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SS 8-2-2 Rotating Type Set 34939 484 35423

SS 8-3 Suitable for 33 kV line

SS 8-3-1 Rocking / Tilting Type Set 40379 504 40883

SS 8-3-2 Rotating Type Set 47576 504 48080

SS 9 Air Break Switch with Earth Switch

Supplying, erecting approved make H.T. out door typegang operated air break, triple pole switch with earthswitch of required capacity with 3 post / pin typeinsulator per phase, mounted in horizontal or verticalposition on provided cross arm with adequate length ofG.I. pipe for operating handle erected on extendedsquare shaft. The operating handle provided with lockand key at suitable height from ground with necessaryclamps.

SS 9-1 Suitable for 11 kV lineRotating Type Set 36425 504 36929

SS 9-2 Suitable for 22 kV line Rotating Type Set 44602 504 45106

SS 9-3 Suitable for 33 kV line Rotating Type Set 53286 504 53790

SS 10 Drop Out Fuse ( Channel mounted )

Supplying, erecting approved make outdoor type DropOut Fuse Channel type with insulator complete withfuse holders fuse barrel with metal fittings, fuseelement, with working current up to 50 Amp, capacitycomplete erected on provided cross arm, each setcomprising 3 units.

SS 10-1 Suitable for 11 kV line Set 10144 723 10867

SS 10-2 Suitable for 22 kV line Set 14445 723 15168

SS 10-3 Suitable for 33 kV line Set 21892 723 22615

SS 11 Horn Gap Fuse ( Channel mounted )

Page 27: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Supplying, erecting approved make outdoor type HornGap Type fuse with insulator, fuse element, withworking current up to 50 Amp, capacity completeerected on provided cross arm, each set comprising 3units.

SS 11-1 Suitable for 11 kV line Set 5240 504 5744

SS 11-2 Suitable for 22 kV line Set 8510 504 9014

SS 11-3 Suitable for 33 kV line Set 13045 504 13549

SS 12 Fuse Barrel

Supplying and erecting fuse barrel with metal fittings.

SS 12-1 Suitable for 11 kV line with metal fitting

SS 12-1-1 With fiber fittingAs Per PWD CSR

SS 12-2 Suitable for 22 kV line with metal fitting

SS 12-2-1 With fiber fitting As Per PWD CSR

SS 13 D.O. Operating Rod

Supplying D.O. Operating rod 20 feet long in threesections made from best quality fine wood with SRBPtube and aluminium head PVC coated suitable for 11 /22 / 33 kV supply with clamps for removing drop outfuses at 6 m height with rain shed porcelain insulatorwith hand grip including earthing chain 1.5m

As Per PWD CSR

SS 14 Hard Drawn Copper solid wire

Supplying and erecting hard drawn copper solid wirecomplete erected for connections on H.T. side.0 to 6 SWG As Per PWD CSR

SS 15 Alkathen Pipe 10 mm dia

Supplying and erecting extra thick alkathene pipe10mm dia erected to enclose bare conductor wires.

As Per PWD CSR

SS 16 Out Door CT

Page 28: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing, erecting and commissioning out door typesingle phase oil filled current transformer for meteringand protection purpose of suitable C.T. ratio and V.A.burden duly erected on provided cross channel.

SS 16-1 Single Core

SS 16-1-1 Suitable for 11 kV system Each 17486 426 17912

SS 16-1-2 Suitable for 22 kV system Each 24362 426 24788

SS 16-1-3 Suitable for 33 kV system Each 25754 426 26180

SS 16-2 Double Core

SS 16-2-1 Suitable for 11 kV system Each 26170 426 26596

SS 16-2-2 Suitable for 22 kV system Each 34060 426 34486

SS 16-2-3 Suitable for 33 kV system Each 34060 426 34486

SS 17 Out Door PT

Providing, erecting and commissioning out door typesingle phase oil filled Potential transformer for meteringpurpose of suitable V.A. burden duly erected onprovided cross channel.

SS 17-1 Single Core

SS 17-1-1 Suitable for 11 kV system Each 15424 426 15850

SS 17-1-2 Suitable for 22 kV system Each 21300 426 21726

SS 17-1-3 Suitable for 33 kV system Each 22553 426 22979

SS 17-2 Double Core

SS 17-2-1 Suitable for 11 kV system Each 15630 426 16056

SS 17-2-2 Suitable for 22 kV system Each 23769 426 24195

SS 17-2-3 Suitable for 33 kV system Each 32168 426 32594

SS 18 Miscellaneous items

Page 29: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SS 18-1 Anticlimbing devices

Supplying and erecting anticlimbing devices fabricatedfrom pole clamps with drooping spikes welded to it anderected on pole.

As Per PWD CSR

SS 18-2 Fencing sections

Supplying and erecting fencing section having size 2.45m height from ground level and 1.2 m width by usingangle iron size 50 X 50 X 6 mm erected in C.C.foundation 15 X 15 X 40 cm deep. The section of theframe shall be fitted with flat iron support of size 25 X 6mm on top, bottom and mid way and chain link jali of3.26 mm dia / 10 SWG G.I. hard wire mesh of 50 X 50mm to the angle iron at every distance of 30 cms, byangle iron at every distance of 30 cms, by iron studscomplete duly painted with one coats of red oxide andtwo coats of aluminium paint.

As Per PWD CSR

Note 4 For sections less than 1200 mm width reduce rate byRs. 120 /- per 100 mm or part there of reduction inwidth of 1200 mm.

SS 18-3 Fencing gate

Supplying and erecting double leaf hinged door each150 cm in width and 185 cm in height using 40 mm dia"B" grade ISI mark G.I. Pipe from all four sides withnecessary bends and cross supports of angle iron 45 X45 X 5 mm with the door leaf covered with chain link jali50 X 50 mm made from 3.26 mm dia / 10 SWG G.I.wire with necessary flat iron covering all around withnecessary number of spikes of size 10 mm dia at topand bottom at 150 mm apart to match the height offencing. The door shall have latches and side channelof 100 X 50 X 5mm rigidly welded for providing lockingarrangement, Godrej/Navtal make medium size lockwith duplicate keys, The fencing complete erected andpainted with anticorrosive red oxide paint and two coatsof prescribed enamel paint / silver paint. The channeliron of size 150 X 75 mm by 2.5 m long shall beprovided and erected at both sides of gate.

As Per PWD CSR

SS 18-4 Angle iron corner support

Page 30: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Supplying and erecting 50 X 50 X6 mm angle ironcorner support 0.5 m way from the fence supports fixedat the middle fencing frame and other side in C.C.foundation 15 X 15 X 40 cm complete duly painted withone coat of red oxide and two coats of aluminium paint.

As Per PWD CSR

SS 18-5 Stone Metal Spreading

Providing and spreading stone metal 25 mm size for100 mm depth above the ground level.

As Per PWD CSR

SS 18-6 M.S. Stand for Fire bucket.

Providing floor mounted stand for keeping 4 nos. of firebucket,1500 mm in length and 900 mm in height madeout of 30 X 30 X 4 mm angle iron welded with 4 hooksand duly painted with one coat of red lead and twocoats of silver paint.

As Per PWD CSR

SS 18-7 Wall Hook for Fire bucket.

Supplying and erecting wall hook 225 mm projection forkeeping fire buckets made out of 15 mm dia MS roundbar grouted in wall to a depth of minimum 15 cm.

As Per PWD CSR

SS 18-8 G.I. Fire bucket 9 lit

Supplying G.I. Fire buckets with round bottom dulypainted having at least 9 lit. capacity and filled with drysand and kept on provided wall hook or stand.

As Per PWD CSR

SS 18-9 First Aid Box

Supplying standard first aid box with all standardcontents.

As Per PWD CSR

SS 18-10 Pair of Rubber hand Glove 11/22/33 kV

Supplying pair of rubber hand gloves suitable forworking on 11 / 22 /33 kV system

As Per PWD CSR

SS 18-11 Instruction Chart

Providing printed instruction chart for treating personssuffering from electric shocks, printed in English andMarathi and duly framed with front glass.

As Per PWD CSR

Page 31: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SS 18-12 Fire Extinguisher

Supplying, erecting D.C.P. type fire extinguishercartridge type, with G.M. cap 150 gram CO2 gascartridge powder brackets conforming to IS 2171 - 1985and having complete erected with necessary clampsmade from 50 X 6 mm MS flat with nuts and boltsgrouted in wall complete.

SS 18-12-1 Fire extinguisher with 5 kg cartridge capacity As Per PWD CSR

SS 18-12-2 Fire extinguisher with 10 kg cartridge capacity As Per PWD CSR

Page 32: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 6 - TR [ TRANSFORMER AND VOLTAGE STABILIZER ]

TR-1 Power Transformer (With Off Load Tap Changer)

Providing, erecting and commissioning out door typecopper wound transformer continuously rated for 3 Ph,50 Hz, at full load and temp. rise not exceeding 45º Cby thermometer in oil and 50ºC by the resistance inwinding after continuous run at full load rating, thetransformer should have oil immersed winding havingvector group DY 11, HT side connected in Delta and LTside connected in Star with neutral brought outconnected to provided separate earthing. Thetransformer shall have power terminal arrangement,bushings / cable end box on HT side and cable end boxon LT side. 2 Nos. channels with stoppers shall beprovided and fixed on the provided plinth for mountingthe transformer. The transformer should have followingstandard fittings. Transformer shall be of latestmanufacturing standards as per amended ISspecifications and the Load & No Load losses shall belimited to the values given below or as per IS or Normsissued by MSEDC Ltd whichever are lower.

1) Oil conservator with filling hole with cap and plainoil level gauge.2) Silica gel dehydrating breather charged with SilicaGel.3) Oil drain valve.4) Oil filter valve.5) Lifting eyes / hooks.6) Two earthing terminals.7) Diagram and rating plate.8) Air Vent.9) Explosion Vent.10) 100 mm dia thermometer with thermometer pocket11) Four bi directional plain roller.

Power Transformer 11000 / 433 Volt

Page 33: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

With off load Tap Changer -12.5% to +2.5% in steps of2.5%

TR 1-1 63 kVA (no load loss 180 w and load loss 1235 w) Each 167899 8715 176614

TR 1-2 100 kVA (no load loss 260 w and load loss 1760 w) Each 215181 8715 223896

TR 1-3 160 kVA (no load loss 400 w and load loss 2600 w) Each 257993 8715 266708

TR 1-4 200 kVA (no load loss 500 w and load loss 3000 w) Each 311629 8715 320344

TR 1-5 250 kVA (no load loss 550 w and load loss 3600 w) Each 362353 8715 371068

TR 1-6 315 kVA (no load loss 580 w and load loss 4200 w) Each 418901 8715 427616

TR 1-7 400 kVA (no load loss 715 w and load loss 5000 w) Each 500356 8715 509071

TR 1-8 500 kVA (no load loss 850 w and load loss 5800 w) Each 589353 14523 603876

TR 1-9 630 kVA (no load loss 1000 w and load loss 7000 w) Each 679877 14523 694400

TR 1-10 750 kVA (no load loss 1500 w and load loss 8000 w) Each 813371 14523 827894

TR 2 Power Transformer 22000 / 433 Volt and otherspecification as per TR-1

With off load Tap Changer -12.5% to +2.5% in steps of2.5%

TR 2-1 63 kVA ( no load loss 230w and load loss 1400w) Each 186899 8715 195614

TR 2-2 100 kVA ( no load loss 300w and load loss 1850w) Each 241042 8715 249757

TR 2-3 160 kVA ( no load loss 400w and load loss 2600w) Each 288126 8715 296841

TR 2-4 200 kVA ( no load loss 470w and load loss 3000w) Each 344160 8715 352875

TR 2-5 250 kVA ( no load loss 470w and load loss 3000w) Each 398419 8715 407134

TR 2-6 315 kVA (no load loss 620w and load loss 4200w) Each 424827 8715 433542

TR 2-7 400 kVA ( no load loss 750w and load loss 5000w) Each 496223 8715 504938

TR 2-8 500 kVA ( no load loss 900w and load loss 5800w) Each 685226 14523 699749

TR 2-9 630 kVA ( no load loss 1080w and load loss 7000w) Each 786608 14523 801131

TR 2-10 750 kVA ( no load loss 1600w and load loss 8000w) Each 956781 14523 971304

TR 3 Power Transformer 33000 / 433 Volt and otherSpecification as per TR-1

Page 34: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

With off load Tap Changer -12.5% to +2.5% in steps of2.5%

TR 3-1 63 kVA Each 205542 8715 214257

TR 3-2 100 kVA Each 269335 8715 278050

TR 3-3 160 kVA Each 333309 8715 342024

TR 3-4 200 kVA Each 389337 8715 398052

TR 3-5 250 kVA Each 453664 8715 462379

TR 3-6 315 kVA Each 524519 8715 533234

TR 3-7 400 kVA Each 602626 8715 611341

TR 3-8 500 kVA Each 738215 14523 752738

TR 3-9 630 kVA Each 827770 14523 842293

TR 3-10 750 kVA Each 1006841 14523 1021364

TR-4 Power Transformer (With On Load Tap Changer)

Providing, erecting and commissioning out door typecopper wound transformer continuously rated for 3 Ph,50 Hz, at full load and temp. rise not exceeding 45ºC bythermometer in oil and 50ºC by the resistance inwinding after continuous run at full load rating, thetransformer should have oil immersed winding havingvector group DY 11, HT side connected in Delta and LTside connected in Star with neutral brought outconnected to provided separate earthing. Thetransformer shall have power terminal arrangement,bushing / cable end box on HT side and cable end boxon LT side. 2 Nos. channels with stoppers shall beprovided and fixed on the provided plinth for mountingthe transformer. The transformer should have followingstandard fittings. The OLTC should be suitable forminimum 50 operations per day. Transformer shall beof latest manufacturing standards as per amended ISspecifications and the Load & No Load losses shall belimited to the values as per IS and Norms issued byMSEDC Ltd whichever are lower.

Page 35: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

1) Oil conservator with filling hole with cap and plain oil level gauge.2) Silica gel dehydrating breather charged with Silica Gel.3) Oil drain valve.4) Oil filter valve.5) Lifting eyes / hooks.6) Two earthing terminals.7) Diagram and rating plate.8) Air Vent.9) Explosion Vent.10) 100 mm dia thermometer with thermometer pocket11) Four bi directional plain roller.12) Bucholtz relay.13) Resistance Temp. detector.14) Marshalling box. 15) Automatic Voltage Regulator (AVR). 16) Remote Tap Changing Controller (RTCC).

Transformer 11000 / 433 Volt

With On Load Tap Changer -15% to +5% in steps of1.25% with RTCC, AVR and marshalling box, andother specification as per TR-1

TR 4-1 750 kVA Each 1051795 14523 1066318

TR 4-2 1000 kVA Each 1431008 14523 1445531

TR 4-3 1250 kVA Each 1552331 14523 1566854

TR 4-4 1600 kVA Each 1789612 14523 1804135

TR 4-5 2000 kVA Each 2024677 14523 2039200

TR 5 Transformer 22000 / 433 Volt

With On Load Tap Changer -15% to +5% in steps of1.25% with RTCC, AVR and marshalling box, andother specification as per TR-4

TR 5-1 750 kVA Each 1248807 14523 1263330

TR 5-2 1000 kVA Each 1623938 14523 1638461

TR 5-3 1250 kVA Each 1796322 14523 1810845

TR 5-4 1600 kVA Each 1997176 14523 2011699

TR 5-5 2000 kVA Each 2297709 14523 2312232

TR 6 Transformer 33000 / 433 Volt

Page 36: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

With On Load Tap Changer -15% to +5% in steps of1.25% with RTCC, AVR and marshalling box, andother specifications as per TR-4

TR 6-1 750 kVA Each 1320247 14523 1334770

TR 6-2 1000 kVA Each 1688346 14523 1702869

TR 6-3 1250 kVA Each 1859341 14523 1873864

TR 6-4 1600 kVA Each 2081197 14523 2095720

TR 6-5 2000 kVA Each 2389737 14523 2404260

H.T. TRANSFORMER

TR 7 Transformer 11000 / 3300 Volt

With On Load Tap Changer -15% to +5% in steps of1.25% with RTCC, AVR and marshalling box, andother specification as per TR-4

TR 7-1 1000 kVA Each 1323211 14523 1337734

TR 7-2 1250 kVA Each 1469295 14523 1483818

TR 7-3 1600 kVA Each 1689479 14523 1704002

TR 7-4 2000 kVA Each 2234866 14523 2249389

TR 7-5 2500 kVA Each 2679617 14523 2694140

TR 7-6 3000 kVA Each 2965780 14523 2980303

TR 8 Transformer 22000 / 3300 Volt

With On Load Tap Changer -15% to +5% in steps of1.25% with RTCC, AVR and marshalling box, andother specification as per TR 4

TR 8-1 1000 kVA Each 1487584 14523 1502107

TR 8-2 1250 kVA Each 1630864 14523 1645387

TR 8-3 1600 kVA Each 1868960 14523 1883483

TR 8-4 2000 kVA Each 2081771 14523 2096294

TR 8-5 2500 kVA Each 2385189 14523 2399712

TR 8-6 3000 kVA Each 2633819 14523 2648342

TR 9 Transformer 33000 / 3300 VoltWith On Load Tap Changer -15% to +5% in steps of1.25% with RTCC, AVR and marshalling box, andother specification as per TR-4

Page 37: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

TR 9-1 1000 kVA Each 1641287 14523 1655810

TR 9-2 1250 kVA Each 1809846 14523 1824369

TR 9-3 1600 kVA Each 2080440 14523 2094963

TR 9-4 2000 kVA Each 2319979 14523 2334502

TR 9-5 2500 kVA Each 2668194 14523 2682717

TR 9-6 3000 kVA Each 2941008 14523 2955531

TR 10 Servo Controlled Automatic Voltage Stabilizer

Providing, erecting Servo Controlled Automatic Voltagestabiliser suitable for out put voltage of 415 Volt +/-1%,3 Ph, 50 Hz, with copper wound transformer (air/oilcooled) as mentioned below. The stabilizer shallfunction satisfactorily even if incoming supply isunbalanced between phases within range of 10%. Thestabilizer should be constructed in cubical box, with bi-directional wheels for easy handling, necessarymonitors and user's controls on front panel such asindication, alarm, volt meter and selector switch formeasuring input and out put voltage, Auto/Manualselector switch, Raise/Low push buttons etc. Suitablecapacity termination strips and bus bars for incomingand out going cable should be provided. All threephases shall be independently monitored andcorrected. Following protections and indications shallbe incorporated

Over Voltage / Under Voltage Single Phasing Cut off contactor with electronic output sensing unit

TR 10-1 Servo Controlled Automatic Voltage Stabiliser(Out put 415 +/-1%)

Input 220 to 460 Volt

TR 10-1-1 3 kVA Air cooled Each 69243 194 69437

TR 10-1-2 5 kVA Air cooled Each 80176 253 80429

Page 38: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

TR 10-1-3 7.5 kVA Air cooled Each 90374 387 90761

TR 10-1-4 10 kVA Air cooled Each 118348 583 118931

TR 10-1-5 12.5 kVA Air cooled Each 130087 775 130862

TR 10-1-6 15 kVA Air cooled Each 141825 775 142600

TR 10-1-7 20 kVA Air cooled Each 154472 968 155440

TR 10-1-8 25 kVA Air cooled Each 170005 1161 171166

TR 10-1-9 30 kVA Air cooled Each 206726 1356 208082

TR 10-1-10 40 kVA Air cooled Each 226840 1549 228389

TR 10-1-11 50 kVA Oil cooled Each 306639 1549 308188

TR 10-1-12 60 kVA Oil cooled Each 371765 1549 373314

TR 10-1-13 75 kVA Oil cooled Each 388744 1549 390293

TR 10-1-14 100 kVA Oil cooled Each 438052 2129 440181

TR 10-1-15 125 kVA Oil cooled Each 544145 2519 546664

TR 10-2 Servo Controlled Automatic Voltage Stabiliser (Output 415 +/-1%)

Input 280 to 460 Volt

TR 10-2-1 3 kVA Air cooled Each 58931 194 59125

TR 10-2-2 5 kVA Air cooled Each 71134 387 71521

TR 10-2-3 7.5 kVA Air cooled Each 76544 387 76931

TR 10-2-4 10 kVA Air cooled Each 81683 583 82266

TR 10-2-5 12.5 kVA Air cooled Each 98561 775 99336

TR 10-2-6 15 kVA Air cooled Each 110191 775 110966

TR 10-2-7 20 kVA Air cooled Each 126070 968 127038

TR 10-2-8 25 kVA Air cooled Each 137004 1161 138165

TR 10-2-9 30 kVA Air cooled Each 154612 1232 155844

TR 10-2-10 40 kVA Air cooled Each 181908 1549 183457

TR 10-2-11 50 kVA Air cooled Each 202399 1549 203948

TR 10-2-12 60 kVA Air cooled Each 230888 1549 232437

TR 10-2-13 60 kVA Oil cooled Each 276137 1549 277686

TR 10-2-14 75 kVA Oil cooled Each 286360 1549 287909

Page 39: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

TR 10-2-15 100 kVA Oil cooled Each 343623 2129 345752

TR 10-2-16 125 kVA Oil cooled Each 395391 2519 397910

TR 10-2-17 150 kVA Oil cooled Each 407116 2713 409829

TR 10-2-18 175 kVA Oil cooled Each 467577 2713 470290

TR 10-2-19 200 kVA Oil cooled Each 510630 3487 514117

Note 1 For oil cooled stabilizer, the supply cost is excludingcost of transformer oil.

TR-11 Transformer oil

Supplying and topping fresh/ filtered Transformer Oil asper IS 335 and giving test certificate.

As Per PWD CSR

TR-12-A Filtration of Transformer oil

Filtration of transformer oil at site and giving testcertificate for other area than that mentioned at TR-12(B).

As Per PWD CSR

TR 12-B For Metro Area of Pune, Mumbai Metro Region &Nagpur, Nashik, Aurangabad, Amravati MunicipalCorporation areas.

As Per PWD CSR

TR-13 Transportation of oil filtering machine Rs. 968/- for first 10 km, & Rs.10/- per km. for remaining distance.

SECTION 7 - LT [ L.T. PANEL ]

LT 1 Panel Fabrication

M.S. sheet of thickness given below to be used forfabrication of boxes, panel boards, etc including cutting,bending, drilling, welding, cleaning, de-rusting andpainting with one coat of red lead paint and two coats ofenamel paint.

LT 1-1 M .S sheet 16 SWG As Per PWD CSR

LT 1-2 M .S sheet 14 SWG As Per PWD CSR

Page 40: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LT 2 G.I. Sheet (Ducting of ventilation)

G.I. Sheet of thickness given below to be used forfabrication, ducting of ventilation or similar work etc,including cutting, bending, drilling, welding, cleaning,derusting and retouching with cold galvanising methodwherever damaged.

LT 2-1 G.I. Sheet 18 SWG As Per PWD CSR

LT 2-2 G.I. Sheet 16 SWG As Per PWD CSR

Note 1 Increase rate by 30% if sheet work for total item in eachestimate is less than 1 sq m.

16 SWG sheet shall be specified for rear, side and top.

14 SWG sheet shall be specified for front and bottom.

Rate of G.I. Sheet fabrication may be adopted for panelfabrication also wherever required.

LT 3 Iron Work for panel board

Iron work for panel board or for other purpose completewith bending, cutting, drilling and welding completeerected at position with necessary material duly paintedwith one coat of red oxide and two coats of enamelpaint to match the switchgear or as per the direction ofthe Engineer.

As Per PWD CSR

LT 4 Bus Bar

Providing and fixing bus bar of required material inprovided cubical panel on internal angle iron framestructure on provided epoxy bus bar insulators orsuitable size bus bar strips, suitably designed fordesired Amp rating for required length with suitablearrangement for fixing cable termination, etc complete.

LT 4-1 Aluminium Bus Bar As Per PWD CSR

LT 4-2 Copper Bus Bar As Per PWD CSR

Note 2 Add 10% for color coded sleeves for bus bar strip kgrate.

Page 41: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Nut bolts holding busbar and cable lugs shall be ofbrass only.Double bus bar should be adequately bolted.For copper bus bar decrease the cross sectional areaby 25% to nearest size available for respective AmpratingWeight of Aluminium is 2700 kg/cum and weight ofcopper is 8900 kg/cum

LT 5 Bus Bar Chamber

Providing, erecting bus bar chamber triple pole withneutral (With 4 Aluminium bus bar) each of 100 cmlength of cross section and rating as below withminimum 3 insulators per bar. Bus bar chamber ofgiven size fabricated from 16 SWG M.S. Sheet and 25X 25 X 4 mm angle iron frame complete, spray paintedwith one coat of red oxide and two coats of good qualityenamel paint and polish.

Chamber size 115 X 40 X 15 cm

LT 5-1 Each bus bar of size 25 X 5mm-- For 100 Amp As Per PWD CSR

LT 5-2 Each bus bar of size 40 X 5mm-- For 200 Amp As Per PWD CSR

Chamber size 115 X 50 X 30 cm

LT 5-3 Each bus bar of size 50 X 5mm-- For 300 Amp As Per PWD CSR

LT 5-4 Each bus bar of size 50 X 10mm-- For 400 Amp As Per PWD CSR

LT 5-5 Bus bar of size 2 Nos-40 X 10mm-- For 630 Amp As Per PWD CSR

LT 5-6 Bus bar of size 2 Nos-50 X 10mm-- For 800 Amp As Per PWD CSR

LT 6 Bus Bar Insulators

Providing and fixing epoxy bus bar insulators inprovided cubical panel on internal angle frame structureof suitable size as per requirement of aluminium stripbeing used for panel, with required hardware material.

LT 6-1 30 X 30 X 30 mm ( T X B X H ) As Per PWD CSR

Page 42: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LT 6-2 30 X 40 X 40 mm ( T X B X H ) As Per PWD CSR

LT 6-3 40 X 50 X 50 mm ( T X B X H ) As Per PWD CSR

LT 6-4 40 X 50 X 60 mm ( T X B X H ) As Per PWD CSR

LT 6-5 40 X 50 X 70 mm ( T X B X H ) As Per PWD CSR

LT 7 Metal Clad T.P.

Supplying and erecting on angle frame, Triple Pole IronClad / Metal Clad switch and rewirable fuse 415 / 500 Vof suitable rating as below of approved make.

LT 7-1 16 Amp As Per PWD CSR

LT 7-2 32 Amp As Per PWD CSR

LT 7-3 63 Amp As Per PWD CSR

LT 7-4 100 Amp As Per PWD CSR

LT 7-5 200 Amp As Per PWD CSR

LT 7-6 300 Amp As Per PWD CSR

LT 8 Metal Clad T.P.N.

Supplying and erecting on angle frame, Triple Pole IronClad / Metal Clad switch with rewirable fuse, 415 / 500V of suitable rating, with Neutral link, of below ratingand of approved make.

LT 8-1 16 Amp As Per PWD CSR

LT 8-2 32 Amp As Per PWD CSR

LT 8-3 63 Amp As Per PWD CSR

LT 8-4 100 Amp As Per PWD CSR

LT 8-5 200 Amp As Per PWD CSR

LT 9 Metal Clad T.P.N. with HRC fuse

Supplying and erecting on angle frame, Triple Pole IronClad / Metal Clad switch with H.R.C. Type fuse (of ISIMark), 415 / 500 V of suitable rating, with Neutral link,of below rating and of approved make.

Page 43: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LT 9-1 100 Amp As Per PWD CSR

LT 9-2 200 Amp As Per PWD CSR

LT 9-3 300 Amp As Per PWD CSR

LT 9-4 400 Amp As Per PWD CSR

LT 10 T.P.N. Switch for Panel Mounting

Supplying and erecting T.P.N. switch suitable for 415Volts , 50 Hz with operating mechanism for panelmounting

LT 10-1 63 Amp As Per PWD CSR

LT 10-2 100 Amp As Per PWD CSR

LT 11 T.P.N. Switch Fuse ( In sheet steel encloser )

Supplying and erecting T.P.N. switch suitable for 415Volts , 50 Hz with operating mechanism

LT 11-1 32 Amp As Per PWD CSR

LT 11-2 63 Amp As Per PWD CSR

LT 11-3 100 Amp As Per PWD CSR

LT 12 Switch- Disconnector Fuse Unit

Supplying and erecting T.P.N. Switch -DisconnectorFuse Unit suitable for 415 Volts, 50 Hz with operatingmechanism for panel mounting or sheet metalenclosed, (Without HRC Fuses).

LT 12-1 125 Amp As Per PWD CSR( In sheet steel encloser)

LT 12-2 125 Amp As Per PWD CSR( For open execution)

LT 12-3 200 Amp As Per PWD CSR

Page 44: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

( In sheet steel encloser)

LT 12-4 200 Amp As Per PWD CSR( For open execution)

LT 12-5 315 Amp As Per PWD CSR( In sheet steel encloser)

LT 12-6 315 Amp As Per PWD CSR( For open execution)

LT 13 H.R.C. Fuse Link

Supplying erecting HRC Fuse link .

LT 13-1 HF Type, Current Rating 2/-----/40 Amp As Per PWD CSR

LT 13-2 HF Type, Current Rating 50 Amp As Per PWD CSR

LT 13-3 HF Type Current Rating 63 Amp As Per PWD CSR

LT 13-4 HN Type Current Rating 63 Amp As Per PWD CSR

LT 13-5 HN Type Current Rating 80/100 Amp As Per PWD CSR

LT 13-6 HN Type 125 Amp As Per PWD CSR

LT 13-7 HN Type 160 Amp As Per PWD CSR

LT 13-8 HN Type 200 Amp As Per PWD CSR

LT 13-9 HN Type 250 Amp As Per PWD CSR

LT 13-10 HN Type 315 Amp As Per PWD CSR

LT 14 Rotary change over switch

Supplying, erecting front operated rotary change overswitch for cubical panel, suitable for 3 Phase, 415 Volt,50 Hz.

LT 14-1 63 Amp As Per PWD CSR

LT 14-2 125 Amp As Per PWD CSR

LT 14-3 200 Amp As Per PWD CSR

LT 14-4 250 Amp As Per PWD CSR

LT 14-5 315 Amp As Per PWD CSR

LT 14-6 400 Amp As Per PWD CSR

LT 15 Cut outs ( Porcelain Base )

Page 45: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Supplying and erecting porcelain base iron clad cut out,500 Volts, of approved make erected on Polished T.W.block.

LT 15-1 16 Amp As Per PWD CSR

LT 15-2 32 Amp As Per PWD CSR

LT 15-3 63 Amp As Per PWD CSR

LT 15-4 100 Amp As Per PWD CSR

LT 15-5 200 Amp As Per PWD CSR

LT 16 Fuse Bridges ( Porcelain Base )

Supplying and erecting H.C. Pattern porcelain fusebridge and fuse link suitable for 500 Volts, ofapproved make erected on Polished T.W. block.

LT 16-1 16 Amp As Per PWD CSR

LT 16-2 32 Amp As Per PWD CSR

LT 16-3 63 Amp As Per PWD CSR

LT 16-4 100 Amp As Per PWD CSR

LT 16-5 200 Amp As Per PWD CSR

LT 16-6 300 Amp As Per PWD CSR

LT 17 Moulded Case Circuit Breakers

Providing erecting Moulded Case Circuit Breaker ofcapacity as below with magnetic thermal releasecomplete erected in provided encloser and connectedwith provided leads of incoming and out going side withcopper PVC leads/ bus in an approved manner.

LT 17-1 40-60-75-100 Amp (10 kA) As Per PWD CSR

LT 17-2 125-150 Amp (16 kA) As Per PWD CSR

LT 17-3 160-175-200-225 Amp (16 kA) As Per PWD CSR

Page 46: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LT 17-4 175 - 200 Amp ( 25 kA) As Per PWD CSR

LT 17-5 225-250 Amp (35 kA) As Per PWD CSR

LT 17-6 300-350-400 Amp (35 kA) As Per PWD CSR

LT 17-7 300-350-400 Amp (50 kA) As Per PWD CSR

LT 17-8 450-500-600-630 Amp (50 kA) As Per PWD CSR

LT 17-9 700-800 Amp (50 kA) As Per PWD CSR

Note 3 Add Rs. 1400/- for shunt release coil Add Rs. 1575/- for front operating mechanism

LT 18 Air Circuit Breaker

Providing erecting Air Circuit Breaker manuallyoperated draw out type with magnetic Thermal release,C.T. and auxillary contact and all standard accessories.

Manually operated draw out type

LT 18-1 800 Amp ( 25 kA) As Per PWD CSR

LT 18-2 1000 Amp (25 kA) As Per PWD CSR

LT 18-3 1250 Amp (35 kA) As Per PWD CSR

LT 18-4 1600 Amp (35 kA) As Per PWD CSR

LT 18-5 2000 Amp (35 kA) As Per PWD CSR

LT 18-6 2500 Amp ( 50 kA) As Per PWD CSR

LT 18-7 3200 Amp ( 50 kA) As Per PWD CSR

LT 18-8 4000 Amp ( 50 kA) As Per PWD CSR

Note 4 Add Rs.1400/- for shunt release, Rs. 5185/- for undervoltage relay and Rs.2300/- for earth fault relay , ifthese protections are required as a special case.

LT 19 Earth Leakage Circuit Breaker

Page 47: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing, erecting, commissioning Earth leakagecircuit breaker (ELCB/ RCCB) of suitable rating asbelow working on residual current 30 mA sensitivity andmax 30 mSec tripping time, test knob facility free tripmechanism operating for rated leakage at nominal 10 VAC and also in both neutral open snapping condition,etc with short circuit with-stand capacity as per literaturecomplying to BS 4293-1983 complete including allmaterial copper leads, lugs, screws etc erected inprovided MS box with window etc.

LT 19-1 16 / 25 Amp 2 pole As Per PWD CSR

LT 19-2 40 Amp 2 pole As Per PWD CSR

LT 19-3 63 Amp 2 pole As Per PWD CSR

LT 19-4 15/25 Amp 4 pole As Per PWD CSR

LT 19-5 40 Amp 4 pole As Per PWD CSR

LT 19-6 63 Amp 4 pole As Per PWD CSR

LT 19-7 80 Amp 4 pole As Per PWD CSR

LT 19-8 100 Amp 4 pole

LT 20 Panel Board accessories

LT 20-1 Marine Plywood

Supplying and erecting Marine Plywood 19 mm thickfixed to wall or on provided panel board for fixing Kit-Kat fuses and meter , etc with necessary material .

As Per PWD CSR

LT 20-2 Self Locking Arrangement

Supplying and erecting self locking arrangement withduplicate keys duly erected flush with / panel surface ofcup-boards.

As Per PWD CSR

LT 20-3 Pilot lamp

Supplying and erecting set of three pilot lamps all typeindicating lamp with LED colours RED / YELLOW /BLUE, 230 / 250 V on provided box / panel withnecessary wiring, material, connections etc.

As Per PWD CSR

Page 48: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LT 20-4 Ammeter

Providing erecting Ammeter AC 50 Hz 440 Volts ofsuitable range flush type complete erected in providedMS box and connected to supply by PVC copper wire.

LT 20-4-1 Ammeter 144 X 144 mm As Per PWD CSR

LT 20-4-2 Ammeter 96 X 96 mm As Per PWD CSR

LT 20-5 Voltmeter

Providing, erecting Voltmeter AC 50 Hz. 0 to 500 Voltsof suitable range flush type complete erected inprovided MS box and connected to supply by PVCcopper wire.

LT 20-5-1 Voltmeter 144 X 144mm As Per PWD CSR

LT 20-5-2 Voltmeter 96 X 96 mm As Per PWD CSR

LT 20-6 Selector Switch

Providing and erecting selector switch RY - YB - BR- forVolt meter, R - Y - B for ammeter suitable for AC supply500 Volts 50 Hz erected in provided MS box andconnected to Voltmeter, Ammeter with PVC copperwire.

As Per PWD CSR

LT 20-7 L.T Current Transformer

Providing erecting LT current transformer with wound /bar primary 100/5 Amps to 400/5 Amp ratio with 15 VAburden erected in provided MS box duly securedinsulating materials and connected to the meter

As Per PWD CSR

LT 20-8 Power factor meter

Page 49: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing erecting power factor meter 150 mm dia flushor projection type suitable for 400 Volt 50 Hz, 3 phase 4wire balanced or unbalanced load to work withappropriately provided CTs 100/5 Amp to 400/5 Ampratio and other accessories complete erected inprovided MS box and connected to the circuit by meansof PVC copper leads.

As Per PWD CSR

LT 20-9 Hour meter

Supplying and erecting Hour meter on provided panelboard including the hardware required similar to HM700 series of L.& T. working on 240 Volts AC synchron/ 24 VDC in quartz flush / panel mounting with metallicbracket, etc complete including cost of suitable controlwires for connection.

As Per PWD CSR

LT 20-10 kWh meter

Supply and erecting kWH meter provided with MDindicator for unbalanced load 3 Phase 4 wire, 50 Hz,230/440 Volts with incorporated time switch of 30 minintegration period and of 50 sec tune required fordecoupling suitable to work on provided three numbersof instrument transformer of class "C" accuracy withratio 100/5 Amp to 400/5 Amps complete with zeroadjustment and test certificate from manufacturer,erected on provided MS box or panel connected to CTsand circuit by means of PVC copper wire leads.

As Per PWD CSR

LT 20-11 Push Button

Providing erecting shrouded / unshrouded push buttonactuator L. & T. make TK 3 Type

Shrouded push button L&T As Per PWD CSR

LT 20-12 Toggle Switch

Providing erecting selector actuator 2 Position / 3Position

Selector Switch 2/3 Position As Per PWD CSR

LT 20-13 Key actuator

Page 50: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing erecting Key actuator Lockable in oneposition / both position L & T make Key actuatorlockable 1/2 position

LT 20-14 Rubber Matting

Supplying rubber mating of thickness as below and ofrequired length and breadth with good insulationproperty

LT 20-14-1 Rubber mating 6 mm thick 11 kV As Per PWD CSR

LT 20-14-2 Rubber mating 12mm thick 22 kV As Per PWD CSR

LT 20-15 Caution Board.

Providing enameled iron GI Sheet 18 gauge cautionboard of size 200 X 150 mm as per IS 2551 of 1982 inMarathi and Hindi erected at position.

As Per PWD CSR

LT 20-16 Name Board

Providing and fixing wall mounting type Name Boardduly painted all details of Pumping machinery, Make.Models, Frame Number, Sr. No, Capacities, Date ofinstallation, Commissioning, Manufacturing Year ,Agency's name and agreement No etc. Details on GISheet of 18 gauge of required size duly painted with redoxide and enamel paint for displaying the above details. Board shall be provided with suitable size TW bottomon the back side.

As Per PWD CSR

Note 5 For Labour charges for internal wiring of panelsincluding all material Add as below

1) Up to 5 HP twin set panel Rs. 1500/-2) 6 to 10 HP twin set panel Rs. 2000/-3) 11 to 30 HP twin set panel Rs. 2500/-4) For connected load more than 60 HP Add Rs. 45/-per HP

Page 51: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 8 - CP [ CAPACITOR ]

CP 1 All Polypropylene Capacitors.

Supplying and erecting bank of All Polypropylenecondensers with the standard capacities of1,2,3,5,7,12,5,15,20 and 25 KVAR units of power factorcorrection for operation on 3 phase, 50 Hz, 400 V+/-10% with externally discharging resistances, earthingterminals and built on angle iron or channel iron framework and provided with terminal cover box completeerected and tested.

KVAR 326 19 345

CP 2 Mixed Di Electric Capacitors.

Supplying and erecting bank of Mixed Di Electriccondensers with the standard capacities of1,2,3,5,7,12,5,15,20 and 25 KVAR units of power factorcorrection for operation on 3 phase, 50 Hz, 400 V+/-10% with externally discharging resistances, earthingterminals and built on angle iron on channel iron framework and provided with terminal cover box completeerected and tested.

KVAR 545 19 564

CP 3 H.T. Capacitors

Supplying and erecting bank of All Polypropylenecondensers with the standard capacities of75,84,116,133 and 167 KVAR units of power factorcorrection for operation on 3 phase, 50 Hz, 3300 V+/-6% with externally discharging resistances, earthingterminals and built on angle iron on channel iron framework and provided with terminal cover box, H.T.bushing bus bar and HRC fuses etc complete erectedand tested.

KVAR 541 51 592

Page 52: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 9 - LG [ L.T. SWITCHGEAR AND PROTECTION ]

LG L.T. Switchgear and Protection

LG 1 D.O.L. Starter

Supplying and erecting DOL starter to operate squirrelcage induction motor working on 380- 440 Volt, 3phase, 50 Hz with no volt coil and over load elementwith necessary material and connected to supply, etccomplete. Starter with original sheet steel encloser.

LG 1-1 Up to 7.5 HP Each 1697 64 1761

LG 1-2 Up to 10 HP Each 2764 136 2900

LG 2 Assembled D.O.L. Starter

Supplying and erecting assembled DOL starter inprovided cubical panel, with ON-OFF push buttons, novolt coil, over load element and required power andcontrol wiring complete.

LG 2-1 Up to 7.5 HP Each 1604 79 1683

LG 2-2 Up to 10 HP Each 2079 156 2235

LG 3 F.A.S.D. Starter

Supplying and erecting Fully Automatic Star Deltastarter to operate squirrel cage induction motor workingon 380- 440 Volt, 3 phase, 50 Hz with no volt coil, overload element, and ON - OFF push buttons, withnecessary material and connected to supply, etccomplete. Starter with original sheet steel encloser.

Page 53: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LG 3-1 > 7.5 HP & Up to 12.5 HP Each 6679 139 6818

LG 3-2 > 12.5 HP & Up to 20 HP Each 8166 139 8305

LG 3-3 > 20 HP & Up to 25 HP Each 9499 156 9655

LG 3-4 > 25 HP & Up to 40 HP Each 21913 156 22069

Note 1 Contactor rating should be same for STAR, LINE andDELTA Connection.

LG 4 F.A.S.D. Starter ( Assembled )

Supplying and erecting, assembled Fully Automatic StarDelta starter, in a provided cubical panel to operatesquirrel cage induction motor working on 380- 440 Volt,3 phase, 50 Hz with no volt coil, over load relay and ON-OFF push buttons, with necessary material andconnected to supply, etc complete.

LG 4-1 > 7.5 HP & Up to 12.5 HP Each 6584 156 6740

LG 4-2 > 12.5 HP & Up to 20 HP Each 7976 156 8132

LG 4-3 > 20 HP & Up to 30 HP Each 15476 175 15651

LG 4-4 > 30 HP & Up to 40 HP Each 21830 175 22005

Note 2 Contactor rating should be same for STAR, LINE andDELTA Connection.

LG 5 Auto transformer Starter with air break contactor (Locally Fabricated )

Providing erecting and giving test and trial of FullyAutomatic, Auto Transformer Starter with Air BreakContactor, assembled locally with contactors ofapproved make in 14 SWG sheet steel fabricated, floormounted type cubical panel, suitable for operation on380 - 440 Volts, 3 Phase, 50 Hz, fitted with accessoriesas below. The incoming and outgoing cable end boxesshall be on either sides of main panel. The cable entries from auto transformer shall be totally enclosed in sheetmetal. The starter shall have screened louvers on bothsides.

1) Oil immersed copper wound auto transformer with50%,65%, and 80% tapping including first fill of oil.

2) All Air Break Contactors of AC 3 duty of suitablerating as mentioned.3) Bimetallic overload relay.

Page 54: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

4) Timer ON and OFF delay.5) Master timer.6) Ammeter with CTs and selector switch.7) No Volt release.

8) Motor 'ON", "OFF" and "TRIP" indication lamp.9) Motor Protection Relay, solid state with protectionCTs.10) Thermostat with 1 NO + 1 NC for Oil temperature.11) Door interlock switch with 1 NO + 1 NC.12) Control fuse.

Starter for Motor HP / Contactor Rating " Main/ Start/Run".

Cubical Panel Size

1.25 m height X 0.75 m width X 0.45 m deep.

LG 5-1 40 HP (110 / 40 / 40) Each 82770 2129 84899

LG 5-2 60 HP (200 / 70 / 70) Each 115878 2129 118007

LG 5-3 80 HP (200 / 110 / 110) Each 140709 2129 142838

LG 5-4 100 HP (200 / 110 / 110) Each 182202 2129 184331

LG 5-5 120 HP (300 / 150 / 150) Each 231756 2129 233885

Cubical Panel Size

1.5 m height X 0.9 m width X 0.5 m deep.

LG 5-6 150 HP (300/150/150) Each 239106 4260 243366

LG 5-7 180 HP (400/170/170) Each 283849 4260 288109

LG 5-8 200 HP (400/200/200) Each 309229 4260 313489

LG 5-9 220 HP (400/200/200) Each 388103 4260 392363

LG 5-10 250 HP ( 400/300/300) Each 401456 6389 407845

LG 5-11 270 HP (630/300/300) Each 416160 6389 422549

LG 5-12 300 HP (630/300/300) Each 432326 6389 438715

Page 55: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LG 6 Electronic Soft Start Starter

Supplying , erecting, commissioning electronic soft startstarter of three wire system to operate on 380 / 440Volt, 3 Phase, 50 Hz consisting of ..

1) Main contactor AC - 3 Duty and 1.5 times of full loadcurrent rating.2) Suitable Thyristors3) Ammeter with selector switch and CTs.4) Motor protection relay with protection CTs forprotection against, a) Single phasing (Current sensing)b) Under voltage and over voltage c) Phase reversal d)Over current relay having IDMT Characteristic.

LG 6-1 40 HP(110) Each 83684 2129 85813

LG 6-2 60 HP ( 200) Each 99976 2129 102105

LG 6-3 80 HP (200) Each 142560 2129 144689

LG 6-4 100 HP (200) Each 156422 2129 158551

LG 6-5 120 HP ( 300) Each 177439 2129 179568

LG 6-6 150 HP (300) Each 164606 4260 168866

LG 6-7 180 HP (400) Each 213840 4260 218100

LG 6-8 200 HP (400) Each 222151 4260 226411

LG 6-9 220 HP (400) Each 262548 4260 266808

LG 6-10 250 HP ( 400) Each 282528 6389 288917

LG 6-11 270 HP (630) Each 300802 6389 307191

LG 6-12 300 HP (630) Each 314928 6389 321317

LG 6 B) FCMA/HFSR Electrical Soft starter

100 HP (200) Each 214810 2129 216939

120 HP ( 300) Each 239360 2129 241489

150 HP (300) Each 271220 4260 275480

180 HP (400) Each 298635 4260 302895

200 HP (400) Each 320777 4260 325037

Page 56: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

220 HP (400) Each 353745 4260 358005

250 HP ( 400) Each 379287 6389 385676

270 HP (630) Each 402240 6389 408629

300 HP (630) Each 470666 6389 477055

LG 7 Control and protection

LG 7-1 Automatic Multi-programmable Control UnitProviding , erecting multi programmable automaticcontrol unit suitable for submersible pump sets with testand trial with 2 years guarantee and also five visits forperiodical maintenance during the guaranteed period.The control unit shall be suitable for programmingindependently for 2 shifts, shall incorporate runningtime compensation arrangement for loss of time due topower failure and shall have protections against undervoltage, over voltage , single phasing, wrong phasesequence and low water level with time delay to preventnuisance tripping

LG 7-1-1 Suitable for single pump set For single pump Each 18810 0 18810

LG 7-1-2 Suitable for two pumps set (1 working + 1 Stand by)connected through change over switch.For two pumps Each 19498 0 19498

LG 7-2 Phase Failure RelayCurrent sensing Phase Failure Relay with over loadprotection ( without CTs)

Each 1200 181 1381

LG 7-3 Electronic Motor Protection Relay (for LT motors)

Providing, installing in panel EMPR for protection likeoverload, phase failure, locked rotor, phase reversalwith trip indication and adjustable over current function,DIN rail mounted.

Each 12000 1758 13758

Page 57: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 10 - HG[ H.T. SWITCHGEAR AND PROTECTION ]

HG H.T. switchgear and protection

HG 1 Providing and erecting Vacuum Circuit Breaker out door type excluding cost of CT and PT and control relaypanel.

Vacuum Circuit Breaker (Out door type)

HG 1-1 11 kV system 630 Amp 25 kA Each 198408 10648 209056

HG 1-2 22 kV system 630 Amp 25 kA Each 340127 10648 350775

HG 1-3 33 kV system 630 Amp 25 kA Each 340127 10648 350775

HG 1-4 11 kV system1250 Amp 25 kA Each 212580 10648 223228

HG 1-5 22 kV system 1250 Amp 25 kA Each 361385 10648 372033

HG 1-6 33 kV system 1250 Amp 25 kA Each 361685 10648 372333

HG 2 Providing and erecting Vacuum Circuit Breaker Indoortype without CT, PT, and protection relay.

Vacuum Circuit Breaker (Indoor type)

HG 2-1 3.3 kV system 630 Amp 25 kA Each 416656 10648 427304

HG 2-2 6.6 kV system 630 Amp 25 kA Each 416656 10648 427304

HG 2-3 11 kV system 630 Amp 25 kA Each 416656 10648 427304

HG 2-4 22 kV system 630 Amp 25 kA Each 1041640 10648 1052288

HG 2-5 33 kV system 630 Amp 25 kA Each 1041640 10648 1052288

HG 2-6 3.3 kV system 1250 Amp 25 kA Each 431537 10648 442185

HG 2-7 6.6 kV system 1250 Amp 25 kA Each 431537 10648 442185

HG 2-8 11 kV system 1250 Amp 25 kA Each 431537 10648 442185

HG 2-9 22 kV system 1250 Amp 25 kA Each 1116063 10648 1126711

HG 2-10 33 kV system 1250 Amp 25 kA Each 1116063 10648 1126711

Page 58: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

HG 3 Providing and erecting draw out type Vacuum CircuitContactor Panel Indoor type including CT of requiredratio for metering and protection including T.P. 2 O/Cand 1 E/F relay and 1 High speed trip relay.

Vacuum Contactor Panel (Indoor Type)

HG 3-1 3.3 kV system ( 25 kA) Each 452578 10648 463226

HG 3-2 6.6 kV system ( 25 kA) Each 520567 10648 531215

HG 4 Providing and erecting Resin Cast Indoor single phasedouble core CT of required ratio and VA burden formetering and protection purpose.

Resign Cast Indoor Single Phase, Double Core CTof required ratio

HG 4-1 C.T. for 3.3/ 6.6 / 11 kV 15 VA Class 1/10-P-10 Each 13878 968 14846

HG 4-2 C.T. for 22 /33 kV 15 VA Class 1/10-P-10 Each 22585 968 23553

HG 5 Providing and erecting Resin Cast Indoor single phaseSingle core PT of required ratio and VA burden formetering purpose.

Indoor Type Single Core PT of 100 VA capacity

HG 5-1 (11 kV / Root 3) / (110 Volt / √ 3) Each 13878 968 14846

HG 5-2 (22 kV / Root 3) / (110 Volt / √ 3) Each 20687 968 21655

HG 5-3 (33 kV / Root 3) / (110 Volt / √ 3) Each 22257 968 23225

HG 6 Protection and auxiliary relays

Providing and erecting following type protection andauxiliary relay as required for Vacuum Circuit BreakerPanel / control relay panel.

Page 59: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

HG 6-1 Providing, installing static motor protection relay similarto Alstom make for motors controlled through circuitbreaker, providing thermal instantaneous three phaseover current, unbalance and single phasing, earth faultand separate built-in stalling protection.

CTMM 501-510 Each 61360 1020 62380

HG 6-2 Providing, installing static motor protection relay similarto Alstom make for motors controlled by fusedcontactors, providing thermal instantaneous threephase over current, unbalance and single phasing,earth fault and separate built-in stalling protection.

CTMM 401-410 Each 59910 1020 60930

HG 6-3 Over Current and/or Earth Fault Relay

Providing, installing in panel single pole non directionalIDMT O/C or E/F self powered relay, flush mounted,conforming to IS 3231

HG 6-3-1 CDG 11, without High set/ MC 11A Each 6963 583 7546

HG 6-3-2 CDG 21, with High set/ MC 11A Each 11756 583 12339

Providing, installing in panel triple pole non directionalIDMT, 2 O/C and 1 E/F self powered relay , flushmounted, conforming to IS 3231

HG 6-3-3 CDG 31, without High set Each 20742 583 21325

HG 6-3-4 CDG 61 with high set Each 35847 583 36430

HG 6-3-5 Numerical communicable nondirectional overcurrent and earth fault relay, flush mounted similar to ABB model - PQ8nCH2JS

Each 54508 2726 57234

HG 6-4 High Speed Trip Relay

Providing, installing in panel single element high speedtrip relay with mechanical flag and hand reset contacts.

VAJH 13/ MVAJ053/AVAJH13 Each 4083 51 4134

Page 60: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

HG 6-5 Voltage operated auxillary relay without indicator withself reset / hand reset contacts, plug in combiflexmounting similar ABB model RXP8n / RXPQ8n

Each 4224 212 4436

HG 6-5 Auxiliary Relay

HG 6-5-1 Providing, installing in panel voltage operated auxiliaryrelay with flag, 2 NO + 2 NC, self reset contacts.

MVAA 11 Each 3147 51 3198

HG 6-5-2 Providing, installing in panel voltage operated auxiliaryrelay with flag, 2 NO + 2 NC, hand reset contacts.

MVAA 31/ AVA33 Each 5639 51 5690

HG 6-6 Power Factor Controller Relay

HG 6-6-1 Providing, installing static power factor controller relaywith minimum 8 capacitor stages with micro-processorbased capacitor switching with display of power factor -LT make

Each 15680 387 16067

HG 6-6-2 14 stages - LT make Each 17745 387 18132

HG 6-7 Digital Timer

Providing, installing static digital timer with time delayon pick-up.

Each 1848 51 1899

HG 6-8 Automatic Semaphore Indicator

Providing, installing Automatic Semaphore indicator DC/ AC operated for automatic indication of the position ofCircuit Breakers

VAM 21 Each 3376 51 3427

SECTION 11 - CB [ CABLE ]

Page 61: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 1 3 core PVC insulated, PVC sheathed copperconductor flat submersible cable

Supplying and erecting, Flat flexible submersible cablewith, Copper Conductor, PVC insulated, and PVCsheathed.

CB 1-1 3 core 1.5 sq mm m 66 11 77

CB 1-2 3 core 2.5 sq mm m 95 11 106

CB 1-3 3 core 4 sq mm m 140 11 151

CB 1-4 3 core 6 sq mm m 192 11 203

CB 1-5 3 core 10 sq mm m 318 11 329

CB 1-6 3 core 16 sq mm m 487 19 506

CB 1-7 3 core 25 sq mm m 789 19 808

CB 1-8 3 core 35 sq mm m 1122 19 1141

CB 2 Aluminium conductor single core, XLPE /PVCinsulated & armoured cable

Supplying and erecting, XLPE / PVC insulated,armoured cable 1100 V grade with ISI mark single core,stranded aluminium conductor with 6 mm thick 25 mmwidth M.S. spacer with G.I. Earth wire 6 sq mm,complete erected on wall / on pole with 25 X 3 mm M.S.clamps or in provided trench in an approved manner.

CB 2-1 Single core 300 sq mm m 635 19 654

CB 2-2 Single core 400 sq mm m 812 39 851

CB 2-3 Single core 500 sq mm m 1012 39 1051

CB 2-4 Single core 630 sq mm m 1305 39 1344

CB 2-5 Single core 800 sq mm m 1609 59 1668

CB 2-6 Single core 1000 sq mm m 1975 59 2034

CB 3 Aluminium conductor Twin core, XLPE / PVCinsulated & armoured cable

Page 62: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Supplying and erecting XLPE / PVC insulated,armoured cable 1100 V grade with ISI mark Twin core,solid / stranded aluminium conductor with 6 mm thick25 mm width M.S. spacer with G.I. Earth wire 6 sq mm,complete erected on wall / on pole with 25 X 3 mm M.S.clamps or in provided trench in an approved manner.

CB 3-1 Two core 2.5 sq mm m 81 5 86

CB 3-2 Two core 4 sq mm m 109 5 114

CB 3-3 Two core 6 sq mm m 126 5 131

CB 3-4 Two core 10 sq mm m 143 5 148

CB 4 Aluminium conductor Three core, XLPE / PVCinsulated & armoured cable

Supplying and erecting XLPE / PVC insulated,armoured cable 1100 V grade with ISI mark Three core,solid / stranded aluminium conductor with 6 mm thick25 mm width M.S. spacer with G.I. Earth wire 6 sq mm,complete erected on wall / on pole with 25 X 3 mm M.S.clamps or in provided trench in an approved manner.

CB 4-1 3 Core 2.5 sq mm m 103 5 108

CB 4-2 3 Core 4 sq mm m 124 5 129

CB 4-3 3 Core 6 sq mm m 139 5 144

CB 4-4 3 Core 10 sq mm m 169 5 174

CB 4-5 3 Core 16 sq mm m 201 13 214

CB 4-6 3 Core 25 sq mm m 244 13 257

CB 4-7 3 Core 35 sq mm m 265 13 278

CB 4-8 3 Core 50 sq mm m 368 13 381

CB 4-9 3 Core 70 sq mm m 493 21 514

CB 4-10 3 Core 95 sq mm m 627 21 648

CB 4-11 3 Core 120 sq mm m 755 39 794

CB 4-12 3 Core 150 sq mm m 903 39 942

CB 4-13 3 Core 185 sq mm m 1062 39 1101

CB 4-14 3 Core 240 sq mm m 1424 39 1463

CB 4-15 3 Core 300 sq mm m 1676 39 1715

Page 63: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 5 Aluminium conductor 3.5 Core, XLPE / PVCinsulated & armoured cable

Supplying and erecting, XLPE / PVC insulated,armoured cable 1100 V grade with ISI mark Three andhalf core, stranded aluminium conductor with 6 mmthick 25 mm width M.S. spacer with G.I. Earth wire 6 sqmm, complete erected on wall / on pole with 25 X 3 mmM.S. clamps or in provided trench in an approvedmanner.

CB 5-1 3.5 Core 25 sq mm m 283 13 296

CB 5-2 3.5 Core 35 sq mm m 332 13 345

CB 5-3 3.5 Core 50 sq mm m 409 28 437

CB 5-4 3.5 Core 70 sq mm m 541 28 569

CB 5-5 3.5 Core 95 sq mm m 725 28 753

CB 5-6 3.5 Core 120 sq mm m 855 28 883

CB 5-7 3.5 Core 150 sq mm m 996 43 1039

CB 5-8 3.5 Core 185 sq mm m 1250 43 1293

CB 5-9 3.5 Core 240 sq mm m 1692 61 1753

CB 5-10 3.5 Core 300 sq mm m 2014 61 2075

CB 5-11 3.5 Core 400 sq mm m 2604 61 2665

CB 6 Aluminium conductor 4 Core, XLPE / PVC insulated& armoured cable

Supplying and erecting, XLPE / PVC insulated,armoured cable 1100 V grade with ISI mark Four core,solid / stranded aluminium conductor with 6 mm thick25 mm width M.S. spacer with G.I. Earth wire 6 sq mm,complete erected on wall / on pole with 25 X 3 mm M.S.clamps or in provided trench in an approved manner.

CB 6-1 4 Core 4 sq mm m 142 13 155

CB 6-2 4 Core 6 sq mm m 163 13 176

CB 6-3 4 Core 10 sq mm m 190 13 203

CB 6-4 4 Core 16 sq mm m 236 13 249

CB 7 Copper conductor PVC insulated, armouredcontrol cable

Page 64: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 7-1 Supplying and erecting armoured control cable with ISImark stranded / solid copper conductor 1.1 kV gradecomplete erected on wall / panel or in provided trenchin an approved manner.

1.5 sq mm Copper conductor PVC insulated,armoured control cable

CB 7-1-1 2 core 1.5 sq mm m 123 4 127

CB 7-1-2 3 core 1.5 sq mm m 141 4 145

CB 7-1-3 4 core 1.5 sq mm m 165 4 169

CB 7-1-4 5 core 1.5 sq mm m 189 4 193

CB 7-1-5 6 core 1.5 sq mm m 210 4 214

CB 7-1-6 7 core 1.5 sq mm m 226 4 230

CB 7-1-7 8 core 1.5 sq mm m 288 4 292

CB 7-1-8 9 core 1.5 sq mm m 312 4 316

CB 7-1-9 10 core 1.5 sq mm m 350 4 354

CB 7-2 2.5 sq mm Copper conductor PVC insulated,armoured control cable

CB 7-2-1 2 core 2.5 sq mm m 171 4 175

CB 7-2-2 3 core 2.5 sq mm m 194 4 198

CB 7-2-3 4 core 2.5 sq mm m 245 4 249

CB 7-2-4 5 core 2.5 sq mm m 266 4 270

CB 7-2-5 6 core 2.5 sq mm m 300 4 304

CB 7-2-6 7 core 2.5 sq mm m 342 4 346

CB 7-2-7 8 core 2.5 sq mm m 417 4 421

CB 7-2-8 9 core 2.5 sq mm m 441 4 445

CB 7-2-9 10 core 2.5 sq mm m 477 4 481

Copper conductor PVC insulated, Un-armouredcontrol cable

Supplying and erecting Un-armoured control cable withISI mark stranded / solid copper conductor 1.1 kVgrade complete erected on wall / panel or in providedtrench in an approved manner.

1.5 sq mm Copper conductor PVC Un-armouredcontrol cable

CB 8-1-1 2 core 1.5 sq mm m 68 4 72

Page 65: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 8-1-2 3 core 1.5 sq mm m 90 4 94

CB 8-1-3 4 core 1.5 sq mm m 115 4 119

CB 8-1-4 5 core 1.5 sq mm m 146 4 150

CB 8-1-5 6 core 1.5 sq mm m 171 4 175

CB 8-1-6 7 core 1.5 sq mm m 190 4 194

CB 8-1-7 8 core 1.5 sq mm m 220 4 224

CB 8-1-8 9 core 1.5 sq mm m 244 4 248

CB 8-1-9 10 core 1.5 sq mm m 269 4 273

CB 8-2 2.5 sq mm Copper conductor PVC Un-armouredcontrol cable

CB 8-2-1 2 core 2.5 sq mm m 97 4 101

CB 8-2-2 3 core 2.5 sq mm m 135 4 139

CB 8-2-3 4 core 2.5 sq mm m 171 4 175

CB 8-2-4 5 core 2.5 sq mm m 227 4 231

CB 8-2-5 6 core 2.5 sq mm m 269 4 273

CB 8-2-6 7 core 2.5 sq mm m 300 4 304

CB 8-2-7 8 core 2.5 sq mm m 342 4 346

CB 8-2-8 9 core 2.5 sq mm m 397 4 401

CB 8-2-9 10 core 2.5 sq mm m 439 4 443

CB 9 Aluminium conductor XLPE / PVC insulated,armoured Cable

Supplying and erecting Aluminium conductor, XLPE /PVC - 3.3 kV, armoured cable complete erected inprovided trench or on provided trays in an approvedmanner as per direction of Engineer In Charge

3.3 kV- XLPE / PVC

CB 9-1 3 Core 25 sq mm m 675 21 696

CB 9-2 3 Core 35 sq mm m 702 21 723

CB 9-3 3 Core 50 sq mm m 801 21 822

Page 66: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 9-4 3 Core 70 sq mm m 940 21 961

CB 9-5 3 Core 95 sq mm m 1141 21 1162

CB 9-6 3 Core120 sq mm m 1284 39 1323

CB 9-7 3 Core 150 sq mm m 1512 39 1551

CB 9-8 3 Core 185 sq mm m 1693 39 1732

CB 9-9 3 Core 240 sq mm m 2096 39 2135

CB 9-10 3 Core 300 sq mm m 2454 61 2515

CB 9-11 3 Core 400 sq mm m 3052 61 3113

CB 10 Supplying and erecting Aluminium conductor, XLPE /PVC - 6.6 kV, armoured cable complete erected inapproved trench or on trays as per direction of EngineerIn Charge

6.6 kV -- XLPE / PVC

CB 10-1 3 Core 35 sq mm m 806 21 827

CB 10-2 3 Core 50 sq mm m 900 21 921

CB 10-3 3 Core 70 sq mm m 1048 21 1069

CB 10-4 3 Core 95 sq mm m 1240 21 1261

CB 10-5 3 Core120 sq mm m 1442 39 1481

CB 10-6 3 Core 150 sq mm m 1638 39 1677

CB 10-7 3 Core 185 sq mm m 1862 39 1901

CB 10-8 3 Core 240 sq mm m 2222 39 2261

CB 10-9 3 Core 300 sq mm m 2680 61 2741

CB 10-10 3 Core 400 sq mm m 3592 61 3653

CB 11 Supplying and erecting Aluminium conductor, XLPE /PVC - 11 kV , armoured cable complete erected inapproved trench or on trays as per direction of EngineerIn Charge

11 kV -- XLPE / PVC

CB 11-1 3 Core 35 sq mm m 918 21 939

CB 11-2 3 Core 50 sq mm m 1036 21 1057

CB 11-3 3 Core 70 sq mm m 1159 21 1180

CB 11-4 3 Core 95 sq mm m 1393 21 1414

CB 11-5 3 Core120 sq mm m 1584 39 1623

CB 11-6 3 Core 150 sq mm m 1754 39 1793

CB 11-7 3 Core 185 sq mm m 2022 39 2061

Page 67: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 11-8 3 Core 240 sq mm m 2378 39 2417

CB 11-9 3 Core 300 sq mm m 3086 61 3147

CB 11-10 3 Core 400 sq mm m 3492 61 3553

CB 12 Supplying and erecting Aluminium conductor, XLPE /PVC - 22 kV, armoured cable complete erected inapproved trench or on trays as per direction of EngineerIn Charge

22 kV -- XLPE / PVC

CB 12-1 3 Core 35 sq mm m 1360 21 1381

CB 12-2 3 Core 50 sq mm m 1502 21 1523

CB 12-3 3 Core 70 sq mm m 1760 21 1781

CB 12-4 3 Core 95 sq mm m 1845 21 1866

CB 12-5 3 Core120 sq mm m 2061 39 2100

CB 12-6 3 Core 150 sq mm m 2263 39 2302

CB 12-7 3 Core 185 sq mm m 2628 39 2667

CB 12-8 3 Core 240 sq mm m 3017 39 3056

CB 12-9 3 Core 300 sq mm m 3445 61 3506

CB 12-10 3 Core 400 sq mm m 4173 61 4234

CB 13 Supplying and erecting Aluminium conductor, XLPE /PVC - 33 kV, armoured cable complete erected inapproved trench or on trays as per direction of EngineerIn Charge

33 kV -- XLPE / PVC

CB 13-1 3 Core 50 sq mm m 2043 21 2064

CB 13-2 3 Core 70 sq mm m 2236 21 2257

CB 13-3 3 Core 95 sq mm m 2504 21 2525

CB 13-4 3 Core120 sq mm m 2760 39 2799

CB 13-5 3 Core150 sq mm m 2981 39 3020

CB 13-6 3 Core185 sq mm m 3373 39 3412

CB 13-7 3 Core240 sq mm m 3807 39 3846

CB 13-8 3 Core 300sq mm m 4218 61 4279

Page 68: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 13-9 3 Core 400 sq mm m 5119 61 5180

CB 14 MAKING TRENCH

Making a trench of suitable width and 0.9 m deep andlaying provided cable and refilling the same withscreened sand bed of 0.2 m thick to embed the cableand bricks placed on both side length wise and on topwidth wise all over the cable run and refilling theexcavated earth without stone or hard material andmaking the surface proper with 0.15 m crown on top.

CB 14-1 In Soft Soil As Per PWD CSR

CB 14-2 In Hard Murum or Tar Road As Per PWD CSR

Note 1 Add Rs 20/- per m length if Additional cable is to be laidby the side in the same trench with two Additional bricksto form another compartment.

Note 2 For cable size up to 10 sq.mm, single brick is to be laidon the cable length wise and the above rate be reducedby 25%.

CB 15 CABLE MARKER

Supplying and erecting cast iron cable marker plate of100 mm dia and 6 mm thick welding with 0.7 m longgalvanised iron rod of 12 mm dia and cross bars of 15cm length welding at bottom of iron rod buried alongwith route of cable.

As Per PWD CSR

CB 16 Cable enclosing G.I. Pipe "A" Grade

Supplying, erecting G.I. Pipe "A" grade erected forenclosing PVC armoured cable on wall or pole withclamp and upper end closed with T.W. bush and sealedwith compound.

CB 16-1 G.I. Pipe , 25 mm dia As Per PWD CSR

CB 16-2 G.I. Pipe , 40 mm dia As Per PWD CSR

CB 16-3 G.I. Pipe , 50 mm dia As Per PWD CSR

CB 17 Cable enclosing RCC Pipe

Page 69: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Supplying and laying RCC hume pipe with couplingcollar of standard thickness below ground / roadsurfacing for inclosing provided cable. The rates areinclusive of the work of required excavation of trenchfor pipe laying and refilling the trench with light rammingto make the road / ground surface as it was.

CB 17-1 100 mm dia, RCC pipe As Per PWD CSR

CB 17-2 150 mm dia, RCC pipe As Per PWD CSR

CB 17-3 250 mm dia, RCC pipe As Per PWD CSR

CB 18 Cable enclosing G.I. Pipe "B" Class

Providing and laying 75 mm dia G.I. Pipe "B" grade ISImark for enclosing provided cable to lay underground atrequired depth up to 90 cm with required excavationand refilling with light ramming to make the groundsurface as it was.

As Per PWD CSR

CB 19 Cable Lugs-- Aluminium

Supplying and erecting crimpling type aluminium lugsconforming to IS suitable for cable as below evenlycrimped with high pressure tool and connected toswitch gear terminals with brass / cadmium plated nutbolts in an approved manner.

CB 19-1 16 sq mm As Per PWD CSR

CB 19-2 25 sq mm As Per PWD CSR

CB 19-3 35 sq mm As Per PWD CSR

CB 19-4 50 sq mm As Per PWD CSR

CB 19-5 70 sq mm As Per PWD CSR

CB 19-6 95 sq mm As Per PWD CSR

CB 19-7 120 sq mm As Per PWD CSR

CB 19-8 150 sq mm As Per PWD CSR

CB 19-9 185 sq mm As Per PWD CSR

CB 19-11 240 sq mm As Per PWD CSR

CB 19-12 300 sq mm As Per PWD CSR

Page 70: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 19-13 400 sq mm As Per PWD CSR

CB 20 Cable Glands ( Brass )

Supplying and erecting heavy duty Siemens type brasscable glands of suitable size for PVC armoured cableas mentioned below with brass washers, rubber rings,complete erected with cable ends and leadconnections.

CB 20-1 2 to 4 core 2.5 to 4 sq mm As Per PWD CSR

CB 20-2 3 to 4 core 6 to 10 sq mm As Per PWD CSR

CB 20-3 3 to 4 core 16 to 25 sq mm As Per PWD CSR

CB 20-5 3 to 3.5 core 50 sq mm As Per PWD CSR

CB 20-6 3 to 3.5 core 70 sq mm As Per PWD CSR

CB 20-7 3 to 3.5 core 95 sq mm As Per PWD CSR

CB 20-8 3 to 3.5 core 120 sq mm As Per PWD CSR

CB 20-9 3 to 3.5 core 150 sq mm As Per PWD CSR

CB 20-10 3 to 3.5 core 185 sq mm As Per PWD CSR

CB 20-11 3 to 3.5 core 240 sq mm As Per PWD CSR

CB 20-12 3 to 3.5 core 300 sq mm As Per PWD CSR

CB 20-13 3 to 3.5 core 400 sq mm As Per PWD CSR

Note 3 For Flange type glands increase overall rate by 50% .

CB 21 Cable Jointing Kit for Submersible cable

Providing cable jointing Kit with cable jointingcompound and material for various size of submersiblecable up to 35 sq mm etc complete.

As Per PWD CSR

Providing and erecting IN-DOOR type terminationkit, for 3.3 kV / 6.6 kV / 11 kV / 22kV / 33 kV XLPEScreened 3 core cable

CB 22 INDOOR TERMINATION KIT for 3.3 kV / 6.6 kVXLPE 3 Core cable.

CB 22-1 25-50 sq.mm Each 3496 1935 5431

CB 22-2 70-120 sq.mm Each 3872 1935 5807

Page 71: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 22-3 150-185 sq.mm Each 4386 1935 6321

CB 22-4 240-400 sq.mm Each 4887 1935 6822

CB 23 OUT DOOR TERMINATION KIT for 3.3 / 6.6 kV XLPE3 Core cable.

CB 23-1 25-50 sq.mm Each 5703 1935 7638

CB 23-2 70-120 sq.mm Each 5940 1935 7875

CB 23-3 150-185 sq.mm Each 6404 1935 8339

CB 23-4 240-400 sq.mm Each 8057 1935 9992

CB 24 STRAIGHT THROUGH JOINT for 3.3 / 6.6 kV XLPE3 Core cable.

CB 24-1 25-50 sq.mm Each 13103 1935 15038

CB 24-2 70-120 sq.mm Each 14671 1935 16606

CB 24-3 150-185 sq.mm Each 18663 1935 20598

CB 24-4 240-400 sq.mm Each 20410 1935 22345

CB 25 INDOOR TERMINATION KIT for 11 kV XLPEScreened 3 core cable.

CB 25-1 25-50 sq.mm Each 5050 1935 6985

CB 25-2 70-120 sq.mm Each 6115 1935 8050

CB 25-3 150-225 sq.mm Each 7321 1935 9256

CB 25-4 240-400 sq.mm Each 8245 1935 10180

CB 26 OUT DOOR TERMINATION KIT for 11 kV XLPEScreened 3 core cable.

CB 26-1 25-50 sq.mm Each 8659 1935 10594

CB 26-2 70-120 sq.mm Each 9850 1935 11785

CB 26-3 150-185 sq.mm Each 10575 1935 12510

CB 26-4 225 sq. mm Each 11891 1935 13826

CB 26-5 240-400 sq.mm Each 12507 1935 14442

Page 72: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 27 STRAIGHT THROUGH JOINT for 11 kV XLPEScreened 3 core cable.

CB 27-1 25-50 sq.mm Each 16050 1935 17985

CB 27-2 70-120 sq.mm Each 17969 1935 19904

CB 27-3 150-185 sq.mm Each 22856 1935 24791

CB 27-4 240-300 sq.mm Each 25000 1935 26935

CB 28 INDOOR TERMINATION KIT FOR 22 kV XLPEScreened 3 core cable.

CB 28-1 25-50 sq.mm Each 6479 1935 8414

CB 28-2 70-120 sq.mm Each 8257 1935 10192

CB 28-3 150-185 sq.mm Each 10089 1935 12024

CB 28-4 240-400 sq.mm Each 11868 1935 13803

CB 29 OUT DOOR TERMINATION KIT for 22 kV XLPEScreened 3 core cable.

CB 29-1 25-50 sq.mm Each 11340 1935 13275

CB 29-2 70-120 sq.mm Each 13609 1935 15544

CB 29-3 150-185 sq.mm Each 15588 1935 17523

CB 29-4 240-400 sq.mm Each 20727 1935 22662

CB 30 STRAIGHT THROUGH JOINT for 22 kV XLPEScreened 3 core cable.

CB 30-1 50 sq.mm Each 28268 1935 30203

CB 30-2 70-95 sq.mm Each 33015 1935 34950

CB 30-3 120-150 sq.mm Each 34841 1935 36776

CB 30-4 185-240 sq.mm Each 44127 1935 46062

CB 30-5 300-400 sq.mm Each 48066 1935 50001

CB 31 INDOOR TERMINATION KIT for 33 kV XLPEScreened 3 core cable.

Page 73: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

CB 31-1 50 sq.mm Each 10953 1935 12888

CB 31-2 70-95 sq.mm Each 11958 1935 13893

CB 31-3 120-185 sq.mm Each 18082 1935 20017

CB 31-4 240-400 sq.mm Each 20502 1935 22437

CB 32 OUT DOOR TERMINATION KIT for 33 kV XLPEScreened 3 core cable.

CB 32-1 50 sq.mm Each 15451 1935 17386

CB 32-2 70-95 sq.mm Each 19206 1935 21141

CB 32-3 120-185 sq.mm Each 24894 1935 26829

CB 32-4 240-400 sq.mm Each 32949 1935 34884

CB 33 STRAIGHT THROUGH JOINT for 33 kV XLPEScreened 3 core cable.

CB 33-1 50-70 sq.mm Each 37941 1935 39876

CB 33-2 95-150 sq.mm Each 47946 1935 49881

CB 33-3 185-300 sq.mm Each 66609 1935 68544

CB 33-4 400 sq.mm Each 74596 1935 76531

CB 34 CABLE TRAY

Providing and fixing G.I. Perforated cable trays of sizeas below including fixing on provided angles.

CB 34-1 80mm X 20mm m 79 9 88

CB 34-2 200mm X 20mm m 159 13 172

CB 34-3 400mm X 20mm m 317 13 330

CB 35 CABLE DUCT RCC M-150

Page 74: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Providing and laying RCC ( M-150) cable duct of sizegiven below for laying electric cable including form workfor centering M.S. bar reinforcement, necessaryexcavation bolder filling, PCC (M100), compacting,curing , plastering, including providing and fixing 35 X35 X 5 mm M.S. angles, RCC pre cast cover ofAdequate length with 100 mm over lap on either wallsetc complete and providing RCC pre cast covers.

CB 35-1 Cable duct 2 tier-750W X 750 D m 1613 0 1613

CB 35-2 Cable duct 3 tier-750W X 1000 D m 1894 0 1894

CB 35-3 Cable duct 2x3 tier-1000W X 1000D m 2354 0 2354

SECTION 12 - MO [ MOTORS ]

MO 1 Foot Mounted Motors SPDP 1000 RPM

Providing, erecting and giving test and trial of FootMounted SPDP motor 1000 RPM, squirrel cageinduction motor, conforming to IS 325 havingcontinuous rating suitable for operation at 415 Volts +/-10%, 3 Phase, 50 Hz +/-3% with "F" class insulationtemperature rise limited to class "B" insulation.

MO 1-1 45 kW ( 60 HP ) Each 243354 2904 246258

MO 1-2 55 kW ( 75 HP ) Each 282926 2904 285830

MO 1-3 75 kW ( 100 HP ) Each 336423 3875 340298

MO 1-4 90 kW ( 120 HP ) Each 428690 3875 432565

MO 1-5 110 kW ( 150 HP ) Each 548057 5808 553865

MO 1-6 125 kW ( 170 HP ) Each 618585 5808 624393

MO 1-7 135 kW ( 180 HP ) Each 654653 5808 660461

MO 1-8 150 kW ( 200 HP ) Each 696592 5808 702400

MO 1-9 160 kW ( 215 HP ) Each 755062 5808 760870

MO 1-10 180 kW ( 240 HP ) Each 851001 7747 858748

Page 75: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MO 1-11 187 kW ( 250 HP ) Each 864597 7747 872344

MO 1-12 200 kW ( 270 HP ) Each 887412 7747 895159

MO 1-13 225 kW ( 300 HP ) Each 1013405 7747 1021152

MO 2 Foot Mounted Motors SPDP 1500 RPM

Providing, erecting and giving test and trial of FootMounted SPDP motor 1000 RPM, squirrel cageinduction motor, conforming to IS 325 havingcontinuous rating suitable for operation at 415 Volts +/-10%, 3 Phase, 50 Hz +/-3% with "F" class insulationtemperature rise limited to class "B" insulation.

MO 2-1 18.5 kW ( 25 HP ) Each 83341 1935 85276

MO 2-2 22 kW ( 30 HP ) Each 89354 1935 91289

MO 2-3 30 kW ( 40 HP ) Each 98867 1935 100802

MO 2-4 37 kW ( 50 HP ) Each 132891 2904 135795

MO 2-5 45 kW ( 60 HP ) Each 167517 2904 170421

MO 2-6 55 kW ( 75 HP ) Each 208880 2904 211784

MO 2-7 75 kW ( 100 HP ) Each 261357 3875 265232

MO 2-8 90 kW ( 120 HP ) Each 296388 3875 300263

MO 2-9 110 kW ( 150 HP ) Each 354376 5808 360184

MO 2-10 125 kW ( 170 HP ) Each 375154 5808 380962

MO 2-11 135 kW ( 180 HP ) Each 410408 5808 416216

MO 2-12 150 kW ( 200 HP ) Each 490950 5808 496758

MO 2-13 160 kW ( 215 HP ) Each 595428 5808 601236

MO 2-14 180 kW ( 240 HP ) Each 612066 7747 619813

MO 2-15 187 kW ( 250 HP ) Each 620556 7747 628303

Page 76: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MO 2-16 200 kW ( 270 HP ) Each 681995 7747 689742

MO 2-17 225 kW ( 300 HP ) Each 810111 7747 817858

MO 3 Foot Mounted Motor SPDP 3000 RPM

MO 3-1 11 kW ( 15 HP ) Each 53418 1935 55353

MO 3-2 15 kW ( 20 HP ) Each 70561 1935 72496

MO 3-3 18.5 kW ( 25 HP ) Each 90776 1935 92711

MO 3-4 22 kW ( 30 HP ) Each 96607 1935 98542

MO 3-5 30 kW ( 40 HP ) Each 106051 1935 107986

MO 3-6 37 kW ( 50 HP ) Each 150050 2908 152958

MO 3-7 45 kW ( 60 HP ) Each 183096 2908 186004

MO 3-8 55 kW ( 75 HP ) Each 241445 2908 244353

MO 3-9 75 kW ( 100 HP ) Each 277794 3875 281669

MO 4 Foot Mounted Motor TEFC 1500 RPM

MO 4-1 1.1 kW ( 1.5 HP ) Each 10947 194 11141

MO 4-2 1.5 kW ( 2 HP ) Each 11857 194 12051

MO 4-3 2.2 kW ( 3 HP ) Each 15778 194 15972

MO 4-4 3.7 kW ( 5 HP ) Each 20278 291 20569

MO 4-5 5.5 kW ( 7 HP ) Each 27910 484 28394

MO 4-6 7.5 kW ( 10 HP ) Each 32661 484 33145

MO 4-7 9.3 kW ( 12 HP ) Each 50761 968 51729

MO 4-8 11 kW ( 15 HP ) Each 53347 968 54315

MO 4-9 15 kW ( 20 HP ) Each 66247 968 67215

MO 4-10 18.5 kW ( 25 HP ) Each 10439 1935 12374

MO 4-11 22 kW ( 30 HP ) Each 97075 1935 99010

MO 4-12 30 kW ( 40 HP ) Each 131211 1935 133146

MO 4-13 37 kW ( 50 HP ) Each 169959 2908 172867

MO 4-14 45 kW ( 60 HP ) Each 205587 2908 208495

Page 77: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MO 4-15 55 kW ( 75 HP ) Each 280281 2908 283189

MO 4-16 75 kW ( 100 HP ) Each 358907 3875 362782

MO 5 Vertical Hollow Shaft Motor SPDP 1500 RPM

MO 5-1 18.5 kW ( 25 HP ) Each 130227 1935 132162

MO 5-2 22 kW ( 30 HP ) Each 144074 1935 146009

MO 5-3 30 kW ( 40 HP ) Each 157255 1935 159190

MO 5-4 37 kW ( 50 HP ) Each 181255 2908 184163

MO 5-5 45 kW ( 60 HP ) Each 231670 2908 234578

MO 5-6 55 kW ( 75 HP ) Each 294619 2908 297527

MO 5-7 67 kW ( 90 HP ) Each 390248 3875 394123

MO 5-8 75 kW ( 100 HP ) Each 393819 3875 397694

MO 5-9 90 kW ( 120 HP ) Each 407508 3875 411383

MO 5-10 110 kW ( 150 HP ) Each 486072 5808 491880

MO 5-11 125 kW ( 170 HP ) Each 497254 5808 503062

MO 5-12 135 kW ( 180 HP ) Each 573906 5808 579714

MO 5-13 150 kW ( 200 HP ) Each 673285 5808 679093

MO 5-14 160 kW ( 215 HP ) Each 725589 5808 731397

MO 5-15 180 kW ( 240 HP ) Each 753726 7747 761473

MO 5-16 187 kW ( 250 HP ) Each 762924 7747 770671

MO 5-17 200 kW ( 270 HP ) Each 806211 7747 813958

MO 5-18 225 kW ( 300 HP ) Each 840660 7747 848407

MO 6 Vertical Solid Shaft Motor SPDP / TEFC - 1500 RPM

Note 1 Add 5 % on the rate of Horizontal foot mounted( SPDP / TEFC ) motor for vertical flange mounted solidshaft motor

Page 78: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MO 7 3.3 kV Foot Mounted Motor SPDP 1000 RPM

Providing, erecting and giving test and trial of FootMounted SPDP motor 1000 RPM, squirrel cageinduction motor, conforming to IS 325 havingcontinuous rating suitable for operation at 3300 Volts +/-10%, 3 Phase, 50 Hz +/-3% with "F" class insulationtemperature rise limited to class "B" insulation. Motorshall be fitted with suitable space heater and six nos.RTD.

MO 7-1 225 kW ( 300 HP ) Each 794376 7747 802123

MO 7-2 250 kW ( 335 HP ) Each 901506 9680 911186

MO 7-3 280 kW ( 375 HP ) Each 1068643 11616 1080259

MO 7-4 340 kW ( 456 HP ) Each 1126138 11616 1137754

MO 7-5 390 kW ( 523 HP ) Each 1187114 13555 1200669

MO 7-6 440 kW ( 590 HP ) Each 1262319 13555 1275874

MO 7-7 510 kW ( 684 HP ) Each 1443216 13555 1456771

MO 7-8 580 kW ( 777 HP ) Each 1559073 15491 1574564

MO 7-9 660 kW ( 885 HP ) Each 1750526 15491 1766017

MO 8 3.3 kV Foot Mounted Motor SPDP 1500 RPM

MO 8-1 225 kW ( 300 HP ) Each 696863 7747 704610

MO 8-2 250 kW ( 335 HP ) Each 790764 9680 800444

MO 8-3 280 kW ( 375 HP ) Each 937108 11616 948724

MO 8-4 330 kW ( 442 HP ) Each 979793 11616 991409

MO 8-5 370 kW ( 495 HP ) Each 1126138 13552 1139690

MO 8-6 425 kW ( 569 HP ) Each 1168820 13552 1182372

MO 8-7 510 kW ( 683 HP ) Each 1274513 13552 1288065

MO 8-8 660 kW ( 885 HP ) Each 1550943 15491 1566434

Page 79: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

MO 9 3.3 kV Vertical Flange Mounted Motor SPDP 1000RPM

MO 9-1 225 kW ( 300 HP ) Each 820091 7747 827838

MO 9-2 250 kW ( 335 HP ) Each 930801 9680 940481

MO 9-3 280 kW ( 375 HP ) Each 1103181 11616 1114797

MO 9-4 340 kW ( 456 HP ) Each 1158658 11616 1170274

MO 9-5 390 kW ( 523 HP ) Each 1219635 13552 1233187

MO 9-6 440 kW ( 590 HP ) Each 1294839 13552 1308391

MO 9-7 510 kW ( 684 HP ) Each 1465575 13552 1479127

MO 9-8 580 kW ( 777 HP ) Each 1581431 15491 1596922

MO 9-9 660 kW ( 885 HP ) Each 1772074 15491 1787565

MO 10 3.3 kV Vertical Flange Mounted Motor SPDP 1500RPM

MO 10-1 225 kW ( 300 HP ) Each 728610 7747 736357

MO 10-2 250 kW ( 335 HP ) Each 826843 9680 836523

MO 10-3 280 kW ( 375 HP ) Each 925075 11616 936691

MO 10-4 330 kW ( 442 HP ) Each 1024510 11616 1036126

MO 10-5 370 kW ( 495 HP ) Each 1158658 13552 1172210

MO 10-6 425 kW ( 569 HP ) Each 1201343 13552 1214895

MO 10-7 510 kW ( 683 HP ) Each 1307035 13552 1320587

MO 10-8 660 kW ( 885 HP ) Each 1573300 15491 1588791

Note 2 For all types of motors above 200 HP the cost isinclusive of 2 space heater and for all types of HTmotor the cost is inclusive of 2 Nos. space heater and 6Nos. RTD. Necessary provision for control wiring andsuitable contactor shall be made in the estimate of LTpanel board.

Note 3 For any special purpose if RTD and space heater arerequired in addition, add following extra chargesa) Space heater (240 Volts) Rs 5250/- for set of twob) RTD Rs. 7500/- for six Nos.

Page 80: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Code No Description

Labour charges

for Removing

Labour charges

for Disman-tling

Labour charges

for Assem-bling

Labour charges for Re-

erection

SECTION 13 - LB [ REMOVING , DISMANTLING , ASSEMBLING & RE-ERECTION ]

Note The rates in this schedule are stated as percentage of rate for erection given in Section 1, 6,12 and Section of Civil CSR as applicable.

LB 1 Labour charges for removing, disassembling,assembling and re-erection of pumps

LB 1-1 Submersible pump set 80% 10% 20% 90%

LB 1-2 Monoblock pump motor set 25% 10% 20% 30%

LB 1-3 Rotating assembly of H.S. casing pump - 20% 30% -

LB 1-4 Coupled pump (without motor )Not applicable for HS casing Pump

10% 15% 30% 30%

LB 1-5 Vacuum pump ( Monoblock ) 25% 10% 20% 30%

LB 1-6 Vacuum pump ( Coupled with out motor ) 10% 15% 30% 30%

LB 1-7-a Vertical Turbine pump (upto 6 stage)( Without motor) 60% 15% 30% 90%

LB 1-7-b Vertical Turbine pump (above 6 stages & upto 12stages)( Without motor)

70% 25% 35% 90%

LB 1-8 Conventional sewage pump ( Without motor) 65% 65% 50% 50%

LB 1-9 Submersible sewage pump 20% 40% 40% 10%

LB 2 Motor 20% 15% 20% 25%

LB 3 Transformer

LB 3-1 Up to 315 kVA capacity 70% 20% 35% 90%

LB 3-2 Above 315 to 750 kVA 80% 20% 35% 90%

Page 81: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

LB 4 Valves

LB 4 Sluice Valve , Non return valve , butter fly valve and airvalve

40% 50% 50% 60%

Note 1) Above rates are exclusive of transportation chargesof equipments

2) Rates of re-erection are inclusive of jointing materialsbut excluding cost of fasteners

3) For removing and re-erection of transformer by usingcrane, rates mentioned above are not applicable

Page 82: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Code No Description Unit Supply Rate Rs.

Erection Rate Rs.

Total Amount

Rs.

SECTION 14 - TL [ TOOLS ]

TL 1 D.E. Open Jaw fix spanner 12 piece set Set 630 0 6306 -32 mm

TL 2 Bi-hexagon Ring spanner 12 piece set Set 1098 0 10986-32mm

TL 3 Ball pen hammer with handle Each 284 0 284800 gm

TL 4 Combination side cutting plier Each 208 0 208200 mm KDPE coated

TL 5 Adjustable wrench crome vanadium Each 270 0 270250 mm - 30 mm

TL 6 Pipe wrench stillson pattern carbon steel Each 531 0 531450 mm - 60 mm

TL 7 Pipe wrench stillson pattern carbon steel Each 953 0 953600 mm - 76 mm

TL 8 Screw driver Engineering pattern 6 X 300 mm Each 90 0 90

TL 9 Screw driver Engineering pattern 8 X 200 mm Each 79 0 79

TL 10 Screw driver Engineering pattern 5 X 200 mm Each 56 0 56

TL 11 Screw driver Engineering pattern 5 X 300 mm Each 58 0 58

TL 12 Screw driver with green neon bulb line tester Each 56 0 563.6 X 60 mm

TL 13 Hack saw frame 300 mm size with heavy duty blade Each 64 0 64

TL 14 Tool box fabricated from MS sheet of 18 SWG of size 50 X 30X 30 cm with locking arrangement

Each 1012 0 1012

TL 15 Cold chisels chrome vanadium hexagonal 19/14 Each 139 0 139200 mm

TL 16 Chain pipe wrench IS 54123 -- 210 - 4" Each 3764 0 3764

TL 17 Chain pipe wrench IS 54123 -- 210 - 6" Each 5525 0 5525

TL 18 25 mm dia heavy duty 1.2 m long crow bar Each 190 0 190

TL 19 12 mm size 2 NT capacity wire rope 3 m long with dog bolt 2Nos.

Each 253 0 253

Page 83: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

TL 20 50 mm size G.I. "B" class pipe 1.5 m long with coupling onboth side, for use as lever

Each 228 0 228

TL 21 Central punch Chrome Vanadium steel 175 mm Each 58 0 58

TL 22 Triangular file 300 mm size of "Standard" make Each 317 0 317

TL 23 Half round file of 300 mm size " Standard" make Each 317 0 317

TL 24 Bearing puller three legs -- 8" Each 334 0 334

TL 25 Bearing puller three legs -- 10" Each 437 0 437

TL 26 Bearing puller three legs -- 12" Each 531 0 531

TL 27 Hydraulic flip flop crimping tool suitable for 6 to 500 sq mm sizecable lugs (Usha-Ismail or similar make)

Each 31365 0 31365

TL 28 Hand operated crimping tool with set of dies ranging from 6 to185 sq mm cable lug, in pairs of hand ratches

Each 8855 0 8855

TL 29 Insulator tester ( Megger ) cranking type having metal body ofrange 100 Volts 1000 Ohms.

Each 4072 0 4072

T 30 Earth Tester- 4 terminals of range Each 6263 0 62630-10-100-1000-10000 Ohms

T 31 Tong Tester ( Clip on meter ) of range Each 3075 0 30750-10-30-100-1000 Amps and 0-300-600 Volts

T 32 Engineer's precision steel level of size 300 mm Each 380 0 380

T 33 Precision stainless steel rules 500 mm Each 253 0 253

T 34 Allen Head Wrench Crome Vanadium 10 piece Set 307 0 3076-10mm

T 35 Tubler box spanner set with Tommy bar 8 piece Set 760 0 7606-22mm

T 36 Diagonal cutting pliers 150 mm PVC coated Each 182 0 182

T 37 Long nose pliers carbon steel 200 mm PVC coated Each 175 0 175

T 38 Water pump pliers chrome vanadium Each 255 0 255259 mm - 40 mm

Page 84: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 15 - EC [ ELECTRO CHLORINATION SYSTEM ]

EC Providing, erecting, commissioning & giving test & trial for aperiod of one month including one year free maintenance aftercommissioning of Electro chlorinator capable of generatingchlorine form common salt by electrolysis using electrodes inform of sodium hypo chlorite solution containing 6-8 gms/lit ofavailable chlorine in batch or continuous process and capableof providing 8 hrs storage of hypochlorite in case of powerfailure. The electro chlorinator shall comprise of following.

* Electrolytic cell consisting dimensionally stable electrodesmade from Gr I Titanium sheet with multi metal Oxide coating.

* Electolyzer tank made from PVC -FRP or Acrylic.

* Power pack consisting of transformer rectifier for generatingsuitable DC current from AC supply along with the controlswitch for dosing pumps, etc through MCB's contacts, relaysand wiring.

* Control panel for the electro chlorinator consisting of DCvoltage and current display income phase status unit on-offswitches fuses etc.

* Dosing tank of suitable capacity made from PVC/FRP.

* Dosing pumps of special quality (1W+1S) suitable to handlehypo chlorite solution.

* Entire chlorine solution pipeline shall be of PVC

Chlorine test kit suitable to measure residual chlorine up to5ppm.

EC 16-1 25 gms / hr Each 176985 13640 190625

EC 16-2 50 gms / hr Each 262200 20205 282405

EC 16-3 100 gms / hr Each 464312 35780 500092

EC 16-4 150 gms / hr Each 518938 39988 558926

EC 16-5 250 gms / hr Each 622725 47987 670712

EC 16-6 350 gms / hr Each 731975 56406 788381

Page 85: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

EC 16-7 500 gms / hr Each 928625 71559 1000184

EC 16-8 750 gms / hr Each 1178000 90775 1268775

EC 16-9 1000 gms / hr Each 1431175 110285 1541460

EC 16-10 1500 gms / hr Each 1802625 138907 1941532

EC 16-11 2000 gms / hr Each 2026588 156165 2182753

Page 86: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

SECTION 16 - GC [ AUTOMATIC GAS CHLORINATION SYSTEM ]

GC Providing, Erecting commissioning & giving test and trial including one year supervision of the system in day shift (General shift) and one year free maintenance of fully automatic gas chlorination system confirmation to all applicable NEC and Compressed Gas Associations recommendations and comprising of following

* Automatic Vacuum operated Chlorinator unit of capacity as mentioned below with Actuator rotameter, injector, vacuum tubing special PVC Piping for Chlorine solution & suitable booster pumps(1W+1S) with GI piping valves, fittings etc.

* Automatic Switchover type vacuum regulators(2 nos.) installed on tonners with suitable mounting & showing tonner status indication as standby, empty & in use.

* Auto Control Panel of suitable capacity ,wall mounted industrial type with voltmeter, ammeter, starter MCB indicating lamps having automatic operation.

* Microprocessor based Multi functional controller with digital & graphical display.

* Online residual Chlorine Analyser without need of reagent utilizing unique, internally buffered sensor.

* Gas leak & temperature detection two channel measuringsystem designed for gas and temperature monitoring in up totwo rooms with necessary wiring & battery backup cum voltagestabilizer system of suitable capacity with batteries.

* Preventing maintenance kit for injector, Rotameter & Vacuumregulator.

GC 16-1 4 kg / hr ( 200PPD ) Each 1324112 159058 1483170

GC 16-2 10 kg / hr (500 PPD) Each 1385862 159058 1544920

SECTION 17 - WM [ WATER METERS ]

WM 1 Mechanical Type Meters.

Page 87: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

A) Domestic Meters

Providing, installing and giving satisfactory field testing ofDomestic water meter, horizontal inferential single or multijettype with magnetic drive and dry dial suitable for ambient 50º CTemperature duly sealed against tampering complete withcouplings at both ends and conforming to class B as per IS779/1994 (VI Revision) with ISI mark along with manufacturer'stest certificate and guarantee certificate, including cost of allmaterials and labour.

a) I S I mark as per IS 779/1994 (without remote reading facility)

1 15 mm dia No 823 132 9552 20 mm dia No 1872 132 20043 25 mm dia No 2654 132 27864 40 mm dia No 5813 132 5945

b) E E C mark(with remote reading facility) ( Single Jet )1 15 mm dia No 1852 132 19842 20 mm dia No 2013 132 2145

c) E E C mark(without remote reading facility) (Single jet )

1 15 mm dia No 966 132 10982 20 mm dia No 1489 132 1621

d) E E C mark (without remote reading facility) (Multi jet) 1 15 mm dia No 2042 132 21742 20 mm dia No 2404 132 25363 25 mm dia No 4206 132 43384 40 mm dia No 8003 132 8135

e) E E C mark (suitable for remote reading attachment) (Multi jet)

1 15 mm dia No 3168 132 33002 20 mm dia No 3496 132 36283 25 mm dia No 5326 132 54584 40 mm dia No 9122 132 9254

B) Bulk Meters.Providing, installing and giving satisfactory field testing offlanged ends Bulk water meter of following type and asmentioned below in (a) and (b) with FGI-250 cast iron body,class "B" confirming to IS : 2373 or as per ISO- 4064, markedto read in metric system, alongwith manufacturer's test andguarantee certificate including cost of all materials and labourwith ISI mark or EEC mark.

a) Enclosed type as per IS 2373

Page 88: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

1 50 mm dia No 5106 279 5385

2 80 mm dia No 6163 682 6845

3 100 mm dia No 9040 967 10007

4 150 mm dia No 13544 1509 15053

b) Removable mechanism type as per IS2373

1 200 mm dia No 29961 1612 31573

2 250 mm dia No 57552 2125 59677

3 300 mm dia No 76056 2754 78810

4 400 mm dia No 119393 3764 123157

5 500 mm dia No 155330 4422 159752

c) E E C mark Removable mechanism type(without remote reading facility)as per ISO 4064

1 50 mm dia No 17846 279 18125

2 80 mm dia No 19829 682 20511

3 100 mm dia No 21811 967 22778

4 150 mm dia No 27701 1509 29210

5 200 mm dia No 36503 1612 38115

6 250 mm dia No 87878 2125 90003

7 300 mm dia No 176658 2754 179412

8 400 mm dia No 272798 3764 276562

9 500 mm dia No 324473 4422 328895

d) E E C mark Removable mechanism type(suitable for remote reading attachment) as per ISO 4046

1 50 mm dia No 19078 279 19357

2 80 mm dia No 21031 682 21713

3 100 mm dia No 23074 967 24041

4 150 mm dia No 28842 1509 30351

5 200 mm dia No 37736 1612 39348

6 250 mm dia No 89081 2125 91206

7 300 mm dia No 177859 2754 180613

Page 89: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

NOTE 1) The domestic and bulk water meter shall be suitable forwater, minimum, maximum and transitional flow conforming toIS 779-(1994-6th edition), I S 2373 or ISO-4064 as applicableand shall be installed so as to have laminar flow with piperunning full.

2) Pressure rating (maximum working pressure 16 Kg. sqcm)suitable for forward and reverse flow.

3) Strainers (also called as filters or dirt boxes) arerecommended for installation upstream of the water meter at alength not less than 12D - D is diameter of pipe)

4) For tapers, non-return valves, specials, pumps the metershall be installed at a distance of not less than 15 D (D isdiameter of pipe) downstream i.e. in the direction of flow.

5) The cost of cutting existing pipe, welding flanges,excavation, construction of chamber is not included in aboverates.

6) Cost of Strainer (Filter/dirt box ) is not included in aboverates.

7) Guarantee period shall be12 months.

8) The rates are inclusive of all taxes , erection andcommissioning.

9) Octroi charges are not included in above rates and shall beas per actuals which will be included wherever in estimates formeter but not in tenders.

WM 2 Strainers (Filter or Dirt Box)

Providing, and fixing Strainer for water meters including cost ofall material and labour.

a) Brass Forged Strainer "Y" Type with screwed ends1 15 mm dia No 442 68 510

2 20 mm dia No 662 68 730

3 25 mm dia No 934 68 1002

4 40 mm dia No 1699 68 1767

b) C.I. Strainer "T" (Basket) Type with flanged endsC.I. Strainer "T" (Basket) Type with flanged ends and withstainless steel or brass mesh with openings of 2.5. Mm to 3mm and suitable for operating pressure of 16 Kg./cm2 and testpressure of 24 Kg./cm2

Page 90: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

1 50 mm dia No 3948 279 4227

2 80 mm dia No 5706 682 6388

3 100 mm dia No 8151 967 9118

4 150 mm dia No 14943 1509 16452

5 200 mm dia No 28650 1612 30262

6 250 mm dia No 46186 2125 48311

7 300 mm dia No 64798 2754 67552

8 400 mm dia No 122124 3764 125888

9 500 mm dia No 163193 4422 167615

NOTE 1) The cost of cutting existing pipe, welding flanges excavation,construction of chamber is not included in above rates.

2) Octroi charges are not included in above rates and shall beas per actuals which will be included wherever applicable inestimates for meter but not in tenders.

WM 3 Ultrasonic Flow Meter:

Providing, installing and giving satisfactory test & trial ofUltrasonic Flow meter of ISO working on 85 -260 V AC, 50 HZelectric power supply of following type working on time of flightprinciple suitable for satisfactory continuous operation in allseasons & with following accessories, working conditions,specifications & duly tested as specified below :

a) Ultrasonic Clamp-on portable type Flow Meter (SingleChannel)

Providing, installing and giving satisfactory test & trial ofultrasonic clamp on portable type flow meter working onconditions & specifications, calibration, inspection, testing,training, guarantees and manufacturers test certificate/declaration copy along with accessories as mentioned abovealong with accessories like

No 348611

a) Magnetic Clamps-1 Pair &

b) Suitable carrying case-1 No.

Page 91: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

b) Ultrasonic Clamp-on Fixed type Flow Meter (SingleChannel)

Providing, installing and giving satisfactory test & trial ofultrasonic clamp on Fixed type flow meter working onconditions & specifications, calibration, inspection, testing,training, guarantees and manufacturers test certificate/declaration copy along with accessories as mentioned in a (1)to (14) below.

No 340000

c) Ultrasonic Insertion Fixed type Flow Meter (SingleChannel)

Providing, installing and giving satisfactory test & trial ofultrasonic Insertion Fixed type flow meter working on conditions& specifications, calibration, inspection, testing, training,guarantees and manufacturers test certificate/ declaration copyalong with accessories as mentioned in a (1) to (14) below &with inbuilt assembly to fix the insertion type transducer on thepipeline.

No 325000

A) Mandatory Accessories:

1) Integrated signal converter transmitter enclosed in die castaluminum case / any anticorrosive material confirming to IP-65or better - 1 No.

2) Pair of transducers (Sensors) confirming to IP-68 or betterwith junction boxes - 1 No.

3)Stainless steel straps for mounting clamp on type sensors - 2Nos. (only required for category A,B)

4) Grease count plant, 100 ml : Bottle - 5 Nos. (only requiredfor category A,B)

5) Signal & power cables for each transducer -50 Mtrslength/each (insertion type flow meter) & 10 mtrs length /each(portable type flow meter)

6) a) for fixed type flow meter-UPS working on 230 V AC, 50Hz power supply suitable for 12 hrs continuous operation.-1 No.(only required for category B,C) b) Built in portable type battery back up for minimum 5 Hrscontinuous operation with spare battery and separate batterycharger working on 230 V AC, 50 Hz power supply for chargingbattery- 1 No. (only required for category A) c) Aluminium / anticorrosive carrying case for flow meter and allaccessories (only required for category A)

Page 92: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

7)Data storage capacity with built in or separate for date, time,actual flow rate, totaliser & error messages if any with storagecapacity of 120 days and at 5 minutes interval data loggingalong with local indication and necessary cables and softwareto download data to laptop -1 No

8) Dot matrix printer of EPSON, WIPRO, WEP or HewlettPackard make with built in or separate printer interface unit forprinting of stored data with online / offline printing facility -1 No.

9) Proper earthing shall be provided for protection against highvoltage surge (only required for category B,C)

10) Suitable over voltage protection unit for protection ofinstrument from higher voltage (upto 275 V-300 V AC)

11) M.S. sensor protection boxes with suitable size for aboveground lines where construction of chamber is not possible.(only required for category B,C)

12) Magnetic clamp for metallic pipe lines and Nylon / SSstrips, chain arrangement for clamp on sensors suitable forpipe diameters 50 mm to 3000 mm (only required for categoryA,B)

13) Battery powered ultrasonic thickness gauge along withcharger, test sample, coupling agent and carrying case suitablemeasuring thickness of 1 mm to 100 mm (only required forcategory A)

14) 5 meter steel measurement tape with level bottle (onlyrequired for category A)

B) Additional/Optional Accessories:

1) Pressure transducer, which should be connected to thepressure lead of dual cannel data loggers, compatible with thedual channel loggers of appropriate type with a pressure rangeof 5m to 150 m with an accuracy of not less than +/-1% to besupplied and installed at the upstream of the flow meters.

No 25000

2) Fixing flow meter transmitter to internal walls of buildings in asuitably designed panel cabinet with proper lockingarrangement with glass window on front door for seeing thereadings of flow transmitter and data logger without opening ofthe panel cabinet. It should house complete ancillaries andincluding the provision for connection of electrical power supplyfrom nearby apparatus. The panel cabinet shall be prewiredand with suitable gland entries.

No 26500

Page 93: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

3) Laptop with core 2 duo processor, 2 GB RAM, 256 GB HDD,DVD writer, web cam, 14" LCD screen with carrying case,windows XP professional branded with necessary software &upload data should be provided.

No 30000

4) The portable Device shall be compatible to the logger & flowmeters for the purpose of retrieving data & resetting the dataloggers. The portable device should be simple to operate &robust in design. The portable hand held units shall havesufficient memory to download & store data up to 6 flowmeters. Hand held units shall be supplied with necessarycommunication leads for data logger to hand held & hand heldto commercial PC. All the necessary software for download &upload to be provided.

No 30000

5) Remote monitoring system for data acquisition/data transfer& alert SMS /warning based on GSM technology with completehardware like wireless communication device, cables,necessary software system (BOM with each GSM system is asgiven below) for each flow meter excluding data SIM card & itsregular billing.

Set 50000

a) Wireless communication device to communicate betweencentral computer & flow transmitter installed at remote site withGSM based system

b) DA Scheduler software for CSV file storage and dataacquisition

c) Cables for pressure, flow & totalized details from transmitterto field gate system (10 Mtrs with each GSM / GPRS system)

d) OPC Software to be installed in central PC for SCADAinterface as may be necessary

e) Commissioning charges for each locations.

f) Customized page with Java Applets XML-Data importsoftware for online MIMIC

g) R.F. Module / Cyble for operation of AMR shall be taken as Rs.7000 per meter.

h) RTU ( Remote Terminal Unit) for each meter shall be taken as Rs.12000 per meter.

6) Sensor/Transmitter cable of following specification:

Page 94: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

3 x 0.38 mm² PVC cable with common branded copper shield7mm dia and individually shielded cores-with empty pipedetection 9 EPD

Mtr. 230

4 x 0.38 mm² PVC cable with common branded copper shield7 mm dia and individually shielded cores.

Conductor resistance : </=50 Ohm/Km

7) Conduit pipe (PVC / HDPE plumbing) 32 mm diameter withsuitable digging, laying and concealing the duct

Mtr. 18

8) Other Civil Works:a) Flow meter chamber work with suitable man hole forentering the chamber & removal of flow meter for maintenancein future,

No As Per Civil CSR

b) Construction of meter room with roof slab (100 mm) brickmasonry with pile foundation of minimum 1.5 M x 1.5 M or asper instruction from Engineer-in -Charge with RCCbeam/column minimum 0.15mx0.15m size with steel door &cement jali ventilator and plinth height of minimum 0.5 M aboveGL and roof slab shall be 2.1 M from plinth inner and outerplaster with water proof cement painting

No As Per Civil CSR

C) Working Condition & Specifications

a) Water Temp : 10º to 50º C

b) Water Quality: Raw water, turbid in nature. Potablechlorinated water

c) Operating pressure:10-15 Kg./cm²

d) Pipeline MOC : CI, DI, MS with /without mortar lined, Non-metallic pipes.

e) Pipe diameter :> 1000 mm -4000 mm

f) Flow -Up to 300 Mld

g) Pipe condition: Pipe shall be running full.

h) Ultrasonic flow meters shall be designed, manufactured tointernational standards with accuracy of +/-2% of actual flow.The supplier should have full ISO -9000 series accreditation &facility for fully traceable calibration flow rig as per internationalstandard

i) Functional details: Freely programmable.

j) Measurement - Volumetric flow rate, totalized flow.

Page 95: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

k) Flow direction- Forward & Reverse.

l) Display- LCD display with suitable lines, digits, segments,markers, for identification of current output. The digit shall beclear, bold & can be read from 1 Mtrs distance.

m) Out put- for current-4 m A-20mA HART (active/passive) formeasuring flow in pipeline. Frequency output shall be 1 khz,Open collector, passive.

n) Status output-open collector.

o) Meter shall be suitable for remote facility.

p) Power supply-85-260 V AC(45-65 Hz)/20-55 V AC (45-65Hz)/16-62 V DC.

q) Galvanic isolation- input & output galvanically isolated frompower supply from the sensor and from each other

r) Instruments must carry "CE" mark.

s) Functionality verification check should be possible inlineusing recommended software tools.

t) Future upgradation to field bus foundation. Profibus shouldbe possible with minimal changes.

D) Calibration, Testing & Inspection

The 10% of total supply quantity shall be inspected and tested.The flowmeter shall be calibrated at manufacturers place asper international standard given above.Manufacturer havingNABL lab accrediation ,the calibration testing shall be witnessby Third party approved by MJP .The manufacturer not havingNABL lab accrediation shall be tested at FCRI/CWPRS/IDEMIetc. for which third party inspection is not required.

E) Manufacturer's Guarantee, Certificate & training

Page 96: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

The flow meters shall be supplied with manufacturer's testcertificate as per international standards given above.calibration certificates. 12 months guarantee for the trouble freeperformance and given Adequate training for handling flowmeter and installation in field so that trainees can carryout thejob independently.

F) 36 Month's O & M towards flow meter & accessories:

The O & M shall be decided based on " planned preventivemaintenance" Program (PPM) to be finalized with suppliers withfollowing service included (but not limited) for 36 monthsbeyond standard warranty terms as per H) However for projectcases user must discuss with supplier for lumpsum O & M costfor the overall project.Planned Preventive Maintenance (PPM):

a) Regular visit to the flow meters (once in 2 month to checkthe healthyness of instruments)

b) Repairs/ replacement of components/spare parts as may benecessary during the flow meter inspection.

c) Free replacement of the spare parts and consumables asnecessary.

d) Emergency visit to site within 48 hours for attending anymajor trouble shooting and break downs.

e) Technical training/ trouble shooting training to the user bythe supplier.

f) Providing complete technical details on instrument withnecessary manuals

G) General Terms & Conditions

a) General Specifications with accessories (except required foreach type of meter specified) working conditions, mandatoryaccessories, calibration, inspection testing manufacturers testcertificates, installation and commissioning, guarantee andtraining shall be common for all flow meters as mentionedabove. The Additional/ optional accessories mentioned aboveto be considered as per project and site requirements.

b) The above prices are inclusive of import duty as applicablein year-2006

Page 97: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

c) The above prices inclusive of counter vailing duty (CVD) asapplicable in year 2006 with education cess of 2% on CVD .Also includes necessary charges for customs clearancesclearing and forwarding charges in India.

d) The above prices are includes local inland transportationfrom manufacturer's godown /custom's godown upto sitesanywhere in Maharashtra.

e) The above prices includes necessary packing & forwardingcharges as applicable for each project

f) VAT @ 12.5% currently applicable are included in aboverates.

g) Octroi charges are not included in above rates and shall beas per actuals which will be included wherever applicable inestimates for meter up to site storage

h) The above prices are inclusive of Marine & inland insuranceof flow meters up to site storage

i) Meter shall be procured with prior permission from concernedsuperintending Engineer/Chief Engineer.

j) Planning for installation for meter shall be done duringexecution of pipe work. Straight pipe length of 5 D or more onup stream side and 2 D or more on down stream side of meteris necessary (D is diameter of flow meter) The meters shall beinstalled so as to have a laminar flow with pipe running full

WM 4 Full-Bore Electromagnetic Flow Meter:

Manufacture, supply and commission Electromagnetic FlowMeter (EMF), for Raw/Pure water with accuracy 0.5% ofmeasured value & protection as per given specifications forsize 100 mm-1000mm Including sensor, transmitter surgearrestor, cable GI duct if suitable size for 25 mtrs. sensor,transmitter surge arrestor, 25 Mtrs / each flow meter, includingthe pipe cutting, leveling and installation of flow meter in thepipelines with necessary tool tackles, cranes etc., as may berequired at site & based on technical specifications (Annexure-A) attached

a) 100 mm Nominal Diameter Flowmeter No. 153284 3000 156284

b) 150 mm Nominal Diameter Flowmeter No. 164445 3646 168091

c) 200 mm Nominal Diameter Flowmeter No. 195590 3860 199450

d) 250 mm Nominal Diameter Flowmeter No. 215737 4483 220220

e) 300 mm Nominal Diameter Flowmeter No. 246764 5487 252251

Page 98: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

f) 350 mm Nominal Diameter Flowmeter No. 342656 6872 349528

g) 400 mm Nominal Diameter Flowmeter No. 388915 7924 396839

h) 450 mm Nominal Diameter Flowmeter No. 415530 9069 424599

i) 500 mm Nominal Diameter Flowmeter No. 485460 9491 494951

j) 550 mm Nominal Diameter Flowmeter No. 537570 10340 547910

k) 600 mm Nominal Diameter Flowmeter No. 559890 10705 570595

l) 700 mm Nominal Diameter Flowmeter No. 601560 11384 612944

m) 750 mm Nominal Diameter Flowmeter No. 644580 12071 656651

n) 800 mm Nominal Diameter Flowmeter No. 722880 13362 736242

o) 900 mm Nominal Diameter Flowmeter No. 823680 15002 838682

p) 1000 mm Nominal Diameter Flowmeter No. 882280 17500 899780

A) Mandatory Accessories:

1) The sensor should be as per IP-68 protection & with flangesof up to PN 10 rating from CS-1 No.

2) The sensor coil housing shall be IP-68.This protectedagainst external magnetic field.

3) The transmitter shall have one current 4 m A-20 mA output.

4) The current output shall be galvanically / optically isolated. Itshall be fitted with switched mode power supply capability 85-260 V & 45-65 Hz to cope with power transients withoutdamage.

5) Signal & power cables shall be of 50 Mtrs length/each.

6) Conduit pipe ( PVC Plumbing schedule 4 ) 25 mm diameterwith suitable rating of cable with digging, laying & concealed theduct - 25 mtrs/each.

7) UPS working on 230 V AC, 50 Hz power supply suitable for12 hrs continuous operation-1 No.

8) Data storage capacity with built in or separate for date time,actual flow rate, totaliser & error messages if any with storagecapacity of 120 days at 1 hour interval data logging-1 No.

9) 21",80 column Dot matrix printer of EPSON, WIPRO, orHewlett Packard make with printer interface unit for printing ofstored data as per 8 )-1 No.

10) Proper earthing shall be provided for protection againsthigh voltage surge.

Page 99: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

11) Suitable over voltage protection unit for protection ofinstrument from higher voltage (upto 275 V-300 V AC)

B) Additional/Optional Accessories:

1) Pressure transducer, which should be connected to thepressure lead of dual channel data loggers & should becompatible with the dual channel loggers. The pressuretransducer should be of appropriate type with a pressure rangeof 5 m to 300 m with an accuracy of not less than 1% to besupplied and installed at the upstream of the flow meters.

No 25000

2) Fixing flow meter transmitter to internal walls of buildings in asuitably designed panel cabinet with proper lockingarrangement with glass window on front door for seeing thereadings of flow transmitter and data logger without opening ofthe panel cabinet. It should house complete ancillaries andincluding the provision for connection of electrical power supplyfrom near by apparatus. The panel cabinet shall be prewiredand with suitable gland entries.

No 26500

3) Laptop with core 2 duo processor, 2 GB RAM, 256 GB HDD,DVD writer, web cam, 14" LCD screen with carrying case,windows XP professional branded with necessary software &upload data should be provided.

No 30000

4) The portable device shall be compatible to the logger & flowmeters for the purpose of retrieving data & resetting the dataloggers. The portable device should be simple to operate &robust in design. The portable hand held units shall havesufficient memory to download & store data upto 6 flow meters.Hand held units shall be supplied with necessarycommunication leads for data logger to hand held & hand heldto commercial PC. All the necessary software for download &upload to be provided.

No 30000

5) Providing and supplying DI/CI in-line adapters withmechanical joints & concentric tapers with flanges along withsuitable gasket of SBR, complete with mild steel nut boltscoated or otherwise protected from rusting and suitable for DIpipes as may be necessary for the following line size x flowmeter sizes. Applicable only for Sr.No. (2) ElectromagneticFlow meters.

As per PWD CSR

Page 100: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

6) Remote monitoring system for data acquisition/data transfer& alert SMS /warning based on GSM technology with completehardware like wireless communication device, necessarysoftware system is as given below for each flow meterexcluding data SIM card & its regular billing.

Set 50000

Note : a) The rates are for the entire system & not for theindividual meter. For RTU of individual meter, separate rateshall be evaluated & got approved from the competentauthority.b) Wireless communication device to communicate betweencentral computer & flow transmitter installed at remote site withGSM based systemc) DA Scheduler software for CSV file storage and dataacquisition d) OPC Software to be installed in central PC for SCADAinterface as may be necessary e) Commissioning charges for each locations.f) R.F.Module / Cyble for operation of AMR shall be taken as Rs.7000 per meter.g) RTU ( Remote Terminal Unit) for each meter shall be taken as Rs.12000 per meter.

7) Sensor/Transmitter cable of following specification:3 X 0.38 mm² PVC cable with common, braided copper shield (-7mm dia) and individually shielded cores- with empty pipedetection 9 EPD): 4X0.38 mm² PVC cable with common,braided copper shield (-7 mm dia) and individually shieldedcores-conductor resistance: </=50 Ohm/Km-Capacitance:core/shield: </=420 pF/m.-permanent operating temperature:-20.........+80 Deg C

Mtr. 230

8) Coil cable of following specifications :3 X 0.75 mm² PVC cable with common, braided copper shield (-7mm dia) Conductor resistance : </=37 Ohm/Km-Capacitance:core/core, shield grounded :</=120 pF/m.-permanent operatingtemperature:-20+/-80 Deg C

Mtr. 210

9) Pressure Transmitter able of following specifications :3 X 0.75 mm² PVC cable with common, braided copper shield (-7mm dia) Conductor resistance : </=37 Ohm/Km-Capacitance:core /core, shield grounded :</=120 P F/m- permanentoperating temperature: -20……+80 Deg C.

Mtr. 210

10) GI Duct of 100 mm with suitable rating: for layingunderground with all the necessary fittings, joints etc., forhousing the cables between sensor & transmitter. The cableshall be installed in a suitable GI duct to minimize the risk ofdamage during excavation. All cable laid at a minimum depth of0.5 M below the ground. GI duct shall be of 100 mm dia.

Mtr. 332

Page 101: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

11) Other Civil Works:a) Flow meter chamber work with suitable manhole for enteringthe chamber & removal of flow meter for maintenance in future,

No As Per Civil CSR

b) Construction of meter room with roof slab (100 mm) No As Per Civil CSR

C) Working Condition & Specifications

a) Water Temp : 10 Deg to 50 Deg

b) Water Quality: Raw water, turbid in nature. Potablechlorinated water

c) Operating pressure:10-15 Kg./cm²

d) Pipeline MOC:CI,DI,MS with /without mortar lined, Non-metallic pipes.HS & PSC

e) Pipe condition: pipe shall be running full.

f) Full-Bore Bi-directional Electromagnetic Flow meters shall bedesigned, manufactured & calibrated to international standardswith accuracy of +/-0.5% of reading.

g) The supplier should have full ISO-9000 series accreditation& full it aceable calibration methods to either of the two primarystandard means of testing i.e. mass (ISO 4185) or volume (ISO6817)

h) Each meter shall be wet calibrated at the place ofmanufacturing with 3 point calibration at sufficient flow rates.The testing facility shall be duly accredited in accordance toISO 17025

i) The sensor shall be of standard length as per ISO 13359

j) The sensor shall have built in stainless steel GroundingElectrode & Empty pipe Detection. Any ground probes, rings,flanges or straps will be strictly not acceptable.

k) The liner material shall be either Certified Hard Rubber (HR)with Drinking water Approval or Polyurathane (PU) & teflon.

l) The sensor & transmitter shall be capable of working intropical environment.

m) The Meter body shall be flanged or with custom connectoras per the requirement. Wafer designs will not be acceptable.

Page 102: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

n) The housing of flow meter shall be Die castAluminum/painted steel with suitable anti-corrosive paint.

o) The flow meter shall be suitable for both submergence aswell as burial installation & shall withstand all necessary naturalshocks.

p) The transmitter & sensor shall not have any EMIinterferences in the actual flow meter reading.

q) The transmitter shall be wall-mounted type with a 2-linedisplay for the indication of Actual Flow rate & Totalized value.The material enclosure shall be sufficient to guarantee 5 yearoperation life.

r) The transmitter shall be capable of fully programmed withpush button/using HART communicator. It shall have a set-upmenu so that all relevant parameters may be user-set from theself-prompting driven menu. The repeatability shall be 0.1% orreading or better, minimum+/-0.5mm/s

s) The transmitter shall have one scalable pulse output. Onecurrent (HART) output. The current output shall be galvanicallyisolated. It shall be fitted with switched mode power supplycapability 85-260 V & 45-65 Hz to cope with power transientswithout damage.

t) The totalizer value shall be protected by EEPROM duringpower outage, and utilizes an overflow counter.

u) The flow meter shall be provided with remote display suitable without any signal booster/amplifier for distance upto 150 Mtrs.for online MIMIC

D) Calibration, Testing & Inspection

The 10% of total supply quantity shall be inspected and tested.The flowmeter shall be calibrated at manufacturers place asper international standard given above.Manufacturer havingNABL lab accrediation ,the calibration testing shall be witnessby Third party approved by MJP .The manufacturer not havingNABL lab accrediation shall be tested at FCRI/CWPRS/IDEMIetc. for which third party inspection is not required.

E) Manufacturer's Guarantee, Certificate & training The flow meters shall be supplied with manufacturer's testcertificate as per international standards given above.calibration certificates. 12 months guarantee for the trouble freeperformance and given adequate training for handling flowmeter and installation in field so that trainees can carryout thejob independently.

F) 36 Month's O & M towards flow meter & accessories

Page 103: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

The O & M shall be decided based on "planned preventivemaintenance" Program (PPM) to be finalized with suppliers withfollowing service included (but not limited) for 36 monthsbeyond standard warranty terms as per H) However for projectcases user must discuss with supplier for lumpsum O & M costfor the overall project.

Planned Preventive Maintenance (PPM):a) Regular visit to the flow meters (once in 2 month to checkthe healthyness of instruments)b) Repairs/ replacement of components/spare parts as may benecessary during the flow meter inspection.c) Free replacement of the spare parts and consumables asnecessary.d) Emergency visit to site within 48 hours for attending anymajor trouble shooting and break downs.e) Technical training/ trouble shooting training to the user bythe supplier.f) Providing complete technical details on instrument withnecessary manuals

G) General Terms & Conditions

a) General Specifications with accessories (except required foreach type of meter specified) working conditions, mandatoryaccessories, calibration, inspection testing manufacturers testcertificates, installation and commissioning, guarantee andtraining shall be common for all flow meters as mentionedabove. The additional/ optional accessories mentioned aboveto be considered as per project and site requirements.

b) The above prices are inclusive of import duty as applicablein year-2006c) The above prices inclusive of counter vailing duty (CVD) asapplicable in year 2006 with education cess of 2% on CVD .Also includes necessary charges for customs clearancesclearing and forwarding charges in India.d) The above prices are includes local inland transportationfrom manufacturer's godown /custom's godown upto sitesanywhere in Maharashtra.e) The above prices includes necessary packing & forwardingcharges as applicable for each projectf) VAT @ 12.5% currently applicable are included in aboverates g) Octroi charges are not included in above rates and shall beas per actuals which will be included wherever applicable inestimates for meter up to site storageh) The above prices are inclusive of Marine & inland insuranceof flow meters up to site storagei) Meter shall be procured with prior permission from concernedsuperintending Engineer/Chief Engineer.

Page 104: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

j) Planning for installation for meter shall be done duringexecution of pipe work. Straight pipe length of 5 D or more onup stream side and 2 D or more on down stream side of meteris necessary (D is diameter of flow meter) The meters shall beinstalled so as to have a laminar flow with pipe running full

Note :- While preparing the estimate of water meter /flowmeter, 7% of amount of supply rate of water meter /flowmeter shall be added for comprehensive maintenance ofwater for 2 years after the guarantee period of one year.

Page 105: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Sr. No.

Conductor Size

in Sq.mm.

no. no. 2 Core Multi Core 2 Core Multi Core Single Core Multi Core1 1.5 18 16 16 14 15 14

2 2.5 25 21 21 18 20 19

3 4 32 28 27 23 27 26

4 6 40 35 34 30 46 42

5 10 55 46 45 39 46 42

6 16 70 60 58 50 62 57

7 25 90 76 76 63 80 71

8 35 110 982 92 77 102 91

9 50 135 110 115 95 138 120

10 70 160 135 140 115 214 165

11 95 190 165 170 140 254 200

12 120 210 185 190 155 300 225

13 150 240 210 210 175 340 -

14 185 275 235 240 200 390 -

15 240 320 275 275 235 460 -

16 300 355 305 305 260 - -

17 400 385 335 345 290 - -

HP Vs Current

Approximate full load current for submersible pump motor, 3 phase, 50 cycles, 415-425 V.

HP AMP HP AMP5.0 7.5 25.0 35.6

7.5 11.0 30.0 42.3

10.0 14.9 35.0 50.4

12.5 18.9 40.0 62.1

15.0 22.5 50.0 67.5

17.5 25.2 55.0 73.8

20.0 28.4

CABLE SECTION CHART

Aluminium Conductor PVC insulated cable Plain Copper Conductor PVC insulated flexible cable

(Maximum) in Ground (Minimum) in Duct Current Carrying Capacity in Amp

Page 106: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Sr. No.

Conductor Size

Approximate Wt. of Cable

Approximate Wt. of Cable

in Kg/Mtr. Kg/Mtr.

In Ground In Air In Ground In Air1 25 - - 93 100 - -

2 35 115 140 110 120 3.470 59

3 50 135 170 130 145 3.830 62

4 70 135 210 150 180 4.330 66

5 95 200 255 190 220 4.940 70

6 120 225 295 215 255 5.580 75

7 150 255 335 240 285 6.180 78

8 185 285 385 270 330 6.820 82

9 350 330 455 315 385 8.040 89

10 300 375 520 355 440 9.080 94

11 400 425 610 405 510 10.240 101

12 500 480 700 455 590 12.170 108

13 630 550 830 - - - -

14 800 650 950 - - - -

15 1000 690 1080 - - - -

Note Standard current carrying capacities are mentioned in the table for fixed basic assumptions, however for actual field conditions necessary de-rating factor should be applied for ambient temperature method of laying, etc.

Std. weight and overall dimensions are given in the table and the same should be considered for designing width and size of trench / duct / cable tray for PVC and XLPE cables.

XLPE Cable Selection Chart

Current Carrying Capacity in AMP

Single Core 3 Core

Page 107: MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL … · MAHARASHTRA JEEVAN PRADHIKARAN ELECTRICAL & MECHANICAL CSR 2012-13 ... km (except Matheran) ... PM 1-4-5 30.0 HP Each

Recommended Height of the Pump House

A) For V.T. Pumps

i) Single floor pump house

Sr. No. Pump Floor to corbel

top

Corbel top to roof slab

bottom

Pump floor to bottom of roof

slab Total

Lifting Equipments

1 Upto 50 HP - - 5.5 m Monorail

2 From 51 HP to 150 HP 5 m 1.5 m 6.5 m HOT

3 From 151 HP to 300 HP 5.5 m 1.5 m 7 m HOT

4 From 301 HP to 500 HP 5.5 m 2 m 7.5 m EOT

5 501 HP and above 5.5 m 2.5 m 8 m EOT

ii) Double floor pump house

Generally double floor arrangement shall be provided for the delivery pipes of ;diameter 350 mm or aboveThe height of pump house shall be as below

Pump floor to Panel floor 2.5 mPanel floor to Corbel 5 mCorbel to bottom of roof slab 2.5 m

B) For Centrifugal and Submersible Pumps

Sr. No. Pump Floor to corbel

top

Corbel top to roof slab

bottom

Pump floor to bottom of roof

slab Total

Lifting Equipments

1 Upto 150 HP - - 4 m Monorail

2 From 151 HP to 300 HP 3.5 m 1.5 m 5 m HOT

3 301 HP and above 4 m 2.5 m 6.5 m EOT

HP of Pump

HP of Pump