Louvers Penthouses Sunshades Grilles Sight Screens Selection …€¦ · Louvers Penthouses...
Transcript of Louvers Penthouses Sunshades Grilles Sight Screens Selection …€¦ · Louvers Penthouses...
SELE
CTI
ON
GU
IDE
Water Penetration Ratings
Model Blade Blade Blade Free Velocity Air Volume PageDepth Angle Style Area (fpm) (cfm)
1United States Court House, WA
Miami-Dade LouversECD-545-MDEFD-637-MDWind-Driven Rain LouversECV-445ECD-545ECD-635ECV-545ECV-645ECD-745EFJ-745Drainable LouversEFD-245EFD-435EFD-437EFD-445EFD-637EFD-645ERD-645Drainable-Head LouversEFJ-437-HPEFJ-637-HPNon-Drainable LouversEFJ-245EFY-245EFJ-430EFK-430EFJ-437EFK-437EFJ-445EFK-445EFY-445EFK-637EFJ-645Operable LouversEOJ-445EOD-445EOJ-637EOD-637Formed Metal LouversSFJ-245SFJ-430SFD-445SFJ-445SFK-445SFV-445SFJ-630SFD-635SFJ-645SFK-645Acoustical LouversEAA-645EAA-845SAJ-835SAJ-1235EAA-1245FAA-1245Combination LouversEBE-445EBI-445EXD-437EXD-645Sight ScreensHJ-445HJ-645HT-401HZ-200VT-250VT-654VV-400VV-500GrillesSunshadesPenthousesEFD-637-MDPHEPJ-445
5"6"
4"5"6"5"6"7"7"
2"4"4"4"6"6"6"
4"6"
2"2"4"4"4"4"4"4"4"6"6"
4"4"6"6"
2"4"4"4"4"4"6"6"6"6"
6"8"8"12"12"12"
4"4"4"6"
4"6"4"2-1/4"2"4"4"5"
6"4"
HorizontalHorizontal
VerticalHorizontalHorizontalVerticalVerticalHorizontalHorizontal
Thinline-DrainableDrainableDrainableDrainableDrainableDrainableRecessed-Drainable
High Performance-JHigh Performance-J
Thinline-JThinline-Inverted YJKJKJKInverted YKJ
Operable-JOperable-DrainableOperable-JOperable-Drainable
JJDrainableJKChevronJDrainableJK
Extruded-AirfoilExtruded AirfoilFormed-JFormed-JExtruded-AirfoilFormed-Airfoil
J-BD-ExhaustJ-BD-IntakeCombinationCombination
Horizontal-Inverted JHorizontal-Inverted JHorizontal AirfoilHorizontal-CladdingVertical-CladdingVertical-CladdingVertical-VVertical-V
Extruded AluminumExtruded Aluminum
46%59%
36%46%54%42%46%53%50%
43%58%58%47%59%55%51%
56%56%
47%38%57%57%57%57%50%50%39%50%50%
49%43%56%58%
42%51%53%48%48%38%65%62%50%50%
30%33%33%31%26%26%
49%49%45%44%
50%50%60%19%24%21%39%54%
59%51%
1250990
1250125012171250125011971250
955966903990990
1050990
912915
583383889889721721689689745832800
6831024810990
603847715775775600825815800800
980870808924999999
689689
11611050
————————
990689
92509405
71259250
1050883759250
1001810000
6494898483987425940592408059
82208226
43732336809080906547654755495549458966736416
5396709672829108
4040694560925991599136488580804464006400
470446114293452841964196
5396539683597455
————————
94055549
22
3333333
4444444
55
66666666666
7777
8888888888
999999
10101010
11111111111111111213
1414
45°37-1/2°
45°45°35°45°45°45°45°
45°35°37-1/2°45°37-1/2°45°45°
37-1/2°37-1/2°
45°45°30°30°37-1/2°37-1/2°45°45°45°37-1/2°45°
45°45°37-1/2°37-1/2°
45°30°45°45°45°45°30°35°45°45°
45°45°35°35°45°45°
45°45°37-1/2°37-1/2°– 45°
————————
37-1/2°45°
Miami-Dade Louvers
EFD-637-MD
Certified Ratings:All-Lite certifies that model ECD-545-MD shown hereon islicensed to bear the AMCA seal. The ratings shown arebased on test and procedures performed in accordancewith AMCA Publication 511 and comply with the require-ments of the AMCA Certified Ratings Program. The AMCACertified Ratings Seal applies to air performance, waterpenetration and wind-driven rain ratings.
Certified Ratings:All-Lite certifies that model EFD-637-MD shown hereon islicensed to bear the AMCA seal. The ratings shown arebased on test and procedures performed in accordancewith AMCA Publication 511 and comply with the require-ments of the AMCA Certified Ratings Program. The AMCACertified Ratings Seal applies to air performance andwater penetration ratings.
ECD-545-MD
Mosaic Condominiums, FL
(Sight Proof)
The EFD-637-MD and ECD-545-MD are engineered and tested to withstand extreme loads, debris impact, and cyclic fatigue failure associated with the severe weather effects of hurricanes (ECD-545-MD has Miami-Dade approval # 11-0429.02 and the EFD-637-MD has Miami-Dade approval # 11-0429.01).
Constructed from 6063-T5 extruded aluminum, both models have single section assemblies up to 48” wide by 144” high. Specially designed water-resistant seam covers further enhance performance and aesthetics of these industry leading products. Single-section louvers are now available with the option of a factory-installed sleeve which allows louver installation without any mechanical anchoring to the building condition.
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute peri-od. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin ofsafety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louver size having 39-3/8” x 39-3/8” core area.
6"
2
All-Lite architectural products are designed for use in most geographical areas within the United States. All-Lite can also design, modify or reinforce standard products for special requirements, such as high wind, heavy snow, industrial environments, specialmounting conditions, etc. Consult your local representative for more information.
5"
Maximum Size Wall Construction Installation Method
Single Section - 48"w x 144"hMultiple Section - Unlimited width x 144"h Multiple Section - 48"w x Unlimited Height
Structural steel mullion supportrequired for installations more than
one section wide.
Installations of unlimited width andheight available with additional
engineer-approved support structure.
All Types SteelDirect Connection - Clip angles*
MasonryTension or Shear Connection - Clip angles*
WoodDirect Connection - Clip angles*All Types (Single Section Only)
Flanged sleeve with continuous retaining angles(No anchors required)
*Anchors supplied by others
Model
ECD-545-MD
EFD-637-MD
Depth
5"
6"
BladeAngle
45°
37.5°
BladeStyle
Horizontal
Horizontal
Material(6063-T5 Ext. Alum.)
0.081"
0.081"
Free Area(%) (Sq. Ft.)
46
59
7.4
9.5
Class
A (29 mph)
-
Miami DadeApproval
#11-0429.02
#11-0429.01
Velocity(fpm)
1250
990
Beginning Point of Water Penetration Ratings
Airflow(cfm)
9250
9405
PressureDrop (In. Wg.)
0.22
0.11
‹ › ‹ ›
Wind-Driven Rain Louvers
ECV-445
ECV-445
ECV-645ECV-545
ECV-645ECV-545
ECD-545ECD-635 ECD-745EFJ-745
5"6"
5"6" 7"7"
Backed by AMCA certification our wind-driven rain louvers offer exceptional protection under the most severe conditions and areavailable in frame depths from 4" to 7". The closely spaced vertical blade design of the Florida Building Code approvedECV-645 provides our most effective wind-driven rain performance with 100% effectiveness at wind velocities up to 50 mph and rainfall up to 8 in/hr. When aesthetic requirements demand a more conventional horizontal blade profile our EFJ-745 is the idealsolution with 5" on center traditional J-blade fascia and 100% effectiveness @ 3 in/hr rainfall.
Certified Ratings:All-Lite certifies that model ECV-645 and EFJ-745 shown hereonare licensed to bear the AMCA seal. The ratings shown are basedon test and procedures performed in accordance with AMCAPublication 511 and comply with the requirements of the AMCACertified Ratings Program. The AMCA Certified Ratings Sealapplies to wind driven rain ratings.
Certified Ratings:All-Lite certifies that model ECV-445 shown hereon is licensed tobear the AMCA seal. The ratings shown are based on test andprocedures performed in accordance with AMCA Publication 511and comply with the requirements of the AMCA Certified RatingsProgram. The AMCA Certified Ratings Seal applies to wind driv-en rain and air performance ratings.
Certified Ratings:All-Lite certifies that model ECD-545, ECD-635, ECD-745 and ECV-545shown hereon are licensed to bear the AMCA seal. The ratings shown arebased on test and procedures performed in accordance with AMCAPublication 511 and comply with the requirements of the AMCA CertifiedRatings Program. The AMCA Certified Ratings Seal applies to water pen-etration ratings, air performance and wind driven rain ratings.
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of asimple linear regression of test data and the line of 0.01 ounces of water per square foot of free areaand is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration testprovides a method for comparing louver models and designs as to their efficiency in resisting the pene-tration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected witha reasonable margin of safety below the beginning point of water penetration in order to avoid unwantedpenetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louversize having 39-3/8” x 39-3/8” core area.
All-Lite architectural products are designed for use in most geographical areas within the United States. All-Lite can also design, modify or reinforce standard products for special requirements, such as highwind, heavy snow, industrial environments, special mounting conditions, etc. Consult your local representative for more information.
plan view
plan view
3
4"
Dallas Cowboys Stadium, TX
Model
ECV-445
ECD-545
ECD-635
ECV-545
ECV-645
ECD-745
EFJ-745
Depth
4"
5"
6"
5"
6"
7"
7"
BladeStyle
Vertical
Horizontal
Horizontal
Vertical
Vertical
Horizontal
Horizontal
Free Area(%) (Sq. Ft.)
36
46
54
42
46
53
50
5.7
7.4
8.6
6.7
7.4
8.4
8.0
WindVelocity
29 mph
29/50 mph
29 mph
29/50 mph
50 mph
29 mph
29 mph
Rainfall(In/Hr)
3
3/8
3
3/8
8
3
3
Class
A
A/B
B
A
A
A
A
VentilationRate (cfm)
3115
7196/7276
1998
7356/9485
1421
4531
6339
EffectivenessRatio (%)
99.8
100.0/97.9
96.6
99.9/99.6
100.0
99.9
100.0
Velocity(fpm)
1250
1250
1217
1250
1250
1197
1250
Wind-Driven Rain Ratings Beginning Point of Water Penetration Ratings
Airflow(cfm)
7125
9250
10508
8375
9250
10018
10000
PressureDrop (In. Wg.)
0.76
0.22
0.29
0.25
0.15
0.50
0.62
Florida BuildingCode Approval
-
#13683.1
-
-
#13683.2
-
-
‹ › ‹ › ‹ ›
‹
›
‹
›
Drainable LouversDrainable blade louvers are designed to prevent water penetration in non-wind-driven rainapplications by collecting water in the blade gutters and channeling it into frame down-spouts and away from airflow paths. Our ERD-645 incorporates a recessed mullion anddownspout that provides the appearance of a continuous drainable blade design.
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safetybelow the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.
EFD-435EFD-437EFD-637
EFD-245EFD-445EFD-645 ERD-645
4" 4"6" 6"
2"4"6"
Certified Ratings:All-Lite certifies that models EFD-435, EFD-437, EFD-445, EFD-637 andEFD-645 shown hereon are licensed to bear the AMCA seal. The ratingsshown are based on test and procedures performed in accordance withAMCA Publication 511 and comply with the requirements of the AMCACertified Ratings Program. The AMCA Certified Ratings Seal applies to airperformance and water penetration ratings. Models EFD-245 and ERD-645 are not licensed to bear the AMCA seal.
4
Columbus International Airport, OH
Model
EFD-245
EFD-435
EFD-437
EFD-445
EFD-637
EFD-645
ERD-645
Depth
2"
4"
4"
4"
6"
6"
6"
BladeAngle
45°
35°
37.5°
45°
37.5°
45°
45°
Free Area(%) (Sq. Ft.)
43
58
58
46
59
55
51
6.8
9.3
9.3
7.4
9.5
8.8
8.1
BladeStyle
Thinline-Drainable
Drainable
Drainable
Drainable
Drainable
Drainable
Recessed-Drainable
Material(6063-T5 Ext. Alum.)
0.081"
0.081"
0.081"
0.081"
0.081"
0.081"
0.081"
Velocity(fpm)
955
966
903
990
990
1050
990
Beginning Point of Water Penetration Ratings
Airflow(cfm)
6494
8984
8398
7425
9405
9240
8059
PressureDrop (In. Wg.)
0.14
0.12
0.13
0.14
0.11
0.15
0.11
Florida BuildingCode Approval
-
-
#13683.3
#13683.4
#13683.5
#13683.6
-
‹ › ‹ › ‹ › ‹ ›
Drainable Head Louvers
Certified Ratings:All-Lite certifies that model EFJ-437-HP shown hereon is licensed tobear the AMCA seal. The ratings shown are based on test and pro-cedures performed in accordance with AMCA Publication 511 andcomply with the requirements of the AMCA Certified RatingsProgram. The AMCA Certified Ratings Seal applies to air perform-ance and water penetration ratings. Model EFJ-637-HP is notlicensed to bear the AMCA seal.
EFJ-437-HP EFJ-637-HP
4" 6"
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free areaand is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the pene-tration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwant-ed penetration during severe storm conditions.
5Pennsylvania State University Chemical Laboratory, PA
Pennsylvania State University, PA
Model
EFJ-437-HP
EFJ-637-HP
Depth
4"
5"
Blade Angle
37.5°
37.5°
Blade Style
High Performance - J
High Performance - J
Material/Free Area(6063-T5 Ext. Alum.)
0.081"
0.081"
Velocity(fpm)
912
915
Beginning Point of Water Penetration Ratings
Airflow(cfm)
8220
8226
PressureDrop (In. Wg.)
0.14
0.12
Free Area(%) (Sq. Ft.)
56
56
9.0
9.0
Drainable head louvers blend the aesthetic appeal of a non-drainable blade with the high performance water penetration protection of a drainable blade louver These louvers incorporate a drainable head member to capture water that cascades down the face of the building and channels it into downspouts and away from the airflow paths.
These louvers are available in a wide array of anodized and painted finishes including custom color matching. They are available withan optional hidden vertical mullion
‹ › ‹ ›
Non-Drainable LouversAvailable in a wide array of blade shapes and frame depths non-drainable louvers offer value and economy for exhaust applications or intake conditions where protection against water infiltration is not critical. Optional hidden mullions provide a continuous blade appearance on multiple section assemblies. Ideally suited for special shapes and transitional designs.
Certified Ratings:All-Lite certifies that models EFJ-437, EFK-437, EFJ-445, and EFK-445 shown hereon are licensed to bear the AMCAseal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 andcomply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies toair performance and water penetration ratings. Models EFJ-245, EFY-245, EFJ-430, EFK-430, EFY-445, EFK-637, andEFJ-645 are not licensed to bear the AMCA seal.
EFY-245EFY-445
EFJ-245EFJ-445EFK-445EFJ-645
EFJ-430EFK-430
2"4"
2"4"6"
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute peri-od. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safe-ty below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.
4"6"
4"(102)
6
Clayton Elementary School, GA
EFJ-437EFK-437EFK-637
4"6"
Model
EFJ-245
EFY-245
EFJ-430/EFK-430
EFJ-437/EFK-437
EFJ-445/EFK-445
EFY-445
EFK-637
EFJ-645
Depth
2"
2"
4"
4"
4"
6"
6"
6"
BladeAngle
45°
45°
30°
37.5°
45°
45°
37.5°
45°
BladeStyle
Thinline – J
Thinline – Inverted
J/K
J/K
J/K
Inverted Y
K
J
Material(6063-T5 Ext. Alum.)
0.060"
0.060"
0.081"
0.081"
0.081"
0.081"
0.081"
0.081"
Free Area(%) (Sq. Ft.)
47
38
57
57
50
39
50
50
7.5
6.1
9.1
9.1
8.0
6.2
8.0
8.0
Velocity(fpm)
583
383
889
721
689
745
832
800
Beginning Point of Water Penetration Ratings
Airflow(cfm)
4373
2336
8090
6547
5549
4589
6673
6416
PressureDrop (In. Wg.)
0.06
0.06
0.09
0.07
0.08
0.18
0.05
0.10
Florida Building CodeApproval
-
-
-
#13683.7/13683.9
#13683.8/13683.10
-
-
‹ › ‹ › ‹ › ‹ ›
7
Operable LouversOperable blade louvers provide weather protection when open and positive shutoff when no airflow is required. These units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand crank; or automatically with electric or pneumatic actuators.
EOJ-445
4"
EOD-445
4"
EOD-637 EOJ-637
6"
The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measuredthrough a 48"x 48" louver during a 15 minute period. The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific labconditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.
6"
Model
EOJ-445
EOD-445
EOD-637
EOJ-637
Depth
4"
4"
6"
6"
BladeAngle
45°
45°
37.5°
37.5°
BladeStyle
Operable-J
Operable - Drainable
Operable - Drainable
Operable -J
Material(6063-T5 Ext. Alum.)
0.081"
0.081"
0.081"
0.081"
Free Area(%) (Sq. Ft.)
49
49
58
56
7.9
6.9
9.2
9.0
Velocity(fpm)
683
1024
990
810
Beginning Point of Water Penetration Ratings
Airflow(cfm)
5396
7096
9108
7282
PressureDrop (In. Wg.)
0.10
0.16
0.11
0.12
‹ › ‹ › ‹ › ‹ ›
8
Formed Metal LouversTypically formed from galvanized steel, these units offer an economical solution for basic ventilation requirements. Optionally available in a wide array of exotic metals including copper and stainless steel our formed metal louvers can also serve to accent building architecture or withstand corrosion in caustic environments.
SFV-445
4"
SFK-445SFJ-245SFJ-445SFJ-645SFK-645
2"4"6"
SFJ-430SFJ-630
4"6"
SFD-635
6"
SFD-445
4"
The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety belowthe beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.
Model
SFJ-245
SFJ-430
SFD-445
SFJ-445/SFK-445
SFV-445
SFJ-630
SFD-635
SFJ-645/SFK-645
Depth
4"
4"
4"
4"
4"
6"
6"
6"
BladeAngle
45°
30°
45°
45°
45°
45°
45°
45°
BladeStyle
J
J
Drainable
J/K
Chevron
J
Drainable
J
Material(Galvanized Steel)
20GA
20GA
20GA
20GA
20GA
20GA
20GA
20GA
Free Area(%) (Sq. Ft.)
42
51
53
48
38
65
62
50
6.7
8.2
8.5
7.7
6.1
10.4
9.9
8.0
Velocity(fpm)
603
847
715
775
600
825
815
800
Beginning Point of Water Penetration Ratings
Airflow(cfm)
4040
6945
6092
5991
3648
8580
8044
6400
PressureDrop (In. Wg.)
0.06
0.13
0.11
0.13
0.25
0.08
0.08
0.09
Valley Metro,Phoenix, AZ
‹ › ‹ › ‹ › ‹ › ‹ ›
9
Acoustical Louvers
8"12"
Certified Ratings:
All-Lite certifies that models SAJ-835, SAJ-1235, EAA-845 and FAA-1245, shown hereon is licensed tobear the AMCA seal. The ratings shown are based on test and procedures performed in accordance withAMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. TheAMCA Certified Ratings Seal applies to air performance and water penetration ratings. Models EAA-645and EAA-1245 are not licensed to bear the AMCA seal.
SAJ-835SAJ-1235
EAA-645EAA-845
EAA-1245FAA-1245
Recommended for installation in noisy environments, acoustical louvers incorporate insulated blades that restrict sound transmission through the louver over a wide range of frequencies. Our airfoil blade designs offer lower static pressure lossand softer aesthetics for critical airflow performance applications.
6"8" 12"
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and ismeasured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rain-fall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration duringsevere storm conditions.
West Refrigeration Plant, Washington D.C.
Model
EAA-645
EAA-845
SAJ-835
SAJ-1235
EAA-1245
FAA-1245
Depth
6"
8"
8"
12"
12"
12"
Blade Style
Extruded - Airfoil
Extruded - Airfoil
Formed - J
Formed - J
Extruded - Airfoil
Formed - Airfoil
Noise Reduction125 250 500 1K 2K 4K
Free Area(%) (Sq. Ft.)
30
33
33
31
26
26
4.8
5.3
5.3
4.9
4.2
4.2
11
8
13
15
13
13
11
8
13
17
14
14
13
10
19
22
17
17
16
14
26
27
19
19
18
15
28
31
18
18
17
13
23
28
17
17
Velocity(fpm)
980
870
808
924
999
999
Beginning Point of Water Penetration Ratings
Airflow(cfm)
4704
4611
4293
4528
4196
4196
PressureDrop (In. Wg.)
0.10
0.05
0.07
0.08
0.09
0.09
‹ › ‹ › ‹ ›
10
Combination LouversEXD Combination louvers feature stationary front blades and operable rear blades to ensure proper weather protection when open as well as a consistent appearance in both the open and closed positions. Optional low leakage seals provide further environmental protection in the closed position. Operable blade louvers provide weather protection when open and positive shutoff when no airflow is required. These units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand crank; or automatically with electric or pneumatic actuators.
EBE-445 and EBI-445 incorporate backdraft damper blades for automatic shutoff when there is no airflow and can be used for either exhaust and intake applications.
EBE-445
4"
EBI-445
4"
EXD-437
4"
EXD-645
Fixed Blades
Fixed Blades
OperableBlade
s
OperableBlade
sGravityBlades
GravityBlade
s
Fixed Blade
sFixed Blade
s
The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. All-Lite recommends that intake louvers are selected with a reasonable margin of safety belowthe beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.
6"(152)
6"
Loren Cook Facility, MO
Model
EBE-445
EBI-445
EXD-437
EXD-645
Depth
4"
4"
4"
4"
BladeAngle
45°
45°
37.5°
37.5° - 45°
BladeStyle
J-BD-Exhaust
J - BD-Intake
Combination
Combination
Material(6063-T5 Ext. Alum.)
0.081"
0.081"
0.081"
0.081"
Free Area(%) (Sq. Ft.)
49
49
45
44
7.9
7.9
7.2
7.1
Velocity(fpm)
689
689
1161
1050
Beginning Point of Water Penetration Ratings
Airflow(cfm)
5396
5396
8359
7455
PressureDrop (In. Wg.)
0.10
0.10
0.16
0.19
‹ › ‹ › ‹ › ‹ ›
11
Sight ScreensWhether the design calls for total sight concealment, partial screening, high volume airflow, specialty shapes, or thermal shading our sight screens are engineered to meet the most stringent project parameters while satisfying exacting aesthetic requirements. The unique concealed support system of the HT-401 ensures proper structural support and a true continuous blade look without the use of unsightly frames or vertical angles.
HJ-445HJ-645
VT-250 VT-654 VV-500 VV-400
plan viewplan view
plan viewplan view
HZ-200 HT-401
21/2 "
4"6"
4"21/4"
5" 4"4"
Valet at Collins Park, FL
Model
HJ-445
HJ-645
HT-401
HZ-200
VT-250
VT-654
VV-400
VV-500
Blade Depth
4"
6"
4"
2-1/4"
2-1/2"
4"
4"
5"
Blade Style
Horizontal - Inverted J
Horizontal - Inverted J
Horizontal - Airfoil Tube
Horizontal - Cladding
Vertical - Cladding
Vertical - Cladding
Vertical - V
Vertical - V
Free Area (%)
50
50
60
19
24
21
39
54
‹› ‹
›
‹
›
‹
›
‹ › ‹ ‹ ‹ ›
Grilles Custom designed to meet each project’s unique requirements our extruded aluminum grilles are ideally suited for architectural accents, facades, screening and security barriers either inside or outside the building. In addition to traditional welded construction we can engineer unique and creative concealed fastening systems and hidden weld joints that offer improved aesthetics and superior structural integrity.
The illustrated designed for these Bar Grilles were created to a design load of 30lbs per square foot. Changes may be required to accommodate other design loads.
Angle
Offset
Bar Continuous
12
Angle Grille
Angle Grille Installed Sentry
Model
All-Lite Standard Grilles
Material/Free Area(6063-T5 Ext. Alum.)
0.125" thick
Minimum Size
12" x 12"
Maximum Size
Single Section: 60" x 180"
One Dimension must be 60"
Sunshades
Airfoil Rectangular Tube J-Blade
Blade Styles
Outriggers
Concealed Connection
Shroud Connection Strut Connection
Exposed Connection
Connections
Fascia
Our sunshades provide distinctive architectural style to a building’s exterior while considerably reducing glare. They do not cause snow load or water infiltration problems associated with solid membrane awnings. Sunshades also reduceheat from sunlight in the summer. This keeps the building cool and saves energy, ideal for sustainable or “green” building construction. Configured to meet each project’s individual requirements, our team can transform even the most complexconcepts into a stunning reality. Our standard sunshade information is shown below.
13
Flat Bar RadiusDouble Tapered RadiusRound Rectangular
Model DepthSSA-445 4"SSA-645 6"SSA-845 8"
Model DepthSSR-445 4"SSR-645 6"SSR-845 8"
Model DepthSSJ-445 4"SSJ-645 6"
Gull Lake High School, MI
Curtain Wall Connection
14
PenthousesAccommodating individual job requirements, penthouses are constructed to virtually any dimension. For added performance and flexibility these units are available with most louver models and include mitered or box corner designs, insulated roof systems, operable and removable sections for equipment access as well as specialty screens and filtration options. The EFD-637-MD-PH is 6" deep with 37-1/2° horizontal blades and the EPJ-445 is 4" deep with 45° blades.
Throat Opening
Support Angle
Insulation
Curb (by others)
Mitered Corner
Boxed Corner
EPJ-445
U.S. Embassy, Kazakhstan
‹ › Throat Opening‹ ›
‹ ‹
‹
Curb (by others)‹
Support Angle‹
Insulation
‹
Model
EFD-637-MD-PH
EPJ-445
Depth
6"
4"
BladeAngle
37.5°
45°
BladeStyle
Drainable
J - Blade
Material(6063-T5 Ext. Alum.)
0.081"
0.081"
Free Area(%) (Sq. Ft.)
59
51
9.5
8.1
Velocity(fpm)
990
689
Beginning Point of Water Penetration Ratings
Airflow(cfm)
9405
5549
PressureDrop (In. Wg.)
0.11
0.08
ALB May 2012
Finishes
Underground Railroad Museum, OH
Finish Type Description/Application Color Selection Warranty2-coat 100% FluoropolymerNewlar/Decaflon Meets AAMA2605. Dry film thickness 2 mil.Equivalent to Kynar 500®/Hylar5000®, Duranar®, Fluoropon®
2-coat Polyester Powder CoatMeets AAMA 2604. Dry filmthickness 2 mil. Equivalent toBaked Enamel.
Integral Color AnodizeAA-M10C22A42 (>0.7 mil)
Clear Anodize 215 R-1AA-M10C22A41 (>0.7 mil)
Alkyd Prime Coat
Mill
Our premier finish for extruded aluminum. Tough, long lasting, environmentally friendly powder coating has superiorcolor retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.
Environmentally friendly powder coating has good color retention and abrasive properties. Resists chalking, fading,chemical abrasion and weathering.
Electrochemically deposited inorganic color pigment whichis sealed to convert an aluminum oxidation into a corrosion resistant finish. Some shade variation will occur.
Electrochemically oxidized aluminum surface for uniform clearfinish. More resistant to natural oxidizing. Improved luster andless glossy than mill finish.
Preparation for field applied epoxy, vinyl, urethane, or other heavy-duty coatings. Must be finished within 60 months ofapplication. Contamination can occur in transmit and in the field;requires field cleaning prior to painting.
Aluminum or Galvanized Steel. Normal weathering will occur.
Standard Colors: 20 standardcolors plus Premium Pearlfinishes. Custom colors areavailable. Consult factory.
20 standard colors for aluminum products and acousticallouvers, 18 colors for steel. Customcolors are available. Consult factory.
Champagne; Light, Medium or DarkBronze; Black
Clear
N/A
N/A
5 Years (consult factory for availabilityof extended warrantyup to 20 years).
5 Years
5 Years
5 Years
N/A
N/A
Finishes enhance louver appearance by matching or contrasting with adjacent surfaces and extend weather resistance. Color matching is available upon request.
5101 Blue Mound Road, Fort Worth, Texas 76106 • Phone: 817-509-2300 • Fax: 817-831-3110 • www.alllite-louvers.com
Our superior performance paint systems are available in a wide range of colors and we can also custom color match to any of your specifications. Ourexpertise in applying architectural coatings assures you of a quality finish. With our options, you get the color you need when you need it!
PRODUCT FACTS