LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560 1 PART 1 – GENERAL 3.1 DESCRIPTION OF EXISTING SUBSTRATES A. This specification is intended to outline the requirements for application of the PremiumCoat® system, in conjunction with the appropriate product technical data sheets, over approved roof substrates in acceptable condition. Specific addenda address each surface at the end of this guide specification. 1.2 DESCRIPTION OF LIQUID APPLIED ROOFING SYSTEM A. The Liquid Applied System consists of a polyesterreinforced elastomeric acrylic system specifically designed for roofing installation. The system is 1) Approved by FMRC (Factory Mutual Research Corporation) according to the complete Standard 4470 for Class 1 Roof Constructions; 2) Classified and subjected to followup by UL (Underwriters Laboratories); 3) Accepted by MiamiDade County; and 4) Manufactured in accordance with ISO 9001:2008 & 14001:2004 regulations. 1.3 SECTION INCLUDES A. Liquid Applied flexible acrylic waterproofing system for use over new or existing roofing. Work shall include the preparation of the roof surface, flashing, detailing, application of the roof system, and cleanup. 1.4 RELATED WORK A. Contractor shall review all sections of the project specifications to determine items of work that will interface with the application of this roofing system. Compliance with applicable building codes shall be assured by the specifier or project engineer, while coordination and execution of related sections shall be the responsibility of the approved contractor. 1.5 REFERENCES A. NRCA Roofing and Waterproofing Manual B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. MiamiDade County Product Control Section, Board and Code Administration E. ASTM D503409(2013) Breaking Strength and Elongation of Textile Fabrics F. ASTM D378707(2011) Bursting Strength of Textiles G. ASTM D111701 Guide for Evaluating Nonwoven Fabric H. ASTM D177796(2011) Thickness of Textile Materials I. ASTM B11711 Standard Practice for Operating Salt Spray (Fog) Apparatus J. ASTM G2996(2010) Test Methods for Algae Resistance K. ASTM E10811 Test Method for Fire Tests of Roof Coverings L. ASTM D165313 Water Vapor Transmission of Organic Coating Films

Transcript of LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters...

Page 1: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

PART  1 – GENERAL 

3.1  DESCRIPTION OF EXISTING SUBSTRATES 

A. This specification is intended to outline the requirements for application of the PremiumCoat® 

system, in conjunction with the appropriate product technical data sheets, over approved roof 

substrates in acceptable condition. Specific addenda address each surface at the end of this guide 

specification. 

 

1.2  DESCRIPTION OF LIQUID APPLIED ROOFING SYSTEM 

A. The Liquid Applied System consists of a polyester‐reinforced elastomeric acrylic system specifically 

designed for roofing installation. The system is 1) Approved by FMRC (Factory Mutual Research 

Corporation) according to the complete Standard 4470 for Class 1 Roof Constructions; 2) Classified 

and subjected to follow‐up by UL (Underwriters Laboratories); 3) Accepted by Miami‐Dade County; 

and 4) Manufactured in accordance with ISO 9001:2008 & 14001:2004 regulations. 

 

1.3  SECTION INCLUDES A. Liquid Applied flexible acrylic waterproofing system for use over new or existing roofing.  Work shall 

include the preparation of the roof surface, flashing, detailing, application of the roof system, and 

cleanup. 

 

1.4  RELATED WORK 

A. Contractor shall review all sections of the project specifications to determine items of work that will 

interface with the application of this roofing system. Compliance with applicable building codes shall 

be assured by the specifier or project engineer, while coordination and execution of related sections 

shall be the responsibility of the approved contractor. 

 

1.5  REFERENCES A. NRCA Roofing and Waterproofing Manual  

B. Factory Mutual RoofNav Directory 

C. Underwriters Laboratories Building Materials Directory 

D. Miami‐Dade County Product Control Section, Board and Code Administration 

E. ASTM D5034‐09(2013)   Breaking Strength and Elongation of Textile Fabrics 

F. ASTM D3787‐07(2011)   Bursting Strength of Textiles 

G. ASTM D1117‐01     Guide for Evaluating Nonwoven Fabric 

H. ASTM D1777‐96(2011)  Thickness of Textile Materials 

I. ASTM B117‐11    Standard Practice for Operating Salt Spray (Fog) Apparatus 

J. ASTM G29‐96(2010)  Test Methods for Algae Resistance 

K. ASTM E108‐11     Test Method for Fire Tests of Roof Coverings 

L. ASTM D1653‐13     Water Vapor Transmission of Organic Coating Films 

  

Page 2: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

M. ASTM G155‐13           Practice for Operating Xenon Arc Light Apparatus for Exposure  of                                                     Non‐Metallic Materials 

N. ASTM D412‐06a (2013)   Tensile Properties of Vulcanized Rubber & Thermoplastic Elastomers 

O. ASTM D6083‐05e1     Standard Specification for Liquid Applied Acrylic Coating 

P. ASTM C1549‐09   Determination of Solar Reflectance at Near Ambient Temperature Using a Portable Solar Reflectometer 

Q. ASTM C1371‐04a (2010)e1   Determination of Emittance of Materials at Near Room Temperature Using Portable Emissometers 

R. FM 4470   Standard for Class 1 Spread of Flame, Windstorm Pressure,Windstorm 

Pull, Hail Damage, Resistance to Foot Traffic, and Susceptibility to 

Leakage 

1.6  REVIEW / SUBMITTALS 

A. Shop Drawings: Submit a scale drawing illustrating layout of joint reinforcing and all flashing details. 

A. Product Data: Provide manufacturer’s published technical literature, MSDS, and warranty on 

products that make up the roofing system, including coatings, reinforcing fabrics, flashing materials, 

roof drains, fasteners, etc. 

B. Installation Instructions: Submit all data sheets available from the manufacturer on the installation 

of the roofing system applicable to the project. 

C. Submit manufacturer's Certificates of Compliance or Analysis that all products meet or exceed 

project requirements. If required, Contractor to supply samples or mockup. 

D. Applicator is responsible for submitting proof of appropriate GAF Certified Contractor Status. 

E. Prior to bid, all project specifications, details, and submittals shall be reviewed by manufacturer for 

pre‐approval and to comply with warranty requirements. Successful bidder should initiate warranty 

pre‐inspection process before commencing work. 

 

1.7  QUALIFICATIONS 

A. Contractor Qualifications: The Applicator of the specified roofing material shall be a Certified 

Contractor designated by GAF.  The Applicator shall provide a certified contractor letter from the 

roofing system manufacturer verifying the Contractor’s status, level, and ability to furnish the 

specified warranty type and term.  

B. Manufacturer Qualifications: Manufacturer shall have a minimum twenty (20) years manufacturing 

experience in the roof coating industry. 

 

1.8  QUALITY CONTROL 

A. Codes and Standards: The contractor shall become thoroughly familiar with all codes, regulations 

and   standards governing the specified work. Any contradiction between the manufacturer’s 

requirements and these specifications shall be brought to the attention of the manufacturer and the 

specifier or project engineer.  

B. Deviations: There shall not be any deviations from these specifications unless the deviation is 

submitted in writing to the specifier/project engineer.   Any request for deviation must be approved 

in writing from the roofing manufacturer’s technical department delineating the details of the 

deviation. 

C. Training and Documentation: The Contractor is responsible for ensuring a trained foreman is on site 

during the installation of any GAF / Hydrostop™ products. A daily log of application activities and 

Page 3: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

environmental conditions should be maintained and available on‐site with copies of technical 

data/application instructions & MSDS. 

D. Technical Inspections:  The Manufacturer may require Technical Inspections based on warranty 

types and terms.  These inspections include, but not limited to, pre‐construction, interim, and final 

inspections.  Consult GAF Technical Services or a GAF Technical Sales Representative to confirm 

inspection requirements. 

 

1.9  DELIVERY, STORAGE & HANDLING A. Deliver materials to jobsite in manufacturer's unopened and undamaged containers bearing the 

following information:  

1. Name and Address of Manufacturer 

2. Identification of Contents – Including Product Code 3. Net Volume of Contents  

4. Lot or Batch Number  

5. VOC Content 6. Storage Temperature Limits  

7. Shelf Life and Expiration Date  8. Mixing Instructions and Proportions of Contents  

9. Safety Information and Instructions 

B. Store and protect materials from damage and weather in accordance with manufacturer's published 

instructions. 

C. Ambient temperatures should range between 50 and 90°F (10 to 32°C). Keep out of direct sunlight. 

D. Place stored material containers on pallets and cover with tarpaulin tied to bottom of pallets. 

 

1.10  ENVIRONMENTAL REQUIREMENTS 

A. Do not apply if ambient temperatures are expected to fall below 50°F (10°C), or if rain or heavy dew 

is anticipated before liquid coating component has cured. 

 

1.11  WARRANTIES AND ELIGIBILITY 

A. Contractor to furnish GAF Warranty or Guarantee in accordance with project specifications. 

Contractor shall follow written application process in accordance with manufacturer’s warranty 

program. 

1. GAF Liquid Applied Limited Product Warranty 

a. GAF Commercial Master or Master Select Restoration Contractors – Up to 10 Years 

b. GAF Premium Coating Systems Contractors – Up to 20 Years 

B. GAF Liquid Applied Emerald Pledge Labor and Material Warranty 

1. GAF Commercial Master or Master Select Restoration Contractors – Up to 10 Years 

2. GAF Premium Coating Systems Contractors – Up to 25 Years 

C. GAF Liquid Applied Diamond Pledge NDL Guarantee 

1. GAF Premium Coating Systems Contractors Only – Up to 25 Years 

Refer to individual addenda at the end of this guide specification for application instructions as they relate to 

warranty / guarantee coverage. 

 

 

Page 4: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

PART  2 – PRODUCTS 2.1  MANUFACTURUER 

A. GAF ‐ 1 Campus Drive Parsippany, New Jersey 07054, 1‐973‐628‐3000, www.gaf.com. 

 

2.2  MEMBRANE COMPUND MATERIAL A. Waterproofing Material: PremiumCoat® System: three stage, fabric‐reinforced, flexible acrylic 

coating, fluid‐applied in successive steps to form a continuous, seamless, watertight membrane; 39 

to 60 mils (1,143 to 1,524 micron) minimum cured total system thickness, comprised of the 

following: 

1. Foundation and Saturation Coats: PremiumCoat® FoundationCoat (highly flexible, water‐ based, 

100% pure acrylic polymer resin coatings). 

2. Fabric: PremiumCoat® Fabric (polyester, non‐woven, stitch‐bonded and heat‐set fabric). 

3. FinishCoat: PremiumCoat® FinishCoat (ultraviolet light‐resistant blend of highly flexible, water‐

based, 100% pure acrylic polymer resin coating). Color as selected from manufacturer's standard 

color chart.  

B. Reinforcing Fabric: PremiumCoat® Fabric shall be non‐woven, 100% polyester, stitch bonded, heat‐

set fabric with the following characteristics: 

Weight:      3 oz. / per square yard (102 grams/m²)  Tensile Strength                 MD: 124 lbs. (56 kg)     ASTM D5034  

CD: 77 lbs. (35 kg)  Elongation @ Break   MD: 26%       ASTM D5034  

CD: 64%  Ball Burst     109 lbs. (49 kg)      ASTM D3787  Trapezoid     MD: 17 lbs. (7.7 kg)     ASTM D1117           CD: 20 lbs. (9.1 kg)  Thickness     0.018 inches (0.457 mm)   ASTM D1777 

 

 

 

 

 

 

   

Page 5: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

C. Cured Membrane Characteristics 

ASTM D‐6083 Material Properties 

Property  Method  PremiumCoat® FinishCoat  PremiumCoat® FoundationCoat 

Krebs Viscosity  D-562  130 123 Brookfield 6 rpm Viscosity D-2196 66,400 34,000 Volume Solids D-2697 52 52 Weight Solids D-1644 66 66 Tensile D-2370 207 173 Elongation D-2370 306 323 Elongation, Post 1,000 hrs Xenon D-2370 148 122 Tear Resistance D-624 93 82 Accelerated Weathering @ 1,000 hrs D-4798 Pass, no change Pass, no change Low Temp Flex, Post 1,000 hrs Xenon D-522 Pass -15F Pass -15F Water Swelling @ 7 days D-471 9.2 7.8 Permeance (wet cup) D-1653 3.9 4.9 Wet Adhesion D-903 8.7 7.3 Fungi Resistance G-21 0 rating 0 rating

Membrane Properties 

Property  Method  PremiumCoat® System 

Wind Driven Rain TT-C-555B/D6904 Pass 0.0 lbs weight gain Elongation of Membrane (40 mils DFT)

ASTM D4798 (G155) and D2370 MD: 36% @ 8000 hrs weathering CD: 41% @ 8000 hrs weathering

Tensile Strength of membrane (40 mils DFT)

ASTM D4798 (G155) and D2370 MD: 65lbs/in-width @ 8000 hrs weathering CD: 69lbs/in-width @ 8000 hrs

Tensile strength of membrane (40 mils DFT)

ASTM D-412 2210 PSI (13,789 kPa)

Water vapor permeability (40 mils DFT)

ASTM E-96

3-5 perms; a Class III vapor retarder

Cured Weight Generic 0.33 lbs per ft2 (56.8 oz. per m2) Salt Spray ASTM B-117 No effects Algae Resistance: ASTM G-29 0 rating

IBC Code Approval Properties 

Property  IBC Test Reference  Rating  A2LA/ANSI Approved Lab 

Exterior Fire ASTM E108/UL790 Class A up to 4”/12” slope File R26758 and FM RoofNav Interior Fire FM 4470 Calorimeter Class 1 FM RoofNav Wind FM 4470/4474 and TAS

114 D&J and TAS 125 Concrete: 6,089 (psf) LWIC: 4,621 (psf) Polyisocyanurate: 1,189 (psf) Smooth BUR: 2,261 (psf) Granulated Cap Sheet: 1,753 (psf)

FM RoofNav Dade County NOAs

Impact/Durability FM 4470 Foot Traffic Pass FM RoofNav Leakage FM 4470 ASTM D7281 Pass a free standing membrane FM RoofNav Report J.I. 3000150 Hail FM 4470 Hail Pass-Severe FM RoofNav Weathering ASTM D4798 (G155) and

D2370 40 mil system: Pass, maintained over 90% tensile strength after 8,000 hrs ASTM Xenon-Acr.

PRI-CMT HSI-012-02-01

ASTM Material Properties ASTM D-6083 Pass PRI-CMT Solar Reflectance 79% initial, 70% aged Pass all standards CRRC/UL Thermal Emittance 0.9 initial and aged Pass all standards CRRC/UL SRI Index 99 initial, 86 aged Pass all standards CRRC/UL Safety Generic ISO 14001:2004 ANSI/PJR Quality Generic ISO 9001:2008 ANSI /PJR

 

 

 

Page 6: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

2.3  ACCESSORIES 

B. Cant  Strips:  Approved  composition  materials  are  EPS  (Expanded  Polystyrene),  ISO 

(Polyisocyanurate), and wood  (Non‐Pressure Treated). Refer to construction details for  installation 

requirements as specified by GAF. 

C. Polyisocyanurate:  EnergyGuard™  Polyisocyanurate  Insulation  with  glass‐based  facer  meeting  or 

exceeding the requirements for ASTM C1289 [min. 16 psi (1.1 kg/cm) compressive strength].    1.5” 

(3.8 cm) minimum thickness.  Max board size: 4’ x 8’ (1.2 m x 2.4 m) if mechanically fastened or 4’ x 

4’ 1.2 m x 1.2 m) if adhered with Factory Mutual approved roofing adhesive.  

D. Polyisocyanurate: EnergyGuard™ Polyisocyanurate HD or HD Plus.   0.5” minimum  thickness.   Max 

board size: 4’ x 8’ (1.2 m x 2.4 m) if mechanically fastened or 4’ x 4’ 1.2 m x 1.2 m) if adhered with 

Factory Mutual approved roofing adhesive. 

E. Pywood: ¾” (2 cm) minimum thickness, tongue and groove exterior B & C grade. Plywood  is to be 

adhered with sub‐floor adhesive and deck fasteners.  

F. Densdeck or Securock: ¼”  (6 mm) minimum  thickness  if used over an approved,  smooth existing 

substrate. The standard thickness recommendation is ½” (1.3 cm).  

G. Insulation Adhesives:   GAF OlyBond, GAF LRF‐M, or GAF 2 Part Roofing Adhesive. 

H. Mechanical  Fasteners:   GAF Drill‐Tec™ membrane  fasteners  and  plates,  insulation  fasteners  and 

plates, and flashing fasteners and termination bars. 

I. BarrierGuard:  Polymer modified  cementitious  slurry  to  fill  cracks,  voids,  or  low  depressions  on 

various substrates or embedded in PremiumCoat® Fabric as below grade waterproofing. 

J. Butter Grade: Single package, high solids acrylic, elastomeric sealant.  

K. HydroFiber:  Bulking material  used  in  conjunction  with  PremiumCoat®FoundationCoat  or  Butter 

Grade.  

L. HydroCaps: Fabric reinforcement for sealing metal fasteners. 

M. StableRust  Primer: Water‐based,  surfactant‐free  primer  used  on  direct‐to‐metal  applications  to 

stabilize and protect metal surfaces.  

N. CleanAct Primer: Water‐based cleaner used in EPDM surface preparation.  

O. SureBond Primer: Water‐based acrylic primer for sealing masonry, metal, and chalky surfaces.   

P. Unibase Primer: Penetrating adhesive/primer for saturating fabric and adhering coating.  

Q. GAF TPO Red Primer: VOC‐compliant,  solvent‐based  thermoplastic  liquid  to be applied  to TPO  to 

promote adhesion of water‐based coatings.  

R. TrafficCoat: Durable wear coating to provide additional abrasion resistance and color selection. 

Page 7: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

S. UCC ‐ United Cleaning Concentrate: Non‐Toxic cleaner for use on existing elastomeric roof coatings 

metal surfaces, concrete and masonry substrates, as well as uncoated roof, deck and wall surfaces. 

T. GAF Epoxy Primer:   Use  to penetrate and seal porous substrates and  to  improve  the adhesion of 

high performance topcoats. 

PART  3 – EXECUTION 

3.1  EXAMINATION 

A. When applying a Liquid Applied Roofing System as a  recover over an existing  roofing  system, GAF 

requires  investigation of moisture  in the existing system through various Moisture Survey methods.  

See Substrate Preparation Guide for Liquid Applied Roofing Systems for requirements. 

B. Verify that substrate surfaces are durable, free of frozen matter, dampness,  loose particles, cracks, 

pits,  projections,  and/or  foreign matter  detrimental  to  adhesion  or  application  of waterproofing 

system. 

C. Verify that substrate surfaces are smooth and not detrimental to full contact bond of waterproofing 

materials. Perform test patches to verify substrate suitability to receive the HydroStop PremiumCoat 

System.  Field test methods are outlined in the GAF Substrate Preparation Guide for Liquid Applied 

Roofing Systems. 

D. Verify  items  that  penetrate  surfaces  to  receive waterproofing  are  securely  installed  and  suitably 

flashed.  

E. Verify that substrate areas are adequately supported and firmly fastened in place.  

F. Verify that roof deck has a minimum slope of 0.25”/foot (2.1 cm/meter). 

G. Verify that roof does not have areas of ponding water. 

H. Verify that all contiguous walls are properly waterproofed. 

1.1  PREPARATION 

A. Protect adjacent surfaces not designated to receive waterproofing. 

B. Inspect  and make  all  necessary  repairs  to  substrate.      Remove  and  replace  wet  substrates  and 

insulation, if applicable. 

C. At a minimum, clean and prepare surfaces to receive waterproofing by removing all dirt, dust, loose 

and  flaking  particles,  grease  and  debris with  the  use  of  a  stiff bristle  push  broom.   Apply United 

Cleaning Concentrate and rinse per manufacturer’s  instructions.   Care should be taken not to  inject 

water  into  the  substrate during  the preparation phase.   Allow adequate  time  for  complete drying 

after the cleaning process.   

Page 8: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

D. Substrates with heavy  contamination of  grease, oils, dirt,  etc. may  require  supplemental  cleaning 

methods.    Contact  a  GAF  Technical  Services  or  Technical  Sales  Representative  for  additional 

information. 

E. At a minimum, seal cracks and joints with Butter Grade and PremiumCoat Fabric.   Repair additional 

substrate conditions per approved GAF details. Contact a GAF Technical Services or Technical Sales 

Representative for additional information. 

F. Refer to GAF Substrate Preparation Guide for Liquid Applied Roofing Systems for detailed substrate 

preparation procedures by individual substrate. 

G. Do  not  apply  waterproofing  to  surfaces  unacceptable  to  manufacturer,  or  under  inclement 

environmental conditions. 

1.2  APPLICATION A. Refer to individual addenda at the end of this guide specification for preparation and application 

requirements for specific substrates.  

 

1.3  PROTECTION OF FINISHED WORK 

A. Monitor finished system for seven days, sweeping off any birdbaths to allow for full cure.  

 

1.4  CLEANING  A. Immediately clean surfaces not scheduled to receive waterproofing in accordance with 

manufacturer's instructions.  

 END OF SECTION 

 

 

 

 

 

 

 

 

   

Page 9: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

ADDENDUM 1 – Existing Membranes (BUR / APP / SBS / EPDM / Hypalon / PVC / TPO) 

3.3  APPLICATION 

A. Preparation and Priming by Substrate: 

1. Asphaltic Membranes (Smooth BUR / APP / SBS) 

a. Verify Adhesion per Section 3.1.C. and prepare substrate per Section 3.2 of this Specification. b. Prime new asphaltic surfaces with UniBase Primer at a rate of .5 ‐1.0 gallon per square using a 

roof brush, roller, or airless sprayer.  Coverage rate will vary by substrate porosity.  For aged asphaltic surfaces, Unibase Primer is recommended to promote adhesion and enhance bleed‐blocking. 

2. PVC and Hypalon 

a. Verify Adhesion per Section 3.1.C. and prepare substrate per Section 3.2 of this Specification. b. Adhesion test is required.  If results are less than 2.0 pli, contact a GAF Technical Services or 

Technical Sales Representative to identify supplemental cleaning or priming requirements. 3. TPO 

a. Verify Adhesion per Section 3.1.C. and prepare substrate per Section 3.2 of this Specification. b. Apply GAF TPO Red Primer at a rate of .5 gallons per square. 

4. EPDM 

a. Apply CleanAct Primer at a rate of .2 gallons per square (5 squares per gallon). CleanAct should remain on the EPDM surface for 10‐30 minutes, followed by two separate power rinses, using clean water, at a minimum of 3,000 psi (20,680 kPa). 

b. Using a clean white towel, verify that all carbon black has been removed from the surface of the EPDM.  Verify adhesion per Section 3.1.C. and repeat cleaning if necessary. 

 B. PremiumCoat® FoundationCoat & Fabric Components – This procedure consists of one coat of 

PremiumCoat® FoundationCoat (“FoundationCoat”) applied to the substrate at the rate of 1.25 to 2.0 gallons / square.  HydroStop PremiumCoat® Fabric (“Fabric”) (sizes vary) laid into the wet FoundationCoat, and a second coat of FoundationCoat immediately applied over the top at the rate of of 1.25 to 2.0 gallons / square to saturate the Fabric. FoundationCoat is applied at a total rate of 2.5 to 4.0 gallons / square, depending on the texture and porosity of the substrate. FoundationCoat should only be applied using approved roof brushes. Rolling and/or spraying FoundationCoat is strictly prohibited.  Total Dry Film Thickness of FoundationCoat & Fabric Components is a minimum 27 mils. 1. Roof Perimeter‐ Using 12” (30 cm) Fabric and FoundationCoat components (described above), 

waterproof entire roof perimeter. Continue waterproofing up vertical surfaces and onto the deck a minimum of 6” (15 cm) in each direction. 

2. Roof Penetrations‐ Using 12” (30 cm) Fabric and FoundationCoat components (described above), seal any items projecting through waterproofing material to render them watertight. Extend waterproofing vertically up penetrations a minimum of 6” (15 cm).  

3. Roof Field – Using 40” (1.0 m) Fabric and FoundationCoat components (as described above), reinforce the entire roof field. Overlap adjacent runs of Fabric a minimum of 4” (10 cm).  

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat perpendicularly to the previous coat. 

Page 10: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

10 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to promote faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat may be applied. 

3. Precautions: a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in a single coat.   

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per coat to allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats installed based on conditions such as ambient temperature, relative humidity, and future weather forecasting as they relate to a specific application of the PremiumCoat® system. 

 D. System Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate 

of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 12.5 

mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate 

of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 16.5 

mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness. 

20‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate 

of 3.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 25 

mils.  Completed PremiumCoat® System must be installed to a minimum 52 mil total cured thickness. 

25‐Year Option – Apply a minimum of 3 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate 

of 4.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 33 

mils.  Completed PremiumCoat® System must be installed to a minimum 60 mil total cured thickness. 

 

End of Addendum   

Page 11: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

11 

ADDENDUM 2 – Lightweight, Structural and Precast Concrete 

3.3  APPLICATION 

A. Preparation and Priming by Substrate 

1. Structural and Precast Concrete  

a. New concrete must be allowed to cure for a minimum 28 days prior to application of primers. 

b. Verify Adhesion per Section 3.1.C. and prepare substrate per Section 3.2 of this Specification. 

c. Apply one or more coats of GAF Epoxy Primer at .5 gallons per square depending on   porosity of 

substrate. 

2. Lightweight Insulating Concrete 

a. Due to variations in the applications and formulations of Lightweight Insulating Concrete, 

HydroStop PremiumCoat Systems over Lightweight Concrete must be reviewed and approved 

by GAF Technical Services on a project specific basis.  Contact your Technical Service 

Representative for additional information. 

B. PremiumCoat® FoundationCoat & Fabric Components – This procedure consists of one coat of 

PremiumCoat® FoundationCoat (“FoundationCoat”) applied to the substrate at the rate of 1.25 to 2.0 

gallons / square.  HydroStop PremiumCoat® Fabric (“Fabric”) (sizes vary) laid into the wet 

FoundationCoat, and a second coat of FoundationCoat immediately applied over the top at the rate 

of of 1.25 to 2.0 gallons / square to saturate the Fabric. FoundationCoat is applied at a total rate of 

2.5 to 4.0 gallons / square, depending on the texture and porosity of the substrate. FoundationCoat 

should only be applied using approved roof brushes. Rolling and/or spraying FoundationCoat is 

strictly prohibited.  Total Dry Film Thickness of FoundationCoat & Fabric Components is a minimum 

27 mils. 

1. Roof Perimeter‐ Using 12” (30 cm) Fabric and FoundationCoat components (described above), 

waterproof entire roof perimeter. Continue waterproofing up vertical surfaces and onto the deck a 

minimum of 6” (15 cm) in each direction.  

2. Roof Penetrations‐ Using 12” (30 cm) Fabric and FoundationCoat components (described above), 

seal any items projecting through waterproofing material to render them watertight. Extend 

waterproofing vertically up penetrations a minimum of 6” (15 cm).  

3. Roof Field – Using 40” (1.0 m) Fabric and FoundationCoat components (as described above), 

reinforce the entire roof field. Overlap adjacent runs of Fabric a minimum of 4” (10 cm). 

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat perpendicularly to the 

previous coat. 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to promote 

faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat may be applied. 

3. Precautions: 

Page 12: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

12 

a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in a single 

coat.   

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per coat to 

allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats 

installed based on conditions such as ambient temperature, relative humidity, and future weather 

forecasting as they relate to a specific application of the PremiumCoat® system. 

D. System Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 12.5 mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 16.5 mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness. 

20‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate of 3.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 25 mils.  Completed PremiumCoat® System must be installed to a minimum 52 mil total cured thickness. 

25‐Year Option – Apply a minimum of 3 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished rate of 4.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 33 mils.  Completed PremiumCoat® System must be installed to a minimum 60 mil total cured thickness. 

 End of Addendum 

 

   

Page 13: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

13 

ADDENDUM 3 – Polyisocyanurate Insulation, DensDeck, Securock, and Plywood 

3.3  APPLICATION 

Newly Installed Polyisocyanurate Insulation, DensDeck, Securock, and Plywood do not require cleaning or 

priming.  If using these substrates as a recovery board over an existing roof assembly, the contractor must apply 

proper Examination and General Preparation practices to the existing roof assembly as outlined in Sections 3.1 

and 3.2 of this document. 

A. Attachment:  Adhere or fasten insulation to deck with polyurethane adhesive or approved 

fasteners in accordance with manufacturer's installation instructions to meet a minimum uplift 

requirement of 1‐90. Verify the proper uplift requirements with the specifier or the local   

building code authority. 

1. Stagger all board joints. Lay boards with edges in moderate contact, without forcing. Cut 

insulation to fit neatly to perimeter blocking and around penetrations through the roof.  

2. Apply no more insulation than can be covered with waterproofing on the same day.  

3. Install cant strips at internal corners and metal drip edge on outside perimeter.  

 

B. PremiumCoat® FoundationCoat & Fabric Components – This procedure consists of one coat of PremiumCoat® FoundationCoat (“FoundationCoat”) applied to the substrate at the rate of 1.25 to 2.0 gallons / square.  HydroStop PremiumCoat® Fabric (“Fabric”) (sizes vary) laid into the wet FoundationCoat, and a second coat of FoundationCoat immediately applied over the top at the rate of of 1.25 to 2.0 gallons / square to saturate the Fabric. FoundationCoat is applied at a total rate of 2.5 to 4.0 gallons / square, depending on the texture and porosity of the substrate. FoundationCoat should only be applied using approved roof brushes. Rolling and/or spraying FoundationCoat is strictly prohibited.  Total Dry Film Thickness of FoundationCoat & Fabric Components is a minimum 27 mils. 

 1. Recovery Board Seams – Using 6” (30 cm) Fabric and FoundationCoat components (as 

described above), waterproof all board seams, cracks and non‐working joints. Center 6” (15 

cm) fabric over all seams.  

2. Roof Perimeter‐ Using 12” (30 cm) Fabric and FoundationCoat components (described 

above), waterproof entire roof perimeter. Continue waterproofing up vertical surfaces and 

onto deck a minimum of 6” (15 cm) in each direction.  

3. Roof Penetrations‐ Using 12” (30 cm) Fabric and FoundationCoat components (described 

above) seal any items projecting through waterproofing material so they are watertight. 

Waterproof up penetrations a minimum of 6” (15 cm).  

4. Roof Field‐ Using 40” (1.0 m) Fabric and FoundationCoat components (as described above) 

seal the entire roof field. Overlap adjacent runs of fabric a minimum of 4” (10 cm). 

 

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat 

perpendicularly to the previous coat. 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to 

promote faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat 

may be applied. 

3. Precautions: 

Page 14: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

14 

a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in 

a single coat.   

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per 

coat to allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats 

installed based on conditions such as ambient temperature, relative humidity, and future 

weather forecasting as they relate to a specific application of the PremiumCoat® system. 

 

D. System Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

12.5 mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

16.5 mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness. 

20‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 3.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

25 mils.  Completed PremiumCoat® System must be installed to a minimum 52 mil total cured thickness. 

25‐Year Option – Apply a minimum of 3 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 4.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

33 mils.  Completed PremiumCoat® System must be installed to a minimum 60 mil total cured thickness. 

End of Addendum 

 

 

 

 

 

 

   

Page 15: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

15 

ADDENDUM 4 – Commercial Standing Seam Metal 3.3  APPLICATION 

PART  4 Newly Installed Polyisocyanurate Insulation, DensDeck, Securock, and Plywood do not require cleaning or priming.  If using these substrates as a recovery board over an existing roof assembly, the contractor must apply 

proper Examination and General Preparation practices to the existing roof assembly as outlined in Sections 3.1 

and 3.2 of this document. 

A. Attachment:  Adhere or fasten insulation to deck with polyurethane adhesive or approved 

fasteners in accordance with manufacturer's installation instructions to meet a minimum uplift 

requirement of 1‐90. Verify the proper uplift requirements with the specifier or the local   

building code authority. 

1. Stagger all board joints. Lay boards with edges in moderate contact, without forcing. Cut 

insulation to fit neatly to perimeter blocking and around penetrations through the roof.  

2. Apply no more insulation than can be covered with waterproofing on the same day.  

3. Install cant strips at internal corners and metal drip edge on outside perimeter.  

 

B. PremiumCoat® FoundationCoat & Fabric Components – This procedure consists of one coat of PremiumCoat® FoundationCoat (“FoundationCoat”) applied to the substrate at the rate of 1.25 to 2.0 gallons / square.  HydroStop PremiumCoat® Fabric (“Fabric”) (sizes vary) laid into the wet FoundationCoat, and a second coat of FoundationCoat immediately applied over the top at the rate of of 1.25 to 2.0 gallons / square to saturate the Fabric. FoundationCoat is applied at a total rate of 2.5 to 4.0 gallons / square, depending on the texture and porosity of the substrate. FoundationCoat should only be applied using approved roof brushes. Rolling and/or spraying FoundationCoat is strictly prohibited.  Total Dry Film Thickness of FoundationCoat & Fabric Components is a minimum 27 mils. 

 1. Recovery Board Seams – Using 6” (30 cm) Fabric and FoundationCoat components (as 

described above), waterproof all board seams, cracks and non‐working joints. Center 6” (15 

cm) fabric over all seams.  

2. Roof Perimeter‐ Using 12” (30 cm) Fabric and FoundationCoat components (described 

above), waterproof entire roof perimeter. Continue waterproofing up vertical surfaces and 

onto deck a minimum of 6” (15 cm) in each direction.  

3. Roof Penetrations‐ Using 12” (30 cm) Fabric and FoundationCoat components (described 

above) seal any items projecting through waterproofing material so they are watertight. 

Waterproof up penetrations a minimum of 6” (15 cm).  

4. Roof Field‐ Using 40” (1.0 m) Fabric and FoundationCoat components (as described above) 

seal the entire roof field. Overlap adjacent runs of fabric a minimum of 4” (10 cm). 

 

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat 

perpendicularly to the previous coat. 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to 

promote faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat 

may be applied. 

3. Precautions: a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in 

a single coat.   

Page 16: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

16 

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per 

coat to allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats 

installed based on conditions such as ambient temperature, relative humidity, and future 

weather forecasting as they relate to a specific application of the PremiumCoat® system. 

 

D. System Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

12.5 mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

16.5 mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness. 

20‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 3.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

25 mils.  Completed PremiumCoat® System must be installed to a minimum 52 mil total cured thickness. 

25‐Year Option – Apply a minimum of 3 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 4.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

33 mils.  Completed PremiumCoat® System must be installed to a minimum 60 mil total cured thickness. 

End of Addendum 

 

   

Page 17: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

17 

ADDENDUM 4 – Commercial Standing Seam Metal 

3.3  APPLICATION  

A. Cleaning and Priming 

1. Verify Adhesion per Section 3.1.C. and prepare substrate per Section 3.2 of this Specification. 2. For mild rust: Prime substrate using Acrylex 400 Primer or StableRust Primer @ .33‐.67 gallon per 

square depending on substrate. 

3. For severe rust : Prime substrate with Lock Down Primer @ .25 gallons per square 

4. For Kynar® coated metal panels: Prime substrate using XR‐2000 @ .75 gallons per square. 

5. For residual asphalt areas: Prime areas with UniBase Primer @ .50‐1.0 gallons per square 

depending on prepared substrate. 

 

B. PremiumCoat® FoundationCoat & Fabric Components – This procedure consists of one coat of 

PremiumCoat® FoundationCoat (“FoundationCoat”) applied to the substrate at the rate of 1.25 to 

2.0 gallons / square.  HydroStop PremiumCoat® Fabric (“Fabric”) (sizes vary) laid into the wet 

FoundationCoat, and a second coat of FoundationCoat immediately applied over the top at the rate 

of of 1.25 to 2.0 gallons / square to saturate the Fabric. FoundationCoat is applied at a total rate of 

2.5 to 4.0 gallons / square, depending on the texture and porosity of the substrate. FoundationCoat 

should only be applied using approved roof brushes. Rolling and/or spraying FoundationCoat is 

strictly prohibited.  Total Dry Film Thickness of FoundationCoat & Fabric Components is a minimum 

27 mils. 

1. Roof Penetrations – Using 12” Fabric and Foundation Coat components (described above), seal 

any items projecting through waterproofing material watertight. Waterproof penetrations 

vertically a minimum of 6”. 

2. Vertical Seams – Sealing vertical standing seams with Butter Grade is recommended, but may not 

be required for all standing seam profiles.  Consult GAF Technical Services to verify flashing 

requirements by individual standing seam profile. 

3. Horizontal laps – using 12” Fabric and Foundation Coat components (described above), seal all 

horizontal laps. Foundation Coat and Fabric components must be centered on the panels laps. 

Protect from weather until dry. 

4. Exposed Mechanical Fasteners – Using either a Hydro Cap or a 6” x 6” piece of Fabric and 

Foundation Coat Component (described above), seal all mechanical fasteners. Protect from 

weather until dry. 

5. Parapet & Vertical Wall junctions – Using 12” fabric Foundation Coat components (described 

above), waterproof all roof/wall junctions. Continue waterproofing up vertical surfaces and onto 

deck a minimum of 6” in each direction. 

 

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat perpendicularly to 

the previous coat. 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to promote 

faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat may be applied. 

3. Precautions: a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in a 

single coat.   

Page 18: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

18 

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per coat 

to allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats 

installed based on conditions such as ambient temperature, relative humidity, and future 

weather forecasting as they relate to a specific application of the PremiumCoat® system. 

D. Systems Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

12.5 mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness 

where fabric is utilized. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

16.5 mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness 

where fabric is utilized. 

20‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 3.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

25 mils.  Completed PremiumCoat® System must be installed to a minimum 52 mil total cured thickness where 

fabric is utilized. 

25‐Year Option – Apply a minimum of 3 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 4.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

33 mils.  Completed PremiumCoat® System must be installed to a minimum 60 mil total cured thickness where 

fabric is utilized 

End of Addendum 

   

Page 19: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

19 

ADDENDUM 6 – Historic Standing Seam Metal  

3.3  APPLICATION  

A. Cleaning and Priming 

a. Verify Adhesion per Section 3.1.C. and prepare substrate per Section 3.2 of this Specification. b. For mild rust: Prime substrate using Acrylex 400 Primer or StableRust Primer @ .33‐.67 gallon 

per square depending on substrate. 

c. For severe rust : Prime substrate with Lock Down Primer @ .25 gallons per square 

d. For Kynar® Coated metal panels: Prime substrate using XR‐2000 @ .75 gallons per square. 

e. For residual asphalt areas: Prime areas with UniBase Primer @ .50‐1.0 gallons per square 

depending on prepared substrate. 

 

B. PremiumCoat® FoundationCoat & Fabric Components – This procedure consists of one coat of 

PremiumCoat® FoundationCoat (“FoundationCoat”) applied to the substrate at the rate of 1.25 to 

2.0 gallons / square.  HydroStop PremiumCoat® Fabric (“Fabric”) (sizes vary) laid into the wet 

FoundationCoat, and a second coat of FoundationCoat immediately applied over the top at the rate 

of of 1.25 to 2.0 gallons / square to saturate the Fabric. FoundationCoat is applied at a total rate of 

2.5 to 4.0 gallons / square, depending on the texture and porosity of the substrate. FoundationCoat 

should only be applied using approved roof brushes. Rolling and/or spraying FoundationCoat is 

strictly prohibited.  Total Dry Film Thickness of FoundationCoat & Fabric Components is a minimum 

27 mils. 

1. Roof Penetrations – Using 12” Fabric and Foundation Coat components (described above), seal 

any items projecting through waterproofing material watertight. Waterproof penetrations 

vertically a minimum of 6”. 

2. Valleys and Peaks – using 12, 16, 24” Fabric and Foundation Coat components (described above), 

seal all valets and peaks. Foundation Coat and Fabric components must be centered in the valleys 

or on the peaks overlapping adjoining fabric. Protect from weather until dry. 

3. Vertical or Horizontal Seams  – using 6” Fabric and Foundation Coat components (described 

above), seal all vertical seams. Foundation Coat and Fabric components must be centered on the 

panels seams. Protect from weather until dry. 

4. Vertical Pans – using 16” or 24” Fabric and Foundation Coat components (described above), seal 

all vertical pans. Foundation Coat and Fabric components must be centered in the vertical pans 

overlapping both adjoining 6” fabrics used on the vertical seams. Protect from weather until dry. 

(Note: most historical standing seam metal roofs have standing seams that are centered on 17” or 

25”. For seams centered on 17” use 16” fabric and for 25” seams use 24” fabric.). 

5. Parapet & Vertical Wall junctions – Using 12” fabric Foundation Coat components (described 

above), waterproof all roof/wall junctions. Continue waterproofing up vertical surfaces and onto 

deck a minimum of 6” in each direction. 

 

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat perpendicularly to 

the previous coat. 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to promote 

faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat may be applied. 

3. Precautions: 

Page 20: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

20 

a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in a 

single coat.   

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per coat 

to allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats 

installed based on conditions such as ambient temperature, relative humidity, and future 

weather forecasting as they relate to a specific application of the PremiumCoat® system. 

D. System Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

12.5 mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness 

where fabric is utilized. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

16.5 mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness 

where fabric is utilized. 

20‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 3.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

25 mils.  Completed PremiumCoat® System must be installed to a minimum 52 mil total cured thickness where 

fabric is utilized. 

25‐Year Option – Apply a minimum of 3 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 4.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

33 mils.  Completed PremiumCoat® System must be installed to a minimum 60 mil total cured thickness where 

fabric is utilized. 

End of Addendum    

Page 21: LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT …B. Factory Mutual RoofNav Directory C. Underwriters Laboratories Building Materials Directory D. Miami‐Dade County Product Control

LIQUID APPLIED ROOFING HYDROSTOP PREMIUMCOAT SYSTEM SECTION 07560

21 

ADDENDUM 7 – Renewal of Existing HydroStop Roofing Systems  

3.3  APPLICATION  

A. EXAMINATION 

1. The HydroStop Roofing System will be inspected by a GAF Field Service or Technical Sales 

Representative to determine eligibility for a recoat guarantee or warranty. 

2. The GAF Field Service or Technical Sales Representative will provide a scope of repair to restore the system to a warrantable condition. 

  

B. Preparation 1. Contractor shall restore the roofing system per the established scope of work. 

2. Clean per section 3.2C of this specification.  

C. PremiumCoat® Finish Coat Component: 

1. Apply PremiumCoat® FinishCoat in multi‐directional passes.  Apply each coat perpendicularly to 

the previous coat. 

2. When applying PremiumCoat® FinishCoat in 3 or more coats on a single project, or to promote 

faster dry times of individual coats, alternate colors of PremiumCoat® FinishCoat may be applied. 

3. Precautions: a. PremiumCoat® FinishCoat should not be applied at rates exceeding 1.5 gallons / square in a 

single coat.   

b. Atmospheric conditions may require application rates of less than 1.5 gallons /square per coat 

to allow for reasonable cure times, as well as preventing “cracking” of the FinishCoat.   

c. The installing contractor is responsible for adjusting application rates and number of coats 

installed based on conditions such as ambient temperature, relative humidity, and future weather 

forecasting as they relate to a specific application of the PremiumCoat® system. 

 

D. System Options for Warranty and Guarantee Coverage: 

10‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 1.5 gallons / square. Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

12.5 mils.  Completed PremiumCoat® System must be installed to a minimum 39 mil total cured thickness 

where fabric is utilized. 

15‐Year Option – Apply a minimum of 2 coats of PremiumCoat® FinishCoat (“FinishCoat”) at a total finished 

rate of 2.0 gallons / square.  Allow to dry between coats.  Total Dry Film Thickness of FinishCoat Component is 

16.5 mils.  Completed PremiumCoat® System must be installed to a minimum 43.5 mil total cured thickness 

where fabric is utilized. 

End of Addendum