1 Liebert® InteleCool®2
LIEBERT INTELECOOL2Product Specification Sheet
Features/Options
• Self-ContainedAll components are enclosed in the painted steel or optional corrosion-resistant aluminum cabinet. The standard color for the painted steel is tan, with optional colors available.
• Space-Saving DesignMounted outside the shelter to save valuable space.
• Range of CapacitiesUnits are available in 2, 3, 4 and 5 ton 60Hz models, and 3, 4 and 5 ton 50Hz models.
• Compressor OptionsA high-efficiency scroll compressor is standard on all models. It is ideal in applications where noise is a factor because of its low noise and vibration.
• Optional Compressor Location• Evaporator Supply and Return Openings
Match industry standard dimensions.• Easy to Install
Wired, piped, charged with refrigerant and factory-tested as a system to ensure trouble-free installation and startup.
• Outside Air OptionsA fixed fresh air damper option allows for adding fresh air/pressurization. The Economizer option allows for cooling using outdoor air when it is cool enough to meet the room conditions.
• Telecom Package “T-Pack”This configuration incorporates popular telecom options: low pressure switch, fan cycle control and low pressure bypass. Many other component options are also available.
• Control/Monitor OptionsThe Liebert Dual Unit Control™ thermostat can control two units and provides autochangeover control. Other autochangeover control options are also available.
Model Number Designation
LIEBERT INTELECOOL22, 3, 4 and 5 Ton Models
ET 0 36 7 R P F B TExternal Telecommunication
Nominal BTU/Hs (1000)7 = Scroll Compressor
with POE oil-R407C
P = 208/230V – 1 ph - 60 HzS = 220/240 – 1 ph - 60 HzA = 460V – 3 ph - 60 HzY = 208/230V – 3 ph - 60 HzN = 200/230 – 3 ph - 50 HzM = 380/415V – 3ph - 50 Hz
0 = StandardF = Fixed Outside Air DamperE = Economizer
0 = No HeatA = 5kW HeatB = 10kW HeatC = 15kW Heat
T = Tan, Painted Steel PanelsC = Custom Color, Painted
Steel PanelsA = Aluminum Panels
R = Right CompressorL = Left Compressor
0 = Standard Supply & Return Openings
Liebert® InteleCool®2 2
60Hz Capacity data - 60Hz indoor ambient listed, outdoor ambient 95°F (35°C)MODEL ET024 ET036 ET048/ET348 ET060/ET360
Compressor Type Scroll Scroll Scroll Scroll
80°F DB/67°F WB (26.7°C DB/19.4°C WB)
Total - BTU/H (kW) 21400 (6.3) 32900 (9.6) 45600 (13.4) 53800 (15.8)
Sensible - BTU/H (kW) 16900 (5.0) 23800 (6.9) 34600 (10.2) 37700 (11.1)
75°F DB/62.5°F WB (23.9°C DB/16.9°C WB)
Total - BTU/H (kW) 19900 (5.8) 30700 (9.0) 42300 (12.4) 49800 (14.6)
Sensible - BTU/H (kW) 16400 (4.8) 23100 (6.8) 34100 (10.0) 36900 (10.8)
Evaporator Air Flow - Dry Coil External Static Pressure, CFM (m3/hr)
0.0 - in. wg. (0.0 Pa) 930 (1580) 1300 (2210) 2030 (3450) 2030 (3450)
0.1 - in. wg. (25 Pa) 880 (1500) 1220 (2070) 1910 (3240) 1910 (3240)
0.2 - in. wg. (50 Pa) 840 (1430) 1130 (1920) 1770 (3010) 1770 (3010)
0.3 - in. wg. (75 Pa) 800 (1360) 1030 (1750) 1650 (2800) 1650 (2800)
0.4 - in. wg. (100 Pa) 730 (1240) 920 (1560) 1520 (2580) 1520 (2580)
0.5 - in. wg. (125 Pa) 650 (1100) 820 (1390) 1390 (2360) 1390 (2360)
Evaporator Air Flow - Wet Coil External Static Pressure, CFM (m3/hr)
0.0 - in. wg. (0.0 Pa) 910 (1550) 1200 (2040) 1800 (3060) 1800 (3060)
0.1 - in. wg. (25 Pa) 860 (1460) 1120 (1900) 1680 (2850) 1680 (2850)
0.2 - in. wg. (50 Pa) 820 (1390) 1030 (1750) 1580 (2680) 1580 (2680)
0.3 - in. wg. (75 Pa) 780 (1320) 940 (1600) 1470 (2500) 1470 (2500)
0.4 - in. wg. (100 Pa) 710 (1210) 850 (1440) 1360 (2310) 1360 (2310)
0.5 - in. wg. (125 Pa) 620 (1050) 750 (1270) 1250 (2120) 1250 (2120)
Evaporator
Motor, hp (kW) 0.25 (0.19) 0.25 (0.19) 0.50 (0.37) 0.50 (0.37)
Filter Sizes, in. (Quantity) 16x32.5x2 (1) 16x32.5x2 (1) 21x36.25x2 (1) 21x36.25x2 (1)
Drain Connection, ID in. 3/4 3/4 3/4 3/4
Weight, lb. (kg)
Standard Unit 330 (150) 330 (150) 470 (213) 470 (213)
Unit with Economizer 350 (159) 350 (159) 490 (222) 490 (222)
Electrical data, 60 Hz - amps
Model Volts Phase
No Heat 5 kW Heat 10 kW Heat
15 kW Heat*
Circ1 Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0187 208/230 1 14.5 17.2 25 23.4 29.3 30 44.4 55.5 60 NA — — — — —
ET0247 208/230 1 15.2 18.1 30 23.4 29.3 30 44.4 55.5 60 NA — — — — —
ET0247 208/230 3 12.4 14.6 20 14.4 18 20 26.4 33 35 NA — — — — —
ET0247 460 3 5.9 6.9 15 7.3 9.1 15 13.3 16.6 20 NA — — — — —
ET0367 208/230 1 20.9 25.2 40 23.4 29.3 40 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET0367 208/230 3 15.8 18.8 30 15.8 18.8 30 26.4 33 35 38.4 48 50 — — —
ET0367 460 3 8.4 10 15 8.4 10 15 13.3 16.6 20 19.3 24.1 25 — — —
ET0487 208/230 1 31.9 38 50 31.9 38 50 46.2 57.8 60 46.2 57.8 60 21 26.3 30
ET0487 208/230 3 24.7 29 35 24.7 29 35 28.2 35.3 35 40.2 50.3 60 — — —
ET0487 460 3 11.7 13.7 20 11.7 13.7 20 14.1 17.6 20 20.1 25.1 30 — — —
ET0607 208/230 1 37.7 45.2 60 37.7 45.2 60 46.2 57.8 60 46.2 57.8 60 21 26.3 30
ET0607 208/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50 — — —
ET0607 460 3 13.8 16.3 25 13.8 16.3 25 14.1 17.6 25 20.1 25.1 30 — — —
* 15 kW heat option @ 208/230 - 1 phase requires two electrical feeds.Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor. Circuit 2 supplies the remaining 5 kW heat.
Liebert® InteleCool®2 3
50Hz Capacity data - 50Hz indoor ambient listed, outdoor ambient 35°C (95°F)
MODEL ET035 ET047/ET347 ET059/ET359
Compressor Type Scroll Scroll Scroll
26.6°C DB/19.4°C WB (80°F DB/67°F WB)
Total - kW (BTU/H) 7.8 (26600) 11.2 (38300) 13.6 (46600)
Sensible - kW (BTU/H) 6.1 (20700) 8.6 (29300) 9.5 (32400)
23.9°C DB/16.9°C WB (75°F DB/62.5°F WB)
Total - kW (BTU/H) 7.2 (24700) 10.4 (35500) 12.7 (43600)
Sensible - kW (BTU/H) 6.0 (20400) 8.4 (28400) 9.2 (31600)
Evaporator Air Flow - Dry Coil External Static Pressure, m3/hr (CFM)
0.0 Pa (0.0 - in. wg.) 1840 (1080) 2870 (1690) 2870 (1690)
25 Pa (0.1 - in. wg.) 1730 (1020) 2700 (1590) 2700 (1590)
50 Pa (0.2 - in. wg.) 1600 (940) 2500 (1470) 2500 (1470)
75 Pa (0.3 - in. wg.) 1460 (860) 2330 (1370) 2330 (1370)
100 Pa (0.4 - in. wg.) — — —
125 Pa (0.5 - in. wg.) — — —
Evaporator Air Flow - Wet Coil External Static Pressure, m3/hr (CFM)
0.0 Pa (0.0 - in. wg.) 1700 (1000) 2550 (1500) 2550 (1500)
25 Pa (0.1 - in. wg.) 1590 (930) 2380 (1400) 2380 (1400)
50 Pa (0.2 - in. wg.) 1460 (860) 2240 (1320) 2240 (1320)
75 Pa (0.3 - in. wg.) 1330 (780) 2070 (1220) 2070 (1220)
100 Pa (0.4 - in. wg.) — — —
125 Pa (0.5 - in. wg.) — — —
Evaporator
Motor, kW (hp) 0.19 (0.25) 0.37 (0.50) 0.37 (0.50)
Filter Sizes, in. (Quantity) 16x32.5x2 (1) 21x36.25x2 (1) 21x36.25x2 (1)
Drain Connection, ID, in. 3/4 3/4 3/4
Weight, kg (lb.)
Standard Unit 150 (330) 213 (470) 213 (470)
Unit with Economizer 159 (350) 222 (490) 222 (490)
Electrical data, 50 Hz - amps
Model Volts Phase
No Heat 5 kW Heat 10 kW Heat
15 kW Heat*
Circ1 Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0357 220/240 1 18.1 21.7 35 23.4 29.3 35 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET0357 200/230 3 15.8 18.8 25 15.8 18.8 25 26.4 33 35 38.4 48 50 — — —
ET0357 380/415 3 8.4 10.0 15 8.4 10.0 15 15.3 19.1 20 22.3 27.9 30 — — —
ET0477 200/230 3 23.3 27.2 35 23.3 27.2 35 28.2 35.3 35 40.2 50.3 60 — — —
ET0477 380/415 3 11.7 13.7 20 11.7 13.7 20 16.1 20.1 25 23.1 28.9 30 — — —
EF0597 200/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50 — — —
ET0597 380/415 3 13.8 16.3 25 13.8 16.3 25 16.1 20.1 25 23.1 28.9 30 — — —
* 15 kW heat option @ 220/240 - 1 phase requires two electrical feeds.Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.Circuit 2 supplies the remaining 5 kW heat.
Liebert® InteleCool®2 4
© 2005 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-19505_REV3_11-12
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, OH 43229
Telephone: 1-800-877-9222Facsimile: 1-614-841-6022www.liebert.com
Liebert InteleCool2 dimensions, in. (mm)
Dimensions, in. (mm)
Model Wu Ws Wf A B C D E F G H J K L
2 Ton 37-1/8(943)
17-3/4(451)
38-3/4(984)
20(508)
20(508)
9-3/8(238)
9-13/32(239)
8(203)
20-3/4(527)
12(305)
25-1/16(638)
69-3/4(1772)
36-3/16(919)
31-5/8(803)
3 Ton37-1/8(943)
17-3/4(451)
38-3/4(984)
28(711)
28(711)
5-3/8(137)
5-3/8(137)
8(203)
18(457)
14(356)
26(660)
69-3/4(1772)
36-3/16(919)
31-5/8(803)
4/5 Ton 41(1041)
22-1/2(572)
42-3/4(1086)
30-1/4(768)
29-7/8(759)
6-1/4(159)
6-7/16(164)
9-7/8(251)
30(762)
15-7/8(403)
25-25/64(645)
83(2108)
44(1118)
39-1/2(1003)
4"(102mm)
Wu
C
Entrance for high volt connections
Shaded areas indicate a recommended clearance of 34" (864mm) in front and 30" (762mm) each side, or 36" (914mm) each side when mounted adjacent to another unit, for component access.For recommended minimum clearances, refer to the installation manual.See table below for dimensions.
E
F
G
H
D
L
Breturn
Entrance for low volt connections
1-11/16"(43mm)
2-1/4"(58mm)
Ws
J2-1/4"
(58mm)
Wf
K
Asupply
CABINET DIMENSIONAL DATALIEBERT INTELECOOL22, 3, 4 & 5 TON UNITS