LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model...
Transcript of LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model...
![Page 1: LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model ARUN80L M3ARUN100L ARUN120L Capacity Cooling kW 22.4 28.0 33.6 Heating kW 25.2 31.5](https://reader031.fdocuments.net/reader031/viewer/2022021820/5adad1a97f8b9a137f8e034c/html5/thumbnails/1.jpg)
www.lgeaircon.com
Solo
Optimized solution for Light commercial applications.
Distributed by
LG ElectronicsAE Company, Commercial Air Conditioning20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea.Phone : +82-2-3777-7731 Fax : +82-2-3777-3099www.lg.com www.lgeaircon.com
Copyright © 2011 LG Electronics. All rights reserved.
![Page 2: LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model ARUN80L M3ARUN100L ARUN120L Capacity Cooling kW 22.4 28.0 33.6 Heating kW 25.2 31.5](https://reader031.fdocuments.net/reader031/viewer/2022021820/5adad1a97f8b9a137f8e034c/html5/thumbnails/2.jpg)
Enjoy Clean, Quiet, and Comfortable Air Conditioning with LGMulti V III solo is ideal for shops, small offices, restaurants and hotels, and also for multiple owners buldings, symmetrical buldings and mid-large capacity buldings with small rooms (to respect EN378)
Eco-Design, Energy Efficient Reduce CO2 Emissions
![Page 3: LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model ARUN80L M3ARUN100L ARUN120L Capacity Cooling kW 22.4 28.0 33.6 Heating kW 25.2 31.5](https://reader031.fdocuments.net/reader031/viewer/2022021820/5adad1a97f8b9a137f8e034c/html5/thumbnails/3.jpg)
SOLO
Multi V III solo provides the office workers to work under comfortable and silent environment, with 4way cassetts or concealed ducts. It can also use a separate outdoor unit with different indoor units, for spaces such as conference rooms and kitchens, with 130% compatibility.
Multi V III solo offers optimized solution for light commercial applications, such as offices, shops, restaurants, and residential buildings.
Depending on space utilizations, various indoor units can be applied with Multi V III solo. Therefore, customers are allowed to do shopping under perfect environment and conditions.
Concealed ducts, provided by Multi V III solo, are great match with luxurious interior of restaurants. Customers can enjoy their meal with comfort and satisfaction
offices
A building with multiple owners symmetrical building
shop
Restaurants
lG Air Conditioners 2011
Application Example
Different owners may use separate outdoor units for their own operation costs and management.
It is more efficient to use separate outdoor units, rather than a combination of outdoor units to save installation cost.
Regulation EN 378To meet regulation EN378, the amount of refrigerant leakage should satisfy the following equation for human safety.
Total amount of refrigerant in the system
Volume of the room at which Indoor unit of the least capacity is installed <0.44
Project: VRF, capacity of 24HP (12HP+12HP)
Total quantity of R410A in the system = 24.8kg (oDU 12.8kg + IDU&pipes ~12kg)
Two separate 12HP outdoor units providing different solutions with two circuits.
20m2 20m2
24HP12HP 12HP
A combination of two 12HP outdoor units providing a solution with one circuit.
In the project, the smallest room/office is 20m², so 50m3.
The concentration in this room is: 24.8kg/50m3 = 0.50kg/m3
EN 378 not respected
Add ventilation system in all small rooms (20m²)(air flow 40m3/h each), with leakage detectors
Total quantity of R410A in one system (12HP) = 12.4 kg (oDU 6.4kg + IDU&pipes ~6kg)
The concentration in this room is: 12.4kg/50m3 = 0.25kg/m3
EN 378 respected
EN 378 respected
Conventional Conventional
Conventional
MUlTI V lll solo
MUlTI V lll solo
MUlTI V lll solo
![Page 4: LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model ARUN80L M3ARUN100L ARUN120L Capacity Cooling kW 22.4 28.0 33.6 Heating kW 25.2 31.5](https://reader031.fdocuments.net/reader031/viewer/2022021820/5adad1a97f8b9a137f8e034c/html5/thumbnails/4.jpg)
lG Air Conditioners 2011
High cooling and heating COPTechnical innovation for high COPMulti V simple has high effi-ciency parts, advanced interv-er control technology and optimal cycle control technol-ogy, which the system’s uni-fied performance has been improved. Based on these advanced technologies, the product provides customers value through high efficiency and energy saving.
※Coefficient of Performance (CoP) =
Therefore, higher CoP of a product makes its cooling and heating capability higher and energy consumption lower
Cooling / Heating Energy consumption
ConventionalMulti V III Simple5
1
2
6 7
3
4
18%UP
3%UP
4.04
3.41
4.12
4.23
lG BlDC inverter compressor
sine wave inverter control
Cyclone sub-cooling circuit
Newly designed propeller fan
lG BlDC Inverter fan Motor
Uniform distributor for the heat exchanger
Improved the energy efficiency by 11%, compared to the AC inverter compressor, using the high efficiency lG BlDC inverter compressor.
Improved the efficiency of the compressor motor by using the sine wave DC inverter control technology.
Improved the cooling capability by using a cyclone sub-cooling circuit.
Achieved optimal heat exchange by using high air volume and low noise fan.
Improved efficiency by using high efficiency BlDC inverter motor, compared to the AC motor.
Improved heat exchange performance and efficiency by reducing greatly the heat exchanger’s temperature deviation from 5ºC to 1ºC, applying an optimal distributor design to the heat exchanger.
5
6
1
2
3
4
5 1
CompSC EEV
EEVEvaporator
Condenser
Sub Cooling circuit
H
Liquid
Capacity
P
Sub Cooling Circuit
Liquid + Gas
32
4 3
4 3
5 1
2
4 5555
EEVE
44
CoolingCycle
ComppSC EEV
CoolingCoolingCycleCycle
5 1
CompSC EEV
EEVEvaporator
Condenser
Sub Cooling circuit
H
Liquid
Capacity
P
Sub Cooling Circuit
Liquid + Gas
32
4 3
4 3
5 1
2
4 5555
EEVE
44
CoolingCycle
ComppSC EEV
CoolingCoolingCycleCycle
OLD
NEW
OLD
NEW
OLD
NEW
OLD
NEW
Provides low noise levels through pod-shaped design
Minimizes vortex resistance with a curved shape
Provides high air volume and high static pressure with the changed shape
Flexible indoor unit combinationsince up to 20 indoor units can be connected with 13 types of 71 different indoor models selections, a variety of designs tailored for individual construction usage can be made. Up to 130% efficiency can be achieved with different combinations.
Connectable Indoorunit Capacity
Up to Max 130%Various Indoor units
13 types, 71 modelsConnectable Indoor
unit Number
Up to 20
��A combination with maximum 130% efficiency can be achieved only if the changes of the heating and cooling load and the product oper ation rate by time are considered
Extended piping length and elevationInverter control technology and sub-cooling control circuit technology provide best solution for mid-size buildings
Total piping length Max 150m(170m**)
Longest piping length Max 100m
Level difference between ODU*~IDU*
Max 50m
ODU* : Outdoor unitIDU* : Indoor unit** : Equivalent
Longest piping length after 1st branch
Max 40m
Level differentbetween IDU*~IDU*
Max 15m
Automatic detection for incorrect connectionsMulti V III solo automatically checks that connections of piping lines and communication lines with its FDD(Fault Detection & Diagnosis) function providing notification on any errors.
Communicationlines
Incorrect piping line connection(liquid line + gas line)
Incorrect communication line connection
Auto leakage detection
Refrigerant recovery and reuse
No refrigerant leakage design and production
The product monitors the operation status data in real time and decides the appropriate amount of refrigerant and displays it. It also automatically notifies the user of any small refrigerant leakage.
When performing maintenance on the product, the refrigerant is not discharged to the air, but saved by collecting it inside an outdoor unit, a refrigerant pipe, or an indoor unit. This increas-es environmental protection and reduces costs.
Brazing
냉매누설방지용접 가공
Refrigerant recovery
The product is especially designed and produced with brazing to prevent from refrigerant leakage
Wide louver fins for the heat exchangerImproved efficiency by using wide louver fins with an increased heating area.
7
Intelligent simple test runAutomatic test run mode immediately checks and noti-fies various installation and operation problems, reducing installation engineers’ efforts and time.
Compared to the conventional product, It can reduce test run time by more than 60% provides safe, reliable and convenient test run with various data backup functions.
setting
Reporting
MUlTI V lll solo
Real-time fault prediction functionThis product allows you to check the current status for the sensors and the EEV, which are the major compo-nents for system control, through auto test run. And alerts you of which one of them has a problem, you can take action quickly even if a problem occurs within the normal operation range.
에러
고장예측
에러 에러정상 운전 영역
고장예측
Error
Normal operation range
sensor
EEV
Automatic refrigerant charging functionThe FDD algorithm calculates and automatically charges the correct amount of refrigerant without using an elec-tronic scale. Therefore, installation reliability is increased and product performance is guaranteed.
Embedded with the FDD algorithm
Indicated by the LED indicatorwhen fully charged
test runReporting
test runReporting
setting
Connecting lGMV
Connecting PC
Test run
Reporting
Conventional
test runReporting
test runReporting
test runReporting
test runReporting
test runReporting
3hr / Unit1hr / Unit
Automatic test run results
Automatic reporting
submitted to the customer
Data back up
Use of a laptop or PDA
Save 60
% test run tim
e
SOLO
![Page 5: LG Electronics AE Company, Commercial Air … Air Conditioners 2011 specifications HP 8 10 12 Model ARUN80L M3ARUN100L ARUN120L Capacity Cooling kW 22.4 28.0 33.6 Heating kW 25.2 31.5](https://reader031.fdocuments.net/reader031/viewer/2022021820/5adad1a97f8b9a137f8e034c/html5/thumbnails/5.jpg)
lG Air Conditioners 2011
specifications
HP 8 10 12
Model ARUN80LM3 ARUN100LM3 ARUN120LM3Capacity Cooling kW 22.4 28.0 33.6
Heating kW 25.2 31.5 37.8
Power Cooling kW 5.55 7.20 9.30
Input Heating kW 5.96 7.60 9.34
COP Cooling 4.04 3.89 3.61
Heating 4.23 4.14 4.05
Power Supply Ø, V, Hz 3, 380~415, 50
Dimensions(WxHxD) mm 920×1,680×760
Weight kg 175×1 218×1
Color Warm Gray, Morning Gray
Noise level dBA±3 57 58
Fan Type Propeller fan
Air flow rate [CMM] 180 190
Compressor Type DC scroll
Number of compressors 1 2
Heat Exchanger Gold fin
Refrigerant Type R410A
Charge kg 5.0 5.5
Control EEV
Oil Type FVC68D(PVE)
Charge cc 2,825 3,975
Piping Liquid Pipes mm(inch) Ø9.52(3/8) Ø12.7(1/2)
Connections Gas Pipes mm(inch) Ø19.05(3/4) Ø22.2(7/8) Ø28.58(1 1/8)
Operating rangeCool ing °CDB -5 ~ 43
Heating °CWB -20 ~ 15,5
Number of outdoor unit 1
Number of maximum connectable indoor units * 13 16 20
Ratio of the connectable indoor units 50~130%
Longest piping length / Level difference ** 50~130%
• A combination operation over 100% cause to reduce each indoor unit capacity
CAUTION
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C (80.6°F) DB /19°C (66.2°F) WB - outdoor Temperature 35°C (95°F) DB /24°C (75.2°F) WB Piping length - Interconnecting Piping length 7.5m - level Difference of Zero.
2. Capacities are net capacities3. EEV : Electronic Expansion Valve4. Wiring cable size must compaly with the applicable local and national code.5. Due to our policy of innovation some specifications may be changed without notification.
Heating: - Indoor Temperature 20°C (68°F) DB / 15°C(59°F) WB - outdoor Temperature 7°C (44.6°F) DB / 6°C (42.8°F) WB
Note :
* A ratio of the connectable indoor units with the outdoor : Within 50% ~ 130%
Add this note: All remote controllers and central controllers of Multi V range are available with MVS system.
Conversion Formula
RT = kW x 0.284kcal/h = kW x860Btu/h = kW x 3412CFM = m3/min x 35.3
SOLO
Indoor line Up
kW
Btu / h
2 way Cassette
1 way Cassette
Low Static
Built-in
High Static
With Case
Without Case
Ceiling Cassette
Ceiling Concealed Duct
FreshAir Intake Unit
Floor standing
Ceiling & Floor
Ceiling suspended
(840*840)4way Cassette
(570*570)4way Cassette
Mirror
series
Wall mounted
Console
5k 7k 9k 12k 15k 18k 24k 28k 36k 42k 48k 76k 96k
1.5 2.2 2.8 3.6 4.5 5.6 7.1 8.2 10.6 12.3 14.1 22.428.0