LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

6
APPLICATION Al / XLPE / PVC CONSTRUCTION CHARACTERISTICS Conductor Copper (plain annealed): solid class 1 or stranded class 2 or flexible class 5, circular or sector shaped Aluminium: stranded class 2, circular or sector shaped. Insulation XLPE – (Cross-linked polyethylene) Oversheath PVC – (Polyvinyl chloride) GENERAL CHARACTERISTICS Construction and test standards IEC 60228 • IEC 60502-1 Rated voltage U /U 0 0.6 / 1 kV Test voltage 3.5 kV a.c. 5 minutes Conductor maximum operating temperature 90°C Maximum short-circuit temperature 250°C (t 5s) Minimum bending radius (mm) (permanent. after installation) (during installation) 4xd if d<25 • 6xd if d≥25 • 8xd if sector shape cond. 6xd if d<25 • 9xd if d≥25 • 12xd if sector shape cond. Maximum pulling force over conductor (N) Copper – 50 x S Aluminium – 30 x S Flame retardant IEC 60332-1-2 • EN 60332-1-2 (cable vertically mounted, length of charred cable 540 mm) 2 S – conductor cross-section (mm ) d – cable outer diameter (mm) FAST CABLES ADDITIONAL CHARACTERISTICS Fire retardant (frt) IEC 60332-3-24 • EN 60332-3-24 (bunch of cables cable 2.5 m) vertically mounted on a ladder, length of charred CABLE DESIGNATION LOW VOLTAGE CABLES INDUSTRIAL CABLES Cu or Al - XLPE - PVC Standard - Unarmoured IEC-60502-1

Transcript of LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

Page 1: LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

APPLICATION

Al / XLPE / PVC

CONSTRUCTION CHARACTERISTICS

Conductor

Copper (plain annealed): solid class 1 or stranded class 2 or flexible class 5, circular or sector shaped Aluminium: stranded class 2, circular or sector shaped.

Insulation XLPE – (Cross-linked polyethylene)

Oversheath PVC – (Polyvinyl chloride)

GENERAL CHARACTERISTICS

Construction and test standards IEC 60228 • IEC 60502-1

Rated voltage U /U0 0.6 / 1 kV

Test voltage 3.5 kV a.c. 5 minutes

Conductor maximum operating temperature 90°C

Maximum short-circuit temperature 250°C (t ≤ 5s)

Minimum bending radius (mm) (permanent. after installation) (during installation)

4xd if d<25 • 6xd if d≥25 • 8xd if sector shape cond.6xd if d<25 • 9xd if d≥25 • 12xd if sector shape cond.

Maximum pulling force over conductor (N)Copper – 50 x S

Aluminium – 30 x S

Flame retardantIEC 60332-1-2 • EN 60332-1-2 (cable vertically

mounted, length of charred cable ≤ 540 mm)2S – conductor cross-section (mm )

d – cable outer diameter (mm)

≤≤

FAST

CA

BLES

ADDITIONAL CHARACTERISTICS

Fire retardant (frt)IEC 60332-3-24 • EN 60332-3-24 (bunch of cables

cable ≤ 2.5 m)vertically mounted on a ladder, length of charred

CABLE DESIGNATION

LOW VOLTAGE CABLESINDUSTRIAL CABLES

Cu or Al - XLPE - PVCStandard - Unarmoured IEC-60502-1

Page 2: LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

LOW VOLTAGE CABLESINDUSTRIAL CABLES

ELECTRICAL AND DIMENSIONAL CHARACTERISTICS

Cu or Al - XLPE - PVCStandard-Unarmoured IEC-60502-1

Cable compositionn.º cond. x cross-section

2(mm )

Approximateouter diameter

(mm)

Approximateweight

(kg/km)

Current carrying capacity(2)In open air T = 30°C

(A)

2 charged conductors 3 charged conductors

26

36

49

63

90

121

161

200

242

310

377

437

504

575

679

783

940

1083

1287

26

36

49

63

86

115

149

185

225

310

377

437

Cu / XLPE / PVC

1x1.5

1x2.5

1x4.0

1x6.0

1x10

1x16

1x25

1x35

1x50

1x70

1x95

1x120

1x150

1x185

1x240

1x300

1x400

1x500

1x630

2x1.5

2x2.5

2x4.0

2x6.0

2x10

2x16

2x25

2x35

2x50

2x70

2x95

2x120

3x1.5

3x2.5

3x4.0

3x6.0

3x10

5.8

6.2

6.8

7.3

8.2

9.3

10.9

11.9

13.2

15.0

16.9

18.6

20.7

23.0

25.8

28.6

32.2

35.7

41.4

9.6

10.4

11.5

12.6

14.4

16.6

19.8

21.8

24.4

28.2

31.8

35.4

10.1

11.0

12.1

13.4

15.3

50

63

80

103

147

207

302

395

519

724

971

1205

1473

1839

2381

2989

3834

4734

6099

113

140

177

224

319

441

642

840

1079

1517

2042

2537

137

175

228

298

417

20

28

40

53

80

107

141

176

216

279

342

400

484

533

634

736

868

998

1065

23

32

42

54

75

Page 3: LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

LOW VOLTAGE CABLESINDUSTRIAL CABLES

Cu or Al - XLPE - PVCStandard-Unarmoured IEC-60502-1

ELECTRICAL AND DIMENSIONAL CHARACTERISTICS

Cable compositionn.º cond. x cross-section

2(mm )

Approximateouter diameter

(mm)

Approximateweight

(kg/km)

Current carrying capacity(2)In open air T = 30°C

(A)

2 charged conductors 3 charged conductors

3x16

3x25

3x35

3x50

3x70

3x95

3x120

3x150

3x185

3x240

3x300

3x400

3x16+1x10

3x25+1x16

3x35+1x16

3x50+1x25

3x70+1x35

3x95+1x50

3x120+1x70

3x150+1x70

3x185+1x95

3x240+1x120

3x300+1x150

3x400+1x185

4x1.5

4x2.5

4x4.0

4x6.0

4x10

4x16

4x25

4x35

4x50

4x70

4x95

4x120

4x150

17.6

18.0

20.0

22.8

26.0

29.1

32.3

36.1

40.0

44.8

49.5

56.4

19.3

21.6

24.1

27.7

32.2

36.1

40.3

45.0

50.1

56.1

62.0

70.7

10.8

11.9

13.2

14.5

16.7

19.3

21.6

24.1

27.7

32.2

36.1

40.3

45.0

600

846

1125

1495

2087

2834

3552

4361

5434

7059

8877

11145

714

1037

1322

1781

2496

3372

4314

5149

6512

8395

10512

13178

165

210

279

368

537

772

1122

1492

1986

2803

3804

4587

5876

100

127

158

192

246

298

346

399

456

538

626

720

100

127

158

192

246

298

346

399

456

538

626

720

23

32

42

54

75

100

127

158

192

246

298

346

399

Page 4: LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

LOW VOLTAGE CABLES INDUSTRIAL CABLES

Cu or Al - XLPE - PVCStandard-Unarmoured IEC-60502-1

ELECTRICAL AND DIMENSIONAL CHARACTERISTICS

Cable compositionn.º cond. x cross-section

2(mm )

Approximateouter diameter

(mm)

Approximateweight

(kg/km)

Current carrying capacity(2)In open air T = 30°C

(A)

2 charged conductors 3 charged conductors

4x185

4x240

4x300

4x400

50.1

56.1

62.0

70.7

7350

9521

11962

15004

456

538

626

720

Page 5: LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

LOW VOLTAGE CABLESINDUSTRIAL CABLES

Al - XLPE - PVCUnarmoured - Controlled Unscreened - IEC 60502-1

ELECTRICAL AND DIMENSIONAL CHARACTERISTICS

Cable compositionn.º cond. x cross-section

2(mm )

Approximateouter diameter

(mm)

Approximateweight

(kg/km)

Current carrying capacity(2)In open air T = 30°C

(A)

2 charged conductors 3 charged conductors

96

121

150

184

237

289

337

389

447

530

613

740

856

996

Al / XLPE / PVC

1x16

1x25

1x35

1x50

1x70

1x95

1x120

1x150

1x185

1x240

1x300

1x400

1x500

1x630

3x16

3x25

3x35

3x50

3x70

3x95

3x120

3x150

3x185

3x240

3x300

3x25+1x16

3x35+1x16

3x50+1x25

3x70+1x35

3x95+1x50

3x120+1x70

3x150+1x70

3x185+1x95

3x240+1x120

3x300+1x150

9.3

10.9

11.9

13.2

15.0

16.9

18.6

20.7

23.0

25.8

28.6

32.2

35.7

41.4

17.6

18.0

20.0

22.8

26.0

29.1

32.3

36.1

40.0

44.8

49.5

21.6

24.1

27.7

32.2

36.1

40.3

45.0

50.1

56.1

62.0

116

161

196

246

325

417

504

620

764

967

1188

1485

1845

2321

387

485

592

742

969

1253

1559

1882

2309

2926

3557

580

693

892

1172

1521

1872

2250

2759

3488

4272

84

107

135

165

215

264

308

358

413

492

571

694

806

942

77

97

120

146

187

227

263

304

347

407

455

97

120

146

187

227

263

304

347

407

455

Page 6: LOW VOLTAGE CABLES Cu or Al - XLPE - PVC

ELECTRICAL AND DIMENSIONAL CHARACTERISTICS

Cable compositionn.º cond. x cross-section

2(mm )

Approximateouter diameter

(mm)

Approximateweight

(kg/km)

Current carrying capacity(2)In open air T = 30°C

(A)

2 charged conductors 3 charged conductors

Al / XLPE / PVC

4x16

4x25

4x35

4x50

4x70

4x95

4x120

4x150

4x185

4x240

4x300

19.3

21.6

24.1

27.7

32.2

36.1

40.3

45.0

50.1

56.1

62.0

766

613

753

965

1281

1661

2016

2487

3050

3861

4748

77

97

120

146

187

227

263

304

347

407

455

LOW VOLTAGE CABLESINDUSTRIAL CABLES

Al - XLPE - PVCUnarmoured - Controlled Unscreened - IEC 60502-1

Other compositions are available, contact [email protected] for information.

(1) Phase conductors sector shape.(2) Installation in free air or on perforated cable tray, horizontal or vertical.

Single core cables – Flat touching installation.Cables with 2 and 3 conductors: 2 charged conductors.Cables with 4 and 5 conductors: 3 charged conductors.For compositions of 4 conductors. the same characteristics apply if the fourth conductor is the earth conductor or neutral conductor.