Liebert® PST4™ 660 – 850 VA Installer/User Guide

Transcript of Liebert PST4 660-850VA User Manual - Vertiv ·...

Page 1: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

Liebert® PST4™ 660 – 850 VA

Installer/User Guide

Page 2: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

Technical Support Site

If you encounter any installation or operational issues with your product, check the pertinent section ofthis manual to see if the issue can be resolved by following outlined procedures. For additional assistance,visit https://www.VertivCo.com/en-us/support/

Page 3: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

TABLE OF CONTENTS

1 Liebert PST4 Overview 5

1.1 Controls and Indicators 6

1.2 Installation 6

1.3 Setup and Start-up 7

1.4 UPS Operation 7

1.5 Alarms 8

1.5.1 On Battery 8

1.5.2 Low Battery Warning 8

1.5.3 Weak/Bad Battery 8

1.5.4 Overload 8

1.5.5 UPS Fault 8

1.6 Troubleshooting 9

1.7 Maintenance and Battery Replacement 9

1.7.1 Battery Charging 9

1.7.2 Precautions 9

1.7.3 Battery Replacement Precaution 10

1.7.4 Information for the Protection of the Environment 10

1.7.5 Battery Replacement Procedure 10

1.7.6 Specifications 12

Appendices 15

Appendix 1: Technical Support 15

Vertiv | Liebert® PST4™ Installer/User Guide | 3

Page 4: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

Vertiv | Liebert® PST4™ Installer/User Guide | 4

Page 5: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

1 LIEBERT PST4 OVERVIEWThank you for purchasing the Liebert PST4 Uninterruptible Power Supply. It is designed, manufactured,and tested to provide many years of reliable power protection.

Please review this manual and the important safety instructions before installing, operating, ormaintaining your Liebert PST4 UPS.

CAUTION: Connect the UPS only to a properly grounded/earthed outlet that is protected by anappropriate branch circuit protector (circuit breaker or fuse) that meets national and/or localelectrical codes.

The Liebert PST4 should be located near the wall outlet. Do not use extension cords between the walloutlet and the UPS. The Liebert PST4 is designed for small office and home use only. It is notrecommended to be used with life-support equipment or applications.

WARNING: Risk of Electric Shock. Observe all cautions and warnings in this manual. Failure todo so may result in serious injury or death. Refer all UPS and battery service to properly trainedand qualified service personnel. Do not attempt to service this product yourself beyond thebattery replacement procedures. Opening or removing the cover may expose you to lethalvoltages within this unit even when it is apparently not operating and the input wiring isdisconnected from the electrical source. Never work alone.

In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher maycause electric shock. In the event of an emergency, press and hold the ON/OFF button for at least one (1)second to turn off the UPS then unplug the UPS from the wall outlet.

NOTICE: This equipment has been tested and found to comply with the limits for a Class B computingdevice in accordance with the specifications in Subpart J of Part 15 of FCC Rules and also meets the ClassB limits for radio noise emissions from digital apparatus set out in the Radio Interference of the CanadianDepartment of Communications. These limits are designed to provide reasonable protection against suchinterference in a residential installation. This equipment generates and uses radio frequency and if notinstalled and used properly, that is, in strict accordance with the manufacturer's instructions, thisequipment may cause interference to radio and television reception. If this equipment does causeinterference to radio or television reception, which can be determined by turning the equipment off andon, the user is encouraged to try to correct the interference by one or more of the following measures:

• Re-orient the receiving antenna.

• Relocate the computer with respect to the receiver.

• Move the computer away from the receiver.

• Shielded communication-interface cables must be used with this product.

WARNING: Changes or modifications to this unit not expressly approved by the partyresponsible for compliance could void the user's authority to operate the equipment.

Vertiv | Liebert® PST4™ Installer/User Guide | 5

Page 6: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

The Liebert PST4 is shipped with the following items:

• CD with Liebert MultiLink® Shutdown Software and User manual (electronic version)

• USB cable; one 2 m (6-1/2 ft.) long

• Coax cable; one 1 m (3 ft.) long

• Wall-mount template and screws

• User Manual with warnings safety instructions and WEEE recycling sheet(ISO 14001 compliance)

1.1 Controls and Indicators

ITEM DESCRIPTION

1 Battery-backed and surge-protected output power receptacles.

2 Input Circuit Breaker. The input circuit breaker trips in the event the output load exceeds the UPS's power rating.

3 Scroll button, to scroll through the LCD-display parameters and, when on battery power, can silence the audible alarm.

4 On/Off button.

5 LCD Display with icons and numerical information to display UPS status and operational parameters.

6 Input Power Cord.

7 Surge-protected-only output-power receptacles.

8 RJ11/45 connectors for phone/fax/modem or network surge protection.

9 RJ45 connector for USB communications port for UPSmonitoring and control.

10 Coax Cable connections for cablemodem, DSS receiver, or cable-TV converter surge protection.

1.2 Installation

Install the Liebert PST4 in a temperature-controlled environment that is free of corrosive and conductivecontaminants. Avoid locations near heat or water sources and exposed to direct sunlight. For properventilation, leave approximately 2 to 4 inches clearance on all sides of the UPS.

The UPS unit ships with the internal battery connected.

The UPS may be mounted to a wall using the mounting slots on the bottom of the UPS and providedscrews. A template for screw location is provided and the unit should be mounted ensuring they are in awall stud for a secure installation.

Vertiv | Liebert® PST4™ Installer/User Guide | 6

Page 7: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

1.3 Setup and Start-up

Inspect the UPS for any signs of obvious damage. If damage is visible, do not proceed with the setup andcall our warranty support line for a new replacement unit.

The UPS has 4 battery-backed and surge-protected receptacles and 4 surge-protected-only receptacles.Plug your critical equipment (such as computer, monitors, etc.) into the battery-backed receptacles andyour less-critical equipment (such as printers and other less-often used peripherals) into the surge-onlyreceptacles.

If you also want to protect your computer network connection or telephone, you can use thenetwork/telephone surge-protection ports on the side. Use the “IN” port to connect the line from the walljack and the “OUT” port to connect to your device port. Use of this feature is not required for properoperation of the UPS.

If you also want to protect your cable modem, DSS Receiver, or cable-TV converter connection you canuse the Coax surge protection ports on the side of the UPS. Use the “IN” port to connect the line from thewall jack and the “OUT” port to connect to your device port. Use of this feature is not required for properoperation of the UPS.

If you wish to use the USB communications, plug the provided cable into the port on the UPS and theother end into an open USB port on your computer. This allows unattended shutdown of your computerusing either the built-in feature within the Microsoft® Windows® operating system or the LiebertMultilink® Shutdown software located on the CD that shipped with the UPS. Use of this feature is notrequired for proper operation of the UPS.

You are now ready to start the UPS. Plug the UPS input cord into the wall outlet. To turn on the UPS, pressand hold the ON/OFF button until you hear the UPS beep, then release the button. The connectedequipment immediately receives power and the UPS starts a short, self system test (electronics andbattery check). When the unit passes all self checks, only the green LED should be lit indicating normaloperation.

NOTE: While every precaution has been taken to ensure that the battery is in good condition, werecommend allowing the UPS to charge the battery for at least 4 hours prior to providing full back-uptime protection for any utility-power abnormality.

1.4 UPS Operation

The UPS is designed for easy operation. Once the UPS is plugged into the wall outlet, it begins to chargethe battery whether the UPS has been turned on or not.

To turn on the UPS, press and hold the ON/OFF button until the unit beeps, then release the button.

To turn off the UPS, press and hold the ON/OFF button for at least 1 second then release the button. Tocompletely stop all UPS operation, once the UPS is turned off, unplug the input cord from the wall outlet.

During normal operation, the UPS protects the connected equipment from utility abnormalities, such asbrownout/sags, over-voltage/surges, and complete outages. During these periods, the UPS automaticallydraws power from the battery to support the connected equipment that is plugged into the battery-backed outlets. Note that equipment plugged into the surge-only outlets shut down in these conditions. Ifthe utility power problems are long-term, the UPS will eventually shut down because all battery power isexhausted. Once utility power is restored to normal operating parameters for the UPS, it automaticallyrestarts and begins to power the connected equipment and to recharge the battery for the next utilityabnormality.

Vertiv | Liebert® PST4™ Installer/User Guide | 7

Page 8: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

1.5 Alarms

1.5.1 On Battery

When the UPS is operating on the batteries, the On Battery icon on the LCD panel illuminates and theaudible alarm sounds once every 5 seconds. The alarm stops once the UPS returns to the AC normalmode.

1.5.2 Low Battery Warning

The UPS sounds 2 beeps every 5 seconds when the battery reserve runs low. This condition continuesuntil AC returns or the UPS shuts down from battery exhaustion.

1.5.3 Weak/Bad Battery

The UPS automatically tests the battery's condition and, if the battery fails the test because of weakcapacity, bad battery, or battery disconnected:

• The Battery Capacity bar graph on the LCD display flashes on/off

• The alarm beeps 3 times every 30 seconds until the battery is reconnected or replaced.

We recommend that the UPS charge overnight before performing a battery test to confirm a Weak/BadBattery condition.

1.5.4 Overload

When the amount of equipment connected to the UPS exceeds its power rating, the Load Capacity bargraph on the LCD display flashes on/off, and the UPS sounds 1 beep every half second (AC and Batterymodes). The alarm remains on until the excess load is removed or the UPS's self-protection circuit shutsdown the UPS.

1.5.5 UPS Fault

When the UPS detects a hardware fault, the Fault icon on the LCD display illuminates and the UPS soundsa constant alarm. The fault condition, in some instances, may be reset by turning the UPS off and thenback on.

Vertiv | Liebert® PST4™ Installer/User Guide | 8

Page 9: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

1.6 Troubleshooting

SYMPTOM POSSIBLE CAUSE WHATTO DO

UPSwill not turn on. On/Off/ button not pressed. Press and release the On/Off button to start UPS.

UPS operates in battery modeonly, even though normal ACpower is present.

Input AC circuit breaker istripped.

Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker tripsafter UPS starts up, reduce the load on the UPS.

Fault icon is illuminated.UPS has detected aninternal fault.

Call for a replacement unit.

The AC mode icon LED isilluminated, but there is nooutput.

The UPS is being controlledvia its communications port.

Disconnect the computer cable from the UPS and press the On button. If UPSworksnormally, the software has control of the UPS. If the UPS still does not have outputpower, call for service.

UPS does not provide expectedruntime.

The batteries may be weakor at the end of usefulservice life.

Charge the batteries for 8-hours and retest. If the run time is still less than expected,the batteries may need replaced, even though theWeak/ Bad Battery alarm is notsounding.

Battery Capacity bar graph isflashing on and off.

Loose connections at thebatteries, Weak batteries,Bad batteries.

Check battery connections, charge the batteries for 8-hours, replace the batteries.

Load Capacity bar graph isflashing on and off.

The load has exceeded theUPS's capacity.

Check the "Specifications" on page 12 table that follows. Remove part of the load.

1.7 Maintenance and Battery Replacement

1.7.1 Battery Charging

The batteries are valve-regulated, non-spill-able, lead acid and should be kept charged to attain theirdesign life. The Liebert PST4 charges the batteries continuously when it is connected to the utility inputpower. If the Liebert PST4 will be stored for a long time, we recommend connecting the UPS to inputpower for at least 24 hours every 4 to 6 months to ensure full recharge of the batteries.

1.7.2 Precautions

Although the Liebert PST4 is designed and manufactured to ensure personal safety, improper use canresult in electrical shock or fire. To ensure safety, observe the following precautions:

• Turn off and unplug the UPS before cleaning it.

• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.

• Never block or insert any objects into the ventilation holes or other openings of the UPS.

• Do not place the UPS power cord where it might be damaged.

Vertiv | Liebert® PST4™ Installer/User Guide | 9

Page 10: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

1.7.3 Battery Replacement Precaution

Before proceeding, please review the battery safety precautions.

WARNING: Risk of electric shock and explosion. Can cause equipment damage, injury anddeath. Do not dispose of the battery in a fire. The batterymay explode. Do not open or damagethe battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comesinto contact with the skin, wash the affected area immediately with plenty of clean water andget medical attention.

WARNING: Risk of electric shock. Can cause equipment damage, injury and death.A battery can present a risk of electrical shock and high short-circuit current. The followingprecautions should be observed when working on batteries:- Remove watches, rings and other metal objects.- Use tools with insulated handles.Wear rubber gloves and boots.- Do not lay tools or metal parts on top of batteries.- Disconnect charging source prior to connecting or disconnecting battery terminals.- Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove thesource of the ground. Contact with any part of a grounded battery can result in electricalshock. The likelihood of such shock will be reduced if grounds are removed during installationand maintenance (applicable to a UPS and a remote battery supply not having a groundedsupply circuit).

1.7.4 Information for the Protection of the Environment

UPS SERVICING - This UPS makes use of components dangerous for the environment (electronic cards,electronic components). The components removed must be taken to specialized collection and disposalcenters.

NOTICE TO ALL CUSTOMERS: DISPOSAL OF OLD APPLIANCES - This product has beensupplied from an environmentally aware manufacturer that complies with the WasteElectrical and Electronic Equipment (WEEE) Directive 2002/96/CE. The “crossed-outwheelie bin” & recycle symbol is placed on this product to encourage you to recyclewherever possible. Please be environmentally responsible and recycle this product throughyour recycling facility at its end of life. Do not dispose of this product as unsorted municipalwaste. Follow local municipal waste ordinances for proper disposal provisions to reduce theenvironmental impact of waste electrical and electronic equipment (WEEE).

1.7.5 Battery Replacement Procedure

1. Turn the UPS on its side.

2. Remove and set aside the two battery-compartment retaining screw (item 1).

3. Slide the battery compartment cover outward and lift-off to expose the battery (item 2).

4. Grasp the battery and gently pull it out far enough to disconnect the battery wires.

5. Disconnect the battery positive (Red) wire and the battery negative (Black) wire. (item 3).

6. Remove the battery and set aside.

7. Orient the new battery in the same direction as the original battery and place the new batteryclose enough to connect the battery wires.

Vertiv | Liebert® PST4™ Installer/User Guide | 10

Page 11: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

NOTE: Replace the battery with the same type and number as originally installed.

8. Connect the battery negative (Black) wire to the battery negative terminal.

9. Connect the battery positive (Red) wire to the battery positive terminal.

NOTE: when connecting the last wire to the battery there can be a small spark, this is normal.

10. Fully insert the new battery into the UPS and re-install the battery compartment cover.

11. Re-install the battery compartment retaining screw.

12. Properly dispose of the old batteries at an appropriate recycling facility or return them toVertiv™ in the packing material for the new batteries.

13. The UPS is now ready for normal operation.

Vertiv | Liebert® PST4™ Installer/User Guide | 11

Page 12: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

1.7.6 Specifications

MODEL NUMBER PST4-660MT120 PST4-850MT120

Capacity (VA / W) 660 / 400 850 / 500

Unit Dimensions, in. (mm)W x D x H 12.4 x 7.2 x 3.3 (314 x 183 x 83)

Unit Weight, lbs (kg) 9.4 (4.3) 9.7 (4.4)

Shipping Dimensions,in. (mm)W x D x H

14.7 x 10.3 x 6.1 (373 x 261 x 155 mm)

ShippingWeight, lbs (kg) 10.6 (4.8) 11.0 (5.0)

Input AC

Nominal Voltage 120 VAC

Voltage Range 100-140 VAC

Frequency Range 50 or 60 Hz, ±5 Hz, auto-sensing

Protection Resettable Circuit Breaker

Surge Energy Rating 320 Joules

Input Cord 6 ft. attached with NEMA 5-15P

Output AC (OnUtility)

Nominal Voltage 120 VAC

Voltage Range 96-146 VAC

Frequency Range 50 or 60 Hz, ±5 Hz, auto-sensing

Efficiency >90%at full load

Output AC (On Battery)

Nominal Voltage 120 VAC

Voltage Range Nominal ±8%

Frequency Range 50 or 60 Hz, ±1%

Waveform PWM Simulated Sine wave

Transfer Time 6-8ms, typical

Overload Capacity110% for 10 seconds,

120% immediate shutdown

Protection Electronic (over current, short circuit w/ latching shutdown)

Backup Time (Full Load / Half Load), min 2 / 9 2 / 7

Battery Type Valve Regulated Lead Acid (VRLA)

Battery Manufacturer / ModelCSB / GP1272

Leoch / DJW12-7.0

CSB / HR

Leoch / DJW12-9.0

Battery Quantity x VDC x Ah 1 x 12V x 7.0 / 7.2Ah 1 x 12V x 9.0Ah

Battery BackedOutlets (4) NEMA 5-15R

SurgeOnly Outlets (4) NEMA 5-15R

Table 1.1 System Specifications

Vertiv | Liebert® PST4™ Installer/User Guide | 12

Page 13: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

MODEL NUMBER PST4-660MT120 PST4-850MT120

Environmental Requirements

Operating Temperature, deg(degC)

Operating Elevation, feet (meter)

32-104 (0-40) without derating0-4,921 (0-1,500) without derating

Operating Temperature, degF (degC)

Operating Elevation, feet (meter)

32-86 (0-30) without derating

4,922-9,842 (1,500.5-3,000) without derating

Relative Humidity 0-95%non-condensing

Storage Temperature, degF (degC) 5 to 113 (–15 to 45)

Storage Elevation, feet (meter) 0-49,212 (0-15,000)

Audible Noise <40 dBA@3 ft (1 m) from all sides

Agency

Safety cTUVus (UL 1778 / CSA22.2 No. 107.1)

RFI / EMI FCC Subpart J, Class B

Surge Immunity ANSI 62.41 (IEC 62040-2 2nd Edition)

Transportation ISTAProcedure 1A

Table 1.1 System Specifications

Vertiv | Liebert® PST4™ Installer/User Guide | 13

Page 14: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

Vertiv | Liebert® PST4™ Installer/User Guide | 14

This page intentionally left blank.

Page 15: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

APPENDICES

Appendix 1: Technical Support

Our Technical Support staff is ready to assist you with any installation or operating issues you mayencounter with your Liebert product. Please call or e-mail us:

Technical support:

e: [email protected]

p: 1-800-222-5877 menu option 1

Monitoring support:

e: [email protected]

p: 1-800-222-5877 menu option 2

Warranty support:

e: [email protected]

p: 1-800-222-5877 menu option 3

Vertiv | Liebert® PST4™ Installer/User Guide | 15

Page 16: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

Vertiv | Liebert® PST4™ Installer/User Guide | 16

This page intentionally left blank.

Page 17: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,
Page 18: Liebert PST4 660-850VA User Manual - Vertiv · designlife.TheLiebertPST4chargesthebatteriescontinuouslywhenitisconnectedtotheutilityinput power.IftheLiebertPST4willbestoredforalongtime,

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA

© 2017VertivCo. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of VertivCo. All other names and logos referred toare trade names, trademarks or registered trademarks of their respective owners. While everyprecaution has been taken to ensure accuracyandcompleteness herein, VertivCo. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for anyerrors oromissions. Specifications are subject to change without notice.

SL-23289_REV2_3-17/590-1412-501C