LT Cable Datasheet
-
Upload
superstarvirgo -
Category
Documents
-
view
225 -
download
2
description
Transcript of LT Cable Datasheet
-
ANUPPUR THERMAL POWER PROJECT PHASE-I (2X600MW)
AT ANUPPUR, MADHYA PRADESH (INDIA)
Owner: MB POWER (MADHYA PRADESH) LTD. 235-B, OKHLA INDUSTRIAL ESTATE, PHASE-III
NEW DELHI 110 020
Owners Consultant:
EPCContractor: LANCO INFRATECH LTD. (EPC DIVISION)
PLOT NO. 404-405, UDYOG VIHAR PHASE-III GURGAON, HARYANA, INDIA
Vendor:
KEC INTERNATIONAL LIMITED
Document Title: Technical Data Sheet
LITL Document No.: LITL-020-ELV-320-S-71933-R3
Vendor Doc. No.
JB / GVC 12-07-2013
12-07-2013
TCE.5657B-EL-CO-700-601
-
LANCO INFRATECH LTD. (EPC DIVISION) PLOT NO. 404-405, UDYOG VIHAR PHASE-III
GURGAON, HARYANA (INDIA)
ANUPPUR THERMAL POWER PROJECT PHASE-I (2X600MW)
AT ANUPPUR, MADHYA PRADESH (INDIA)
LITL Document No.
R3
REVNO.
DATE STATUS INTLS SGN INTLS SGN INTLS SGN INTLS SGN
PRPD. BY CHKD. BY APPR. BY ISSUE
AUTHORISATION
(This document is a property of LIT Ltd. This is not transferable and shall not be used for any purpose other than for which it is supplied)
-
GUARANTEED TECHNICAL PARTICULARS
1 Make
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India India India
3 Type Designation A2XFY(P):FRLS A2XFY(P):FRLS A2XFY(P):FRLS
4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88 IS:7098 pt(1)/88
5 Cable size 3C x 16 Sq.mm 3C x 35 Sq.mm 3C x 70 Sq.mm
6 No. of core 3 3 3
7 Rated voltage 1100 V 1100 V 1100 V
8
Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C
62 104 158
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.
65 102 146
9
Short circuit withstand capacity and duration for one second
a. Conductor 1.51 3.31 6.61
9 Conductor
a.
Material H4 Grade Aluminium (
Class-2 ) to IS: 8130/1984
H4 Grade Aluminium ( Class-2 ) to IS: 8130/1984
H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
b.
No. of strand/Approx diameter of each strand
7/1.72 7/2.52 19/2.14
c. Shape of Conductor Sector Sector Sector
d. Diameter of conductor 4.1 6.1 8.6
e.
Nominal cross section areain sq. mm.
16 35 70
f. Max. D. C. resistance at 20 deg. C
1.91 0.868 0.443
g. Conductor temperature 90 90 90
h. S/C conductor temprature 250 250 250
10 Insulation
a.
Material Cross Linked
Polyethylene(XLPE) as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE)
as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE)
as per IS:7098/I/1988
b. Nominal thickness (in mm) 0.70 0.90 1.10
c. Minimum thickness(in mm) 0.53 0.71 0.89
d. Identification of cores Red,Yellow & Blue Red,Yellow & Blue Red,Yellow & Blue
e. Insulation temperature 90 90 90
f.
Type of extrusion & curing process
Sioplas single Extrusion & Hot Water
Curing
Sioplas single Extrusion & Hot
Water Curing
Sioplas single Extrusion & Hot
Water Curing
g. Diameter over insulation 5.5 7.9 10.8
11 Inner sheath
a. Min. thichkness 0.30 0.30 0.40
-
b. Wrapped or Extruded Extruded Extruded Extruded
c. Colour Black Black Black
d. Approx. dia. Over inner sheath
13.0 17.9 24.0
e.
Material and Type of inner sheath (if required)
PVC Type `ST2' to IS:5831/84
PVC Type `ST2' to IS:5831/84
PVC Type `ST2' to IS:5831/84
f. Filler material
Gaps can be filled by PVC during the extruded PVC
innersheathing wherever applicable.
Gaps can be filled by PVC during the extruded PVC
innersheathing wherever applicable.
Gaps can be filled by PVC during the extruded PVC
innersheathing wherever applicable.
12 Outer sheath
a. Type of Outer sheath Extruded "FRLS" PVC
Type 'ST2' as per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as
per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as
per IS:5831/84 b. Material
c. Colour Black Black Black
d.
Min. thickness of Outer
sheath 1.24 1.40 1.56
e. Tolerance on diameter
2 mm
2 mm
2 mm
13 Armour
a. Material & shape : Galvanised Steel Flat Strip as per IS:3975
Galvanised Steel Flat Strip as per IS:3975
Galvanised Steel Flat Strip as per IS:3975
b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8 4.0 x 0.8
c. Whether galvanized:(Yes/No)
Yes Yes Yes
d.
Diameter of cable over armouring mm):
15.0 19.9 25.9
e. Armour coverage area (%) 90% 90% 90%
f.
Maximum DC resistance at
20C (ohm/km) 4.77 4.16 3.12
g. No of wires/Strips required 8 11 15
14
Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC
1.91 0.868 0.443
b. A.C resistance at 90degC 2.44 1.11 0.567
c. Reactance at 50Hz(App) 0.0815 0.0794 0.0752
d. Capacitance (App) 0.401 0.464 0.490
e. Impedance(App) 2.4414 1.1128 0.572
15 Finished Cable
a.
Diameter over laid up core (Calculated)
12.7 18.4 25.1
b.
Diameter under armor in mm (Claculated)
13.3 19.0 25.9
c.
Diameter over armor in mm (Calculated)
14.9 20.6 27.5
16 Max. Pulling force 3 kg/mm of
Aluminium area 3 kg/mm of
Aluminium area 3 kg/mm of
Aluminium area
17 Cable Drum
a. Material Wooden Wooden Wooden
b. Dimension of drum(App) 950 x 300 x 650 1400 x 600 x 650 1200 x 575 x 650
c. Shipping Weight(App) 608 1088 886.5
-
d. Drum Weight(Without cable) (App)
105 270 220
e. Cable pulling eye yes/No No No No
18 Recommended bending radius
12 times Overall diameter
12 times Overall diameter
12 times Overall diameter
19 Derating Factor Refer Catalogue Refer Catalogue Refer Catalogue
20 Group rating factor Refer Catalogue Refer Catalogue Refer Catalogue
21
Overall dia. of cable (in
mm)(
2mm tolerance) 18 24 30
22
Weight per 1000 metre (in
Kg.) 503 818 1333
23 Standard drum length offered
1000 1000 500
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29% Min. 29% Min. 29%
25a.
Minimum temperature
index(C) Min. 2500C Min. 2500C Min. 2500C
25b. Maximum smoke density rating(%)
Max. 60% Max. 60% Max. 60%
25c Maximum acid gas generation(%)
20% Max. 20% Max. 20% Max.
25d. Flammability test As per IEC-60332-
1/SS-424-1475 As per IEC-60332-
1/SS-424-1475 As per IEC-60332-
1/SS-424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER
LTD" YEAR."
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER
LTD" YEAR."
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER
LTD" YEAR."
27 Marking on Drums As per IS:7098
part(1)/88 As per IS:7098
part(1)/88 As per IS:7098
part(1)/88
28 Type of end sealing PVC End Caps PVC End Caps PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India India India
3 Type Designation A2XWaY:FRLS A2XWaY:FRLS A2XWaY:FRLS
4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88 IS:7098 pt(1)/88
5 Cable size 1C x 16 Sq.mm 1C x 35 Sq.mm 1C x 70 Sq.mm
6 No. of core 1 1 1
7 Rated voltage 1100 V 1100 V 1100 V
8
Continuous current rating for max. conductor temperature:
a.
When laid in air at an ambient Temp. of 50 deg. C 65 109 169
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.
68 102 148
9
Short circuit withstand capacity and duration for one second
a. Conductor 1.51 3.31 6.61
9 Conductor
a.
Material
H4 Grade Aluminium ( Class-
2 ) to IS: 8130/1984
H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
b.
No. of strand/Approx diameter of each strand
7/1.72 7/2.52 19/2.14
c. Shape of Conductor Compacted Circular Compacted Circular Compacted Circular
d. Diameter of conductor 5.0 6.8 9.6
e.
Nominal cross section areain sq. mm.
16 35 70
f. Max. D. C. resistance at 20 deg. C
1.91 0.868 0.443
g. Conductor temperature 90 90 90
h. S/C conductor temprature
250 250 250
10 Insulation
a.
Material
Cross Linked Polyethylene(XLPE)
as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE)
as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE) as per IS:7098/I/1988
b. Nominal thickness (in mm)
1.00 1.20 1.40
c. Minimum thickness(in mm)
0.80 0.98 1.16
d. Identification of cores Black Black Black
e. Insulation temperature 90 90 90
f.
Type of extrusion & curing process
Sioplas single Extrusion & Hot
Water Curing
Sioplas single Extrusion & Hot
Water Curing
Sioplas single Extrusion & Hot Water Curing
-
g. Diameter over insulation 7.0 9.2 12.4
11 Inner sheath
a. Min. thichkness N.A N.A N.A
b. Wrapped or Extruded N.A N.A N.A
c. Colour N.A N.A N.A
d. Approx. dia. Over inner sheath
N.A N.A N.A
e.
Material and Type of inner sheath (if required)
N.A N.A N.A
f. Filler material N.A N.A N.A
12 Outer sheath
a. Type of Outer sheath Extruded "FRLS"
PVC Type 'ST2' as per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as
per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as per
IS:5831/84 b. Material
c. Colour Black Black Black
d.
Min. thickness of Outer
sheath 1.24 1.24 1.24
e. Tolerance on diameter
2 mm
2 mm
2 mm
13 Armour
a. Material & shape : Hard Drawn
Aluminium Round Wire as per IS:8130
Hard Drawn Aluminium Round Wire as per IS:8130
Hard Drawn Aluminium Round Wire as per
IS:8130
b. Diameter of wire : 1.4 1.4 1.4
c. Whether galvanized:(Yes/No)
N.A N.A N.A
d.
Diameter of cable over armouring mm):
10.2 12.3 15.4
e. Armour coverage area (%)
90% 90% 90%
f.
Maximum DC resistance at 20C (ohm/km) 1.35 0.76 0.99
g. No of wires/Strips required
14.0 19.0 25.0
14
Electrical Parameter at maximum Operating
temperature
a. Max. DC resistance at 20degC
1.91 0.868 0.443
b. A.C resistance at 90degC 2.44 1.11 0.567
c. Reactance at 50Hz(App) 0.101 0.097 0.091
d. Capacitance (App) 0.371 0.45 0.512
e. Impedance(App) 2.4421 1.1142 0.5743
15 Finished Cable
a.
Diameter over laid up core (Calculated)
N.A N.A N.A
b.
Diameter under armor in mm (Claculated)
6.5 9.1 12.2
c.
Diameter over armor in mm (Calculated)
9.3 11.9 15
16 Max. Pulling force 3 kg/mm of
Aluminium area 3 kg/mm of
Aluminium area 3 kg/mm of Aluminium
area
17 Cable Drum
a. Material Wooden Wooden Wooden
-
b. Dimension of drum(App) 950 x 300 x 650 950 x 300 x 650 950 x 300 x 650
c. Shipping Weight(App) 316 408 559
d. Drum Weight(Without cable) (App)
105 105 105
e. Cable pulling eye yes/No No No No
18 Recommended bending radius
15 times Overall diameter
15 times Overall diameter
15 times Overall diameter
19 Derating Factor Refer Catalogue Refer Catalogue Refer Catalogue
20 Group rating factor Refer Catalogue Refer Catalogue Refer Catalogue
21
Overall dia. of cable (in mm)(
2mm tolerance) 13 16 19
22 Weight per 1000 metre (in Kg.)
211 303 454
23 Standard drum length offered
1000 1000 1000
24 FRLS Properties on outer
25 Oxygen index in room (%)
Min. 29% Min. 29% Min. 29%
25a.
Minimum temperature
index(C) Min. 2500C Min. 2500C Min. 2500C
25b. Maximum smoke density rating(%)
Max. 60% Max. 60% Max. 60%
25c Maximum acid gas generation(%)
20% Max. 20% Max. 20% Max.
25d. Flammability test As per IEC-60332-
1/SS-424-1475 As per IEC-60332-
1/SS-424-1475 As per IEC-60332-1/SS-
424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER
LTD" YEAR."
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER
LTD" YEAR."
" KEC INTL. LTD., 'RPG-
CABLES' , 1100V, ELECTRIC CABLE, NO.
OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER LTD"
YEAR."
27 Marking on Drums As per IS:7098
part(1)/88 As per IS:7098
part(1)/88 As per IS:7098
part(1)/88
28 Type of end sealing PVC End Caps PVC End Caps PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India India
3 Type Designation A2XFaY:FRLS A2XFaY:FRLS
4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88
5 Cable size 1C x 300 Sq.mm 1C x 630 Sq.mm
6 No. of core 1 1
7 Rated voltage 1100 V 1100 V
8 Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C 457 732
b.
When buried in soil having thermal Resistivity of 150
deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.
337 499
9 Short circuit withstand capacity and duration for one second
a. Conductor 28.34 59.52
9 Conductor
a.
Material
H4 Grade Aluminium (
Class-2 ) to IS: 8130/1984
H4 Grade Aluminium (
Class-2 ) to IS: 8130/1984
b. No. of strand/Approx diameter of each strand 37/3.18 55/3.84
c. Shape of Conductor
Compacted Circular
Compacted Circular
d. Diameter of conductor 20.0 29.4
e. Nominal cross section area in sq. mm. 300 630
f. Max. D. C. resistance at 20 deg. C 0.100 0.0469
g. Conductor temperature 90 90
h. S/C conductor temprature 250 250
10 Insulation
a.
Material
Cross Linked
Polyethylene(XLPE) as per
IS:7098/I/1988
Cross Linked
Polyethylene(XLPE) as per
IS:7098/I/1988
b. Nominal thickness (in mm) 2.10 2.80
c. Minimum thickness(in mm) 1.79 2.42
d. Identification of cores Black Black
e. Insulation temperature 90 90
f.
Type of extrusion & curing process Sioplas single
Extrusion & Hot Water Curing
Sioplas single Extrusion & Hot
Water Curing
f. Diameter over insulation 24.2 35.0
11 Inner sheath
a. Min. thichkness N.A N.A
b. Wrapped or Extruded N.A N.A
-
c. Colour N.A N.A
d. Approx. dia. Over inner sheath N.A N.A
e. Material and Type of inner sheath (if required) N.A N.A
f. Filler material N.A N.A
12 Outer sheath
a. Type of Outer sheath Extruded "FRLS"
PVC Type 'ST2' as per IS:5831/84
Extruded "FRLS" PVC Type 'ST2'
as per IS:5831/84 b. Material
c. Colour Black Black
d. Min. thickness of Outer sheath 1.56 1.72
e. Tolerance on diameter
2 mm
2 mm
13 Armour
a. Material & shape :
Hard Drawn Aluminium Flat
Strip as per IS:8130
Hard Drawn Aluminium Flat
Strip as per IS:8130
b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8
c. Whether galvanized:(Yes/No) N.A N.A
d. Diameter of cable over armouring mm): 26.4 37.4
e. Armour coverage area (%) 90% 90%
f. Maximum DC resistance at 20C (ohm/km) 0.74 0.51
g. No of wires/Strips required 16 23
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 0.10 0.0469
b. A.C resistance at 90degC 0.128 0.06
c. Reactance at 50Hz(App) 0.0857 0.0843
d. Capacitance (App) 0.693 0.766
e. Impedance(App) 0.154 0.1034
15 Finished Cable
a. Diameter over laid up core (Calculated) N.A N.A
b. Diameter under armor in mm (Claculated) 23.7 33.9
c. Diameter over armor in mm (Calculated) 25.3 35.5
16 Max. Pulling force 3 kg/mm of
Aluminium area 3 kg/mm of
Aluminium area
17 Cable Drum
a. Material Wooden Wooden
b. Dimension of drum(App) 1200 x 575 x 650 1500 x 700 x 800
c. Shipping Weight(App) 859 1538
d. Drum Weight(Without cable) (App) 220 300
e. Cable pulling eye yes/No No No
18 Recommended bending radius
15 times Overall diameter
15 times Overall diameter
19 Derating Factor Refer Catalogue Refer Catalogue
-
20 Group rating factor Refer Catalogue Refer Catalogue
21 Overall dia. of cable (in mm)(
2mm tolerance) 30 42
22 Weight per 1000 metre (in Kg.) 1277 2475
23 Standard drum length offered 500 500
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29% Min. 29%
25a. Minimum temperature index(C) Min. 2500C Min. 2500C
25b. Maximum smoke density rating(%)
Max. 60% Max. 60%
25c Maximum acid gas generation(%) 20% Max. 20% Max.
25d.
Flammability test As per IEC-
60332-1/SS-424-1475
As per IEC-60332-1/SS-424-
1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER LTD",
YEAR."
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER LTD",
YEAR."
27 Marking on Drums As per IS:7098
part(1)/88 As per IS:7098
part(1)/88
28 Type of end sealing PVC End Caps PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India India
3 Type Designation A2XFY(P):FRLS A2XFY(P):FRLS
4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88
5 Cable size 3C x 150 Sq.mm 3C x 240 Sq.mm
6 No. of core 3 3
7 Rated voltage 1100 V 1100 V
8 Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C
261 357
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth
of 1000 mm in ground amb. Temp. of 40 deg. C.
222 291
9 Short circuit withstand capacity and duration for one second
a. Conductor 14.17 22.68
9 Conductor
a.
Material H4 Grade Aluminium
( Class-2 ) to IS: 8130/1984
H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
b.
No. of strand/Approx diameter of each strand
19/3.18 36/2.94
c. Shape of Conductor Sector Sector
d. Diameter of conductor 12.0 15.4
e. Nominal cross section areain sq. mm. 150 240
f. Max. D. C. resistance at 20 deg. C 0.206 0.125
g. Conductor temperature 90 90
h. S/C conductor temprature 250 250
10 Insulation
a.
Material Cross Linked
Polyethylene(XLPE) as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE) as per
IS:7098/I/1988
b. Nominal thickness (in mm) 1.40 1.70
c. Minimum thickness(in mm) 1.16 1.43
d. Identification of cores Red,Yellow & Blue Red,Yellow & Blue
e. Insulation temperature 90 90
f.
Type of extrusion & curing process Sioplas single
Extrusion & Hot Water Curing
Sioplas single Extrusion & Hot Water Curing
g. Diameter over insulation 14.8 18.8
11 Inner sheath
a. Min. thichkness 0.50 0.60
b. Wrapped or Extruded Extruded Extruded
c. Colour Black Black
-
d. Approx. dia. Over inner sheath 32.9 41.5
e.
Material and Type of inner sheath (if required)
PVC Type `ST2' to IS:5831/84
PVC Type `ST2' to IS:5831/84
f. Filler material
Gaps can be filled by PVC during the extruded PVC
innersheathing wherever applicable.
Gaps can be filled by PVC during the extruded PVC innersheathing wherever
applicable.
12 Outer sheath
a. Type of Outer sheath Extruded "FRLS"
PVC Type 'ST2' as per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as per
IS:5831/84 b. Material
c. Colour Black Black
d. Min. thickness of Outer sheath 1.72 2.04
e. Tolerance on diameter
2 mm
2 mm
13 Armour
a. Material & shape : Galvanised Steel Flat Strip as per IS:3975
Galvanised Steel Flat Strip as per IS:3975
b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8
c. Whether galvanized:(Yes/No) Yes Yes
d.
Diameter of cable over armouring mm):
34.8 43.5
e. Armour coverage area (%) 90% 90%
f.
Maximum DC resistance at 20C (ohm/km)
2.19 1.78
g. No of wires/Strips required 21 27
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 0.206 0.125
b. A.C resistance at 90degC 0.264 0.16
c. Reactance at 50Hz(App) 0.0732 0.0719
d. Capacitance (App) 0.569 0.594
e. Impedance(App) 0.274 0.1754
15 Finished Cable
a. Diameter over laid up core (Calculated) 35.9 45.1
b.
Diameter under armor in mm (Claculated)
36.9 46.3
c.
Diameter over armor in mm (Calculated)
38.5 47.9
16 Max. Pulling force 3 kg/mm of
Aluminium area 3 kg/mm of Aluminium
area
17 Cable Drum
a. Material Wooden Wooden
b. Dimension of drum(App) 1500 x 700 x 800 1800 x 700 x 800
c. Shipping Weight(App) 1479 2287
d. Drum Weight(Without cable) (App) 300 500
e. Cable pulling eye yes/No No No
18 Recommended bending radius 12 times Overall
diameter 12 times Overall diameter
-
19 Derating Factor Refer Catalogue Refer Catalogue
20 Group rating factor Refer Catalogue Refer Catalogue
21
Overall dia. of cable (in mm)(
2mm
tolerance) 39 49
22 Weight per 1000 metre (in Kg.) 2358 3574
23 Standard drum length offered 500 500
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29% Min. 29%
25a. Minimum temperature index(C) Min. 2500C Min. 2500C 25
b. Maximum smoke density rating(%) Max. 60% Max. 60%
25c Maximum acid gas generation(%)
20% Max. 20% Max.
25d.
Flammability test As per IEC-60332-
1/SS-424-1475 As per IEC-60332-1/SS-
424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB POWER
LTD" YEAR."
" KEC INTL. LTD., 'RPG-CABLES' , 1100V,
ELECTRIC CABLE, NO. OF CORES X SIZE
Sq.mm.,Type of Insulation,FRLS,ISI Mark, "MB POWER LTD" YEAR."
27 Marking on Drums As per IS:7098
part(1)/88 As per IS:7098 part(1)/88
28 Type of end sealing PVC End Caps PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India India
3 Type Designation A2XFY(P):FRLS A2XFY(P):FRLS
4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88
5 Cable size 3.5C x 35 Sq.mm 3.5C x 70Sq.mm
6 No. of core 3.5 3.5
7 Rated voltage 1100 V 1100 V
8 Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C
104 158
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a
depth of 1000 mm in ground amb. Temp. of 40 deg. C.
102 146
9 Short circuit withstand capacity and duration for one second
a. Conductor 3.31 6.61
9 Conductor
a.
Material H4 Grade Aluminium (
Class-2 ) to IS: 8130/1984
H4 Grade Aluminium ( Class-2 ) to IS: 8130/1984
b.
No. of strand/Approx diameter of each strand
7/2.52 19/2.14
c. Shape of Conductor Sector Sector
d. Diameter of conductor 6.8 9.6
e. Nominal cross section areain sq. mm. 35 70
f. Max. D. C. resistance at 20 deg. C 0.868 0.443
g. Conductor temperature 90 90
h. S/C conductor temprature 250 250
10 Insulation
a.
Material Cross Linked
Polyethylene(XLPE) as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE) as per
IS:7098/I/1988
b. Nominal thickness (in mm) 0.90 1.10
c. Minimum thickness(in mm) 0.71 0.89
d. Identification of cores Red,Yellow,Blue & Black Red,Yellow,Blue & Black
e. Insulation temperature 90 90
f.
Type of extrusion & curing process Sioplas single Extrusion
& Hot Water Curing Sioplas single Extrusion &
Hot Water Curing
g. Diameter over insulation 8.6 11.8
11 Inner sheath
a. Min. thichkness 0.30 0.40
b. Wrapped or Extruded Extruded Extruded
c. Colour Black Black
-
d. Approx. dia. Over inner sheath 20.3 27.5
e.
Material and Type of inner sheath (if required)
PVC Type `ST2' to IS:5831/84
PVC Type `ST2' to IS:5831/84
f. Filler material
Gaps can be filled by PVC during the extruded
PVC innersheathing wherever applicable.
Gaps can be filled by PVC during the extruded PVC innersheathing wherever
applicable.
12 Outer sheath
a. Type of Outer sheath Extruded "FRLS" PVC
Type 'ST2' as per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84
b. Material
c. Colour Black Black
d. Min. thickness of Outer sheath 1.40 1.56
e. Tolerance on diameter
2 mm
2 mm
13 Armour
a. Material & shape : Galvanised Steel Flat Strip as per IS:3975
Galvanised Steel Flat Strip as per IS:3975
b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8
c. Whether galvanized:(Yes/No) Yes Yes
d.
Diameter of cable over armouring mm):
22.3 29.5
e. Armour coverage area (%) 90% 90%
f.
Maximum DC resistance at 20C (ohm/km)
3.6 2.7
g. No of wires/Strips required 12 17
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 0.868 0.443
b. A.C resistance at 90degC 1.11 0.567
c. Reactance at 50Hz(App) 0.0794 0.0752
d. Capacitance (App) 0.464 0.49
e. Impedance(App) 1.1128 0.572
15 Finished Cable
a. Diameter over laid up core (Calculated) 19.0 26.2
b.
Diameter under armor in mm (Claculated)
19.6 27.0
c.
Diameter over armor in mm (Calculated)
21.2 28.6
16 Max. Pulling force 3 kg/mm of Aluminium
area 3 kg/mm of Aluminium
area
17 Cable Drum
a. Material Wooden Wooden
b. Dimension of drum(App) 1400 x 600 x 650 1400 x 600 x 650
c. Shipping Weight(App) 1220 1035.5
d. Drum Weight(Without cable) (App) 270 270
e. Cable pulling eye yes/No No No
18 Recommended bending radius 12 times Overall
diameter 12 times Overall diameter
-
19 Derating Factor Refer Catalogue Refer Catalogue
20 Group rating factor Refer Catalogue Refer Catalogue
21
Overall dia. of cable (in mm)(
2mm
tolerance) 26 33
22 Weight per 1000 metre (in Kg.) 950 1531
23 Standard drum length offered 1000 500
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29% Min. 29%
25a. Minimum temperature index(C) Min. 2500C Min. 2500C 25
b. Maximum smoke density rating(%) Max. 60% Max. 60%
25c Maximum acid gas generation(%)
20% Max. 20% Max.
25d.
Flammability test As per IEC-60332-1/SS-
424-1475 As per IEC-60332-1/SS-
424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' , 1100V,
ELECTRIC CABLE, NO. OF CORES X SIZE
Sq.mm.,Type of Insulation,FRLS,ISI
Mark, "MB POWER LTD" YEAR."
" KEC INTL. LTD., 'RPG-CABLES' , 1100V,
ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of Insulation,FRLS,ISI Mark,
"MB POWER LTD" YEAR."
27 Marking on Drums As per IS:7098
part(1)/88 As per IS:7098 part(1)/88
28 Type of end sealing PVC End Caps PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India
3 Type Designation A2XFY(P):FRLS
4 Applicable Standard IS:7098 pt(1)/88
5 Cable size 4C x 16Sq.mm
6 No. of core 4
7 Rated voltage 1100 V
8 Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C 62
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.
65
9 Short circuit withstand capacity and duration for one second
a. Conductor 1.51
9 Conductor
a.
Material H4 Grade Aluminium ( Class-2 ) to
IS: 8130/1984
b. No. of strand/Approx diameter of each strand 7/1.72
c. Shape of Conductor Sector
d. Diameter of conductor 4.6
e. Nominal cross section areain sq. mm. 16
f. Max. D. C. resistance at 20 deg. C 1.91
g. Conductor temperature 90
h. S/C conductor temprature 250
10 Insulation
a.
Material Cross Linked Polyethylene(XLPE)
as per IS:7098/I/1988
b. Nominal thickness (in mm) 0.70
c. Minimum thickness(in mm) 0.53
d. Identification of cores Red,Yellow,Blue & Black
e. Insulation temperature 90
f.
Type of extrusion & curing process Sioplas single Extrusion & Hot
Water Curing
g. Diameter over insulation 6.0
11 Inner sheath
a. Min. thichkness 0.30
b. Wrapped or Extruded Extruded
c. Colour Black
-
d. Approx. dia. Over inner sheath 14.9
e. Material and Type of inner sheath (if required) PVC Type `ST2' to IS:5831/84
f. Filler material Gaps can be filled by PVC during the extruded PVC innersheathing
wherever applicable.
12 Outer sheath
a. Type of Outer sheath
Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84
b. Material
c. Colour Black
d. Min. thickness of Outer sheath 1.40
e. Tolerance on diameter
2 mm
13 Armour
a. Material & shape : Galvanised Steel Flat Strip as per
IS:3975
b. Diameter of wire : 4.0 x 0.8
c. Whether galvanized:(Yes/No) Yes
d. Diameter of cable over armouring mm): 16.9
e. Armour coverage area (%) 90%
f. Maximum DC resistance at 20C (ohm/km) 4.32
g. No of wires/Strips required 9
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 1.91
b. A.C resistance at 90degC 2.44
c. Reactance at 50Hz(App) 0.0815
d. Capacitance (App) 0.401
e. Impedance(App) 2.4414
15 Finished Cable
a. Diameter over laid up core (Calculated) 14.3
b. Diameter under armor in mm (Claculated) 14.9
c. Diameter over armor in mm (Calculated) 16.5
16 Max. Pulling force 3 kg/mm of Aluminium area
17 Cable Drum
a. Material Wooden
b. Dimension of drum(App) 1200 x 575 x 650
c. Shipping Weight(App) 837
d. Drum Weight(Without cable) (App) 220
e. Cable pulling eye yes/No No
18 Recommended bending radius 12 times Overall diameter
-
19 Derating Factor Refer Catalogue
20 Group rating factor Refer Catalogue
21 Overall dia. of cable (in mm)(
2mm tolerance) 21
22 Weight per 1000 metre (in Kg.) 617
23 Standard drum length offered 1000
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29%
25a. Minimum temperature index(C) Min. 2500C 25b. Maximum smoke density rating(%) Max. 60%
25c Maximum acid gas generation(%) 20% Max.
25d. Flammability test As per IEC-60332-1/SS-424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' , 1100V, ELECTRIC CABLE, NO. OF
CORES X SIZE Sq.mm.,Type of Insulation,FRLS,ISI Mark, "MB
POWER LTD" YEAR."
27 Marking on Drums As per IS:7098 part(1)/88
28 Type of end sealing PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make
KEC International Ltd 'RPG-Cables'
KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India India
3 Type Designation Str. A2XWY(P):FRLS Str. A2XWY(P):FRLS
4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88
5 Cable size 3C x 10Sq.mm 4C x 10Sq.mm
6 No. of core 3 4
7 Rated voltage 1100 V 1100 V
8 Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C
59 59
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth
of 1000 mm in ground amb. Temp. of 40 deg. C.
80 80
9 Short circuit withstand capacity and duration for one second
a. Conductor 0.94 0.94
9 Conductor
a. Material
H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
b.
No. of strand/Approx diameter of each
strand 7/1.35 7/1.35
c. Shape of Conductor Circular Circular
d. Diameter of conductor 4.1 4.1
e. Nominal cross section areain sq. mm. 10 10
f. Max. D. C. resistance at 20 deg. C 3.08 3.08
g. Conductor temperature 90 90
h. S/C conductor temprature 250 250
10 Insulation
a.
Material Cross Linked
Polyethylene(XLPE) as per IS:7098/I/1988
Cross Linked Polyethylene(XLPE) as per IS:7098/I/1988
b. Nominal thickness (in mm) 0.70 0.70
c. Minimum thickness(in mm) 0.53 0.53
d. Identification of cores Red, Yellow & Blue
Red, Yellow, Blue & Black
e. Insulation temperature 90 90
f. Type of extrusion & curing process
Sioplas single Extrusion & Hot Water Curing
Sioplas single Extrusion & Hot Water
Curing
g. Diameter over insulation 5.5 5.5
11 Inner sheath
a. Min. thichkness 0.30 0.30
b. Wrapped or Extruded Extruded Extruded
c. Colour Black Black
-
d. Approx. dia. Over inner sheath 13.4 15.0
e.
Material and Type of inner sheath (if required)
PVC Type `ST2' to IS:5831/84
PVC Type `ST2' to IS:5831/84
f. Filler material
Gaps can be filled by PVC during the extruded PVC innersheathing wherever
applicable.
Gaps can be filled by PVC during the extruded PVC
innersheathing wherever applicable.
12 Outer sheath
a. Type of Outer sheath Extruded "FRLS" PVC
Type 'ST2' as per IS:5831/84
Extruded "FRLS" PVC Type 'ST2' as per
IS:5831/84 b. Material
c. Colour Black Black
d. Min. thickness of Outer sheath 1.24 1.40
e. Tolerance on diameter
2 mm
2 mm
13 Armour
a. Material & shape : Galvanised Steel Round
Wire as per IS:3975
Galvanised Steel Round Wire as per
IS:3975
b. Diameter of wire : 1.4 1.4
c. Whether galvanized:(Yes/No) Yes Yes
d.
Diameter of cable over armouring mm):
16.2 17.8
e. Armour coverage area (%) 90% 90%
f. Maximum DC resistance at 20C (ohm/km) 3.57 3.20
g. Approx. No of wires/Strips required 26 29
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 3.08 3.08
b. A.C resistance at 90degC 3.94 3.94
c. Reactance at 50Hz(App) 0.0852 0.0852
d. Capacitance (App) 0.347 0.347
e. Impedance(App) 3.9409 3.9409
15 Finished Cable
a. Diameter over laid up core (Calculated) 10.8 12.1
b.
Diameter under armor in mm (Claculated)
11.4 12.7
c.
Diameter over armor in mm (Calculated)
14.2 15.5
16 Max. Pulling force 3 kg/mm of Al. area 3 kg/mm of Al. area
17 Cable Drum
a. Material Wooden Wooden
b. Dimension of drum(App) 1000 x 300 x 600 1200 x 575 x 650
c. Shipping Weight(App) 817 1027
d. Drum Weight(Without cable) (App) 130 220
e. Cable pulling eye yes/No No No
18 Recommended bending radius 12 times Overall diameter
12 times Overall diameter
19 Derating Factor Refer Catalogue Refer Catalogue
-
20 Group rating factor Refer Catalogue Refer Catalogue
21
Overall dia. of cable (in mm)(
2mm
tolerance) 19 21
22 Weight per 1000 metre (in Kg.) 687 807
23 Standard drum length offered 1000 1000
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29% Min. 29%
25a. Minimum temperature index(C) Min. 2500C Min. 2500C 25b. Maximum smoke density rating(%) Max. 60% Max. 60%
25c Maximum acid gas generation(%) 20% Max. 20% Max.
25d. Flammability test As per IEC-60332-1/SS-
424-1475 As per IEC-60332-
1/SS-424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' , 1100V,
ELECTRIC CABLE, NO. OF CORES X SIZE
Sq.mm.,Type of Insulation,FRLS,ISI Mark,
YEAR."
" KEC INTL. LTD., 'RPG-CABLES' ,
1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, YEAR."
27 Marking on Drums As per IS:7098 part(1)/88
As per IS:7098 part(1)/88
28 Type of end sealing PVC End Caps PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India
3 Type Designation Str. 2XWY(P):FRLS
4 Applicable Standard IS:7098 pt(1)/88
5 Cable size 2C x 2.5 Sq.mm
6 No. of core 2
7 Rated voltage 1100 V
8
Continuous current rating for max. conductor
temperature:
a. When laid in air at an ambient Temp. of 50 deg. C 35
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.
38
9
Short circuit withstand capacity and duration for
one second
a. Conductor 0.36
9 Conductor
a.
Material Annealed Stranded Copper ( Class-2 ) to
IS:8130/84
b. No. of strand/Approx diameter of each strand 7/0.67
c. Shape of Conductor Circular
d. Diameter of conductor 2.0
e. Nominal cross section areain sq. mm. 2.5
f. Max. D. C. resistance at 20 deg. C 7.41
g. Conductor temperature 90
h. S/C conductor temprature 250
10 Insulation
a.
Material Cross Linked Polyethylene(XLPE) as per
IS:7098/I/1988
b. Nominal thickness (in mm) 0.70
c. Minimum thickness(in mm) 0.53
d. Identification of cores Red & Black
e. Insulation temperature 90
f.
Type of extrusion & curing process Sioplas single Extrusion & Hot Water Curing
g. Diameter over insulation 3.4
11 Inner sheath
a. Min. thichkness 0.30
b. Wrapped or Extruded Extruded
-
c. Colour Black
d. Approx. dia. Over inner sheath 8.4
e. Material and Type of inner sheath (if required) PVC Type `ST2' to IS:5831/84
f. Filler material Gaps can be filled by PVC during the
extruded PVC inner sheathing wherever applicable.
12 Outer sheath
a. Type of Outer sheath
Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84
b. Material
c. Colour Black
d. Min. thickness of Outer sheath 1.24
e. Tolerance on diameter
2 mm
13 Armour
a. Material & shape : Galvanised Steel Round Wire as per IS:3975
b. Diameter of wire : 1.4
c. Whether galvanized:(Yes/No) Yes
d. Diameter of cable over armouring mm): 11.2
e. Armour coverage area (%) 90%
f. Maximum DC resistance at 20C (ohm/km) 6.07
g. No of wires/Strips required 15
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 7.41
b. A.C resistance at 90degC 9.48
c. Reactance at 50Hz(App) 0.1007
d. Capacitance (App) 0.071
e. Impedance(App) 9.4805
15 Finished Cable
a. Diameter over laid up core (Calculated) 6.4
b. Diameter under armor in mm (Claculated) 7.0
c. Diameter over armor in mm (Calculated) 9.8
16 Max. Pulling force 5 kg/mm of Copper area
17 Cable Drum
a. Material Wooden
b. Dimension of drum(App) 950 x 300 x 650
c. Shipping Weight(App) 508
d. Drum Weight(Without cable) (App) 105
e. Cable pulling eye yes/No No
18 Recommended bending radius 12 times Overall diameter
-
19 Derating Factor Refer Catalogue
20 Group rating factor Refer Catalogue
21 Overall dia. of cable (in mm)(
2mm tolerance) 14
22 Weight per 1000 metre (in Kg.) 403
23 Standard drum length offered 1000
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29%
25a. Minimum temperature index(C) Min. 2500C 25b. Maximum smoke density rating(%) Max. 60%
25c Maximum acid gas generation(%) 20% Max.
25d. Flammability test As per IEC-60332-1/SS-424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' , 1100V, ELECTRIC CABLE, NO. OF CORES X SIZE
Sq.mm.,Type of Insulation,FRLS,ISI Mark,"MB POWER LTD" YEAR."
27 Marking on Drums As per IS:7098 part(1)/88
28 Type of end sealing PVC End Caps
-
GUARANTEED TECHNICAL PARTICULARS
1 Make KEC International Ltd 'RPG-Cables'
2 Country of Manufacturer India
3 Type Designation A2XFaY:FRLS
4 Applicable Standard IS:7098 pt(1)/88
5 Cable size 1C x 120 Sq.mm
6 No. of core 1
7 Rated voltage 1100 V
8 Continuous current rating for max. conductor temperature:
a. When laid in air at an ambient Temp. of 50 deg. C 245
b.
When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.
206
9 Short circuit withstand capacity and duration for one second
a. Conductor 11.34
9 Conductor
a.
Material H4 Grade Aluminium ( Class-2 ) to IS:
8130/1984
b. No. of strand/Approx diameter of each strand 19/2.94
c. Shape of Conductor Compacted Circular
d. Diameter of conductor 12.8
e. Nominal cross section area in sq. mm. 120
f. Max. D. C. resistance at 20 deg. C 0.253
g. Conductor temperature 90
h. S/C conductor temprature 250
10 Insulation
a.
Material Cross Linked Polyethylene(XLPE) as per
IS:7098/I/1988
b. Nominal thickness (in mm) 1.50
c. Minimum thickness(in mm) 1.25
d. Identification of cores Black
e. Insulation temperature 90
f.
Type of extrusion & curing process Sioplas single Extrusion & Hot Water
Curing
f. Diameter over insulation 15.8
11 Inner sheath
a. Min. thichkness N.A
b. Wrapped or Extruded N.A
c. Colour N.A
-
d. Approx. dia. Over inner sheath N.A
e. Material and Type of inner sheath (if required) N.A
f. Filler material N.A
12 Outer sheath
a. Type of Outer sheath
Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84
b. Material
c. Colour Black
d. Min. thickness of Outer sheath 1.40
e. Tolerance on diameter
2 mm
13 Armour
a. Material & shape : Hard Drawn Aluminium Flat Strip as per
IS:8130
b. Diameter of wire : 4.0 x 0.8
c. Whether galvanized:(Yes/No) N.A
d. Diameter of cable over armouring mm): 18.0
e. Armour coverage area (%) 90%
f. Maximum DC resistance at 20C (ohm/km) 1.18
g. No of wires/Strips required 10
14 Electrical Parameter at maximum Operating temperature
a. Max. DC resistance at 20degC 0.253
b. A.C resistance at 90degC 0.324
c. Reactance at 50Hz(App) 0.0879
d. Capacitance (App) 0.641
e. Impedance(App) 0.3357
15 Finished Cable
a. Diameter over laid up core (Calculated) N.A
b. Diameter under armor in mm (Claculated) 15.4
c. Diameter over armor in mm (Calculated) 17
16 Max. Pulling force 3 kg/mm of Aluminium area
17 Cable Drum
a. Material Wooden
b. Dimension of drum(App) 1200 x 575 x 650
c. Shipping Weight(App) 821
d. Drum Weight(Without cable) (App) 220
e. Cable pulling eye yes/No No
18 Recommended bending radius 15 times Overall diameter
19 Derating Factor Refer Catalogue
20 Group rating factor Refer Catalogue
-
21 Overall dia. of cable (in mm)(
2mm tolerance) 22
22 Weight per 1000 metre (in Kg.) 601
23 Standard drum length offered 1000
24 FRLS Properties on outer
25 Oxygen index in room (%) Min. 29%
25a. Minimum temperature index(C) Min. 2500C 25b. Maximum smoke density rating(%) Max. 60%
25c Maximum acid gas generation(%) 20% Max.
25d. Flammability test As per IEC-60332-1/SS-424-1475
26 Embossing on outer Sheath
" KEC INTL. LTD., 'RPG-CABLES' , 1100V, ELECTRIC CABLE, NO. OF CORES X
SIZE Sq.mm.,Type of Insulation,FRLS,ISI Mark, "MB POWER LTD", YEAR."
27 Marking on Drums As per IS:7098 part(1)/88
28 Type of end sealing PVC End Caps