Load Estimation Presented By : Parth Prajapati Mechanical Engineering Department

Transcript of Load estimation in Air Conditioning

Page 1: Load estimation in Air Conditioning

Load Estimation

Presented By : Parth Prajapati Mechanical Engineering Department

Page 2: Load estimation in Air Conditioning

Introduction Heating and cooling load calculations are carried out to estimate the

required capacity of heating and cooling systems. Information regarding indoor and outdoor conditions, specifications of

the building, specifications of the conditioned space, occupancy,

equipment used should be known. Comfort applications : on basis of thermal comfort Industrial or commercial applications : on basis of particular processes

being performed or products being stored.

Page 3: Load estimation in Air Conditioning

Heating Load Heating Load Calculations are carried out to estimate the amount heat

energy that should be added to the building to arrive at required heating

capacities. During winter, peak heating load occurs before sunrise and after sunset. Internal heat sources are beneficial as they assist in heat addition

process. Normally, to simplify the problem, heat load calculations are carried out

assuming steady state conditions i.e. no solar radiation and steady

outdoor conditions and neglecting internal sources This is simple but it leads to over-estimation of the heating capacity For accurate results, each and every factor should be taken into account

which makes the calculation complex

Page 4: Load estimation in Air Conditioning

Cooling Load For cooling load calculations, one has to consider unsteady outdoor

conditions (as the peak load occurs during the daytime) In addition, all internal sources and solar radiation will have their effect on

the average room temperature and neglecting them would lead to under-

estimation of the required system. Thus cooling load are more complicated as it involves unsteady equations

with unsteady boundary conditions.

Page 5: Load estimation in Air Conditioning

Outside Temperature For any building there exists a balance point at which the solar radiation

(Qsolar) and internal heat generation rate (Qint) exactly balance the heat

losses from the building.

where UA is the product of overall heat transfer coefficient and heat

transfer area of the building, Tin is the required indoor temperature and Tout

is the outdoor temperature.

Page 6: Load estimation in Air Conditioning

Outside Temperature If the outdoor temperature is greater than the balanced outdoor

temperature given by the above equation, i.e., when T(out) > T(out,bal),

then there is a need for cooling the building. On the other hand, when the outdoor temperature is less than the

balanced outdoor temperature, i.e., when T(out) < T(out,bal), then there

is a need for heating the building. When the outdoor temperature exactly equals the balanced outdoor

temperature, i.e., when T(out) = T(out,bal), then there is no need for

either cooling or heating the building

Page 7: Load estimation in Air Conditioning

Outside Temperature For residential buildings (with fewer internal heat sources), the balanced

outdoor temperature may vary from 10 to 18oC. A cooling system is

required when the outdoor temperature exceeds 18oC. If the building is well insulated (small UA) and/or internal loads are high,

then the balanced outdoor temperature will reduce leading to extended

cooling season and shortened heating season. If there are no internal heat sources and if the solar radiation is negligible,

then from the heat balance equation, Tout,bal = Tin. This implies that if

the outside temperature exceeds the required inside temperature (say,

25oC for comfort) then there is a need for cooling otherwise there is a need

for heating.

Page 8: Load estimation in Air Conditioning

Methods of Estimation Generally, heating and cooling load calculations involve a stepwise

procedure, taking into account all the building energy flows. Variety of methods ranging from simple rules-of-thumb (based on

assumptions) to complex Transfer Function Methods are used in

practice to arrive at the building loads. Thumb rules are useful in preliminary estimation of the equipment size

and cost. The main conceptual drawback of rules-of-thumb methods is

the presumption that the building design will not make any difference.

Thus the rules for a badly designed building are typically the same as for a

good design.

Page 9: Load estimation in Air Conditioning

Required Cooling capacities for various applications based on rules-of-thumb

Page 10: Load estimation in Air Conditioning

Methods of Estimation More accurate load estimation methods involve a combination of analytical

methods and empirical results obtained from actual data, For example the use of Cooling Load Temperature Difference (CLTD)

for estimating heat gain and the use of Solar Heat Gain Factor (SHGF)

for estimating heat transfer through arrangement of windows in a building. Widely used by air conditioning engineers. Accurate results and

estimations can be carried out manually in a relatively short time. More accurate methods that require the use of computers have been

developed for estimating cooling loads, e.g. Transfer Function Method

(TFM). These methods are expensive and time consuming they are generally

used for estimating cooling loads of large commercial or institutional

buildings.

Page 11: Load estimation in Air Conditioning

Cooling Load Calculations Design cooling load takes into account all the loads experienced by a

building under specific set of assumed conditions. Assumptions:

Outside conditions are selected from a long term statistical database.

Design data for outside conditions for various locations of the world

have been collected and are available various handbooks. The load on the building due to solar radiation is estimated for clear

sky conditions. The building occupancy is assumed to be at full design capacity. All building equipment and appliances are considered to be operating

at rated capacity

Page 12: Load estimation in Air Conditioning

Cooling Load Calculations External Load: It consists of heat transferred through the building

envelope (walls, roof, floor, windows, doors etc.) Internal Load: Heat generated by occupants, equipment, and lights. The percentage of external versus internal load varies with building type,

site climate, and building design. The total cooling load on any building consists of both sensible as well as

latent load components. The sensible load affects dry bulb temperature, while the latent load

affects the moisture content of the conditioned space.

Page 13: Load estimation in Air Conditioning

Sensible Load Heat flowing into the building by conduction through exterior walls, floors,

ceilings, doors and windows Heat received from solar radiation Heat given off by lights, motors, machinery, cooking operations, industrial

processes etc. Heat liberated by occupants Heat carried out by outside air which leaks in through the cracks in doors,

windows and through frequent openings

Page 14: Load estimation in Air Conditioning

Latent Load Heat gain due to moisture in the outside air entering by infiltration Heat gain due to condensation of moisture from occupants The heat gain due to condensation of moisture from any process such as

cooking foods etc. Heat gain due to moisture passing directly into the conditioned space

through permeable walls or partitions from the outside region where the

water vapour pressure is higher

Page 15: Load estimation in Air Conditioning

Heat transfer through conduction

Page 16: Load estimation in Air Conditioning

Heat transfer through conduction

Page 17: Load estimation in Air Conditioning

Overall Heat Transfer Coefficient

Page 18: Load estimation in Air Conditioning

Sensible heat gain through outside walls and roofs

Temperature of wall rises with rise in outside air temperature and the heat

is stored in wall which has a considerable storage capacity. Thus the heat transferred to the room is reduced. The stored heat in wall is given off to the room when the outside air

temperature falls. Shaded area above the actual load shows

the heat stored and below the actual load

shows the heat released by the walls and

other structures

Page 19: Load estimation in Air Conditioning

Sensible heat gain through outside walls and roofs

A convenient method of taking into account this lagging effect is to use an

equivalent temperature differential.

Page 20: Load estimation in Air Conditioning

Sol Air Temperature

A hypothetical temperature used to calculate the heat received by the

outside surface of a building wall by the effect of convection and radiation.

Page 21: Load estimation in Air Conditioning

Heat gain due to infiltration

Heat transfer due to infiltration consists of both sensible as well as latent

components. The sensible heat transfer rate due to infiltration is given by:

The latent heat transfer rate due to infiltration is given by:

The infiltration rate is obtained by using either the air change method or the

crack method. Air changes per hour, or air change rate, is a measure of the air volume

added to or removed from a space (normally a room or house) divided by the

volume of the space. If the air in the space is either uniform or perfectly mixed, air changes per hour

is a measure of how many times the air within a defined space is replaced.

Page 22: Load estimation in Air Conditioning

The infiltration rate by the crack method is given by: where A is the effective leakage area of the cracks, C is a flow coefficient

which depends on the type of the crack, ΔP is the difference between

outside and inside pressure and n is an exponent whose value depends

on the nature of the flow in the crack. The pressure difference ΔP arises due to pressure difference due to the

wind (ΔPwind), pressure difference due to the stack effect (ΔPstack) and

pressure difference due to building pressurization (ΔPbld)

Heat gain due to infiltration

Page 23: Load estimation in Air Conditioning

heat transfer depends mainly on the population and activity level of the

occupants.

Heat Gain from occupants

Page 24: Load estimation in Air Conditioning

Heat Gain through power equipments

For other equipment such as computers, printers etc, the load is in the form

of sensible heat transfer and is estimated based on the rated power

consumption.

Page 25: Load estimation in Air Conditioning

If the cooling coil has a some by-pass factor, then some amount of

ventilation air directly enters the conditioned space, which becomes a part

of the building cooling load. The sensible and latent heat transfer rates due to the by-passed

ventilation air can be calculated by replacing V with (V x BPF) In addition to this, sensible and latent heat transfer to the building also

occurs due to heat transfer and air leakage in the supply ducts.

Miscellaneous External Load

Page 26: Load estimation in Air Conditioning

Overall Balance