Liberator - ProIDEA · The T-Liberator and W-Liberator mechanical smoke vents may be used for day...
Transcript of Liberator - ProIDEA · The T-Liberator and W-Liberator mechanical smoke vents may be used for day...
!Group Product Technical Specification
Confidential © Colt International Licensing Ltd 2014
The T-Liberator and W-Liberator mechanical smoke
vents may be used for day to day ventilation as well as
for smoke extract.
Typical applications include:
- Single and multi storey shopping centres
- Single and multi storey industrial buildings and
warehouses
- Atria and complex buildings
- Enclosed car parks
- Stairways
- Theatres
G.P.T.S. No 1105
Issue 02/2014
LiberatorMechanical Smoke Ventilator
Type W-LIBERATOR-FCO
Type T-LIBERATOR
Type W-LIBERATOR-Flap
!Group Product Technical Specification
G.P.T.S. N° 1105
Issue 04
Page 1 . 1
Date February 2014
T-LiberatorGENERAL INFORMATION
Confidential © Colt International Licensing Ltd 2014
1.1 Applications
Suitable for mechanical smoke control with an option to provide day to day ventilation.
Installation up to max. 20° inclination angle.
All units fulfill the F200, F300 and F400 categories in accordance with EN 12101-3, as well as snow classes SL 125
(125N/m²) - TL version and SL 500 (500 N/m²) - WL version in accordance with EN 12101-3. They are CE marked.
1.2 Limitations of use
- High wind pressures
- High buildings
- Installation in coastal regions
The undesirable effect of installation in such places or in such conditions can be that the non-return
shutters clatter.
1.3 Construction
Major components made of aluminium alloy AlMn1Mg0,5.
An aerodynamically shaped square aluminium shroud discharges air vertically. Four non-return shutters in
the shroud ensure that the ventilator closes automatically when the fan is at rest. An internal rain channel
and neoprene seals guarantee that the ventilator is rain-proof.
The unit is available with a single speed motor only.
1.4 Operation
The movement of the fan impeller produces a negative pressure and draws air out of the building.
Simultaneously, a cushion of pressurised air builds up above the impeller, which opens the return flaps
and allows the smoke to be sucked out of the room to the outside. When the power is switched off, the
impeller gradually comes to a standstill. Once the impeller stops moving, four sprung non-return shutters in
the shroud close automatically.
1.5 Product stats groupB 01.
1.6 Performance classes
Requirements of EN 12101-3TL/3/... WL/3/../FCO WL/3/../FLAP
Time-Temperature Class F200 200°/120Min yes yes yes
Time-Temperature Class F300 300°/60Min yes yes yes
Time-Temperature Class F400 400°/120Min yes yes yes
Snowload Class SL 125 125 N/m² yes not applic. yes
Snowload Class SL 250 250 N/m² no not applic. yes
Snowload Class SL 500 500 N/m² no not applic. yes
Powered Extract Unit with double yes yes yes
function of smoke and day to day extract
Opening time for flap(s) Immediate 16 sec. 22 sec.
Closing time for flap(s) Immediate 150 sec. 22 sec.
Yes = requirements fulfilled
No = requirements not fulfilled
T-Liberator W-Liberator
!Group Product Technical Specification
T-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 2 . 1
Date February 2014
Confidential © Colt International Licensing Ltd 2014
2.1.1 Dimensions TL/3
Size
TL/3/06/NF/23
TL/3/06/NF/16
TL/3/08/NF/16
TL/3/08/NF/12
Weight
kg
61
61
77
77
2.1.2 Weights TL/3 2.1.3 Cable requirements TL/3
- halogen free, not flammable, norm NF C 32-070
- Non flammable (Norm IEC 332-1)
- Temperatures for continuous operation:
-60°C to +400°C, max +500°C
- Cable type: MA-VAS 4x1,5mm² or
MA-CNVAS 4x2,5mm²
Any contractor which lays the cable on cable trays or
places it into the ceiling must be qualified to carry out such
work. The cables provided with the product are not allowed
to be used outdoors.
Size
TL/3/06
TL/3/08
K
mm
255
340
G
mm
600
670
E
mm
915
1067
max.
mm
1200
-
min.
mm
1001
-
N5/LB**
Std.
mm
1250
-
Base dimensions*
C x D
max.
mm
950
1250
min.
mm
740
980
N5/SB**
Std.
mm
950
1200
min.
upstand
opening
A
mm
725
875
* Standard N2, N3 and N5 base dimensions correspond with the standard N4 base minus 50 mm.
** SB = Short base, LB = Large base
!Group Product Technical Specification
T-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 2 . 2
Date February 2014
Confidential © Colt International Licensing Ltd 2014
2.1.5 Acoustic data TL/3
Measured without ducting. Ducting can be added, but this alters both the acoustic and volume flow
characteristics.
2.1.4.1 Performance data TL/3 - 300°C / 60min (F300)
* Average sound pressure level measured at 3m distance in free field conditions.
IP 55 rated, with insulation class H.
2.1.4.2 Performance data TL/3 - 200°C / 120min or 400°C / 120min (F200 / F400)
63
66.0
71.0
60.5
60.5
69.0
69.0
68.0
69.0
125
73.0
77.0
73.5
75.0
83.0
84.5
81.5
86.5
250
85.0
95.0
77.0
76.5
84.5
87.5
79.0
83.0
500
85.0
85.0
75.0
74.0
84.0
84.0
76.5
78.5
1,000
85.0
83.0
74.0
73.0
83.0
81.5
76.0
74.5
2,000
82.0
80.0
72.0
71.5
81.0
78.5
74.0
72.0
4,000
78.0
76.0
64.5
64.0
76.5
74.5
67.0
64.5
8,000
68.0
66.0
55.5
55.0
66.0
63.5
57.5
54.5
Size
TL/3/06..
23
16
TL/3/08..
16
12
Position
inlet
discharge
inlet
discharge
inlet
discharge
inlet
discharge
Sound power level (dB)
Centre octave frequency (Hz)
Mean
sound
power
level
dB(A)
89.0
90.0
79.0
78.0
88.0
87.0
81.0
81.0
cos
0.73
Airflow
m³/s
5.88
RPM
min-1
940
Voltage
Volt/Ph.
380-415/3
Current
A
3,71
Power
kW
1,50
Wiring Average
sound
pressure
level*
dB(A)
69.5
Motor
Item-Nr.
WEG
354889
m³/h
21180
Size
TL/3/08..
16
m³/s
4.12
2.69
5.88
4.38
min-1
1420
915
940
705
Volt/Ph.
380-420/3
380-420/3
380-420/3
380-420/3
A
3.19
1.97
3.78
2.42
kW
1.50
0.75
1.50
0.75
dB(A)
72.5
60.5
69.5
63.5
ABB
317935
317932
317933
317934
m³/h
14815
9675
21180
15760
TL/3/06..
23
16
TL/3/08..
16
12
WEG
318948
318945
318946
318947
cos
0.83
0.76
0.74
0.63
!Group Product Technical Specification
T-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 2 . 3
Date February 2014
Confidential © Colt International Licensing Ltd 2014
Type: TL/3/06/23/..
TL/3/06/16/..
Type: TL/3/08/16/..
TL/3/08/12/..
2.1.6 Fan curve TL/3, 06 size
2.1.7 Fan curve TL/3, 08 size
Statis pressure diference (Pa)
Statis pressure diference (Pa)
Air flow V (m³/s)
Air flow V (m³/s)
Value∑
ζValue∑
ζ
!Group Product Technical Specification
W-LiberatorGENERAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 4 . 1
Date February 2014
Confidential © Colt International Licensing Ltd 2014
4.1 Applications
Mechanical smoke control with facility for day to day ventilation.
WL can be fitted either with a FCO ventilator or with a flap. The flap version can be installed in either walls or roofs.
There are two choices of unit:
WL fulfils categories F200, F300 and F400 in accordance with EN 12101-3.
WL with flap version fulfils snow class SL 500 (500 N/m²) in accordance with EN 12101-3.
4.2 W-Liberator with flap
Major components made of aluminium alloy AlMn1Mg0,5. Motor guard painted steel, hinges stainless steel, 30 mm
thick mineral wool insulation for double skin external flap.
4.3 Operation of W-Liberator with flap
For day to day ventilation
The fan starts up and simultaneously the flap is opened: a gas spring pushes the flap and simultaneously
the worm gear motor unwinds the drum and steadily lets the cable go. The external flap opens to
approximately 70° for day to day ventilation, owing to the geometry of the safety locking mechanism.
Once the flap has reached the open end position, a built-in limit switch shuts off the opening mechanism.
The external flap is closed automatically once the fan motor has been switched off using the built-in worm
gear motor coiling up the cable. Once the flap has reached the closed end position, a built-in limit switch
shuts off the closing mechanism.
For smoke control
In a fire situation there is a double safety mechanism:
If the smoke is cool then the fan will start up and the flap will open as above. However if it is hotter than
93°C, then a solder link will part the cable and the flap will automatically open to 90° under pressure from
the gas spring. Should the gas spring fail in its open position, a safety device ensures that the flap does
not close again.
!Group Product Technical Specification
W-LiberatorGENERAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 4 . 2
Date February 2014
Confidential © Colt International Licensing Ltd 2014
4.4 W-Liberator with FCO louvred ventilator
All principal components are manufactured from corrosion resistant aluminium AlMn1Mg0,5.
Guards: steel coated.
WL/03/06/... is delivered with this aluminium bladed FCO unit:
FCO/1ST /0911/A2X/M1C230/1F93/X/FR/N2.
WL/03/08/... is delivered with this aluminium bladed FCO unit:
FCO/1ST/1013/A2X/M1C230/1F93/X/FR/N2.
4.5 Operation of W-Liberator with FCO louvred ventilator
For day to day ventilation
The fan starts up and simultaneously the FCO opens under a spring, since the FCO ventilator is equipped
with a 230V Belimo power to close / spring to open motor. The Belimo closes the ventilator once the fan
has been switched off.
For smoke control
In a fire situation there is a double safety mechanism:
If the smoke is cool then the fan will start up and the flap open as above. If the smoke is hot, then an
additional failsafe device will open the FCO within seconds, without any intervention of the Belimo motor.
4.6 Product stats group
W-LIBERATOR: B 02.
4.7 EN Classifications
Requirements of EN 12101-3TL/3/... WL/3/../FCO WL/3/../FLAP
Time-Temperature Class F200 200°/120Min yes yes yes
Time-Temperature Class F300 300°/60Min yes yes yes
Time-Temperature Class F400 400°/120Min yes yes yes
Snowload Class SL 125 125 N/m² yes not applicable yes
Snowload Class SL 250 250 N/m² no not applicable yes
Snowload Class SL 500 500 N/m² no not applicable yes
Powered Extract Unit with dual yes yes yes
function of smoke and day to day extract
Opening time for flap(s) Immediate 16 sec. 22 sec.
Closing time for flap(s) Immediate 150 sec. 22 sec.
Yes = requirements fulfilled
No = requirements not fulfilled
T-Liberator W-Liberator
!Group Product Technical Specification
W-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 5 . 1
Date February 2014
Confidential © Colt International Licensing Ltd 2014
5.1 Dimensions WL/03/../W..
WL/3/06/W/
WL/3/08/W/
Flap- FCO/0911
- FCO/1013
Size/type
06/W/FCO
08/W/FCO
06/W/Flap
08/W/Flap
open
J
mm
270
270
-
-
closed.
H
mm
220
220
height
G
mm
1015
1148
-
-
width
F
mm
974
1124
-
-
height
E
mm
865
998
-
-
width
D
mm
824
974
-
-
body
inner
K
mm
-
-
680
840
flange
L
mm
-
-
920
1090
flange
outer
M
mm
-
-
740
900
flap
N
mm
-
-
775
935
body
closed
S
mm
-
-
382
382
body
open
T
mm
-
-
1053
1213
body flange body depth
rear guard
front guard
5.1.1 Dimensions and weights WL/3..
Size/type
WL/3/06/W/...
WL/3/08/W/...
C
mm
766
926
B
mm
480
627
A
mm
684
844
a-value*
m³/
hmPa2/3
2.0
2.0
0.47
0.47
weight
kg
60
105
70
115
* a-value = air leakage
!Group Product Technical Specification
W-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 5 . 2
Date February 2014
Confidential © Colt International Licensing Ltd 2014
5.2 Dimensions WL/03/../R/Flap
5.2.1 Dimensions and weights WL/3..
Size/
type
WL/3/06/R
WL/3/08/R
C
mm
766
926
B
mm
-
-
A
mm
684
844
Size/
type
06/R/Flap
08/R/Flap
weight
kg
70
115
body
inner
K
mm
680
840
flange
L
mm
920
1090
upstand
inner
U
mm
700
860
Upstand
!Group Product Technical Specification
W-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 5 . 3
Date February 2014
Confidential © Colt International Licensing Ltd 2014
5.3.1 Performance data WL/3 - 300°C / 60min (F300)
5.3.2 Performance data WL/3 - 200°C / 120min or 400°C / 120min (F200 / F400)
* Average sound pressure level measured at 3m distance in free field conditions.
IP 55 rated, with insulation class H.
Flap Technical data worm gear motor:Voltage : 400V; 3 Ph.; 50 Hz.RPM : 23.0 min-1
Power : 0.09 kWProtection : IP 54
Insulation Class : F
Current : 0.4 A
FCO Technical data actuator:Type : BELIMO AF230Voltage : 230 V AC 50/60 HzTorque : 15 NmProtection : IP 44
Insulation Class : F
Will be delivered with 2m breakout cable. Direct conecting to the motor is not possible.
Airflow
m³/s
6.12
RPM
min-1
940
Voltage
Volt/Ph.
380-415/3
Current
A
3.71
Power
kW
1.50
Wiring Average
sound
pressure
level*
dB(A)
73,5
Motor
EDP no.
ABB
354889
m³/h
22025
Size
WL/3/08..
16
cos
0.73
Size
WL/3/06..
23
16
WL/3/08..
16
Airflow
m³/s
3.75
2.5
6.12
RPM
min-1
1420
915
940
Voltage
Volt/Ph.
380-420/3
380-420/3
380-420/3
Current
A
3.19
1.97
3.78
Power
kW
1.50
0.75
1.50
Wiring Average
sound
pressure
level*
dB(A)
76.5
66.5
73.5
m³/h
13480
9185
22025
Motor
EDP no.
WEG
318948
318945
318946
Motor
EDP no.
ABB
317935
317932
317933
cos
0.83
0.76
0.74
!Group Product Technical Specification
W-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 5 . 4
Date February 2014
Confidential © Colt International Licensing Ltd 2014
5.5 Cabling technical data
- Halogen free, not flammable, norm NF C 32-070
- Non flammable (Norm IEC 332-1)
- Temperatures for continuous operation:
-60°C to +400°C, max +500°C
- Cable type: MGL--NI/Fe (4x2,5mm²)
- The cable connecting to worm gear motor and limit switches is silicone 4x1.5, type SIHF-J*
* See appendix for wiring diagram
The cables provided with the product are not allowed to be used outdoors.
Any contractor which lays the cable on cable trays or places it into the ceiling must be qualified to carry
out such work.
5.4 Acoustic data WL/3
Measured without ducting.
inlet
discharge
inlet
discharge
inlet
discharge
63
66.0
71.0
60.5
60.5
69.0
69.0
125
73.0
77.0
73.5
75.0
83.0
84.5
250
85.0
95.0
77.0
76.5
84.5
87.5
500
85.0
85.0
75.0
74.0
84.0
84.0
1,000
85.0
83.0
74.0
73.0
83.0
81.5
2,000
82.0
80.0
72.0
71.5
81.0
78.5
4,000
78.0
76.0
64.5
64.0
76.5
74.5
8,000
68.0
66.0
55.5
55.0
66.0
63.5
Mean
sound
power
level
dB(A)
89.0
90.0
79.0
78.0
88.0
87.0
Sound power level (dB)
Centre octave frequency (Hz)
Size
WL/3/06..
23
16
WL/3/08..
16
!Group Product Technical Specification
W-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 5 . 5
Date February 2014
Confidential © Colt International Licensing Ltd 2014
5.6 Fan curve 06 size
Type: WL/3/06/23/..
WL/3/06/16/..
5.7 Fan curve 08 size
Type: WL/3/08/NF/16/..
Statis pressure diference (Pa)
Statis pressure diference (Pa)
Air flow V (m³/s)
Air flow V (m³/s)
Value∑
ζValue∑
ζ
!Group Product Technical Specification
W-LiberatorTECHNICAL INFORMATION
G.P.T.S. N° 1105
Issue 04
Page 5 . 6
Date February 2014
Confidential © Colt International Licensing Ltd 2014
5.8 Installation
Installation onto fixing anglesInside of building
rear guard
front guard
Continuous aluminium
angle section 50 x 50 x 5 Fixing angle (by others)
fixing angle (by others)