8
2575 Metropolitan Drive, Trevose, PA 19053 USA TEL: (800) 872 0879 FAX:(215) 244 4208 www.evenlite.com Project name: Approved By: Catalog No: Type No: LiteMinder Fast Transfer System 1.0 to 18.75KVA LED Compatible LM Series Inverter Pure Sine Wave Modular Inverter Technology ARRA Compliant for Levels 1&2 Modularity: LiteMinder features unique inverter modules available in increments from 1.0 to 18.75 KVA capacities(see ordering guide). Modules are interconnected to build the required system capacity, and can even be field upgraded to increase system sizes ! Modules can be configured to provide Single Phase, Split Phase, and Three Phase outputs thereby eliminating costly, inefficient external transformers. Control Features: A keypad and LCD display provides user interface and extensive status diagnostics. Self-test, Self-Diagnostics in compliance with UL 924 is field configurable, and stores 1,000 Test, Event and Alarm logs thereby eliminating the need for costly manual test and data recording. Web Site Monitoring: unique web interface constantly monitors the system status and records all essential data. Users can log on, view, interact and download records as needed. The factory can also monitor, diagnose remotely. Diagnostics: In addition to Self-test, Self- Diagnostics, LiteMinder also includes unique startup diagnostics to aid in installation and maintenance: Eight individual startup alarms (Communications, Set-Up Conflict, Low Battery, Back-feed, Transfer/AC Fuse, Short/Overload, Miswire, Incorrect AC Input) eight individual Charger Alarms and eight individual Inverter Alarms. MODULAR AC SYSTEM Evenlite’s LiteMinder Central Inverter System provides an innovative Emergency Lighting solution for today’s complex energy saving systems, light sources and maintenance requirements. The LiteMinder represents the pinnacle of engineering excellence with features not found in the traditional systems currently available:

Transcript of LiteMinder - Evenlite · Evenlite’s LiteMinder Central Inverter System provides ... Output VA,...

2575 Metropolitan Drive, Trevose, PA 19053 USATEL: (800) 872 0879 • FAX:(215) 244 4208 • www.evenlite.com

Project name: Approved By:

Catalog No: Type No:

LiteMinderFast Transfer System

1.0 to 18.75KVA LED Compatible

LM Series InverterPure Sine Wave Modular

Inverter Technology

ARRA Compliant for Levels 1&2

• Modularity:LiteMinder features unique inverter modules available in increments from 1.0 to 18.75 KVA capacities(see ordering guide). Modules are interconnected to build the required system capacity, and can even be field upgraded to increase system sizes ! Modules can be configured to provide Single Phase, Split Phase, and Three Phase outputs thereby eliminating costly, inefficient external transformers.

• ControlFeatures: A keypad and LCD display provides user interface and extensive status diagnostics. Self-test, Self-Diagnostics in compliance with UL 924 is field configurable, and stores 1,000 Test, Event and Alarm logs thereby eliminating the need for costly manual test and data recording.

• WebSiteMonitoring: unique web interface constantly monitors the system status and records all essential data. Users can log on, view, interact and download records as needed. The factory can also monitor, diagnose remotely.

• Diagnostics:In addition to Self-test, Self-Diagnostics, LiteMinder also includes unique startup diagnostics to aid in installation and maintenance: Eight individual startup alarms (Communications, Set-Up Conflict, Low Battery, Back-feed, Transfer/AC Fuse, Short/Overload, Miswire, Incorrect AC Input) eight individual Charger Alarms and eight individual Inverter Alarms.

MoDuLAr AC SySTEM

Evenlite’s LiteMinder Central Inverter System provides an innovative Emergency Lighting solution for today’s complex energy saving systems, light sources and maintenance requirements. The LiteMinder represents the pinnacle of engineering excellence with features not found in the traditional systems currently available:

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LiteMinder Modular Fast Transfer Sine Wave Inverter

LM-MOD 10 /17

Warranty: (For full warranty details see warranty data sheet CPS-WAR)

Electronics: Evenlite Inc. warrants the LM series electronics assembly (except batteries) against defects in material and workmanship for a period of two years or three years with Factory Startup option.Battery: Evenlite Inc. warrants the LC series Lead Calcium batteries carry a 1 year full, 9 year pro-rated limited warranty.

• PWM MOSFET and IGBT ( Model Dependant) Inverter provide Pure Sine Wave output with less than 3% THD, and fully compatible with LED Lighting Loads

• Fast transfer for H.I.D. compatibility ensures smooth operation of combined lighting loads, transfers in less than 2 mS

• Modular inverter allows operation for single phase or three phase operation to order

• Less than 3% THD, load power factor 0.5 Lag to 0.5 Lead, 98% efficient in standby mode

• Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC

• Automatic restart upon utility power return, no need to manually reset the system

• Input circuit breaker is provided sized to system rating

• Shorted circuit protected to 65KAIC tested and approved to UL 6180-5-1 standard

• UL924 compliant Self-Test/Self-Diagnostics are standard, with interactive LCD display

• Monthly and the annual 90 minute test can be programmed by the user for a specific date and time to ensure NFPA Code Compliance

• Up to 1000 events stored in the memory log on a “FIFO” basis, and is easily accessible thru the MMI

• MMI (Man-Machine Interface) consists of a 5 button keypad for easy menu navigation

• A 4x20 backlit White display with heads-up LED’s allow for a quick diagnosis of the system status and alarms

• Five LED indicators provide the status of the Inverter, Charger, AC present, Ready, and Switched Load (if provided with Switched Output Circuit Breakers)

• An additional six LED indicators provide the alarm status for Alarm Summary, Bypass (if equipped with Maintenance Bypass option) , CB Trip, Startup Fault, Charger Fault, and Inverter Fault

• A dedicated System Test button is provided for a user initiated 30 second on demand test

• An Alarm On/Off LED is provided to indicate that an audible alarm is present.

• A dedicated Alarm Silence On/Off push button allows the user the silence the audible alarm

• SD card slot allows the user to download all Test, Event and Alarm Logs

• The Meter Menu allows the user to access the Input and Output Voltages, Output Current, Output VA, Battery Voltage, Battery Current, Battery Power, Temperature, System Days, Inverter minutes and Inverter Events

• Crest factor >4 for high inrush demanding loads, overload 120 percent for 10 minutes, 400 percent for 500mS

• The inverter and battery cabinets are constructed from 14 gauge CRS and are powder painted with no visible outside bolts or hardware

• Internally the inverter has all galvanized or painted steel parts for all modules and shelves to resist corrosion and provide high durability

• Installer friendly front mounted battery terminals for easier and faster installation

• VRLA Maintenance Free Lead Calcium Battery’s provide the required 90 minute minimum run time

• Battery recharge time is less than 24 hours, meets all UL 924 and NFPA101 Life Safety Code requirements

• Operating temperature 20˚ to 30˚ C

• Three Rate Charger circuit is fully temperature compensated for added reliability

• Brownout protection set for 85% of the nominal line voltage

• Electronics are warranted for 2 years and the VRLA batteries have a 10 year warranty, optional factory startup increases the warranty to 3 years

• Listed to UL924, and meets NFPA101 Life Safety Code, NFPA70-NEC and OSHA Requirements,1.0-2.8KVA models meet CSA C22.2 No. 141-10

LiteMinder Modular Fast Transfer Sine Wave InverterorDErING GuIDE Single Phase

LM

Model VARating PhaseConfiguration InputVoltage OutputVoltage OutputBreakerConfiguration Options

LM 1000VA1600VA2200VA2800VA3000VA4200VA5200VA6250VA8250VA10500VA12500VA

1P Single Phase 120 or 277(L-N)

IA 120V (L-N)

IB 277V (L-N)

OA 120V (L-N)

OB 277V (L-N)

*C(n)20A Normally On Output Breaker

*O(n)20A Normally Off Output Breaker

*S(n)20A Switched Output Breaker

(n) = Quanity Required

BB Indicates Special Breaker Current Requirement, Contact Factory

QuantityLimitations(Any combination of output types)1000VA8 x 20 A without TA option4 x Normal Off With or Without TA Option4 x Switched With or Without TA Option5 x 20A with TA Option1600-3000VA12 x 20 A without TA option4 x Normally off With or Without TA

Option4 x Switched With or Without TA Option8 x 20A with TA Option4200-12500VA24 x 20 A without TA option

6 x Normally Off With or Without TA Option

6 x Switched With or Without TA Option16 x 20A with TA Option

*TATrip Alarm for all circuit breakersTB 1 Summary / 2 programmable terminal

block for form C dry contactsMB Maintenance Bypass Switch

(make before break)DT Delayed Transfer, 60 msZ4 Seismic Zone 4 certified

M(n) Maintenance Plan, n= years (5 max.)EW Extended Warranty to 5 Years

(EW requires FS)

FSStartup commissioning on Site

WM Wall Mount Kit (1KW only)

*Maximum Number of Breaker Trip Alarms Model Dependant

Example: LM-12500-1P-IB-OB-S4-TA-FS

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LM-MOD 10/17

Model No of Cabinets

Width Height Depth Weight Inverter Cabinet

*Weight Battery Cabinet

**Total Shipping Weight

Max. BTU’s/Hr.

at Full Load

LM1000 1 24” 38” 13” 308 lbs. N/A 343 lbs. 68

LM1600 1 32” 52” 13.75” 522 lbs. N/A 552 lbs. 109

LM2200 1 32” 52” 13.75” 600 lbs. N/A 635 lbs. 150

LM2800 1 32” 52” 13.75” 678 lbs. N/A 713 lbs. 190

LM3000 1 32” 52” 13.75” 696 lbs. N/A 731 lbs. 209

LM4200 1 32” 50” 23” 980 lbs. N/A 1,030 lbs. 286

LM5200 1 32” 50” 23” 1,140 lbs. N/A 1,190 lbs. 355

LM6250 1 32” 50” 23” 1,300 lbs. N/A 1,350 lbs. 426

LM8250 2 32” 50” 23” 375 lbs. 1,570 lbs. 2,020 lbs. 563

LM10500 2 32” 50” 23” 375 lbs 1,890 lbs. 2,340 lbs. 716

LM12500 2 32” 50” 23” 375 lbs. 2,210 lbs. 2,660 lbs 852

* Battery cabinet weight is with batteries installed ** Total shipping weight includes pallets and packaging

LiteMinder Modular Fast Transfer Sine Wave InverterorDErING GuIDE Split & Two Phase

LM

Model VARatingPhaseConfiguration

InputVoltage OutputVoltage OutputBreakerConfiguration Options

LM 2200VA4200VA5200VA6250VA8250VA10500VA12500VA

1S Split Phase

2P Two Phase

ID 120V/120V/240V L-N / L-N / L-L 3 Wire + Ground

IC 120V/120V/208VIE 277V/277V/480V L-N / L-N / L-L

3 Wire + Ground

OD 120V/120V/240V L-N / L-N / L-L 3 Wire + Ground

OC 120V/120V/208V OE 277V/277V/480V L-N / L-N / L-L

3 Wire + Ground

*C(n)20A Normally On Output Breaker

*O(n)20A Normally Off Output Breaker

*S(n)20A Switched Output Breaker

(n) = Quanity Required

BB Indicates Special Breaker Cur-rent Requirement, Contact Factory

QuantityLimitations(Any combination of output types)

4200-10500VA24 x 20 A without TA option

6 x Normally Off With or Without TA Option

6 x Switched With or Without TA Option

16 x 20A with TA Option

*TATrip Alarm for all circuit breakersTB 1 Summary / 2 programmable

terminal block for form C dry contacts

MB Maintenance Bypass Switch (make before break)

DT Delayed Transfer, 60 ms Z4 Seismic Zone 4 Certified

M(n) Maintenance Plan, n= years (5 max.)EW Extended Warranty to 5 Years

(EW requires FS)

FSStartup commissioning on Site

*Maximum Number of Breaker Trip Alarms Model Dependant

Example: LM-12500-2P-ID-OD-S4-TA-Z4-FS

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LM-MOD 10/17

Model No of Cabinets

Width Height Depth Weight Inverter Cabinet

*Weight Battery Cabinet

**Total Shipping Weight

Max. BTU’s/Hr.

at Full Load

LM2200 2 24” 38” 13” 180 lbs 420 lbs. 670 lbs. 150

LM4200 2 32” 50” 23” 350 lbs. 680 lbs. 1,030 lbs. 286

LM5200 2 32” 50” 23” 350 lbs. 840 lbs. 1,190 lbs. 355

LM6250 2 32” 50” 23” 350 lbs. 1,000 lbs. 1,350 lbs. 426

LM8250 2 32” 50” 23” 375 lbs. 1,570 lbs. 2,020 lbs. 563

LM10500 2 32” 50” 23” 375 lbs 1,890 lbs. 2,340 lbs. 716

LM12500 2 32” 50” 23” 375 lbs. 2,210 lbs. 2,660 lbs 852

* Battery cabinet weight is with batteries installed ** Total shipping weight includes pallets and packaging

LiteMinder Modular Fast Transfer Sine Wave Inverter

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LM-MOD 10/17

orDErING GuIDE Three PhaseLM

Model VARatingPhaseConfiguration

InputVoltage OutputVoltage OutputBreakerConfiguration Options

LM 3000VA5200VA8250VA10500VA12500VA15750VA18750VA

3P Three Phase 120/208 or 277/480

IF 120V/208 L-N//L-L

IG 277V/480V L-N/L-L

4 wire + Ground

OF 120V/208 L-N//L-L

OG 277V/480V L-N/L-L

4 wire + Ground

*C(n)20A Normally On Output Breaker

*O(n)20A Normally Off Output Breaker

*S(n)20A Switched Output Breaker*(n) = Quantity Required

BB Indicates Special Breaker Current Requirement, Contact Factory

QuantityLimitations(Any combination of output types)3000VA6 x 20 A without TA option3 x Switched With or Without TA

Option3 x 20A with TA Option4200-5200VA12 x 20 A without TA option6 x Switched With or Without TA

Option8 x 20A with TA Option8250-18750VA24 x 20 A without TA option

6 x Switched With or Without TA Option

16 x 20A with TA Option

*TATrip Alarm for all circuit breakersTB 1 Summary / 2 programmable ter-

minal block for form C dry contactsMB Maintenance Bypass Switch

(make before break)DT Delayed Transfer, 60 msZ4 Seismic Zone 4 Certified

M(n) Maintenance Plan, n= years (5 max.)EW Extended Warranty to 5 Years

(EW requires FS)

FSStartup commissioning on Site

*Maximum Number of Breaker Trip Alarms Model Dependant

Example: LM-15750-3P-IG-OG-S6-TA-MB-FS

Model No of Cabinets

Width Height Depth Weight Inverter Cabinet

*Weight Battery Cabinet

**Total Shipping Weight

Max. BTU’s/Hr. at Full Load

LM3000 2 24” 38” 13” 218 lbs. 576 lbs. 820 lbs. 205

LM5200 2 32” 50” 23” 565 lbs. 1,060 lbs. 1,890 lbs. 355

LM8250 2 32” 50” 23” 565 lbs. 1,532 lbs. 2,210 lbs. 563

LM10500 2 32” 50” 23” 565 lbs. 1,850 lbs. 2,530 lbs. 716

LM12500 3 32” 50” 23” 565 lbs 2,161 lbs. 2,850 lbs. 853

LM15750 3 32” 50” 23” 565 lbs. 2,908 lbs. 3,630 lbs. 1,074

LM18750 3 32” 50” 23” 565 lbs. 3,380 lbs. 4,120 lbs. 1,279

* Battery cabinet weight is with batteries installed ** Total shipping weight includes pallets and packaging

LiteMinder Modular Fast Transfer Sine Wave Inverter

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LM-MOD 10/17

Mounting Slot Detail

1.38.31 Dia. holes for1/4” hardwareFloor MountingBrackets andCabinet to CabinetVertical Mounting

.75 x 2.13Slot forFloorMounting

AC Breaker Panel

24

4.0

38

Bracket, Floor Mounting

3 feet minimum clearancein front of all units

Man MachineInterface Panel

Master Inverter Cabinet

Floor Mounting Bolt Pattern

21.00

Mounting SlotSee Detail

Inter-cabinet Battery CablePorts for Vertical Mounting

9.97

1.51.5

21.6

30.3

Knockout patternidentical to left side

13

6x 2.0

3824.5

4x 1.75

2.56.5

Right Side

Top

4x 2.50

24

17.25 2.50

2x 1.75

16x dual knockout1-1/8” and 7/8” dia.

OverallMechanicalDimensions1KVASingleCabinet

LiteMinder Modular Fast Transfer Sine Wave Inverter

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LM-MOD 10/17

13.75

9.75

2.00

4x .88 and 1.13knockoutseach sideof cabinet

2x 1.75

2x 1.75

2.50 2x 2.50

32.00

27.00

45.00

6.504.00

16.00

7.86

55.00

45.87

35.53

4x .76 x 2.26slot

29.001.50

1.71

2x 10,46

6x .88 and 1.13knockouts forAC connection

Floor Mounting Bolt Pattern

12 Circuit BreakerPanel location

MMI InterfacePanel

36.00 min.clearancein front ofall units

OverallMechanicalDimensions1.6-3.0KVASingleCabinet

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

LiteMinder Modular Fast Transfer Sine Wave Inverter

LM-MOD 10/17

Page 8

23.036”Min.

4.0

50.0

32.0

Clearancein front ofall units

Floor Mounting Bolt Pattern

26.84

O.406x per cabinetmounting holes

2.57

2x 13.28

2x 6.64

4.86

Inverter Cabinet

36.3

12 Circuit Breaker Panel location

MMIInterface Panel

37.6

2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com

Page 8

23.036”Min.

4.0

50.0

32.0

Clearancein front ofall units

32.0

Floor Mounting Bolt Pattern

5.16 3x 26.84

O.406x per cabinet

mounting holes

2.57

2x 13.28

2x 6.64

4.86

Inverter Cabinet

Battery Cabinet No. 1 Battery Cabinet No. 2

Cabinet Configuration

Single Phase 16 - 24 Batteries - 1 Inverter cabinet, 1 Battery cabinet

Three Phase 8 - 24 Batteries - 1 Inverter cabinet, 1 Battery cabinetThree Phase 30 - 36 Batteries - 1 Inverter cabinet, 2 Battery cabinets

32.0

28.3

MMIInterface Panel

24 Circuit Breaker Panel location

Battery ConnectionKnockout locations

37.6

LM4200-6250 single phase uses a single cabinet for inverter and batteries

LM8250-12500 single phase requires two cabinets (inverter and batteries)

LM5200-12500 three phase requires two cabinets (inverter and batteries)

LM15750-18750 three phase requires three cabinets (inverter and batteries)

OverallMechanicalDimensions4.2to18.75KVA