Frankfurt (Germany), 6-9 June 2011 LEONARD– CA– S1– 0176 PARTIAL DISCHARGE (PD) SNIFFER FOR WORKERS’ SAFETY IN UNDERGROUND VAULTS Hydro-Québec

description

PARTIAL DISCHARGE (PD) SNIFFER FOR WORKERS’ SAFETY IN UNDERGROUND VAULTS. Hydro-Québec. LEONARD– CA– S1– 0176. Contents. Context and Design Specification Sniffer Hardware Signal Processing and Diagnostic Time Domain Signal Clustering PD mining in PRPD diagram Case studies Conclusion. - PowerPoint PPT Presentation

Transcript of LEONARD– CA– S1– 0176

Page 1: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

PARTIAL DISCHARGE (PD) SNIFFER FOR WORKERS’ SAFETY INUNDERGROUND VAULTS

Hydro-Québec

Page 2: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

Context and Design Specification Sniffer Hardware Signal Processing and Diagnostic Time Domain Signal Clustering PD mining in PRPD diagram Case studies Conclusion

LEONARD– CA– S1– 0176

Contents

Page 3: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

Existing PD analyser - few minutes/component

LEONARD– CA– S1– 0176

Context and Design Specification

Phase sensor

PD sensor

PD sensor

Page 4: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

Existing PD analyser - few minutes/component Manual interpretation done by an PD expert Many components to measure in a vault

LEONARD– CA– S1– 0176

Context and Design Specification

Page 5: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Context and Design Specification

Page 6: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

Existing PD analyser - few minutes/component Manual interpretation done by an PD expert Many components to measure in a vault Safety concern : 20 minutes exposure time Specification: Automated diagnosis under 15 s

LEONARD– CA– S1– 0176

Context and Design Specification

Page 7: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Sniffer Hardware

1 Gs/s

8

8

12 bitsResolutionDatasegment

The phase value commands the trigger enabling

External trigger through FM notch filter

Page 8: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Signal processing and diagnostic

Value>0.5Then PD

Page 9: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Time Domain Signal ClusteringClassic clustering Time signal clustering

Page 10: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Time Domain Signal Clustering

84 segments

48 segments

Seg.1 Seg.2 Seg.3 …

Page 11: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Time Domain Signal Clustering

One segment

, 1i j

j

D

r

Signature

RN

Page 12: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

PD mining in PRPD diagram

2D Sampling of the PRPD diagram

Page 13: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Case studies

Linear scale PRPD

Log scale PRPD

Page 14: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Case studies128 PD cluster (green) captured in the vicinity of a SF6 interrupter

Page 15: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Case studies

Small-amplitude 251 PD cluster – Vault Blast 3 Hours later

Page 16: LEONARD– CA– S1– 0176

Frankfurt (Germany), 6-9 June 2011

LEONARD– CA– S1– 0176

Conclusion

Automated diagnosis is possible in the field Wide-band probe is needed with fast ADC Switching of analog filter bank - essential PD mining in PRDP diagram - essential Time clustering resolves superimposed clusters Sniffer generated 22 real + 150 false alarms for

>40 000 measurements in vaults