Low Pressure Drop - accutrolllc.com

8
Accutrol, LLC Product Sheet Accutrol, LLC 21 Commerce Drive, Danbury, CT 06810 203-445-9991 www.accutrolllc.com Contents and specifications are subject to change without notice. Low Pressure Drop By Design

Transcript of Low Pressure Drop - accutrolllc.com

Page 1: Low Pressure Drop - accutrolllc.com

Accutrol, LLC Product Sheet

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com

Contents and specifications are subject to change without notice.

Low Pressure DropBy Design

Page 2: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 2

AccuValve® Overview

The AccuValve is an electronically operated airflow control valve for critical environments such as laboratories, life science and healthcare. The valve was created for sustainable “green” design, low pressure drop for energy reduction and safety through true airflow measurement.

The AccuValve was introduced as the first critical environments airflow control valve designed for use with electronic actuation. The valve was also designed to meet the needs of the world energy situation by operating with the lowest pressure drop of any critical environments airflow control valve on the market. This low pressure drop offers the owner years of energy savings making their building less costly to operate. For more information on using the low pressure drop AccuValve along with Demand Based Static Pressure Reset Control scheme to maximize savings please refer to the Accutrol paper – “Demand Based Static Pressure Reset Control.”

Low Pressure Drop…

When the design criteria for the AccuValve were being evaluated, minimizing the pressure drop of the valve was the top priority. The largest selling critical environment airflow control valves on the market were venturi valves, which require very high static pressure to operate reliably. The AccuValve provides a more efficient alternative to the energy conscious owner.

…By Design

The inspiration for the design of the AccuValve originated from analysis of the design of a silencer (Figure 1). A rectangular silencer reduces the area in that duct section by roughly 50% however the pressure drop of a silencer is considerably less that what might be expected. This is because of the airfoil shape of the silencer battens. An airfoil shape creates less drag for a given surface area (Figure 2) thereby creating a minimal pressure drop. This is especially true with a properly designed static pressure regain section as is provided on the AccuValve.

Figure 1

Figure 2

FLOW

FLAT PLATE

Cd = 1.28

Cd = 1.14

Cd = .295

Cd = .07–.5

Cd = .045Streamline Design

PRISM

Source

BULLET

SPHERE

AIR FOIL

Cd = DrAV2/2

All objects have the same frontal area.

Glenn Research Center

Page 3: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 3

AccuValve® Design

Much like a silencer, the AccuValve divides the airflow into two airstreams using an airfoil shaped compression section (Figure 3). By compressing the air it increases the velocity and makes the airstream more laminar. This improves the turndown of the measuring system and eliminates the need for the straight runs into the valve.

By adding a static pressure regain section after the control blades this further reduces the pressure drop of the valve making it the lowest pressure drop airflow valve on the market.

Cost & Environmental Benefits of Low Pressure Drop Design

Reducing the overall pressure drop in a ventilation system allows the system to be run at a lower static pressure. This requires less fan horsepower resulting in a significant reduction in energy cost. This energy savings also reduces the building’s environmental impact and carbon footprint. Reducing the

operating static pressure has the added benefit of lowering noise levels in the duct, making the building environment more pleasant to work in.

A laboratory building running at an average airflow of 50,000 CFM can be expected to see a reduction of .75”wc static pressure in the supply system by using low pressure drop AccuValves in place of venturi valves. This represents a reduction of 9.53 required fan HP. At a rate of 0.12/kWh, this results in an annual energy cost savings of $10,018 and an environmental impact reduction of nearly 35.9 tons of CO2. Over the 20 year life of a system, this becomes a savings of more than $200,000. Similar savings could be expected for the exhaust system, resulting in a total savings of over $400,000 and over 1400 tons of CO2.

AccuValve Minimum Operating Pressure

The minimum operating pressure for each size AccuValve has been tested in accordance with ANSI/ASHRAE 130 and the resulting performance is included on the following graphs.

Figure 3

FLOW SENSOR

FLOW SENSOR

COMPRESSION SECTION REGAIN SECTION

Page 4: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 4

Airflow Vol. (cfm)

Valve DP ("wc)

50 0.01075 0.030100 0.050125 0.080150 0.110175 0.150200 0.190225 0.240250 0.290275 0.350300 0.410

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 50 75 100 125 150 175 200 225 250 275 300

8" Round AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

6" Round AccuValve Pressure Drop

Airflow Vol. (cfm)

Valve DP ("wc)

100 0.010150 0.020200 0.035250 0.050300 0.069350 0.094400 0.117450 0.145500 0.179550 0.215600 0.258650 0.300700 0.349750 0.393800 0.451

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800

8" Round AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

8" Round AccuValve Pressure Drop

Page 5: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 5

Airflow Vol. (cfm)

Valve DP ("wc)

100 0.00200 0.01300 0.02400 0.04500 0.07600 0.10700 0.13800 0.17900 0.221000 0.281100 0.341200 0.391300 0.45

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

10" Round AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

10" Round AccuValve Pressure Drop

Airflow Vol. (cfm)

Valve DP ("wc)

200 0.01400 0.02600 0.05800 0.091000 0.141200 0.201400 0.271600 0.361800 0.45

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 200 400 600 800 1000 1200 1400 1600 1800

12" Round AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

12" Round AccuValve Pressure Drop

Page 6: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 6

Airflow Vol. (cfm)

Valve DP ("wc)

300 0.006600 0.022900 0.0461200 0.0801500 0.1281800 0.1782100 0.2402400 0.3272500 0.440

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 300 600 900 1200 1500 1800 2100 2400 2500

14" Round AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

14" Round AccuValve Pressure Drop

Airflow Vol. (cfm)

Valve DP ("wc)

400 0.007800 0.0301200 0.0661600 0.1212000 0.1882400 0.2662800 0.3483200 0.442

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 400 800 1200 1600 2000 2400 2800 3200

12"x18" Rectangular AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

12"x18" Rectangular AccuValve Pressure Drop

Page 7: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 7

Airflow Vol. (cfm)

Valve DP ("wc)

500 0.0061000 0.0221500 0.0462000 0.0802500 0.1283000 0.1783500 0.2404000 0.327

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 500 1000 1500 2000 2500 3000 3500 4000

12"x24" Rectangular AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

12"x24" Rectangular AccuValve Pressure Drop

Airflow Vol. (cfm)

Valve DP ("wc)

800 0.0001600 0.0302400 0.0703200 0.1204000 0.1904800 0.2605600 0.3506400 0.440

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 800 1600 2400 3200 4000 4800 5600 6400

12"x24" Rectangular AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

12"x36" Rectangular AccuValve Pressure Drop

Page 8: Low Pressure Drop - accutrolllc.com

Accutrol, LLC • 21 Commerce Drive, Danbury, CT 06810 • 203-445-9991 • www.accutrolllc.com 9/18

AccuValve – Low Pressure Drop – By Design 8

Airflow Vol. (cfm)

Valve DP ("wc)

1000 0.0102000 0.0303000 0.0704000 0.1205000 0.1806000 0.2607000 0.3508000 0.450

0.45

0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 1000 2000 3000 4000 5000 6000 7000 8000

12"x24" Rectangular AccuValve Pressure Drop

Maximum Airflow (cfm)

Valv

e D

P ("

wc)

12"x48" Rectangular AccuValve Pressure Drop