Lightning Protection Manual 2.pdf
Transcript of Lightning Protection Manual 2.pdf
-
1
-
2
-
3
This manual is intended to provide guidance on the principles and practices of
lightning protection for a wide range of structures and systems.
In general, it is not economically possible to provide total protection against all
the possible damaging effects of lightning, but the recommendations in this
manual will reduce the probability of damage to a calculated acceptable level.
Will minimize any lightning damage that does occur.
The decision to provide lightning protection may be taken without carrying out
a risk assessment . Where doubt exists as to the need for lightning protection,
further advice should be sought from a lightning protection consultant.
First decision has to be whether lightning protection is needed or not.
Realization that it is possible to provide effective protection against lightning
began with Franklin and for over a hundred years international standards
have been developed to provide guidance on the principles and practice of
lightning protection. Until about ten years ago, risk assessment was used to
determine if there was a need to provide lightning protection
This selection takes into account both efficiency and cost of their provision.
In the risk management approach, the lightning threats that create risk are
identified, the frequencies of all risk events are estimated, the consequences of
the risk events are determined, and if these are above a tolerable level of risk,
protection measures are applied to reduce the risk (R) to tolerable level (Ra).
This involves a choice from a range of protection level efficiencies for
protection against direct (d) strikes to the structure and decisions about the
extent of other measures for protecting low-voltage and electronic equipment
against indirect (i) lightning stresses incident from nearby strikes. In short:-
Risk = Rx = Rd + Ri ( Total risk is the sum of the direct & indirect risks) Rx = Nx Px x Px = kx px
R Ra
-
4
where Nx is the frequency of dangerous events, Px is the probability of damage
or injury, x is the relative amount of damage or injury with any consequential effects, and kx is a reduction factor associated with the protection measure
adopted and equals 1 in the absence of protection measures when Px = px .
The lightning protection measures include an LPS for the structure and its
occupants, protection against the lightning electromagnetic pulse (LEMP)
caused by direct and nearby strikes, and transient protection (TP) of incoming
services. The LPS for the structure comprises an air terminal network to
intercept the lightning strike, a downconductor system to conduct the discharge
current safely to earth and an earth termination network to dissipate the current
into the earth. The LEMP protection includes a number of measures to
protect sensitive electronic equipment such as the use of a mesh of
downconductors to minimize the internal magnetic field, the selection of
lightning protection zones, equipotential bonding and earthing, and the
installation of SPDs. The TP for incoming services includes the use of isolation
devices, the shielding of cables and the installation and coordination of SPDs.
Air terminal
A vertical or horizontal conductor of an LPS, positioned so as to intercept a lightning discharge, which establishes a zone of protection.
Damage () Mean relative amount of loss to a specified type of damage due to a lightning event, when damage factors are not taken into account.
Earth impedance (Z) The electrical impedance of an earthing electrode or structure to earth, derived from the earth potential rise divided by the impulse current to earth causing that rise. It is a relatively complex function and depends on :
The resistance component (R) as measured by an earth tester.
The reactance component (X), depending on the circuit path to the general body of earth.
A modifying (reducing) time-related component depending on soil ionization caused by high current and fast rise times.
-
5
Earth potential rise (EPR) The increase in electrical potential of an earthing electrode, body of soil or earthed structure, with respect to distant earth, caused by the discharge of current to the general body of earth through the impedance of that earthing electrode or structure.
Finial It is a term referring to short vertical air terminals.
Lightning flash density (Ng) The number of lightning flashes occurring on or over unit area in unit time. This is commonly expressed as per square kilometre per year
(km2 year1). The ground flash density is the number of ground flashes per unit area and per unit time, preferably expressed as a long-term (>10 years) average value.
Protection level (I to IV) Four levels of lightning protection. For each protection level, a set of maximum and minimum lightning current parameters is fixed, together with the corresponding rolling sphere radius.
CONCEPT OF RISK In this Standard, risk R is the probable annual loss due to lightning. Expressed as a number, it represents the probability of loss occurring over the period of a year. Thus a risk of 10-3 represents a chance of 1 in 1000 of a loss occurring during a year.
-
6
DAMAGE DUE TO LIGHTNING
Sources of damage The current in the lightning discharge is the potential source of damage. In this Section, the following sources of damage, relating to the proximity of the lightning strike, are taken into account : S1direct strike to the structure. S2strike to the ground near the structure. S3direct strike to a conductive electrical service line. S4strike to ground near a conductive electrical service line.
Conductive electrical service lines include electricity supply service lines and telecommunications service lines. The greater the height and collection area, the more lightning strikes will influence the structure. Tall trees and surrounding buildings may shield a structure from lightning strikes.Incoming conductive electrical service lines add to the lightning collection area as they can conduct lightning current into the building. Direct strikes to structure or incoming conductive electrical lines may cause mechanical damage, injury to people / animals and may cause fire and/or explosion.Indirect strikes as well as direct strikes may cause failure of electrical and electronic equipment due to overvoltages resulting from coupling of the lightning current.
Risk components S1 Lightning strikes directly to the structure
These may generate:
o Component Rh due to step and touch voltages outside the structure around downconductors causing shock to human beings
o Component Rs due to mechanical and thermal effects of the lightning current or by dangerous sparking causing fire, explosion, mechanical and chemical effects inside the structure .
o Component Rw due to overvoltages on internal installations and incoming services causing failure of electrical / electronic systems.
-
7
S2 Lightning strikes to ground near the structure These may generate component Rm due to overvoltages on internal installations and equipment (mainly induced by the magnetic field associated with the lightning current) causing failure of electrical and electronic systems .
S3 Lightning strikes directly to conductive electrical service lines. These may generate:
o Component Rg due to touch overvoltages transmitted through incoming lines causing shock of living beings inside the structure .
o Component Rc due to mechanical / thermal effects including dangerous sparking between external installation and metallic parts (generally at the point of entry of the incoming line into the structure) causing fire, mechanical / chemical effects on the structure and/or its content .
o Component Re due to overvoltages, transmitted through incoming lines to structure, causing failure of electrical / electronic systems .
S4 Lightning strikes to ground near conductive electrical service line conductors. These may generate component Rl due to induced overvoltages, transmitted through incoming lines to the structure, causing failure of electrical and electronic systems.
PROCEDURE FOR RISK ASSESSMENT The procedure for the risk assessment requires:
(a) Identification or defining of the structure / facility to be protected.. In most
cases it is a stand-alone building. The structure may encompass a building and
its associated outbuildings .Under certain conditions, a facility that is a part of a
building may be considered as the structure for risk assessment purposes. An example might be a communications installation at the top of an office building.
This segregation of a part of a building is only valid under the following
conditions:
-
8
(i) There is no risk of explosion in the remainder of the building.
(ii) Suitable fire barriers exist around the structure being considered (fire rating
of not less than 120 min).
(iii) Overvoltage (SPD) protection is provided on all conductive electrical
service lines at point-of-entry to the structure being considered.
(b) Determination of all the relevant physical, environmental and service
installation factors applicable to the structure.
(c) Identification of all the types of loss relevant for the structure or facility.
Structures involved in the provision of public service utilities such as water, gas,
electricity and telecommunications.
(d) For each type of loss relevant to the structure, determine the relevant
damage factors x and special hazard factors.
(e) For each type of loss relevant to the structure, determine the maximum
tolerable risk,Ra.
(f) For each type of loss relevant to the structure, calculate the risk due to
lightning by
(i) identifying the components Rx that make up the risk (see Figure 2.1);
(ii) calculating the identified risk components Rx; and
(iii) calculating the total risk due to lightning, R. (g) Compare the total risk R with the tolerable value Ra for each type of loss relevant to the structure.
-
9
The selection of the most suitable protection measures shall be made by the
consultant according to the contribution of each risk component to the total risk,
and according to the technical and economic aspects of the different protection
measures available. Technical considerations include addressing the highest risk
components while economic considerations involve minimizing the total cost to
achieve a suitable level of protection.
P E R S O N A L S A F E T Y The 30/30 safety guideline. An approaching thunderstorm is treated as dangerous when the time interval between seeing a lightning flash and hearing the thunder is less than 30 s . A receding local thunderstorm is no longer a threat when more than 30 min have elapsed after the last thunder is heard. Dont shelter under trees, particularly an isolated tree. If surrounded by trees, seek position outside the foliage , crouch, keeping feet together.
If on a boat deck, keep a low profile and avoid contacts with or being close to masts, rails, or other metallic objects. Avoid unnecessary contacts with communication or navigation equipment. Do not enter the water, and in general avoid contact with it. Additional protection may be gained by anchoring under high objects :jetties and bridges, provided that direct contact is not made with them. Isolated buoys and pylons should be avoided. Do not take a bath / shower and do not wash hands or dishes. Do not use personal computers and other electronic / electrical equipment, and avoid contacts with sinks, refrigerators, metallic pipes and other large metallic objects in the house. Disconnect television sets, personal computers, and other electronic / electrical appliances from antennas, conductive telecommunication connections and electricity supply outlets to avoid damage to them. Switching off an appliance does not disconnect neutral and earth wiring. Isolation / unplugging is the safest.
-
10
P R O T E C T I O N O F S T R U C T U R E S Following are recommendations for installation practices and selection of equipment to prevent damage caused by lightning discharge. The recommendations apply generally to the protection of structures using LPSs comprising air terminals, downconductors, equipotential bonding and earth terminations. If, after completing the LPS risk assessment, it is evident that surge protection is required to protect internal systems within the building and services at entry , an investment shall not be ignored.
LPS DESIGN RULES It is obvious that air terminals must be installed providing conductive paths for the lightning current from the air terminals to the earth . The downconductors should assist in preventing side-flashes to nearby metal elements. This is best done by locating downconductors immediately below the air terminals used to protect the most vulnerable parts. Rules for air terminals
(a) First, provide air terminals to protect the most vulnerable parts (points and corners);second, use the RSM method to check if the less vulnerable parts(edges) are protected and, if not, add more terminals to protect them; third, also check if the least vulnerable parts (such as flat surfaces) are protected and, if not, add more terminals.
(b) Air terminals shall be placed close to the most vulnerable parts; if a strip conductor is used, it shall be directly on the part it is to protect; if a vertical rod is used, its length shall be not less than 50cm, and it shall preferably be mounted within 1 m or 1/2 its length . Maximum allowable length of a rod terminal is 6 m. (c) If the structure has horizontal or gently sloping upper parts that are essentially cylindrical or oval in shape, then the edges are the vulnerable parts and shall be protected by air terminals; if a strip conductor is used, it shall be run along the edge(s); if vertical rods are used, there shall be a minimum of two evenly spaced terminals.
-
11
Rules for downconductors (a) Main conductors shall interconnect all air terminals and shall form one or more paths to earth via downconductors, such that the spacing between the downconductors does not exceed 20 m. (b) A downconductor shall be connected directly below an air terminal used to protect most vulnerable parts.If air terminal is on an exposed roof corner, its downconductor will also act as a continuation of air terminal to protect vertical edge below it, as required for tall structures.
Rules for earth terminations (a) Low earth resistance is desirable and all practical measures should be taken to achieve 10 or less for the whole interconnected LPS earth termination network.There shall be equipotential bonding at ground level for all metallic surfaces. (b) There shall be one earth termination per downconductor.
ZONES OF PROTECTION FOR LIGHTING INTERCEPTION
The protection efficiency against direct lightning strikes is achieved by installing an LPS in such a way that its air terminals establish zones of protection enclosing the whole structure. For the calculation of these zones of protection, the RSM,with a modification for large flat surfaces, is used. The RSM generally ensures that for lightning striking distances determined by the radius of the rolling sphere, the shortest distance between a lightning leader tip and any part of the structure is an air terminal.This method of analysis is suitable for conventional lightning terminals, which may be vertical rods, horizontal wires or strip conductors, railings, metal sheets, fascias and so on.
-
12
In the rolling sphere technique of determining zones of protection, a sphere of specified radius (a) is theoretically brought up to and rolled over the total structure. All sections of the structure that the sphere touches are considered to be exposed to direct lightning strokes and would need to be protected by air terminals. In general, air terminals need to be installed so that the sphere only touches their interception surfaces. This is illustrated below in next page, showing that the top corner/edge of the structure requires protection by an air terminal but the sides and lower section do not. The values of the rolling sphere radius (a) for the four protection levels (PL) I, II, III, IV are given in Table 4.2 together with the corresp.min. lightning current that will be intercepted.
-
13
ZONE OF PROTECTION ON A STRUCTURE BY A ROLLING
SPHERE
It is common to consider that PL III using a sphere of radius a, 45 m provides standardprotection. PL I and II with a, 20 and 30 m provide higher degrees of protection and should be used if required by the risk management calculations. Conversely, PL IV with a, 60 m provides a lower degree of protection. For PL III, the protection ensures that, for striking distances of 45 m or more, the shortest distance to the structure is to an air terminal. From table in previous page, such striking distances correspond to peak currents of 10 kA , and interception effic of 91%, there being only of the order of 9% of strikes having a lower current. In the RSM, lightning is considered most likely to follow the path of shortest distance. This path will have the highest average electric field produced by the potential difference between the tip of the lightning leader and the structure .
-
14
Buildings without structural steel frames The required conditions of protection for non-metallic buildings are generally
met by placing metal air terminals on the uppermost parts of the building or its
projections, with conductors connecting the air terminals to each other and to
earth. By this means a relatively small amount of metal properly positioned and
distributed can afford a satisfactory degree of protection and, if desired, the
material may be placed so as to give minimum interference to the appearance of
the building. A typical LPS is shown in
-
15
Reinforced concrete buildings The following recommendations apply to the use of steel reinforcement in
reinforced concrete buildings as part of the LPS. As far as possible, the steel reinforcement should be made electrically continuous in all concrete elements
having a structural purpose, e.g. columns, beams and also in non-structural
concrete elements, e.g. concrete wall panels, where the element, or a part of it, if
dislodged, could endanger persons below.
Where the steel reinforcement is used as the downconductor system, an
effective electrical connection should be made from the air terminal network to
the steel reinforcement at the top of the building. Such connections should be
made, by means such as welding or clamping to a minimum of four vertical
and/or horizontal bars, to ensure a multiplicity of conductive paths for the
discharge of lightning current.
NOTE: Steel reinforcement that is overlapped and tied by means of wire is not considered to provide an effective electrical connection for the purpose of air termination connection.
MATTER CONSIDERED WHEN PLANNING PROTECTION Design considerations
(a) Metal used in the roof, walls, framework or reinforcement above. .
NOTE: For a non-metallic roof, the position of any conduit, piping, water mains or other earthed metal immediately beneath the roof should be noted, as this may inadvertently attract a discharge if not shielded by an adjacent roof or structure, or downconductor . (b) Available positions for downconductors providing the required number of
low impedance paths from the air terminal network to the earth termination.
(c) The resistivity of the soil to design a suitable earth termination.
(d) Services entering the structure above ground.
(e) Radio and television antennas and microwave communications antennae.
(f) Flag masts, roof plant rooms:- lift rooms, boiler rooms, and water tanks .
-
16
(g) The provision of bonding connections to steel frame, reinforcement rods or
internal metalwork to allow for the free passage of the lightning conductor.
(h) The choice of metal most suitable for the conductor, e.g. aluminium
conductors for structures where aluminium is employed externally.
(i) Accessibility of test joints; protection by non-metallic casing from
mechanical damage and hazard ; lowering of flagmasts / tall chimneys.
(j) Preparation of a drawing detailing and showing positions of the main
components to form the lightning protection system .
Route for conductors Conductors should be installed with a view offering the least impedance to the
passage of discharge current between the air terminals and earth. The
impedance to earth is approximately inversely proportional to the
number of widely separated paths, so that from each air terminal there should be
as many paths to earth as practicable. The number of paths is increased and the
impedance decreased by connecting the conductors to form a cage enclosing the
building.
Economy of installation Economy of installation can be effected by taking advantage of constructional
features already installed as far as practicable.
Corrosion Corrosion resulting from contact of dissimilar metals can exist where a
conductor is held by fixing devices on or against external metal surfaces of a
building or structure.
Bonding connections between air terminal and down conductor should be sealed
against the ingress of moisture.
-
17
-
18
The design of the earth termination network should assume that each earthing
electrode will be bonded, directly to the following : the electrical installation
earthing system , the building structural steelwork , any water, sewer and fire
system supply pipes ( if metallic ) and pipelines for gaseous or liquid fuels( if
metallic ).
There is a hazard arising from the bonding of other service earthing electrodes.
The electricity supply service has many loads connected to it that
generate a direct current component; this direct current is an electrolytic hazard
to other earthing systems to which the electricity supply service earth is bonded.
The amount of direct current is limited but it is still sufficient to place at risk
some types of earthing electrodes. In particular, steel rods clad with copper or
stainless steel suffer premature failure when a small amount of direct
current such as this perforates the cladding, initiating a process of self-
destruction of the rod core.
It will be clear that the selection of any common metal or alloy for the earth
termination network places either itself or other systems or services at some risk
from galvanic corrosion.For lower cost installations ,the use of one of the
common metals or alloys may be satisfactory. The extent to which the material
combination can be damaging is related to soil moisture. Soil resistivity
typically below 30 . Expert advice on the selection of an appropriate earth termination network should normally be where such soil conditions exist.
-
19
FORM AND SIZE OF DOWN CONDUCTORS Factors influencing selection The form and size of the down conductors of the LPS should be selected having
regard to their minimum cross-sectional area required of a main current carrying component of a LPS is 35 mm2.
The dimensions of typical conductors are given below in table.
Electrical and thermal considerations
Air terminals and downconductors that may carry the full lightning current,
should have an adequate cross-sectional area and conductivity such that
they are able to carry without attaining temperatures that may give rise to risk of
fire. Copper conductors having a cross-sectional area of not less than 35 mm2 will normally be necessary for this purpose.
-
20
Conductors, which because of their arrangement in the LPS, will carry only a
proportion of the lightning current, may have a cross-sectional area that is
proportionately reduced but should be not less than 1/5 th of the cross-sectional
area to carry the full lightning current, or 6 mm2, whichever is the greater.
JOINTS Effectiveness of joints The LPS should have as few joints as possible. Joints and bonds should be
mechanically and electrically effective, e.g. clamped, screwed, bolted, crimped,
riveted or welded. All mechanical connections should be inspected on a regular
basis in accordance to ensure integrity of the connection over time. Particular
attention should be given to joints of dissimilar metals.
Fasteners. Conductors should be securely attached to the building or other object upon
which they are placed. Fasteners should be substantial in construction and not
subject to breakage, and should be, together with the nails, screws, or other
means by which they are fixed, of the same material as the conductors, or of
such nature that there will be no serious tendency towards galvanic corrosion in
the presence of moisture because of contact between the different parts.
Downconductors should be fastened at spacings not exceeding 1.0 m on
horizontal runs and not exceeding 1.5 m on vertical runs.
Plastics may be used for the fixing of conductors provided such materials are
suitable long-term exposure to the outdoor environment against the harmful
effects of ultraviolet radiation .
AIR TERMINALS May consist of a vertical rod , a single horizontal conductor as on the ridge of a
small dwelling, or a network of horizontal conductors with vertical rods for the
protection of roofs of large horizontal dimensions .
Protection may also be provided with a horizontal overhead wire supported, if
necessary, independently of the building to be protected or by a vertical air
-
21
terminal network .The upper portions of the downconductors on tall buildings
should be regarded as a continuation of the air terminal network and should be
positioned so as to intercept side strikes to the building. Preference should be
given to placing downconductors as near as possible to the exposed outer
vertical corners of a building.
All metallic projections, on or above the main surface of the roof, should be
bonded to, and form part of, the air terminal network. In the case of
telecommunications antennas, which have to be insulated from earth, a spark
gap connection to earth or an SPD should be provided.
Where roof construction consists of electrically continuous metallic materials,
such metallic roofs may form part of an LPS, obviating the need for air
terminals. If portions of a structure vary considerably in height, any necessary
vertical air terminal or air terminal network of the lower portions should, in
addition to their own downconductors,be bonded to the downconductors of the
taller portions
Air terminals may be of any form provided the section used and the means of
attaching it to the building structure have adequate mechanical strength to
withstand the expected winds.
Protection of roofs
The parts of roofs most likely to be struck by lightning are corners and edges of
flat roofs, chimneys, and the ridges and eaves of sloping roofs.
Preference should be given to positioning the air terminals so as to protect these
highly exposed parts.The height of a vertical air terminal should be such that the
tip will be not less than 50 cm above the object to be protected. On large flat
and gently sloping roof areas , a number of vertical rods of greater than 50 cm
in height may be needed to establish a zone of protection over the whole roof .
Horizontal conductors such as strap on metallic objects such as flagpoles, metal
railings, steel plant surrounds and roof access ladders may be used as air
terminals to protect a planar roof surface. When positioned at a height of more
than 50 cm above the area to be protected , the conductors or objects will
be at a suitable height to achieve the selected interception efficiency.
-
22
All metallic objects at roof level such as sheeting, plant, plant screens, tanks,
gutters,walkways, ladders, antennas, masts, poles, vents, chimneys, conduits,
piping, cable trays, ..etc should be bonded to the air termination network.
DOWNCONDUCTORS Structures Downconductors should be installed at each external corner of the building and
additional downconductors , as necessary, at spacings not exceeding 20 m.
Any extended metal running vertically through the structure should be bonded
to the lightning downconductor,.
A structure on bare rock, to be with at least 2 downconductors equally spaced.
EARTH TERMINATIONS The design of earth terminations should be such that lightning currents
are discharged into the earth in a manner that will minimize step and touch
potentials and also side-flashing . This can be achieved by ensuring that the
potential with respect to earth at each earth termination is limited by enough
low resistance to earth, so that the discharged current flows in as close to
uniform manner as possible in all directions away from the structure.
Ionization of the soil near an earthing electrode carrying lightning current tends
to reduce the potential of the earthing electrode relative to remote earth to a
lower value than the potential that would be calculated using the earth resistance
measured at low currents.
Recommended values for earth resistance. In general, the whole of an interconnected LPS should have an earthing
resistance not exceeding 10 before any bonding is effected to services that are not part of the LPS. Where the installation has two or more air terminal
networks not directly interconnected,such as a twin-tower building, then for the
purpose of determining the required earthing resistance, it should be considered
as consisting of separate LPSs.
-
23
Where buildings are used for telecommunications services or sensitive
electronic equipment, an earthing resistance not exceeding 5 should be required.A reduction of earthing resistance can be achieved by extending or
adding to the earth termination network or by interconnecting the individual
earth terminations of downconductors.
Notwithstanding the above recommendations, earthing electrodes complying
with either of the following, need not comply with the 10 criterion:
(a) For a substantial structure effectively encircled by a buried earthing
electrode, an earthing resistance not exceeding 30 should be satisfactory. A buried earthing electrode covering at least three sides of
the structure may be regarded as effectively encircling the structure.
(b) For any system incorporating two or more downconductors, it should not
be necessary to install a total length of more than 50 m of widely separated
horizontal or vertical earthing electrodes per downconductor, regardless of the
earthing resistance.
Common earthing electrode Where conditions permit potential equalization techniques to be used, a
common earthing electrode may be installed to serve the LPS and other
appropriate services. The earthing electrode should comply with the
recommendations in standards and with any regulations that may govern the
appropriate services .
Where isolation is required, a common earthing electrode should not be used,
but the separate earthing electrodes should be bonded via an SPD to minimize
potential differences between the LPS earth termination network and other
earthing systems in the event of a lightning strike.
Communications earths Where a communications earth, such as a Telecommunications Functional
Earthing Electrode (TFEE), is required to be isolated from other earths, because
of noise or direct current conduction considerations, this earth should be bonded
through a normally nonconducting protector or SPD.
-
24
Joints Joints between earthing conductors and earthing electrodes should be of
adequate strength and current-carrying capacity, and be arranged so as to ensure
that there will be no failure of the connection under conditions of use or
exposure that can reasonably be expected.
GENERAL CONSIDERATIONS FOR PROTECTION
Each building will require specific consideration of the protective measures that
should be applied. Particular attention should be given to possible entry and exit
points for lightning current, which may include one or more of the following:
(a) Rooftop or external structures : TV antennas, dishes, metals, gutters , pipes ,
metal windows, frames, and ventilation outlets not protected by the LPS for the
building structure . These features will invariably be possible entry points for a
lightning discharge.
(b) The electricity supply service entry .This will normally be an entry point for
lightning if the service is aerial or overhead.
(c) The telecommunications services entry .This may be an entry point if the
service is overhead using a dropwire or aerial cable. The service is more
commonly underground and in such cases could be either an entry or exit point.
(d) Gas supply systems These are usually exit points for lightning .
(e) Metallic water supply . This is usually exit points for lightning.
(f) The LPS for the building (if provided) By design these systems provide both
an entry and exit point for a lightning discharge but, because of bonding, will
present an EPR condition to other services.
-
25
An illustration of possible entry and exit points for a lightning discharge.
-
26
Installation of equipotential bonding Consequently, bonding conductors should not be grouped with other
cables that are sensitive to induction unless the other cables are also bonded to
the LPS. If the bonding conductor is long (some tens of metres) it shall be
considered as an impulse transmission line, in which mode the protection
afforded by the bonding will be limited.
(a) Rooftop antennae and dishes. The bonding conductor should be attached to the most substantial part of the structural metal supporting the
equipment consistent with it fulfilling the requirements of an air terminal for the
LPS of a building. The bonding conductor to the antenna or communications
hardware should be insulated , if run within the building, but may be
uninsulated if run externally. The cross-sectional area of the bonding
conductor should be not less than 16 mm2 if made of copper.
(b) The electricity supply service entry .There are two distinct considerations
that apply.Firstly, the electrical installation earth should be bonded to the LPS
earth termination network with a copper conductor of not less than 6 mm2
cross-sectional area.
Secondly, SPDs should be installed for each active conductor of the electricity
supply service. Where an SPD is mounted on, or in, the building, its earthing
system should be bonded to the LPS by a conductor having a cross-sectional
area of not less than that utilized for its own earthing conductor. Where SPD
equipment is separated from the building (e.g. mounted on a customers electricity supply service pole), the SPD earth should not be used as the earthing
termination for the building LPS, however, the LPS earth termination network
and the SPD earth may be bonded together, if desired.
(c) The telecommunications service entry . The service should be regarded as a
potential entry point for lightning and an SPD should be fitted, subject to the
requirements of the telecommunications regulatory authority. The telecoms
service earthing system shall be bonded to the LPS earth termination network.
The bonding conductor should have a cross-sectional area of not less than 6
mm2 if made of copper.
(d) Metallic water supply should be bonded to the LPS and connected to the
electricity supply service earth. Metallic piping systems associated with fire
sprinklers, water, hot water or flammable liquid, that are unavoidably in contact
with the exposed conductive parts of wiring enclosures, cable components or
other electrical equipment shall be connected to such equipment by means of an
equipotential bonding conductor.
-
27
(e) Building earthing systems frequently have several earthing systems that
may be installed independently at different times : Electricity supply service
earthing system, telecoms earthing system some times more than one, the LPS
earth termination network and other special purpose earthing systems. It is
generally desirable to bond all such earthing systems but there may be specific
reasons for not doing so.
(f) The LPS earth termination network .Where an LPS is in place all of the
services earth should be bonded to the LPS earth termination network.
PROTECTION OF EQUIPMENT Lightning induces overvoltages in electrical lines, telecom lines, signalling,
data, and coaxial lines.
Equipment overvoltages may be experienced in the following ways:
(a) By direct conduction of lightning current on the conductors feeding into the
building. Ex. would be lightning striking overhead lines. This mechanism is of
lower probability, but involves higher surge currents.
(b) Indirectly, (through magnetic induction, or electrostatic coupling) where
lightning strikes nearby, and surges are induced on conductors feeding building.
This mechanism has higher probability, but results in lower surge currents.
(c) Lightning striking the LPS or other nearby objects, resulting in an EPR. This
can cause potential differences in earthing systems, causing flashover and
equipmentdamage.
(d) Temporary overvoltages at mains a.c. system frequency that can occur for a
number of reasons. Strategies to deal with involve equipotential bonding of the
earthing systems, and the provision of SPDs.
Equipotential bonding for equipment protection Voltage differences that are insufficient to cause injury to persons can be
extremely damaging to equipment. It is possible to have voltage drops in
bonding conductors that are carrying lightning surges in excess of 1kV per
metre. It is important that bonding conductors be kept short to reduce this
voltage difference, and to achieve this, all services should enter in close
-
28
proximity. For protection of equipment, this concept can be extended to
particular areas within the building. For example, consider
the case of a multistorey building with incoming underground services, and a
telephone system installed on an upper floor. On the lower level, the required
equipotential bonding will be performed, and primary surge protection to both
power and telecom lines can be fitted at that location, and will connect to the
same equipotential earth system.
On this lower level, it may well be that the bonding conductor lengths are not
ideal, depending on where the services enter, and thus the protection provided is
compromised.However, on upper floor where the telephone system is installed,
the same concept can be repeated, but at this point more control is possible over
wiring and equipment locations. That is, at this location all the services should
enter the room at the same point, and secondary surge protection to both power
and telecommunications lines can be provided at this location with short, direct
connections to the common earthing point.
Surge protective devices (SPDs) An SPD is a device intended to mitigate surge overvoltages . That is, it behaves
in a benign state until a voltage or current exceeds a designed value, then the
SPD acts to reduce the voltage or current, in order to prevent damage to
equipment in protection.SPDs often have features, such as mechanisms to
indicate their operational status,normally indicated in colour.
VARISTORS. These are made from metal oxide and are known as metal oxide varistors
(MOVs) or Voltage Dependent resistors (VDRs). The resistance of varistors
drops significantly when the voltage exceeds a limit thus clamping the voltage
near the limit. It normally respond in nanoseconds.
SOLID STATE DEVICES. .
Consists of special zener diodes that exhibit voltage limiting characteristics and
are optimized to handle surge currents. The breakdown voltages of such devices
are typically in the range 5 V to 200 V. They have current ratings up to several
hundred amperes and response times of the order of 10 picoseconds. Another
form consists of thyristors, that switch when their operation voltage is exceeded,
-
29
and act to clamp overvoltages. Their reduced voltage during conduction means
they can handle higher surge currents, compared with the zener diode type.
SPD configuration SPDs are configured as being either shunt or series protectors :
(a) Shunt protector .
Known as a one-port SPD, connected in shunt with the circuit to be protected,
as shown in Figure 5.3(a). A one-port device may have separate input and
output terminals without a specific series impedance between these terminals, as
shown in Figure 5.3(b). The latter arrangement is sometimes known as a series
connected, shunt protector.
A shunt protector with just two terminals (i.e. does not have separate input and
output terminals) has no limitation with regard to the load current of the circuit
to which it is applied. However, its ability to clamp overvoltages is reduced by
the additional voltage drop that occurs across its connecting leads. For this
reason, some shunt protectors are manufactured with separate input and output
terminals. This arrangement substantially reduces the connecting lead voltage
drop problem, but does mean that the full load current passes through the
device, which needs to be designed to handle this current.
FIGURE 5.3 EXAMPLES OF SHUNT (ONE-PORT) PROTECTORS
(b) Series protector known as a two-port SPD, is an SPD with two sets of
-
30
terminals, input and output. A specific series impedance is inserted between
these terminals. Typical examples are shown in Figure 5.4.
The series current limitation of the series protector will typically be determined
by the series impedance. Sometimes a protector is referred to as an n-stage
protector, and although this term is not applied, the n should refer to the number of shunt overvoltage stages that are separated by series.
Multi-service surge protection device (MSPD) An MSPD is a combination protector that combines both power protection and
signalling/telecommunications protection in one . Is an effective way of
protecting IT and sensitive equipment that has more than one connected service.
By including all the protection in the one device, the distance between the SPD
earth connections is very short, which greatly reduces the potential difference
between these services under incident surge conditions. A general diagram of an
MSPD is shown in Figure 5.5.
-
31
Parameters of an SPD. The primary parameters relate to how well an SPD limits overvoltages, how
much surge current it handles, and what voltage system is it designed for. The
following parameters are listed together with the IEC symbols for these
parameters.
Maximum continuous operating voltage (Uc)This is the max voltage that can be continuously applied to protector. For the power system, this should be at
least 275 V for SPDs connected between the phase and neutral conductors.
Rated load current (IL)Max continuous rated r.m.s. or d.c. current that can be supplied to a load connected to the protected output of an SPD.
Maximum surge current (Imax)This is the peak value of the 8/20 s waveshape current impulse that the protector can handle. The protector only has
to be able to withstand this surge current once. Known as the single shot rating.
Nominal surge current (In)This is the peak value of the 8/20 s waveshape current impulse that protector can handle many times. A protector must be able
to withstand at least 15 impulses at In.
Voltage protection level (Up)This is the peak voltage that the protector protects to (limits the voltage to). It is sometimes referred to as the let-through, ,
voltage.
Some SPDs include shunt capacitance that provides a filtering effect at
EMI/RFI frequencies, but provides little benefit at typical lightning surge
frequencies. Similarly, surge current levels may cause inductor saturation in
standard EMI/RFI filters, which will degrade the filter action.
Temporary overvoltage (TOV)
It is when the power voltage on an a.c power system rises above its normal
value. This can be caused by many factors including poor regulation,
faults on the LV or HV distribution system (including phase shorts to neutral or
earth, and loss of neutral conductor), capacitor switching, HV contact on
LV circuits.
These events typically last from 0.2 s up to 5 s. And considered a surge.
-
32
Application of SPDs The following aspects should be considered :
(a) Modes of protection . With any signal or electrical transmission system employing two lines
and a separate protection earth, two types of transients can occur. The first
type appears as a difference between the two lines, independent of their
potential differences to earth; this is known as a differential mode transient ,
where the transient voltage source is superimposed onto the normal signal
carried by the lines.
The second type appears as a transient between each line and the earth,
and is known as a common mode transient , where the transient voltage sources
are superimposed onto the normal potentials between the lines and earth.
The use of two non-earthed lines is common. Telephone lines use two wires
over which the signal is transmitted, with neither line tied to earth. RS-422
signalling for computer data uses two lines for each data channel, which is
known as balanced-pair signalling.When protective equipment is connected to
such lines, both differential and common mode transients must be suppressed.
Placing a protective device across the two signalling lines alone is not
sufficient. The high potentials to earth created by common mode transients can
cause insulation breakdown and arc-over, and damage electronic components.
Protection against transients can be achieved by the provision of voltage
clamping or diversion devices between the lines, and between the
lines and earth. These will shunt common mode transients to earth before they
are allowed to reach breakdown potentials.
Equipment to be protected is typically more robust to transients from line to
earth . Experience has shown that mains equipment is more easily damaged
from line to neutral transients, and although protection could be provided in all
modes , good protection is usually obtained by providing LN and NE protection modes only.
-
33
SPD location.
There are many possible locations where SPDs could be installed within a
facility. The aim is to provide effective protection to the equipment nominated
for protection, and to do so economically. The most effective is to provide SPDs
at the building service point-of-entry (known as primary protection), and then, if
necessary, to provide additional surge protection within the building closer to
the equipment to be protected (known as secondary protection).
Primary protection is important because the main function of such an SPD is to
keep most of the surge current from entering the building, by diverting it
directly to earth.
When considering mains power circuit protection, the concept of location
categories can be used . Building point-of-entry is where primary protection
would be installed. Further within the building are for secondary protection, to
be fitted as required, especially in the following situations:
(i) Where sensitive equipment is present; cctvs , Pcs, telecoms equip,etc.
(ii) Where the distance between the SPD located at the entrance and the
equipment to be protected is too long
(iii) Where there is internal equipment generating switching surges, or other
internal interference sources, inside the building.
Surge ratings
A lightning surge, travelling within a building is attenuated by the SPDs. Thus
higher levels of surge current are likely to be encountered at the building point-
of entry, compared to the distant end of a branch circuit;
The lightning surge current to be handled by a point-of-entry SPD has
traditionally been considered to come into the building via the service
conductors. If lightning strikes the building LPS, or even the ground or an
object nearby, a local EPR occurs. The incoming service conductors are
typically referenced to a distant earth (such as the neutral conductor grounded at
the secondary transformer some distance down the street, with the phase
conductor also being referenced to that distant earth by virtue of the transformer
winding).
-
34
The effect of the local EPR is that a proportion of the lightning current flows
out through the point-of-entry SPDs on its way to reaching the distant earth. The
surge current in the SPDs in this case is very large, being a significant
proportion of the lightning current itself.
While Table below gives a surge rating for SPDs in this case (Category C3)
using the 8/20 s waveshape, it should be acknowledged that the IEC standards make reference to a 10/350 s waveshape for use in this case, and the symbol given to the current rating using this waveshape is Iimp.
For example, an SPD withstanding a 100 kA 8/20 s impulse might be expected to withstand a 10 kA 10/350 s impulse. Given this discussion, for mains power system SPDs, the following surge current ratings are recommended, where the
surge rating is the Imax, or single shot, 8/20 s value, and apply for each SPD from the phase to neutral conductors.
Coordination
Often the approach taken is to have the primary SPD handle the bulk
surge current. A secondary protector that will not need to handle such a high
value of surge current,can be installed close to the equipment and can be chosen
to have an acceptable Up value.
However, to achieve this result, careful coordination between the two devices
needs to be undertaken. This is quite a complex matter, and a total examination
of the issues is beyond the scope of this Standard. However, simple rule is to
ensure there is at least 10 to 20 m of electrical cabling between two . If
this cannot be achieved, purpose built inductors are available that can be placed
in the circuit to achieve this effective separation.
-
35
Wiring considerations. It is essential to provide a fuse or circuit breaker ahead of the SPD to provide
for the safe disconnection of a failed SPD. SPDs should be installed after the
main switch but prior to any RCD.
If the terminals of the SPD are rated for the required load current level, a
configuration as shown in Figure below (B) is preferred.
This wiring method is known as Kelvin connection . Failing this, twisting the
connecting conductors together as shown in above ( C ) can have a substantial
impact on reducing the voltage drop.
Failure modes of SPDs Typically an SPD initially fails to a low impedance state, and the resulting
current that then flows into the SPD either causes the SPDs internal fusing to
operate, or causes external fusing/protection to operate. Consideration needs to
be given to the most desirable location for the external fuse, and whether it is
desirable for power to be disconnected from the load when the SPD fails. If the
external fuse/protection is in series with the load current, power will be
disconnected from the load when the SPD fails. In some applications this is
considered beneficial, since the SPD is no longer protecting the load. However,
locating the fuse in the non-load carrying SPD connection wiring, means that a
ruptured fuse will isolate the SPD, but allow power to continue to the load.
SPDs are fitted with a visual indication to show their operational status, and
may additionally be fitted with contacts to allow for remote monitoring.
-
36
Withstand voltage of equipment.
The equipment to be protected may have a level of resistability to surges
designed into it. In particular, a resistance level to electromagnetic interference
(EMI) disturbances is mandated. Ideally, the Up of the externally provided SPDs should be lower than the Up of any equipment internal surge protection components, otherwise the internal components may be damaged instead of
being protected by the external SPDs.
Lightning surges need not physically damage equipment for it to experience
problems. Erratic operation, that may or may not require manual resetting, can
occur and lead to data loss at surge levels which are lower than those required to
cause hardware failure.
Rapid changes in the voltage supply, even those for which the
amplitude does not exceed the normal mains power peak, can cause problems.
This dv/dt problem can be reduced by utilizing SPDs with filters.
Magnetic shielding and line routing. Magnetic shielding reduces electromagnetic fields, and can also provide a
reduction in the emissions from electrical noise. The complexity of shielding
can range from the use of metallic conduits, to simple metal enclosures or
cabinets, and up to whole rooms being comprised of shielding
materials. Such shields need to be earthed to be effective, and any SPDs
provided to conductors entering the shielded area need to be effectively
connected to the shield.
The amount of surge energy directly induced into building conductors from
nearby lightning strikes depends on the closeness of the current source, and the
loop area formed by the conductors. Conductors of the same service should be
run together, along with an earthing conductor, or otherwise run in close
proximity to other earthed components, such as earthed cable trays. To reduce
the inductive loop area, such cables should be neatly tied together and not
allowed to splay out over the whole tray width.
-
37
Practical installation examples.
Determine protection needs. Simple methodology for determining where SPDs are required. Method asks
what requires protection , and then drawing an imaginary box around it. Each
location where electrical lines cross the box is a potential location for SPDs, and
they should be provided where the particular electrical line is prone to having
surges on it. Then the earths of the SPDs are connected together to the earths of
the equipment, and taken to earth.
Typically it will be necessary to consider the following points for SPDs:
(a) At point-of-entry of external services e.g. electricity supply and telecoms.
(b) At the connection of the external services to the equipment.
(b) At the connection of long internal cabling to the equipment e.g. communications and LAN. The two latter mentioned can damage
equipment:
(i) An excessive voltage/current enters the building via a service due to either a
lack of protection or incorrectly installed protection. Both the mains and
telecomms point of entry SPDs earths are bonded to the main earth bar by conductors of 1.5 m or less where SPDs are installed.
(ii) An excessive voltage/current is induced into the internal wiring loop.
The procedure for protecting equipment is as follows:
(a) Install secondary protection at equipment when risk of damage due to
induction into the external service conductors and the building conductors
exceeds an acceptable level.
(b) Install point-of-entry protection when the risk of damage due to a direct
strike to the structure or service conductors exceeds an acceptable level. A
prime role of the point-of-entry protection, apart from preventing dangerous
discharges is to protect the secondary protection from damage.
-
38
Protection examples.
Example 1.
A central PLC and remote sensor . It is determined that a particular industrial process must be protected. It consists
of a central controller (PLC), and various sensors and controls. For simplicity,
the example will show two sensors, one at a considerable distance from the
PLC, and another close to the PLC. The arrangement is shown in Fig. below.
-
39
EXAMPLE OF CENTRAL PLC AND REMOTE SENSOR.
The PLC has a console and modem to allow communication, and consequently
has electrical and telephone services. The signal line is over 1 km in length.
Since the operator console is close to the PLC there is no reasonable subjecting
of surges impinging on that connection. Likewise, any sensors or controls close
to the PLC would not normally require protection.
SPDs should be installed close to equipment they are to protect, and must have
their earths connected together, and connected to the PLC earth, and taken to
earth. The PLC and modem are mounted next to each on a rack. Just below ,
them, the required SPDs are mounted in a row, with an earthing busbar
immediately below them, connected at each end to the rack frame. Each SPD
will have a short direct connection to the busbar not exceeding 10 cm, and the
PLC will also have a direct connection to the busbar. In this manner, effective
equipotential bonding will be achieved .
The SPD on the signal line at the PLC end does not provide protection for the
remote sensor. The only line here is the signal line, and so an SPD is provided
on it. This SPD is earthed with a direct short connection to the sensor earth (and
associated pipe ), and taken to a local earth. There is no point in trying to
connect this very distant earth to the PLC earth via a bonding conductor.
In addition to secondary SPDs installed closed to the equipment, considerations
as whether it is run in metallic conduit or not, it may be prudent to include
primary point-of-entry protection on the PLC signal lines where they enter the
building, in addition to the secondary protection shown at the PLC.
Example 2.
A video surveillance system .
This example is similar in eg 1. The DVR will have surge protection applied to
the long camera feeds and to the a.c. power line. The video feeds that are
selected for protection will need all their signal lines protected, and this may
include the video feed, the power supply leads, and any pan and tilt control
signals.
The earths of these SPDs will connect to each other and to the equipment earth.
Video cameras that are located nearby in the same building may not need surge
protection fitted. Those video cameras that are located a long distance from the
central monitoring and recording equipment will need the same protection fitted
at the remote end as was fitted at the central end.
-
40
The earths of these SPDs must be connected to the video camera earth, and then
be taken to a local earth. Although all earth connections should be as short as
possible, it is particularly important to keep the length of the SPD earths to
video camera earth short.
Example 3
A multistorey building with PABX on upper floor .
his is a multistorey building with services entering on grnd floor, and PABX on
an upper flr. Regardless of whether the point-of-entry location of the telecoms
and power services are co-located , there can be induction into the internal
wiring between the grnd floor and PABX. Therefore the electricity supply, the
exchange line and the outdoor extensions will require protection at the PABX.
The local handsets do not need protection . To ensure adequate protection of the
PABX it is necessary to have a DB and a telecoms distributor (IDF) co-located
with the PABX. SPDs are installed in the DB and the IDF. Where direct strike
protection is required SPDs need to be installed at the point-of-entry .
-
41
Example 4
A domestic computer and ADSL modem . The simplest way to provide SPDs with short bonding conductors to a common
earth point is to use an MSPD so this has been used, along with a power board
to provide additional protected outlets. A Fax machine at the same physical
location has also been protected using a second MSPD.
-
42
Example 5
A rooftop cellular base station. In this example a cellular base station is located on the roof of a multistorey
building.Fig belowshows an effective means of providing lightning, earthing
and surge protection.
-
43
The a.c. power supply is fed to the base station dist.board from a main switch
board located in the basement of the building. An SPD (diverter )would be
installed at the MSB. A second SPD (surge filter) is installed on the a.c. power
feed to the rooftop distribution board.
All other metallic services, for example antenna feeders should be bonded and
fitted with SPDs. All equipment should be referenced to a common earth
bonding bar in the cabin and this in turn bonded to the tower and building LPS.
There will be a connection to the main a.c. earth via the earth conductor in the
power cable to the roof.
Good practice suggests that all metallic services should enter the cabin on the
same side and the common earth to the tower and LPS should exit the same
side.
It should be noted that in the event of a lightning strike to the tower, conducted
currents will flow through the power earth conductor, and care should be taken
to segregate cables if possible.Antennas installed on the tower that contain
electronics may require additional protection measures.
P R O T E C T I O N O F M I S C E L L A N E O U S
S T R U C T U R E S A N D P R O P E R T Y.
STRUCTURES WITH ANTENNAS Indoor antenna system.
This may be indoor radio and television receiving antennas .
Outdoor antennas on protected structures
This may be outdoor radio and television receiving antennas without
further precautions, provided that every part of the antenna system, including
any supporting metalwork, is within the zone of protection of the LPS. Where
these conditions cannot be fulfilled, precautions should be taken to ensure that
the lightning current can be discharged to earth without damage to the structure
or injury to its occupants with an antenna system fitted : -
-
44
(a) Directly onto a protected structure. This can be done by connecting the
antenna bracket structure to the LPS at the nearest point accessible below the
antenna installation; or
(b) On a metallic support structure that projects above the LPS. This can be
accomplished by connecting the antenna support structure to the LPS at the
nearest point accessible below the antenna installation. Consideration should be
given to the fitting of SPDs in the conductors connected to the antenna system.
Antennas on unprotected structures.
Before installing an antenna on an unprotected structure, the need to provide an
LPS should be assessed . The earthing electrode of the LPS may also be used
for the purpose of earthing a radio system.
STRUCTURES NEAR TREES
When a tree is struck by lightning, a voltage drop develops along its branches,
trunk and roots. The side-flash clearances between the tree and adjacent
structures are set by taking 100 kV/m as the flashover strength of unseasoned
wet timber and 500 kV/m as the breakdown strength of air.
If tree is less than the height of the structure , its presence can be disregarded. If
taller , the following clearances between the structure and the tree may be
considered as safe:
(a) For normal structures; one-third of the height of the structure.
(b) For structures with explosive or highly-flammable contents; the height of
the
structure.If the clearances cannot be met then the structure should be fitted with
lightning protection in such a manner that the side-flash always terminates on
the protection system.
If the tree is fitted with LPS, no further protection is necessary for the structure ,
provided that conditions for zone of protection and separation are fulfilled.
PROTECTION OF TREES.
Protection of trees needs to be considered only where the tree is desired for
historical or other reasons.
-
45
A main downconductor should be run from the topmost part of tree to the
earth termination . Large upper branches should be provided with branch
conductors bonded to the main conductor. Allowance should be made for
swaying in the wind and the natural growth of the tree.
The earth termination should consist of two rods driven into the ground on
opposite sides of, and close to, the trunk of the tree. A strip conductor should be
buried to a depth of 3mtrs to encircle the roots of the tree at a minimum distance
of 8 m radius from the centre of the tree or at a distance equal to 1 m beyond the
spread of the foliage, whichever is the greater. This conductor should also be
bonded to the rods by two radial conductors.
Where two or more trees are so close together that their encircling earth
conductors would intersect, one conductor adequately connected to the earth
rods should be buried so as to surround the roots of all the trees.
The recommended is to protect the roots of the tree and to reduce the potential
gradient, in the event of a lightning discharge to the tree.
CHIMNEYS, METAL GUY-WIRES OR WIRE ROPES
Metal guy-wires or wire ropes attached to steel anchor rods set in earth may be
considered as sufficiently earthed. Other guy-wires or wire
ropes should be earthed . Metal chimneys or flues need no protection against
lightning other than be properly earthed.
Metal ladders .
Where chimneys have a metal ladder , they should be connected to the LPS at
their upper and lower ends.
Chimneys Chimneys consisting partly reinforced concrete should be electrically
connected together and electrically connected to the downconductors
at the top and bottom of the concrete.
-
46
PROTECTION OF BOATS
A boat is at risk both because of its method of construction (except
for metal-hulled boats) and because it forms a marked protrusion above the
surrounding water surfaces. Overseas statistics show that in excess of 10 percent
of fatalities occurring on cruising sailing boats are due to lightning.
While the principles to be applied will not differ from those for land-based
structures, the methods employed will depend on the form of construction and
the type of boat to be protected.
Elements of the protection system
Air terminal A metal mast or the metal fitting on a timber mast will act as an adequate air
terminal. The mast, if metallic will both act as downconductors and each should
be connected to an earth termination.
Stays as small as 3 mm diameter steel wire will serve as effective
downconductors, but may be damaged under severe lightning discharges.
Earthing
Any metal surface that is normally submerged in the water will provide
adequate earthing. Propellers, metal rudder surfaces and metal keels may be
used. The earth plate for the radio transmitter may also be used, providing that it
is constructed of solid material and not of the porous type. A metal or a ferro-
cement hull also constitutes an adequate earth.
Metallic objects Metallic objects that are permanent parts of the boat and whose function would
not seriously be affected by earthing should be made part of the LPS by
interconnection with it. The purpose of interconnecting the metal parts of a boat
with a downconductor is to prevent side-flashes to metal objects .
A general rule is, that if the non-conducting part of the alternative path through
such objectis less than one-eighth of the length of downconductor bridged out,
then that object shouldbe electrically interconnected with the downconductor.
-
47
Radio transceivers
A whip antenna consisting of a fine wire embedded in a glass fibre tube cannot
be considered a satisfactory lightning conductor and should be folded down
during a lightning
storm.
All radio equipment or other navigational equipment with exposed transducers
such as radar, wind speed/direction indicators, and the like, should be fitted with
effectively-earthed spark gaps or SPDs. Alternatively, input cabling should be
disconnected from the equipment if there appears to be imminent danger of the
boat being struck by lightning.
Corrosion
Care should be taken that the design of the LPS does not promote the
occurrence of electrolytic or galvanic corrosion. Bonding of dissimilar metals
and interconnection of the earth terminals of different pieces of electrical
equipment should not be undertaken without expert knowledge .
Protection of boats with masts
Sailing or power boats that have a mast or masts of sufficient height must
consider if they give an adequate zone of protection . They may be protected by
earthing the lower ends of the standing rigging and the base of a metallic mast,
or the lower end of a continuous metal sail track on a timber mast.
Where the mast of a boat is stepped on deck, particular care should be taken to
ensure that the conductor from the base of the mast follows a direct route if it
passes through the accommodation section of the boat.
A typical small sailing boat with aluminium mast stepped on deck, glass fibre
hull with the metal ballast encapsulated in the glass fibre and with chainplates
moulded into the hull provides something of a problem.In such cases, it is
suggested that some protection be sought when necessary by temporarily
connecting the mast and stays together at deck level by a length of chain or
other flexible conductor and allowing a short length of chain or the conductor to
hang in the water at each chainplate.
-
48
Protection of boats without masts
Boats without masts do not constitute as high a risk as boats with masts.
However, where the size of the boat is such as to cause a marked protrusion
above the surrounding water surfaces, should be fitted with air terminals that
will give at least the protection for land-based structures.
Precautions for persons and maintenance suggestions
During a lightning storm, persons should remain inside a closed boat and avoid
contact with metallic items such as gear levers . Persons should stay as far as
practicable from any parts of the standing rigging or other items forming part of
a downconductor. No person should dangle arms or legs in the water.
If a boat has been struck by lightning, compasses and navigation instruments
should be checked for calibration. Protective coatings on steel hulls and glass
fibre sheathing over ballast keels should also be checked for damage. All
standing and running rigging and associated fittings should be checked in detail.
Bonding the LPS to the vessels electrical wiring system earth.
The bonding of LPS on a boat should recognize that the electrical
wiring system on a boat is commonly only a final subcircuit. As such, the
wiring will be very light, and neither the live conductors (whether or not
energized) nor the earthing arrangements, are capable of carrying lightning
discharge current. Even with a larger vessel, where the wiring is for a submain
or a complete installation with a generator, this will often still be the case,
though larger wire sizes would be in use.
The ship installation may have common fed accessories off the isolation
transformer secondary, and all systems may incorporate RCD protection. One
side of the isolation transformer secondary may be a pseudo neutral with ship earthing.
When the LPS is completed, the earthing conductor at its final point connection
to its chosen earth termination network should be bonded to the ship earth or
ship bonding point at its termination.
-
49
FENCES If an extended length of metal fence is struck it is raised to a high potential
relative to earth. Persons or livestock in close proximity to, or in contact with,
may therefore be exposed to danger.Fences that give rise to the most risk are
those constructed with posts of poor conducting material, such as wood or
concrete. Fences built with metal posts set in earth are less hazardous, especially
if the electrical continuity is broken. Breaking the electrical continuity prevents
a lightning stroke from affecting the entire length of a fence, as it can if the
stroke is direct and the fence continuous, even though earthed.
In addition, persons or livestock can be endangered by potential differences in
the ground in the proximity of fences . The risk is greatest on rocky ground.
No value can be given for the earth termination resistance, since this must be
largely governed by the physical conditions encountered, but the lower the
resistance to earth the less risk will result to persons and livestock. It should be
borne in mind that because of large body spans and bare contact areas many
types of livestock are more susceptible to electric shock than humans.
-
50
MISCELLANEOUS STRUCTURES
Metal scaffolding , including overbridges. Where metal scaffolding is readily accessible to the general public, particularly
when it is erected over and on part of the common highway or may be used in
the construction of public seating accommodation, it should be efficiently
bonded to earth.
A simple method of bonding such structures consists of running a strip of metal
other than aluminium, 20 mm 3 mm size, underneath and in contact with the base plates carrying the vertical members of
the scaffolding and earthing it at intervals not exceeding 20 m. With public
seating accommodation only the peripheral members of the structure need
bonding to earth. Other such as those used for pedestrian bridges over main
trunk roads, are frequently sited in isolated situations where they may be prone
to lightning strikes and should be bonded to earth, at the approach points.
Tall metal masts, towers ,and cranes.
Masts and their guy-wires, floodlighting towers and other metallic construction,
particularly those to which the general public have access, should be earthed.
Cranes and other tall lifting appliances used for building construction purposes,
shipyards and port installations should also be bonded to earth. For cranes or
revolving structures mounted on rails, efficient earthing of the rails, preferably
at more than one point, will usually provide adequate lightning protection.
In special cases, where concern is felt regarding possible damage by lightning to
bearings, additional measures may be justified.Mobile towers, portable cranes
and similar structures mounted on vehicles with pneumatic
tyres can be given a limited degree of protection against lightning damage by
drag chains or tyres of conducting rubber such as are provided for dissipating
static electricity.
-
51
PROTECTION OF HOUSES AND SMALL BUILDINGS
Houses / small buildings vary greatly in the degree to which their construction
provides inherent lightning protection. Small buildings with mainly non-
metallic materials offer little or no protection against lightning, whereas a
building with a metallic roof, metallic gutters, and metallic downpipes leading
into the ground has a high degree , since the main elements of an LPS are
already present.
If lightning strikes a house with little lightning protection, the lightning is
likely to penetrate the roof and attach to electrical wiring in the roof area. This
will usually result in damage to electrical equipment in the house, and in some
cases, may result in a fire, or in hazard to persons within the house.
The objective in protecting small buildings should be to provide conductors to
intercept the lightning, to provide a low-resistance path to earth, and to provide
at least two earth earthing electrodes for taking lightning current to the earth.
Air terminal network for the building If building roof consists mainly of metallic materials, then it will serve as the air
terminal network. It is necessary to ensure that there is electrical continuity
between the various parts of the roof.
If building roof consists mainly of non-metallic materials, then an air terminal
network should be provided. Copper wire and copper strip are recommended for
their durability. At least one conductor should be run along the highest parts of
the roof, eg. the highest ridge of the building. If the roof has a complicated
shape, it may be necessary to run additional conductors along the highest parts
of each section of the roof. All conductors should be joined together.
The cross-sectional area of the conductors should be not less than 35 mm2,
achieved, for example, by copper strip 25 mm 1.5 mm. However, it should be realized that much thinner conductors are able to carry most lightning
currents without damage. Even if the conductor were to melt, it would have
carried out its function for that one strike, as the lightning current would flow
through the path of the molten metal, rather than penetrate below the roof of the
house.
For a large, flat roof of non-conducting material, the simplest form of air
-
52
terminal network may be a series of vertical metallic rods above the roof level,
all connected together. Metallic gutters may become a strike attachment point.
If there are metallic gutters around the roof, these should be connected to the air
terminal network. With metallic roofs, these connections may already exist in
the fastenings of the guttering to the roof. With non-metallic roofs, the guttering
should be connected to the air terminal network at no less than two points.
Provision of downconductors for the building There should be at least two low-resistance paths to convey the current from
any lightning strike to the roof down to earth. Metallic downpipes from metallic
gutters may be used for this purpose, provided they afford a direct electrically
continuous path for the lightning current. In the absence of any low-resistance
path from roof to earth, at least two conductors should be provided to serve as
downconductors. These may be continuations of the conductors forming part of
the air terminal network.
Provision of earthing electrodes
A path to earth for the lightning current should be provided at no less than two
well separated points, Eg. at opposite ends of the house. Preference should be
given to areas that are usually damp, such as gardens. A metallic water pipe
buried in the ground would be a satisfactory earthing electrode provided that the
water pipe is also connected to the electricity supply service earth.
Each downconductor should be connected to an earthing electrode by the
shortest possible route, with the proviso that downconductors and earthing
electrodes should not be placed close to entry doors, or places where persons are
likely to stay for long periods. Eg. close to swimming pools.
Earthing electrodes and their connected conductors should be examined
periodically to ensure that they are intact, and not suffering corrosion or
mechanical damage.
-
53
I N S T A L L A T I O N & M A I N T E N A N C E P R A C T I C E.
WORK ON SITE
Throughout the period of erection of a structure, all large and prominent masses
of metalwork,Eg. steel frames, scaffolding and cranes, should be effectively
connected to earth. Once work has commenced on the installation of an LPS, an
earth connection should be maintained at all times.
INSPECTION
All LPSs should be inspected after completion, or alteration . A routine
inspection should be made at least every two years. More frequent inspections
may be warranted in some circumstances. Such circumstances include, but are
not limited to
(a) Areas subject to severe weather and lightning activity.
(b) Structures located in areas where aggressive soil or other conditions may
accelerate corrosion or other aspects of system degradation.
(c) Changes in technology use within the structure that may necessitate a review
of the protection means and their continued effectiveness.
(d) Any other time where it is deemed necessary to update the original risk
assessment for lightning damage.
TESTING On the completion of installation or any modification to it, and at time of any
maintenance inspection, the resistance to earth of whole installation and of each
earth termination should be measured, and the electrical continuity of all
conductors, bonds and joints and their mechanical condition verified.
Where regular testing during maintenance reveals that the earthing resistance is
substantially unchanged, the frequency of maintenance testing may be reduced
to each alternate inspection.
-
54
RECORDS
The following records should be kept on site, and by the person responsible for
the upkeep of the installation:
(a) Scale drawings showing the nature, dimensions and position of all
component parts of the LPS.
(b) The nature of the soil and any special earthing arrangements.
(c) Date and particulars of salting, if used.
(d) Test conditions, date and results .
(e) Alterations, additions or repairs to the system.
(f) The name and contact details of the persons responsible for the installation
or for its upkeep.
Detection of occurrence of flashes to structure and magnitude of discharge
current may be estimated by magnetic links, or magnetic tape .
While the use of instruments to count the number of strikes intercepted by
the protection system is highly recommended, in practice, this may be
impractical to achieve on multiple downconductor LPSs.
MAINTENANCE
Some system components will lose their effectiveness over time because of
weathering, corrosion, and stroke damage. Both physical and electrical
characteristics of the LPS must be maintained .
The periodic inspection and tests described in report of maintenance,shall
indicate works done. Particular attention should be paid to any evidence of
corrosion of earthing and to any alterations or extensions to the structure that
may affect the LPS. Examples of such alterations or extensions are as follows:
(a) Changes in the use of a building.
(b) The erection of radio and television antennas.
(c) Installation / alteration to electrical, telecoms or It within the building.
A good maintenance program should also contain provision for the following:
(i) Inspection of all system components.
(ii) Tightening of all accessible clamps and splices.
(iii) Measurement of system resistance, including earth resistance of terminals.
(iv) Inspection or testing of SPDs.
-
55
EXAMPLE OF LIGHTNING RISK CALCULATIONS : Two storey house.
-
56
NATURE OF LIGHTNING & PRINCIPLES OF PROTECTION
THE NATURE OF LIGHTNING
Thunderstorms occur under particular meteorological conditions, and partial
separation of electrical charges within the thundercloud usually results in
regions with negative charge mainly in the lower parts of the thundercloud, and
regions with positive charge in the upper.
A complete ground flash consists of a sequence of one or more high amplitude
short duration current impulses. About 40% of ground flashes
have more than one ground termination, usually separated by distances up to a
few kilometres . The currents are unidirectional and usually negative, i.e. a
negative charge is injected into the object struck. For all practical purposes the
stroke can be considered to be generated by a current source whose waveshape
and magnitude are unaffected by the characteristics of the ground termination.
The lightning attachment process The first stroke of a ground flash is normally preceded by a downward-
progressing low-current discharge that commences in the negatively charged
region of cloud, progresses