LGPI485 GATEWAYINSTALLATION MANUAL
LG
Models: PHNFP14A0PSNFP14A0
IMPORTANT
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
2 485 Gateway(M)
Central Control Unit Use & Care Manual
TABLE OF CONTENTS� Part Installation & Operation precution .....................3~4
� Part Description ...........................................................5
� Installation Guide ..........................................................7
� Installation Steps .................................................................................7
� DIP Switch Configuration.....................................................................8
� Simple Central Controller - Connection Diagram ..............................10
� Deluxe Central Controller - Connection Diagram ..............................12
� Examples For Product Installation.....................................................13
� Accessory Parts .........................................................14
Safety Precautions
Installation Manual 3
Don't touch with thehands while the power ison
• There is risk of fire or electricshock.
Use standardparts(connector).
• Do not disassemble or repairthe product. There is risk of fireor electric shock.
For electrical work, contactthe dealer, seller, a qualifiedelectrician, or an AuthorizedService Center.
• Do not disassemble or repairthe product. There is risk of fireor electric shock.
� Installation
ON
L1 2 3 4
KSDO4H
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
Safety PrecautionsTo prevent injury to the user or other people and property damage, the following instructionsmust be followed.� Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
� Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Safety Precautions
4 485 Gateway(M)
When the product is soaked (flooded orsubmerged), contact an Authorized ServiceCenter.• There is risk of fire or electric shock.
Be cautious that water could not enter theproduct.
• There is risk of fire, electric shock, or productdamage.
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
� Operation
Use the correctly ratedbreaker or fuse.
• There is risk of fire or electricshock.
Do not install, remove, or re-install the unit by yourself(customer).
• There is risk of fire, electricshock, explosion, or injury.
For installation, alwayscontact the dealer or anAuthorized Service Center.
• There is risk of fire, electric
shock, explosion, or injury.
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
Part Description
Installation Manual 5
Part DescriptionPHNFP14A0
PI485 GATEWAY(C)
CN_OUT: Indoor Unit Connector
BUS_B: RS-485 (-) Terminal
BUS_A: RS-485 (+) Terminal
LED01G,02G,03G: Communication Status LED
LED1: RS-485 Communication Status LED
Reset Switch: PI485(C) Reset
DIP Switch: Product Select (Refer Page 8)
S1
BR1
TANS01Y
ZNR01Y
U02YU04YU03Y
SWITCH
LED1
LED0
1GLE
D02G
LED0
3G
OSC0
1BL0
2DL0
1D C01A
IC01
A
CN_COMM
C03Y
C04Y
ON
L1 2 3 4
1
2
3
4
5
6
7
1
234
567
6 485 Gateway(M)
Part Description
PSNFP14A0
PI485 GATEWAY(R)
CN_OUT: Indoor Unit Connector
BUS_A: RS-485 (+) Terminal
BUS_B: RS-485 (-) Terminal
LED01G,02G,03G: Communication Status LED
LED1: RS-485 Communication Status LED
Reset Switch: PI485(C) Reset
DIP Switch: Product Select (Refer Page 9)
ONL1 2 3 4
1
2
3
5
7
6
4
1
234
567
Installation Manual 7
Installation Guide
Installation Steps (PHNFP14A0/PSNFP14A0)
1. Select DIP Switch Configuration(Refer page 8 or 9)
2. Connect The RS-485 BUS_A(+), BUS_B(-) with Other Network Products (ex,Simple Central Controller , CNU.....)
3. Connect CN_OUT with Outdoor Unit by the cable (provided)
4. Check the Communication Status LED
- LED01G(Red): Ok operation-LED blinks for 5times and is OFF. This process is repeated after every 3 minutes• NG operation : Check The Indoor unit address & Wiring Connections
- LED02G(Yellow) ,LED03G(Orange): Ok operation-LED's blinks continuously• NG operation : Check The DIP Switch setting & Wiring Connections
5. Check the RS-485 Communication Status LED:
� Ok operation
(1) LED's blinks 2 Times in every 10~30 seconds (In case Connected CNU)
(2) LED's blinks continuously (In case Connected Simple Central Controller)
� NG operation : Check The Wiring Connections
6. Finally if all the above steps are OK then , Tie the cables by Tie Wraps & Clamp
Installation Guide
1
7
4
5
2 3
8 485 Gateway(M)
Installation Guide
ON KSDO 4HS1
BR1
TANS01Y
ZNR01Y
U02YU04YU03Y
SWITCH
LED1
LED0
1GLE
D02G
LED0
3G
OSC0
1BL0
2DL0
1D C01A
IC01
A
CN_COMM
C03Y
C04Y
ON
L1 2 3 4
L1 2 3 4
Select AirConditioner Type
Select NetworkType
ON KSDO4H
ON KSDO4H
L1 2 3 4
L1 2 3 4
DIP Switch Configuration
3 ON+ALL OFF: Using LGAP CAC/RAC/SRAC/PAC ProductsConfiguration Methods
3, 4 ON+ALL OFF: LGAP CAC/RAC/SRAC/PAC Products + CentralController (ALL type)-Using LGAP
Using LGAP CAC/RAC/SRAC/PAC Products Configuration Methods
• PHNFP14A0
CAUTION: Wrong Products Configuration can lead to malfunctioning
Installation Guide
Installation Manual 9
ON KSDO 4H
L1 2 3 4
Select AirConditioner Type
Select NetworkType
ONL1 2 3 4
ON KSDO4H
ON KSDO4H
L1 2 3 4
L1 2 3 4
3 ON+ALL OFF: LGAP CAC/RAC/SRAC/PAC Products + CentralController (ALL type)-Without LGAP
3, 4 ON+ALL OFF: LGAP CAC/RAC/SRAC/PAC Products + CentralController (ALL type)-Using LGAP
Using LGAP CAC/RAC/SRAC/PAC Products Configuration Methods
• PSNFP14A0
CAUTION: Wrong Products Configuration can lead to malfunctioning
10 485 Gateway(M)
Installation Guide
S1
BR1
TANS01Y
ZNR01Y
U02YU04YU03Y
SWITCH
LED1
LED0
1GLE
D02G
LED0
3G
OSC0
1BL0
2DL0
1D C01A
IC01
A
CN_COMM
C03Y
C04Y
ON
L1 2 3 4
Indoor Main PCB
Simple Central Controller
DC 10V
VCC
Bus BCN_OUTCN_COMM
Bus A
GNDDC
Indoor Main PCB
CN_CC
CN_CC
PI485 GATEWAYSimple Central Controller
CENTRALCONTROLUNIT
Simple Central Controller - Connection Diagram
CAUTION: After Product Installation Tie the cables with the clamps & Tie-Wraps provided.
• PHNFP14A0
Installation Guide
Installation Manual 11
Indoor Main PCB
Simple Central Controller
DC 10V
VCC
Bus B
Bus AGND
DC
Indoor Main PCB
CN_CC
CN_CC
PI485 GATEWAY Simple Central Controller
CENTRALCONTROLUNIT
ONL1 2 3 4
ONL1 2 3 4
CAUTION: After Product Installation Tie the cables with the clamps & Tie-Wraps provided.
• PSNFP14A0
12 485 Gateway(M)
Installation Guide
S1
BR1
TANS01Y
ZNR01Y
U02YU04YU03Y
SWITCH
LED1
LED0
1GLE
D02G
LED0
3G
OSC0
1BL0
2DL0
1D C01A
IC01
A
CN_COMM
C03Y
C04Y
ON
L1 2 3 4
Indoor Main PCB
Bus B
Bus A
Bus B
Bus A
Bus B
Bus A
PI485 GATEWAYPCB
PI485 GATEWAYPCB
CN_CC
Indoor Main PCB
CN_CC
CNUPCB
Bus B
Bus A
CNUPCB
ONL1 2 3 4
Deluxe Central Controller - Connection Diagram
CAUTION: After Product Installation Tie the cables with the clamps & Tie-Wraps provided.
• PHNFP14A0
• PSNFP14A0
Installation Guide
Installation Manual 13
Examples For Product Installation
CAUTION: It can be Different location of installation in order to Each Product structure
(1) The Installation for 4Way CassetteProduct
� Check Screw boss for PCB in 4wayCassette Product Then fix It
(2) The Installation for DUCT Product� Using PCB Holder provided
(3) The Installation for Cassette ProductCover� Check Screw boss for PCB in 4way
Cassette Product Then fix It
14 485 Gateway(M)
Acceassory Parts
Acceassory Parts
S1
BR1
TANS01Y
ZNR01Y
U02YU04YU03Y
SWITCH
LED1
LED0
1GLE
D02G
LED0
3G
OSC0
1BL0
2DL0
1D C01A
IC01
A
CN_COMM
C03Y
C04Y
ON
L1 2 3 4
PCB :6871A20484B Holder for DUCT :3110A 20056A WIRE ASSY 1(for RAC/SRAC/CAC)
Screw 4 EA Installation Manual WIRE ASSY(for Others)
ONL1 2 3 4
PCB :6871A20484C
WIRE ASSY 1(for RAC/SRAC/CAC) WIRE ASSY(for Others)
Screw 4 EA Installation Manual
* Others : Tie Wrap (3 EA) - Cable TieClamp (1 EA)
• PSNFP14A0
• PHNFP14A0