Louvers Penthouses Sunshades Grilles Sight Screens Selection …€¦ · Louvers Penthouses...

16
Louvers Penthouses Sunshades Grilles Sight Screens Selection Technical Information Finishes alllite.com

Transcript of Louvers Penthouses Sunshades Grilles Sight Screens Selection …€¦ · Louvers Penthouses...

LouversPenthousesSunshadesGrillesSight Screens

Selection

TechnicalInformation

Finishes

alllite.com

SELE

CTI

ON

 GU

IDE

Water Penetration Ratings

Model Blade Blade Blade Free Velocity Air Volume PageDepth Angle Style Area (fpm) (cfm)

1United States Court House, WA

Miami-Dade LouversECD-545-MDEFD-637-MDWind-Driven Rain LouversECV-445ECD-545ECD-635ECV-545ECV-645ECD-745EFJ-745Drainable LouversEFD-245EFD-435EFD-437EFD-445EFD-637EFD-645ERD-645Drainable-Head LouversEFJ-437-HPEFJ-637-HPNon-Drainable LouversEFJ-245EFY-245EFJ-430EFK-430EFJ-437EFK-437EFJ-445EFK-445EFY-445EFK-637EFJ-645Operable LouversEOJ-445EOD-445EOJ-637EOD-637Formed Metal LouversSFJ-245SFJ-430SFD-445SFJ-445SFK-445SFV-445SFJ-630SFD-635SFJ-645SFK-645Acoustical LouversEAA-645EAA-845SAJ-835SAJ-1235EAA-1245FAA-1245Combination LouversEBE-445EBI-445EXD-437EXD-645Sight ScreensHJ-445HJ-645HT-401HZ-200VT-250VT-654VV-400VV-500GrillesSunshadesPenthousesEFD-637-MDPHEPJ-445

5"6"

4"5"6"5"6"7"7"

2"4"4"4"6"6"6"

4"6"

2"2"4"4"4"4"4"4"4"6"6"

4"4"6"6"

2"4"4"4"4"4"6"6"6"6"

6"8"8"12"12"12"

4"4"4"6"

4"6"4"2-1/4"2"4"4"5"

6"4"

HorizontalHorizontal

VerticalHorizontalHorizontalVerticalVerticalHorizontalHorizontal

Thinline-DrainableDrainableDrainableDrainableDrainableDrainableRecessed-Drainable

High Performance-JHigh Performance-J

Thinline-JThinline-Inverted YJKJKJKInverted YKJ

Operable-JOperable-DrainableOperable-JOperable-Drainable

JJDrainableJKChevronJDrainableJK

Extruded-AirfoilExtruded AirfoilFormed-JFormed-JExtruded-AirfoilFormed-Airfoil

J-BD-ExhaustJ-BD-IntakeCombinationCombination

Horizontal-Inverted JHorizontal-Inverted JHorizontal AirfoilHorizontal-CladdingVertical-CladdingVertical-CladdingVertical-VVertical-V

Extruded AluminumExtruded Aluminum

46%59%

36%46%54%42%46%53%50%

43%58%58%47%59%55%51%

56%56%

47%38%57%57%57%57%50%50%39%50%50%

49%43%56%58%

42%51%53%48%48%38%65%62%50%50%

30%33%33%31%26%26%

49%49%45%44%

50%50%60%19%24%21%39%54%

59%51%

1250990

1250125012171250125011971250

955966903990990

1050990

912915

583383889889721721689689745832800

6831024810990

603847715775775600825815800800

980870808924999999

689689

11611050

————————

990689

92509405

71259250

1050883759250

1001810000

6494898483987425940592408059

82208226

43732336809080906547654755495549458966736416

5396709672829108

4040694560925991599136488580804464006400

470446114293452841964196

5396539683597455

————————

94055549

22

3333333

4444444

55

66666666666

7777

8888888888

999999

10101010

11111111111111111213

1414

45°37-1/2°

45°45°35°45°45°45°45°

45°35°37-1/2°45°37-1/2°45°45°

37-1/2°37-1/2°

45°45°30°30°37-1/2°37-1/2°45°45°45°37-1/2°45°

45°45°37-1/2°37-1/2°

45°30°45°45°45°45°30°35°45°45°

45°45°35°35°45°45°

45°45°37-1/2°37-1/2°– 45°

————————

37-1/2°45°

Miami-Dade Louvers

EFD-637-MD

Certified Ratings:All-Lite certifies that model ECD-545-MD shown hereon islicensed to bear the AMCA seal. The ratings shown arebased on test and procedures performed in accordancewith AMCA Publication 511 and comply with the require-ments of the AMCA Certified Ratings Program. The AMCACertified Ratings Seal applies to air performance, waterpenetration and wind-driven rain ratings.

Certified Ratings:All-Lite certifies that model EFD-637-MD shown hereon islicensed to bear the AMCA seal. The ratings shown arebased on test and procedures performed in accordancewith AMCA Publication 511 and comply with the require-ments of the AMCA Certified Ratings Program. The AMCACertified Ratings Seal applies to air performance andwater penetration ratings.

ECD-545-MD

Mosaic Condominiums, FL

(Sight Proof)

The EFD-637-MD and ECD-545-MD are engineered and tested to withstand extreme loads, debris impact, and cyclic fatigue failure associated with the severe weather effects of hurricanes (ECD-545-MD has Miami-Dade approval # 11-0429.02 and the EFD-637-MD has Miami-Dade approval # 11-0429.01).

Constructed from 6063-T5 extruded aluminum, both models have single section assemblies up to 48” wide by 144” high. Specially designed water-resistant seam covers further enhance performance and aesthetics of these industry leading products. Single-section louvers are now available with the option of a factory-installed sleeve which allows louver installation without any mechanical anchoring to the building condition.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute peri-od. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin ofsafety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louver size having 39-3/8” x 39-3/8” core area.

6"

2

All-Lite architectural products are designed for use in most geographical areas within the United States. All-Lite can also design, modify or reinforce standard products for special requirements, such as high wind, heavy snow, industrial environments, specialmounting conditions, etc. Consult your local representative for more information.

5"

Maximum Size Wall Construction Installation Method

Single Section - 48"w x 144"hMultiple Section - Unlimited width x 144"h Multiple Section - 48"w x Unlimited Height

Structural steel mullion supportrequired for installations more than

one section wide.

Installations of unlimited width andheight available with additional

engineer-approved support structure.

All Types SteelDirect Connection - Clip angles*

MasonryTension or Shear Connection - Clip angles*

WoodDirect Connection - Clip angles*All Types (Single Section Only)

Flanged sleeve with continuous retaining angles(No anchors required)

*Anchors supplied by others

Model

ECD-545-MD

EFD-637-MD

Depth

5"

6"

BladeAngle

45°

37.5°

BladeStyle

Horizontal

Horizontal

Material(6063-T5 Ext. Alum.)

0.081"

0.081"

Free Area(%) (Sq. Ft.)

46

59

7.4

9.5

Class

A (29 mph)

-

Miami DadeApproval

#11-0429.02

#11-0429.01

Velocity(fpm)

1250

990

Beginning Point of Water Penetration Ratings

Airflow(cfm)

9250

9405

PressureDrop (In. Wg.)

0.22

0.11

‹ › ‹ ›

Wind-Driven Rain Louvers

ECV-445

ECV-445

ECV-645ECV-545

ECV-645ECV-545

ECD-545ECD-635 ECD-745EFJ-745

5"6"

5"6" 7"7"

Backed by AMCA certification our wind-driven rain louvers offer exceptional protection under the most severe conditions and areavailable in frame depths from 4" to 7". The closely spaced vertical blade design of the Florida Building Code approvedECV-645 provides our most effective wind-driven rain performance with 100% effectiveness at wind velocities up to 50 mph and rainfall up to 8 in/hr. When aesthetic requirements demand a more conventional horizontal blade profile our EFJ-745 is the idealsolution with 5" on center traditional J-blade fascia and 100% effectiveness @ 3 in/hr rainfall.

Certified Ratings:All-Lite certifies that model ECV-645 and EFJ-745 shown hereonare licensed to bear the AMCA seal. The ratings shown are basedon test and procedures performed in accordance with AMCAPublication 511 and comply with the requirements of the AMCACertified Ratings Program. The AMCA Certified Ratings Sealapplies to wind driven rain ratings.

Certified Ratings:All-Lite certifies that model ECV-445 shown hereon is licensed tobear the AMCA seal. The ratings shown are based on test andprocedures performed in accordance with AMCA Publication 511and comply with the requirements of the AMCA Certified RatingsProgram. The AMCA Certified Ratings Seal applies to wind driv-en rain and air performance ratings.

Certified Ratings:All-Lite certifies that model ECD-545, ECD-635, ECD-745 and ECV-545shown hereon are licensed to bear the AMCA seal. The ratings shown arebased on test and procedures performed in accordance with AMCAPublication 511 and comply with the requirements of the AMCA CertifiedRatings Program. The AMCA Certified Ratings Seal applies to water pen-etration ratings, air performance and wind driven rain ratings.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of asimple linear regression of test data and the line of 0.01 ounces of water per square foot of free areaand is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration testprovides a method for comparing louver models and designs as to their efficiency in resisting the pene-tration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected witha reasonable margin of safety below the beginning point of water penetration in order to avoid unwantedpenetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louversize having 39-3/8” x 39-3/8” core area.

All-Lite architectural products are designed for use in most geographical areas within the United States. All-Lite can also design, modify or reinforce standard products for special requirements, such as highwind, heavy snow, industrial environments, special mounting conditions, etc. Consult your local representative for more information.

plan view

plan view

3

4"

Dallas Cowboys Stadium, TX

Model

ECV-445

ECD-545

ECD-635

ECV-545

ECV-645

ECD-745

EFJ-745

Depth

4"

5"

6"

5"

6"

7"

7"

BladeStyle

Vertical

Horizontal

Horizontal

Vertical

Vertical

Horizontal

Horizontal

Free Area(%) (Sq. Ft.)

36

46

54

42

46

53

50

5.7

7.4

8.6

6.7

7.4

8.4

8.0

WindVelocity

29 mph

29/50 mph

29 mph

29/50 mph

50 mph

29 mph

29 mph

Rainfall(In/Hr)

3

3/8

3

3/8

8

3

3

Class

A

A/B

B

A

A

A

A

VentilationRate (cfm)

3115

7196/7276

1998

7356/9485

1421

4531

6339

EffectivenessRatio (%)

99.8

100.0/97.9

96.6

99.9/99.6

100.0

99.9

100.0

Velocity(fpm)

1250

1250

1217

1250

1250

1197

1250

Wind-Driven Rain Ratings Beginning Point of Water Penetration Ratings

Airflow(cfm)

7125

9250

10508

8375

9250

10018

10000

PressureDrop (In. Wg.)

0.76

0.22

0.29

0.25

0.15

0.50

0.62

Florida BuildingCode Approval

-

#13683.1

-

-

#13683.2

-

-

‹ › ‹ › ‹ ›

Drainable LouversDrainable blade louvers are designed to prevent water penetration in non-wind-driven rainapplications by collecting water in the blade gutters and channeling it into frame down-spouts and away from airflow paths. Our ERD-645 incorporates a recessed mullion anddownspout that provides the appearance of a continuous drainable blade design.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safetybelow the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

EFD-435EFD-437EFD-637

EFD-245EFD-445EFD-645 ERD-645

4" 4"6" 6"

2"4"6"

Certified Ratings:All-Lite certifies that models EFD-435, EFD-437, EFD-445, EFD-637 andEFD-645 shown hereon are licensed to bear the AMCA seal. The ratingsshown are based on test and procedures performed in accordance withAMCA Publication 511 and comply with the requirements of the AMCACertified Ratings Program. The AMCA Certified Ratings Seal applies to airperformance and water penetration ratings. Models EFD-245 and ERD-645 are not licensed to bear the AMCA seal.

4

Columbus International Airport, OH

Model

EFD-245

EFD-435

EFD-437

EFD-445

EFD-637

EFD-645

ERD-645

Depth

2"

4"

4"

4"

6"

6"

6"

BladeAngle

45°

35°

37.5°

45°

37.5°

45°

45°

Free Area(%) (Sq. Ft.)

43

58

58

46

59

55

51

6.8

9.3

9.3

7.4

9.5

8.8

8.1

BladeStyle

Thinline-Drainable

Drainable

Drainable

Drainable

Drainable

Drainable

Recessed-Drainable

Material(6063-T5 Ext. Alum.)

0.081"

0.081"

0.081"

0.081"

0.081"

0.081"

0.081"

Velocity(fpm)

955

966

903

990

990

1050

990

Beginning Point of Water Penetration Ratings

Airflow(cfm)

6494

8984

8398

7425

9405

9240

8059

PressureDrop (In. Wg.)

0.14

0.12

0.13

0.14

0.11

0.15

0.11

Florida BuildingCode Approval

-

-

#13683.3

#13683.4

#13683.5

#13683.6

-

‹ › ‹ › ‹ › ‹ ›

Drainable Head Louvers

Certified Ratings:All-Lite certifies that model EFJ-437-HP shown hereon is licensed tobear the AMCA seal. The ratings shown are based on test and pro-cedures performed in accordance with AMCA Publication 511 andcomply with the requirements of the AMCA Certified RatingsProgram. The AMCA Certified Ratings Seal applies to air perform-ance and water penetration ratings. Model EFJ-637-HP is notlicensed to bear the AMCA seal.

EFJ-437-HP EFJ-637-HP

4" 6"

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free areaand is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the pene-tration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwant-ed penetration during severe storm conditions.

5Pennsylvania State University Chemical Laboratory, PA

Pennsylvania State University, PA

Model

EFJ-437-HP

EFJ-637-HP

Depth

4"

5"

Blade Angle

37.5°

37.5°

Blade Style

High Performance - J

High Performance - J

Material/Free Area(6063-T5 Ext. Alum.)

0.081"

0.081"

Velocity(fpm)

912

915

Beginning Point of Water Penetration Ratings

Airflow(cfm)

8220

8226

PressureDrop (In. Wg.)

0.14

0.12

Free Area(%) (Sq. Ft.)

56

56

9.0

9.0

Drainable head louvers blend the aesthetic appeal of a non-drainable blade with the high performance water penetration protection of a drainable blade louver These louvers incorporate a drainable head member to capture water that cascades down the face of the building and channels it into downspouts and away from the airflow paths.

These louvers are available in a wide array of anodized and painted finishes including custom color matching. They are available withan optional hidden vertical mullion

‹ › ‹ ›

Non-Drainable LouversAvailable in a wide array of blade shapes and frame depths non-drainable louvers offer value and economy for exhaust applications or intake conditions where protection against water infiltration is not critical. Optional hidden mullions provide a continuous blade appearance on multiple section assemblies. Ideally suited for special shapes and transitional designs.

Certified Ratings:All-Lite certifies that models EFJ-437, EFK-437, EFJ-445, and EFK-445 shown hereon are licensed to bear the AMCAseal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 andcomply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies toair performance and water penetration ratings. Models EFJ-245, EFY-245, EFJ-430, EFK-430, EFY-445, EFK-637, andEFJ-645 are not licensed to bear the AMCA seal.

EFY-245EFY-445

EFJ-245EFJ-445EFK-445EFJ-645

EFJ-430EFK-430

2"4"

2"4"6"

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute peri-od. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safe-ty below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

4"6"

4"(102)

6

Clayton Elementary School, GA

EFJ-437EFK-437EFK-637

4"6"

Model

EFJ-245

EFY-245

EFJ-430/EFK-430

EFJ-437/EFK-437

EFJ-445/EFK-445

EFY-445

EFK-637

EFJ-645

Depth

2"

2"

4"

4"

4"

6"

6"

6"

BladeAngle

45°

45°

30°

37.5°

45°

45°

37.5°

45°

BladeStyle

Thinline – J

Thinline – Inverted

J/K

J/K

J/K

Inverted Y

K

J

Material(6063-T5 Ext. Alum.)

0.060"

0.060"

0.081"

0.081"

0.081"

0.081"

0.081"

0.081"

Free Area(%) (Sq. Ft.)

47

38

57

57

50

39

50

50

7.5

6.1

9.1

9.1

8.0

6.2

8.0

8.0

Velocity(fpm)

583

383

889

721

689

745

832

800

Beginning Point of Water Penetration Ratings

Airflow(cfm)

4373

2336

8090

6547

5549

4589

6673

6416

PressureDrop (In. Wg.)

0.06

0.06

0.09

0.07

0.08

0.18

0.05

0.10

Florida Building CodeApproval

-

-

-

#13683.7/13683.9

#13683.8/13683.10

-

-

‹ › ‹ › ‹ › ‹ ›

7

Operable LouversOperable blade louvers provide weather protection when open and positive shutoff when no airflow is required. These units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand crank; or automatically with electric or pneumatic actuators.

EOJ-445

4"

EOD-445

4"

EOD-637 EOJ-637

6"

The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measuredthrough a 48"x 48" louver during a 15 minute period. The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific labconditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

6"

Model

EOJ-445

EOD-445

EOD-637

EOJ-637

Depth

4"

4"

6"

6"

BladeAngle

45°

45°

37.5°

37.5°

BladeStyle

Operable-J

Operable - Drainable

Operable - Drainable

Operable -J

Material(6063-T5 Ext. Alum.)

0.081"

0.081"

0.081"

0.081"

Free Area(%) (Sq. Ft.)

49

49

58

56

7.9

6.9

9.2

9.0

Velocity(fpm)

683

1024

990

810

Beginning Point of Water Penetration Ratings

Airflow(cfm)

5396

7096

9108

7282

PressureDrop (In. Wg.)

0.10

0.16

0.11

0.12

‹ › ‹ › ‹ › ‹ ›

8

Formed Metal LouversTypically formed from galvanized steel, these units offer an economical solution for basic ventilation requirements. Optionally available in a wide array of exotic metals including copper and stainless steel our formed metal louvers can also serve to accent building architecture or withstand corrosion in caustic environments.

SFV-445

4"

SFK-445SFJ-245SFJ-445SFJ-645SFK-645

2"4"6"

SFJ-430SFJ-630

4"6"

SFD-635

6"

SFD-445

4"

The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety belowthe beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

Model

SFJ-245

SFJ-430

SFD-445

SFJ-445/SFK-445

SFV-445

SFJ-630

SFD-635

SFJ-645/SFK-645

Depth

4"

4"

4"

4"

4"

6"

6"

6"

BladeAngle

45°

30°

45°

45°

45°

45°

45°

45°

BladeStyle

J

J

Drainable

J/K

Chevron

J

Drainable

J

Material(Galvanized Steel)

20GA

20GA

20GA

20GA

20GA

20GA

20GA

20GA

Free Area(%) (Sq. Ft.)

42

51

53

48

38

65

62

50

6.7

8.2

8.5

7.7

6.1

10.4

9.9

8.0

Velocity(fpm)

603

847

715

775

600

825

815

800

Beginning Point of Water Penetration Ratings

Airflow(cfm)

4040

6945

6092

5991

3648

8580

8044

6400

PressureDrop (In. Wg.)

0.06

0.13

0.11

0.13

0.25

0.08

0.08

0.09

Valley Metro,Phoenix, AZ

‹ › ‹ › ‹ › ‹ › ‹ ›

9

Acoustical Louvers

8"12"

Certified Ratings:

All-Lite certifies that models SAJ-835, SAJ-1235, EAA-845 and FAA-1245, shown hereon is licensed tobear the AMCA seal. The ratings shown are based on test and procedures performed in accordance withAMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. TheAMCA Certified Ratings Seal applies to air performance and water penetration ratings. Models EAA-645and EAA-1245 are not licensed to bear the AMCA seal.

SAJ-835SAJ-1235

EAA-645EAA-845

EAA-1245FAA-1245

Recommended for installation in noisy environments, acoustical louvers incorporate insulated blades that restrict sound transmission through the louver over a wide range of frequencies. Our airfoil blade designs offer lower static pressure lossand softer aesthetics for critical airflow performance applications.

6"8" 12"

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and ismeasured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rain-fall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration duringsevere storm conditions.

West Refrigeration Plant, Washington D.C.

Model

EAA-645

EAA-845

SAJ-835

SAJ-1235

EAA-1245

FAA-1245

Depth

6"

8"

8"

12"

12"

12"

Blade Style

Extruded - Airfoil

Extruded - Airfoil

Formed - J

Formed - J

Extruded - Airfoil

Formed - Airfoil

Noise Reduction125 250 500 1K 2K 4K

Free Area(%) (Sq. Ft.)

30

33

33

31

26

26

4.8

5.3

5.3

4.9

4.2

4.2

11

8

13

15

13

13

11

8

13

17

14

14

13

10

19

22

17

17

16

14

26

27

19

19

18

15

28

31

18

18

17

13

23

28

17

17

Velocity(fpm)

980

870

808

924

999

999

Beginning Point of Water Penetration Ratings

Airflow(cfm)

4704

4611

4293

4528

4196

4196

PressureDrop (In. Wg.)

0.10

0.05

0.07

0.08

0.09

0.09

‹ › ‹ › ‹ ›

10

Combination LouversEXD Combination louvers feature stationary front blades and operable rear blades to ensure proper weather protection when open as well as a consistent appearance in both the open and closed positions. Optional low leakage seals provide further environmental protection in the closed position. Operable blade louvers provide weather protection when open and positive shutoff when no airflow is required. These units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand crank; or automatically with electric or pneumatic actuators.

EBE-445 and EBI-445 incorporate backdraft damper blades for automatic shutoff when there is no airflow and can be used for either exhaust and intake applications.

EBE-445

4"

EBI-445

4"

EXD-437

4"

EXD-645

Fixed Blades

Fixed Blades

OperableBlade

s

OperableBlade

sGravityBlades

GravityBlade

s

Fixed Blade

sFixed Blade

s

The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety belowthe beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

6"(152)

6"

Loren Cook Facility, MO

Model

EBE-445

EBI-445

EXD-437

EXD-645

Depth

4"

4"

4"

4"

BladeAngle

45°

45°

37.5°

37.5° - 45°

BladeStyle

J-BD-Exhaust

J - BD-Intake

Combination

Combination

Material(6063-T5 Ext. Alum.)

0.081"

0.081"

0.081"

0.081"

Free Area(%) (Sq. Ft.)

49

49

45

44

7.9

7.9

7.2

7.1

Velocity(fpm)

689

689

1161

1050

Beginning Point of Water Penetration Ratings

Airflow(cfm)

5396

5396

8359

7455

PressureDrop (In. Wg.)

0.10

0.10

0.16

0.19

‹ › ‹ › ‹ › ‹ ›

11

Sight ScreensWhether the design calls for total sight concealment, partial screening, high volume airflow, specialty shapes, or thermal shading our sight screens are engineered to meet the most stringent project parameters while satisfying exacting aesthetic requirements. The unique concealed support system of the HT-401 ensures proper structural support and a true continuous blade look without the use of unsightly frames or vertical angles.

HJ-445HJ-645

VT-250 VT-654 VV-500 VV-400

plan viewplan view

plan viewplan view

HZ-200 HT-401

21/2 "

4"6"

4"21/4"

5" 4"4"

Valet at Collins Park, FL

Model

HJ-445

HJ-645

HT-401

HZ-200

VT-250

VT-654

VV-400

VV-500

Blade Depth

4"

6"

4"

2-1/4"

2-1/2"

4"

4"

5"

Blade Style

Horizontal - Inverted J

Horizontal - Inverted J

Horizontal - Airfoil Tube

Horizontal - Cladding

Vertical - Cladding

Vertical - Cladding

Vertical - V

Vertical - V

Free Area (%)

50

50

60

19

24

21

39

54

‹› ‹

‹ › ‹ ‹ ‹ ›

Grilles Custom designed to meet each project’s unique requirements our extruded aluminum grilles are ideally suited for architectural accents, facades, screening and security barriers either inside or outside the building. In addition to traditional welded construction we can engineer unique and creative concealed fastening systems and hidden weld joints that offer improved aesthetics and superior structural integrity.

The illustrated designed for these Bar Grilles were created to a design load of 30lbs per square foot. Changes may be required to accommodate other design loads.

Angle

Offset

Bar Continuous

12

Angle Grille

Angle Grille Installed Sentry

Model

All-Lite Standard Grilles

Material/Free Area(6063-T5 Ext. Alum.)

0.125" thick

Minimum Size

12" x 12"

Maximum Size

Single Section: 60" x 180"

One Dimension must be 60"

Sunshades

Airfoil Rectangular Tube J-Blade

Blade Styles

Outriggers

Concealed Connection

Shroud Connection Strut Connection

Exposed Connection

Connections

Fascia

Our sunshades provide distinctive architectural style to a building’s exterior while considerably reducing glare. They do not cause snow load or water infiltration problems associated with solid membrane awnings. Sunshades also reduceheat from sunlight in the summer. This keeps the building cool and saves energy, ideal for sustainable or “green” building construction. Configured to meet each project’s individual requirements, our team can transform even the most complexconcepts into a stunning reality. Our standard sunshade information is shown below.

13

Flat Bar RadiusDouble Tapered RadiusRound Rectangular

Model DepthSSA-445 4"SSA-645 6"SSA-845 8"

Model DepthSSR-445 4"SSR-645 6"SSR-845 8"

Model DepthSSJ-445 4"SSJ-645 6"

Gull Lake High School, MI

Curtain Wall Connection

14

PenthousesAccommodating individual job requirements, penthouses are constructed to virtually any dimension. For added performance and flexibility these units are available with most louver models and include mitered or box corner designs, insulated roof systems, operable and removable sections for equipment access as well as specialty screens and filtration options. The EFD-637-MD-PH is 6" deep with 37-1/2° horizontal blades and the EPJ-445 is 4" deep with 45° blades.

Throat Opening

Support Angle

Insulation

Curb (by others)

Mitered Corner

Boxed Corner

EPJ-445

U.S. Embassy, Kazakhstan

‹ › Throat Opening‹ ›

‹ ‹

Curb (by others)‹

Support Angle‹

Insulation

Model

EFD-637-MD-PH

EPJ-445

Depth

6"

4"

BladeAngle

37.5°

45°

BladeStyle

Drainable

J - Blade

Material(6063-T5 Ext. Alum.)

0.081"

0.081"

Free Area(%) (Sq. Ft.)

59

51

9.5

8.1

Velocity(fpm)

990

689

Beginning Point of Water Penetration Ratings

Airflow(cfm)

9405

5549

PressureDrop (In. Wg.)

0.11

0.08

ALB May 2012

Finishes

Underground Railroad Museum, OH

Finish Type Description/Application Color Selection Warranty2-coat 100% FluoropolymerNewlar/Decaflon Meets AAMA2605. Dry film thickness 2 mil.Equivalent to Kynar 500®/Hylar5000®, Duranar®, Fluoropon®

2-coat Polyester Powder CoatMeets AAMA 2604. Dry filmthickness 2 mil. Equivalent toBaked Enamel.

Integral Color AnodizeAA-M10C22A42 (>0.7 mil)

Clear Anodize 215 R-1AA-M10C22A41 (>0.7 mil)

Alkyd Prime Coat

Mill

Our premier finish for extruded aluminum. Tough, long lasting, environmentally friendly powder coating has superiorcolor retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.

Environmentally friendly powder coating has good color retention and abrasive properties. Resists chalking, fading,chemical abrasion and weathering.

Electrochemically deposited inorganic color pigment whichis sealed to convert an aluminum oxidation into a corrosion resistant finish. Some shade variation will occur.

Electrochemically oxidized aluminum surface for uniform clearfinish. More resistant to natural oxidizing. Improved luster andless glossy than mill finish.

Preparation for field applied epoxy, vinyl, urethane, or other heavy-duty coatings. Must be finished within 60 months ofapplication. Contamination can occur in transmit and in the field;requires field cleaning prior to painting.

Aluminum or Galvanized Steel. Normal weathering will occur.

Standard Colors: 20 standardcolors plus Premium Pearlfinishes. Custom colors areavailable. Consult factory.

20 standard colors for aluminum products and acousticallouvers, 18 colors for steel. Customcolors are available. Consult factory.

Champagne; Light, Medium or DarkBronze; Black

Clear

N/A

N/A

5 Years (consult factory for availabilityof extended warrantyup to 20 years).

5 Years

5 Years

5 Years

N/A

N/A

Finishes enhance louver appearance by matching or contrasting with adjacent surfaces and extend weather resistance. Color matching is available upon request.

5101 Blue Mound Road, Fort Worth, Texas 76106 • Phone: 817-509-2300 • Fax: 817-831-3110 • www.alllite-louvers.com

Our superior performance paint systems are available in a wide range of colors and we can also custom color match to any of your specifications. Ourexpertise in applying architectural coatings assures you of a quality finish. With our options, you get the color you need when you need it!

PRODUCT FACTS