Lightning and Surge Protection according to IEC 62305
description
Transcript of Lightning and Surge Protection according to IEC 62305
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 1
Lightning and Surge Protection according to IEC 62305
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 2
Damage due to Lightning and Surges
© 2012 DEHN + SÖHNE / protected by ISO 16016 3Lightning and Surge Protection
Danger due to Lightning Strokes
MCR
110 kV
data
TV 400/230 V
ABC Company
mobile phone2 k
m
approx. 1,900,000 lightning strokes in Germany per year*
*Ref.: BLIDS, Siemens AG, Analysis of 2001 - 2005
telephone
© 2012 DEHN + SÖHNE / protected by ISO 16016 4Lightning and Surge Protection
Quelle: http://thunder.msfc.nasa.gov/images/HRFC_AnnualFlashRate_0.5.png
Lightning flasches cloud to earth
© 2012 DEHN + SÖHNE / protected by ISO 16016 5
Branch-specific Costs caused by a One-hour Loss of Production
Costs of a one-hour loss of production
Paper approx. 10,000 €
Branch
Car Industry approx. 250,000 €(depending on the section)
Computing Centre approx. 500,000 €(the potential data loss can no longer be quantified)
Power Stations approx. 90,000 €
Car Industry Supplier approx. 12,500 €
Brewery approx. 10,000 €
Lightning and Surge Protection
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 6
Generation and Effects
© 2012 DEHN + SÖHNE / protected by ISO 16016 7Lightning and Surge Protection
Causes of Surges due to Lightning Discharges
Direct lightning strike:
L1L2L3
PEN
20 kV
1b
1bInduced voltage in loops
IT network
power supply
1
1 Striking of external lightning protection system, process structure (in industrial plants), cables etc.
Rst
1a
1aVoltage drop at the implse earthing resistance Rst
Distant lightning Strike:
2a
2a Strike into medium- voltage overhead lines
2cFields of the lightning strike
2c
2b
2b Surge travelling waves on overhead lines due to cloud-to-cloud lightning
© 2012 DEHN + SÖHNE / protected by ISO 16016 Surge Protection
Lightning Prot. Level Current amplitude kAI 200II 150
III - IV 100Ref.: IEC 62305
ûE = î · Rst
Example:ûE = 100 kA · 1 = 100 kV
i
t
î
wave form 10 / 350 µs
Galvanic CouplingLightning Voltage for a System
EBB
Rst
© 2012 DEHN + SÖHNE / protected by ISO 16016 9Lightning and Surge Protection
Influences on Electrical InstallationsCauses of Surges
M
Surges (SEMP)• Switching operations• Earth faults / Short circuits• Tripping fuses• Parallel installation of power and IT conductor
systems
Direct lightning strike (LEMP)
• Galvanic coupling• Inductive / Capacitive
coupling
Indirect lightning strike• Conducted partial lightning
currents • Inductive / Capacitive coupling
© 2012 DEHN + SÖHNE / protected by ISO 16016 10Lightning and Surge Protection
Parameters Lightning Protection Level
I II III-IV
Lightning Current Parameters according to IEC 62305
I (kA) 200 150 100
W/R (MJ/) 10 5.6 2.5
Qs (As) 100 75 50
Q long (As) 200 150 100
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 11
International Standardisation
© 2012 DEHN + SÖHNE / protected by ISO 16016 12Lightning and Surge Protection
IEC 62305-1 General Principles
IEC 62305-2 Risk Management
IEC 62305-3 Physical Damage to Structures and Life Hazard
IEC 62305-4 Electrical and Electronic Systems
IEC 62305 International lightning protection standard
© 2012 DEHN + SÖHNE / protected by ISO 16016 13Lightning and Surge Protection
62305-1General Principles
IEC 62305 International lightning protection standard
62305-2Risk
62305-3Physical damage
and life hazard
62305-4Electrical- and
electronic systems
© 2012 DEHN + SÖHNE / protected by ISO 16016 14Lightning and Surge Protection
By working through series of formulae the process allows the user to decide what protection is required. The actual risk (R) must be below the tolerable level (Rt).The ultimate protection may be the installation of a LPS system. Direct strike lightning arresters (LEMP) and surge arresters (SEMP).
IEC 62305-2 Risk Management
© 2012 DEHN + SÖHNE / protected by ISO 16016 15Lightning and Surge Protection
Introductiona)External LPS (air termination system, down
contuctor‘s, earth termination system).b)An internal LPS (preventing dangerous
sparking using equipotential bonding or separation distance (hence electrical insulation) between external LPS and internal metalwork.
IEC 62305-3 Physical damage to structures and life hazard
© 2012 DEHN + SÖHNE / protected by ISO 16016 16Lightning and Surge Protection
Scope:Provides information for design, installation, inspection, maintenance and testing of a LEMP protection system (LPM) for electrical and electronic systems within a structure able to reduce risk of permanent failure due to LEMP.
IEC 62305-4 Electrical- and electronic systems within structures
Basic protection measures in a LPM system– Earthing and Bonding–Magnetic shielding and line routing–Direct strike and surge protection
© 2012 DEHN + SÖHNE / protected by ISO 16016 17Lightning and Surge Protection
Class I Protection Against
Direct Lightning Currents
(Lightning Current Arrester)
(10/350 µs)
IEC 61643-1Performance Requirements of Surge Protective Devices
for Low-Voltage Power Supply Systems
Class IIIProtection Against
Switching Overvoltages
(Surge Arrester)
(1.2/50 µs; 8/20 µs)
Class IIProtection Against Indirect Lightning
Effects(Surge Arrester)
(8/20 µs)
Standardisation of Surge Protective Devices
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 18
External Lightning Protection System
Air Termination System DownconductorEarth Termination System
© 2012 DEHN + SÖHNE / protected by ISO 16016 19Lightning and Surge Protection
External Lightning Protection System
air termination system
down conductor
earth termination system
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 20
EMC-orientatedLightning Protection Zones Concept
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 21
air ventilation
foundation earthing electrode
steel reinforcement
terminal device
spatial shield
M
LPZ 0 A
LPZ 0 A
LEMP
LEMP
EMC-Orientated Lightning Protection Zones Concept
LEMP
LPZ 0 C
air-termination system
down-conductorsystem
IT system
LPZ 3
SEMP
LPZ 2
LPZ 2
LPZ 1
LPZ 1
LPZ 0 B
LPZ 0 B
power supply system
Lightning equipotential bondingLightning current arrester(SPD Type 1)Local equipotential bondingSurge arrester(SPD Type 2, SPD Type 3)
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 22
Internal Lightning Protection
Lightning Equipotential BondingSurge ProtectionCoordination
© 2012 DEHN + SÖHNE / protected by ISO 16016 23Lightning and Surge Protection
Internal Lightning Protection System
Equipotential Bonding at the Boundary of LPZEquipotential bonding for all metal parts and supply lines (e.g. metal pipes, electrical power or data lines) which are entering at the boundary of an internal LPZ shall be carried out at equipotential bonding bars which are installed as closely as possible to the point of entry. SPDs with suitable power carrying capacity for electrical power and data lines at the point of entry into the LPZ have always to be installed.
Based on IEC 62305-4
© 2012 DEHN + SÖHNE / protected by ISO 16016 24Lightning and Surge Protection
powersupply
M
water
gas
heating
LPZ 0 LPZ 1
Lightning Equipotential Bondingfor incoming Lines
cathodic protected tank pipe
foundation earthing electrode
lightning equipotential bonding
exte
rnal
ligh
tnin
g pr
otec
tion
syst
em
EBB
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 25
Lightning current arrester
© 2012 DEHN + SÖHNE / protected by ISO 16016 26Lightning and Surge Protection
Internal Lightning ProtectionSurge Protective Devices
Surge protective devices for lightning equipotential bonding must be capable of safely controlling the partial lightning currents to be expected to flow through them. For this purpose, surge protective devices are chosen according to the requirements on site and installed in accordance with IEC 60364-5-53
Based on IEC 62305-4
The residual voltage at the surge protective device installed into the building, has to be coordinated with the impulse withstand capability of the installation.Surge protective devices Class I to be installed at the entry of the building, keep a significant part of the power of lightning currents away from the inside of the building.
© 2012 DEHN + SÖHNE / protected by ISO 16016 27Lightning and Surge Protection
What is a Lightning Current Arrester installed into a Power Supply System supposed to perform?
Discharging of lightning currents several times without desctruction of the equipment.= Discharge capacity 100 kA (10/350 µs)
Providing of a lower voltage protection level than the voltage strength of the downstream installation.
Extinguishing or limiting of mains follow currents.
Ensuring of the energy coordination to downstream surge protective devices and/or terminal equipment.
© 2012 DEHN + SÖHNE / protected by ISO 16016 28Lightning and Surge Protection
1 Test Impulse Curent for Lightning Current Arresters2 Test Impulse Current for Surge Arresters
20 kA
40 kA
60 kA
80 kA
100 kA
I (kA)
200 µs 350 µs 600 µs 800 µs 1000 µst (µs)
20 µs
50 kA
1
110/350
10050
2.5 · 106
IEC 62305-1
28/20
50.1
0.4 · 103
EN 60060-2
2
Wave form µs]
i max. [kA]Q [As]W/R [J/]
Standard
© 2012 DEHN + SÖHNE / protected by ISO 16016 29Lightning and Surge Protection
household appliances
rated voltage withstand voltage 6 kV
4 kV2.5 kV1.5 kV
SE
230/400 V
sensitive devices
M
SDB terminal device
voltage protectionlevel 2.5kV
1.5 kV
SPD Type 1 2 3 3(SPD class) (I) (II) (III) (IV)
Overvoltage Categories according to IEC 60364-4-44 Use of Surge Protective Devices (SPD)
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 30
Surge Protection
© 2012 DEHN + SÖHNE / protected by ISO 16016 31Lightning and Surge Protection
What is a Surge Arrester installed into a Power Supply System supposed to perform?
Discharging of impulse currents (8/20 µs) several times without destroying the terminal equipment
= 20 x nominal discharge capacity 5 - 20 kA (8/20 µs)
Voltage protection level lower than the electrical strength of the downstream terminal devices
= Voltage protection level 1,500 V
© 2012 DEHN + SÖHNE / protected by ISO 16016 32Lightning and Surge Protection
household appliances
rated voltage withstand voltage 6 kV
4 kV2.5 kV1.5 kV
SE
230/400 V
sensitive devices
M
SDB terminal device
voltage protectionlevel 2.5kV
1.5 kV
SPD Type 1 2 3 3(SPD class) (I) (II) (III) (IV)
Overvoltage Categories according to IEC 60364-4-44 Use of Surge Protective Devices (SPD)
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 33
Coordination of SPDs
© 2012 DEHN + SÖHNE / protected by ISO 16016 34Lightning and Surge Protection
Energy Coordination of SPDs
As soon as two or more SPDs are connected in series, the coordination of the SPDs and the equipment to be protected has to be checked.
Energy coordination is achieved as soon as the ratio of energy for all impulse currents for each SPD is equal or less than corresponds to its power withstand capability.
The power withstand capability can be determined– by an electrical test according to IEC 61643-1,– from the technical data of the manufacturer of the SPDs
Based on IEC 62305-4
Conclusion: The coordination of the SPDs can only be verified by the manufacturer!
© 2012 DEHN + SÖHNE / protected by ISO 16016 35Lightning and Surge Protection
residual interferenceimpulse current 8/20 µs
Energy Coordination of Surge Protective Devices (SPDs)
DEHNguard ® S DEHNbloc® M DEHNsafe
input interference; lightning impulse current 10/350 µs
terminal device
?
varistorS 20 K 275
230 / 400 V
residual interferenceuncritical for terminal
device
© 2012 DEHN + SÖHNE / protected by ISO 16016 Surge Protection
Energy CoordinationOverview: SPDs Type 1
230/400 V MSE
Lightning current arresterVoltage protection level 4 kV
DEHNbloc® H Terminal UnitRed / LineType 3
Red / LineType 2
SDB
Red / LineType 2 Terminal UnitRed / Line
Type 3Coordinated lightning current arresterVoltage protection level 2.5 kV
DEHNbloc® MDEHNgap M
Combined SPDVoltage protection level 1.5 kV
DEHNventil® MDEHNventil® ZP
Terminal UnitRed / LineType 3
© 2012 DEHN + SÖHNE / protected by ISO 16016 Lightning and Surge Protection 37
Examples of Lightning current and surge arrester
© 2012 DEHN + SÖHNE / protected by ISO 16016 38Lightning and Surge Protection
DEHNventil® MCharacteristics
Easy exchange of protection modules ...
... due to module releasing button
Coding in base part and protection module =Safe application
Remote signallingcontact as floating changeover contact
Leakage-current-free operating state and fault indication for all protective circuits
Leakage-current-free protective circuit =Allows for use upstreamof meter panels
Capable of carrying lightning currents =For use in lightning protection level
Plastic snap-in device with “parking position“= Quick installation
Low voltage protection level =Protection for terminal devices
© 2012 DEHN + SÖHNE / protected by ISO 16016 39Lightning and Surge Protection
Coordinated lightning current arrester DEHNbloc M Type: DB M 1 255 (FM) / Part No.: 961 120 (961 125)
Coordinated, single-pole Type 1lightning current arrester in accordance with EN 61643-11with a modular device design
RADAX-Flow technology
Follow current extinguishing capability a.c.: up to 50 kArms
Maximum continuous operating voltage a.c.
UC = 255 V a.c.
Lightning impulse current (10/350 μs): 50 kA
Voltage protection level 2.5 kV
Directly coordinated to DEHNguard S 275 (FM) surge
protective devices without additional cable length
Encapsulated, non-exhaustingcreepage spark gap
Optionally available with remote signalling contact for central monitoring units (floating changeover contact)
Type of connection to earth TN/TT 230/400 V a.c.
© 2012 DEHN + SÖHNE / protected by ISO 16016 40Lightning and Surge Protection
Red / Line DEHNguard® M Family
SPD Type 2
DEHNguard® S (FM)
DEHNguard® M TNC 275 (FM)DEHNguard® M TNS 275 (FM)DEHNguard® M TT 275 (FM)
DEHNguard® M TN 275 (FM)DEHNguard® M TT 2P 275 (FM)
© 2012 DEHN + SÖHNE / protected by ISO 16016 41Lightning and Surge Protection
DEHNguard M Family Characteristics
5 application-specific circuit types with and without remote signalling contact = 10 types of devices
High-capacity varistor-based SPD- Nominal discharge current In (20x) = 20 kA (8/20 µs)- Maximum discharge current Imax (1x) = 40 kA (8/20 µs)- Low voltage protection level at In = 1.25 kV
Energy coordinated within the Red/Line product family
Operating state and fault indication of all protective circuits, free of operating and leakage currents
High safety due to Thermo Dynamic Control SPD controlling device
© 2012 DEHN + SÖHNE / protected by ISO 16016 42Lightning and Surge Protection
Surge Protective Device Type 3Use in Distribution Boards / Switchgear Cabinets
SPS Protector DEHNrail modular (FM) DEHNrail M 4P 255
© 2012 DEHN + SÖHNE / protected by ISO 16016 43Lightning and Surge Protection
Low voltage protection level L to N and L/N to PE
Characteristics of theDEHNrail M (DR M ....) Series
Discharge current up to 8 kA Different nominal voltages, from 24 V up to 230 V Maximum operating current: 25 A
Operating state and fault indication, free of operating and leakage currents