versatile in its application. Fig. 2shows a basic PLC system consistingof three distinct components:

• signal carrying medium (HVtransmission line)

• communication apparatus(transmitters, receivers and associated components)

• coupling/blocking equipmentsuch as coupling capacitors, linetuners (coupling devices) andLine Traps.

Line Traps are connected in serieswith HV transmission lines. Themain function of the Line Trap is topresent a high impedance at thecarrier frequency band while introducing negligible impedanceat the power frequency. The highim pedance limits the attenuationof the carrier signal within thepower system by preventing thecarrier signal from being:

• dissipated in the substation

• grounded in the event of a faultoutside the carrier transmissionpath

• dissipated in a tap line or abranch of the main transmissionpath.

Line Traps for Power Line Carrier(PLC) communication systems re-pre sent a significant applicationsegment for high voltage inductors.

Basic Function of Line Traps

Power Line Carrier (PLC) is a common method of Power SystemCommunication, such as telepro-tection, voice and data communi-cation, etc. It has developed thereputation of being one of themost economical and reliable formsof communication and of beeing

Introduction

With over 40 years of successfulfield experience Trench is the reco-g nized world leader in thedesign and manufacture of air-core dry-type inductors for electricutility applications. The unique custom design approach, alongwith fully integrated engineeringand manufacturing facilities inboth North America and Europehave enabled Trench to becomethe technical leader for highvoltage inductors world wide.

Fig. 1 Post mounted Line Trap

Line Traps

Page 3: Line Traps

3

Design and Construction

Line Traps are designed to meetANSI standard C93.3, IEC stan-dard 60353 or other internationalstandards.

The major components of a LineTrap are the main coil, tuning device and protective device (see Fig. 3).

Fig. 4Suspension mounted

Line Traps

Fig. 2Principle scheme of a

PLC system

Tuning Device

Terminal

Main Coil

Pedestal(Optional)

LightningArrester

Bird Barrier (Optional)

Since Line Traps are series connec-ted with the HV transmission line,they must be designed to with-stand the high mechanical forcesgenerated by the short circuit (s/c)cur rent associated with the HVtransmission system.

Fig. 3Line Trap

components

1 Coupling Capacitor 2 Line Tuner 3 Transmitter/Receiver

Line Trap Line Trap

Station A Station B

Page 4: Line Traps

4

Main Coil

The main coil of a Line Trap is anair-core dry-type power inductor.

Trench offers Line Traps with en-capsulated design.

This technology fully complieswith power system and PLC requirements and is therefore ap-plied over the full range of com-monly specified main coil ratings(see Fig. 5).

The winding utilizes aluminumwire or cable. All power currentcarrying components utilize welded connections.

High mechanical strength of thewinding is achieved by resin im-pregnated, fiberglass rein forcedencapsulation.

The winding is terminated at bothends on a system of aluminumbars, denoted as the spiders whichare tensioned together by fiber-glass ties. These spi ders are addi-tionally used for

• the electrical connection to theLine Trap by terminal pads orstuds

• providing the hardware for lifting (lugs), mounting (pede-stals) and corona pro tection (bells,rings)

• connecting the tuning and protective device across the main coil.

Trench can provide the completerange of standard ratings(inductance, continuous and s/ccurrent ratings, system voltage) inaccordance with IEC 60353 orANSI C93.3 standards (see Fig.5). Customized units are also availableto meet spe cific customer require-ments, such as specific inductance,current (s/c or continuous), lowloss requirements, etc.

a

Page 5: Line Traps

Rated Currents Rated InductanceIEC 60353 IEC 60353

Continuous Short-timeA Series 1 mH at 100 kHz

kA/1sec

100 2,5 0,2 0,25 0,315 0,4 0,5 1,0 2,0200 5 0,2 0,25 0,315 0,4 0,5 1,0 2,0400 10 0,2 0,25 0,315 0,4 0,5 1,0 2,0630 16 0,2 0,25 0,315 0,4 0,5 1,0 2,0800 20 0,2 0,25 0,315 0,4 0,5 1,0 2,0

1000 25 0,2 0,25 0,315 0,4 0,5 1,0 2,01250 31,5 0,2 0,25 0,315 0,4 0,5 1,0 2,01600 40 0,2 0,25 0,315 0,4 0,5 1,0 2,02000 40 0,2 0,25 0,315 0,4 0,5 1,0 2,02500 40 0,2 0,25 0,315 0,4 0,5 1,0 2,03150 40 0,2 0,25 0,315 0,4 0,5 1,0 2,04000 63 0,2 0,25 0,315 0,4 0,5 1,0 2,0

Continuous Short-timeA Series 2 mH at 100 kHz

kA/1sec

100 5 0,2 0,25 0,315 0,4 0,5 1,0 2,0200 10 0,2 0,25 0,315 0,4 0,5 1,0 2,0400 16 0,2 0,25 0,315 0,4 0,5 1,0 2,0630 20 0,2 0,25 0,315 0,4 0,5 1,0 2,0800 25 0,2 0,25 0,315 0,4 0,5 1,0 2,0

1000 31,5 0,2 0,25 0,315 0,4 0,5 1,0 2,01250 40 0,2 0,25 0,315 0,4 0,5 1,0 2,01600 50 0,2 0,25 0,315 0,4 0,5 1,0 2,02000 50 0,2 0,25 0,315 0,4 0,5 1,0 2,02500 50 0,2 0,25 0,315 0,4 0,5 1,0 2,03150 50 0,2 0,25 0,315 0,4 0,5 1,0 2,04000 80 0,2 0,25 0,315 0,4 0,5 1,0 2,0

Rated Currents Rated InductanceANSI C93.3 ANSI C93.3

Continuous Short-timeA kA/2sec

mH at 100 kHz

400 15 0,265 0,53 1,06 1,59 2,12 2,65800 20 0,265 0,53 1,06 1,59 2,12 2,65

1200 36 0,265 0,53 1,06 1,59 2,12 2,651600 44 0,265 0,53 1,06 1,59 2,12 2,652000 63 0,265 0,53 1,06 1,59 2,12 2,653000 63 0,265 0,53 1,06 1,59 2,12 2,654000 80 0,265 0,53 1,06 1,59 2,12 2,65

5

Fig. 5 Values of continuous

current, short time currentand inductance

Page 6: Line Traps

6

Tuning Device

The tuning device, connectedacross the main coil, forms ablocking circuit which provideshigh impedance over a specifiedPLC-frequency range. Depending on the type of tuning(see below) the tuning device consists of capacitors, in ductorsand resistors, all having relativelylow power ratings, compared tothe main coil. For environmentalprotection these components are mounted in one or more fiberglasshousings. The tuning device is in stalled inside the main coil. To meet changing PLC frequencyrequirements the tuning device iseasily accessible for replacementor field ad justment (if applicable).

The bandwidth of a Line Trap isthat frequency range over whichthe Line Trap provides a certainspecified minimum blocking impe-dance or resistance. Minimumblocking resistance should be specified if the potential exists forthe reactive component of theLine Trap impedance to resonatewith the substation impedance.The achievable bandwidth can beexpanded by increasing the maincoil inductance. Different types of tuning may beexpanded by increasing the maincoil inductance.

Different types of tuning may besupplied.

• Single Frequency Tuning

If narrow blocking bands are required single frequency tuning isthe simplest and most economicaltype of tuning available. Fig.6shows a typical schematic andblocking characteristic. Within thisnarrow band, however, high blocking impedance can be provi-ded, resulting in excellent PLC signal isolation.

• Double Frequency Tuning

The double frequency tuning arrangement blocks two relativelynarrow bands of frequencies.Otherwise, the blocking characte-ristic is similar to single frequencytuning.

For proper operation and isolationof the tuned bands a minimumfrequency separation must bemaintained between the peak tuning frequencies. This is 25 kHzor 25 % of the upper tuning frequency peak, whichever is greater. Fig.7 shows a typicaldouble frequency schematic andblocking characteristic.

Fig.6Single frequency tuning

Fig.7Double frequency tuning

Fig.8

Wideband tuning

b

Z Blocking impedanceR Resistive componentf Carrier frequencyfm Resonant frequency

(Geometric Mean Frequency GMF)

f’1 f’2 Frequency limits of blocking impedance

f1 f2 Frequency limits of resistive blocking impedance

Page 7: Line Traps

7

Fig.10Selftuned Line Trap

blocking characteristics

• Wideband Tuning

Wideband tuning is the most common type of tuning as it efficiently utilizes the main coil inductance. Wideband tuned LineTraps are suitable for multi-chan-nel applications, since relativelyconstant impedance is obtainedover a broad frequency range. Thistype of tuning provides high band-width flexibility for future changesor expansion of PLC frequencies.PLC channels can be placedanywhere within the blockedbandwidth. Fig.8 shows a typical widebandfrequency Line Trap schematic andblocking characteristic.

• Selftuned Line Traps

Selftuned Line Traps do not requirethe use of tuning devices. Theblocking characteristic as shown inFig.10 is achieved by simply utili-zing the self-capacitance of themain coil winding. The inductanceof a selftuned Line Trap is higherthan that of a tuned Line Trap.

Fig. 9Suspension mounted 380 kV,

1.0 mH, 2100 A Line Trap

Page 8: Line Traps

8

Protective Device

The protective device is a surgearrester connected in parallel withthe main coil and the tuning device. It protects the main coiland the tuning device by reducingthe transient overvoltages to levelscorresponding to distribution voltage class insulation.

The insulation level of the maincoil and tuning device is coordinatedwith the surge ar rester protectivecharacteristics.

Trench Line Traps are equippedwith advanced metal-oxide typesurge arresters having a dischargecurrent rating of 10kA. Surgearresters with higher dischargecurrent or high energy dissipationarrangements are also available onspecific request.

Mounting and Connection

Trench Line Traps can be mountedin several configurations. Suspen-sion mounted Line Traps areavailable with either single point ormulti-point suspension brackets.Line Traps can also be pedestalmounted directly onto couplingcapacitors (CCs), capacitive voltagetransformers (CVTs) or station postinsulators. Trench offers severaltypes of mounting pedestals:

• single insulator support pedestal

• multi-insulator support pedestal

• insulated pedestal

Other than the insulated pedestal,all pedestals are electricallyconnected to the lower terminalof the Line Trap, and as such canbe used as both the electrical andmechanical connection to the CCor CVT (see Fig.11a). Should it benecessary to utilize the upper LineTrap terminal as the connection tothe CC or CVT, a pedestal insulatedfrom the bottom end (bottom spider) of the Line Trap must beused in conjunction with a specialinsulated connection rod suppliedby Trench (see Fig.11b). All pedestals can be custom madeto suit customer requirements.

Terminals supplied on the Line Trapscan be either pad or stud type.Each type is manufactured tomeet the applicable IEC or NEMAstandards. In addition, terminals can be located on virtually any spider arm,ensuring total flexibility to meetindividual requirements. Terminaldetails and terminal orientationare shown in Fig.12 and Fig.13.

c

Fig. 11a Fig. 11b

Station

Station

Line

Line

CouplingCapacitor

CouplingCapacitor

Line Trap connection

Page 9: Line Traps

9

Fig.12

Fig. 12Terminal orientation(by special request may be situatedat any spider arm location. Number of spider arms is obtainedfrom actual quotation drawing, typically 4, 6 or 8)Et: is used to define the top terminal location, at centre or atany of the spiders.Eb: is used to define the bottomterminal location; at centre or atany of the spider arms.

Fig. 13Standard terminal types plated orbare aluminum

Note:Unless otherwise specified, flatterminal pads will be vertically oriented to reduce eddy currentheating. (ie. terminals oriented sothat the coil’s axis is in the planeof the terminal.)

Fig.13

Top view

Side view

Page 10: Line Traps

10

Calculation of tapping loss (At)and blocking attenuation (Ab)

Z1 = Characteristic impedance ofthe line

The impedance of substation Zs isassumed to be 0 Ohm.

• Center Frequency (fc)

fc is the mean frequency of the blocked bandwidth limit frequencies (f1, f2).

Definition of BlockingTerms

The blocking requirement of aLine Trap is dependent on thecharacteristic impedance of thetransmission line where PowerLine Carrier is to be applied. TheLine Trap blocking characteristicscan be specified in terms of:

• Blocking Impedance (Zb):

Zb is the complex impedance ofthe complete Line Trap within aspecified PLC frequency range.

• Blocking Resistance (Rb):

Rb is the value of the resistive

component of the blocking impedance, within a specifiedPLC frequency range.

• Tapping Loss (At)

At, also known as «InsertionLoss», is a measure of the lossof power sustained by a carrierfrequency signal due to the finite blocking ability of the LineTrap. The tapping loss of anideal Line Trap should be verylow and approach zero.

• Blocking Attenuation (Ab)

Ab is a measure of the relativetransmitted carrier frequencysignal which enters the trappedcircuit section of network. Theblocking attenuation of an idealLine Trap should be infinitelyhigh.

Equ. I At (dB) = 20 log10 (1+ ___ )Z1

2Zb

Equ. II Ab (dB) = 20 log10 (1+ ___ )Zb

Z1

fc=������f1x f2

Page 11: Line Traps

11

1,0 mH Line Trap

0,315 mH Line Trap0,2 mH Line Trap

0,5 mH Line Trap

Page 12: Line Traps

Subject to change whithout notice01.10

E 231

Trench Austria GmbHPaschinger Straße 49AT-4060 Linz-Leonding/AustriaPhone +43.732.6793-0Fax +43.732.671341email [email protected]

Trench Brasil LTDA Via Expressa de Contagem, 2685CEP 32370-485Contagem, Minas Gerais/BrasilPhone +55.31.391-5959Fax +55.31.391-1828email [email protected]

Trench China Limited3658 Jiang Cheng RoadMinhang, Shanghai 200245 P.R. ChinaPhone +86.21.64630088Fax +86.21.64637828email [email protected]

Trench France S.A.16, rue du Général CassagnouB.P. 70FR-68302 St-Louis/FrancePhone +33.3.89 70 23 23Fax +33.3.89 67 26 63email [email protected]

Trench Germany GmbHNürnberger Straße 199DE-96050 Bamberg/GermanyPhone +49.951.1803-0Fax +49.951.1803-224email [email protected]

Trench Italia S.r.l.Strada Curagnata 37IT-17014 Cairo-Montenotte/ItalyPhone +39.019.5161.111Fax +39.019.5161.401email [email protected]

Trench Limited Coil Product Division71 Maybrook Drive, ScarboroughOntario, Canada M1V 4B6Phone +1.416.298-8108Fax +1.416.298-2209email [email protected]

Trench Limited Instrument Transformer Division390 Midwest Road, ScarboroughOntario, Canada M1P 3B5Phone +1.416.751-8570Fax +1.416.751-6952email [email protected]

Trench Switzerland AGLehenmattstraße 353CH-4052 Basel/SwitzerlandPhone +41.61.315 51 11Fax +41.61.315 59 00ema il [email protected]

Trench (UK) LimitedSouth DriveHebburnTyne & WearNE31 1UW, Great BritainPhone +44.191.483.4711Fax +44.191.430.0633email [email protected]

www.trenchgroup.com