Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes...

40
Legionella Control in Building Systems Carl Schultz, PE Mechanical Department Manager National Healthcare Engineering Leader Howard Hoover, CPD Senior Plumbing Designer

Transcript of Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes...

Page 1: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Legionella Control

in Building SystemsCarl Schultz, PE

Mechanical Department Manager

National Healthcare Engineering Leader

Howard Hoover, CPD

Senior Plumbing Designer

Page 2: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water
Page 3: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Legionella Basics

• Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever

• Present widely in water and soil

• The Philadelphia outbreak in 1976 attributed to hotel’s air conditioning system

– Sickened 200 and killed 34

• Transmission: aerosolized water droplets inhaled by a susceptible host

Page 4: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Favorable Conditions

• Temperature

– Grows and multiplies: 68 to 122 deg F

– Reproduces and thrives: 95 to 115 deg F

– @131 deg F takes 5 to 6 hours to die

– @140 deg F takes 32 minutes to die

– @151 deg F dies instantly

• Stagnation

• Scale, Sediment, Biofilms

• Presence of amoebae

Page 5: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Growth Influences

• Natural rubbers: washers,

hoses, spray attachments

• Some plastics

• Wood (think large water tanks)

• Carbon: think twice about providing carbon filtration at ice machines! Carbon also removes chlorine from the water!

Page 6: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Why is this topic important?

• Health of Building occupants

• New guidelines

• Preventable

• Increasing risk of litigation

Page 7: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Cases up 400% since 2000

Page 8: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Health of Building Occupants

• More than 20 outbreaks were reported in 2015 resulting almost 5,000 diagnosed

cases of Legionnaire’s disease

• 12% of population is susceptible

– Heavy cigarette smoking, chronic lung disease, weakened immune system from cancer, diabetes, kidney failure, organ transplantation

Page 9: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Wrongful Death Suit• 53 year old Allstate insurance employee

contracted Legionnaires Disease in Dec 2004

• Died in January 2005

• Used bathroom on ground floor of office building regularly

• Coworker testified that he saw him splash water on his face

• Defense said he drank alcohol and smoked cigarettes

• Summary judgement against plaintiff family

• Absence of statute, regulation, or industry standard

Page 10: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Barrow-in-Furness Case

• 2002 outbreak from cooling tower

• 7 deaths and 188 cases of illness

• A senior architect with the government council was charged with 7 counts of manslaughter

• Technical Manager for government was fired

• Architect was found not guilty but she and her employer paid significant fines

• Contractor settled for 1.5M British Pounds

Page 11: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Legionella Laws

• Bronx Legionnaires’ Outbreak summer 2015

• 12 deaths: Opera House Hotel cooling tower

• NYC Local Law 77: Registration, inspection, cleaning, disinfection, testing of all towers

• Owners: annually certify “in compliance” of law

• $25,000 fine, 1 year in prison for non-compliance

• New crisis = new laws, regulations

• Standards and guidelines used to craft laws and regulations

Page 12: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

ASHRAE Standard 188

“Prevention of Legionellosis Associated with Building Water Systems”

• Much of this document is more useful to building owners and operators

• Gives insight on what O&M staff will need to be doing and how to design accordingly

• Presents opportunities for consultants: – Mapping water systems

– Designing remedies for proper system operation

– Writing risk mitigation plans

Page 13: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

ASHRAE Standard 188

• Determining building Risk Characterization

• Conducting a hazard analysis

• Determining critical control points & limits

• System monitoring

• Establishing corrective actions

• Verification and documentation

Page 14: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Standard 188: Risk Characterization

• Multiple housing units with common water heater(s)

• Building with more than 10 stories

• Inpatient healthcare facility

• Occupants over 65 or receiving chemo or bone marrow transplant

• Whirlpool, spa, or aerosolizing water feature

• Less than 0.5 ppm Cl2 on incoming water supply

Page 15: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

ASHRAE Guideline 12-2000

“Minimizing the Risk of Legionellosis

Associated with Building Water Systems”

• Should be updated soon and the information will be used to supplement Standard 188

• More practical guide for the building engineer

Page 16: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

ASHRAE Guideline 12-2000

Recommended Treatment (Control Limits)

In healthcare facilities, nursing homes, and other high risk facilities:

• Cold water stored and distributed at temperatures below 68 deg F

• Hot water stored above 140 deg F

• HW circulated with a minimum return temperature of 124 deg F

Page 17: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

• Washington DC office

• Updated primarily for Legionella Mitigation

• Impetus: 6 deaths at Pittsburgh VAMC in 2011

VA Plumbing Design Manual

Page 18: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

VA Plumbing Design Manual

• Physical Security Manual: 4 day water supply

• Entering potable water monitored for:

• Pressure, temperature, pH, oxidant levels

• Temperature measured throughout hot & cold water systems

• Hot & cold water to be continuously re-circulated

Page 19: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

VA Plumbing Design Manual

• Minimization of dead ends and fixture run-outs

• DHW must be available within 15 seconds

• Run-out volume and length - International Green Energy Code:

Page 20: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Limiting Pipe Volume In Patient Rooms

Page 21: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

VA Plumbing Design Manual

• Taps for booster heater for thermal eradication and shock chlorination

• No PVC for sanitary due to thermal eradication

• 30 minutes at 160 to 170 deg F

• Water heaters to develop 180 deg F

• TMV to have bypass

Page 22: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

New Hospital Case Study

VA Medical Center, Louisville, KY

- 1.1 million SF

- Mission critical design

Page 23: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Chill your Cold Water?

Page 24: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water
Page 25: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water
Page 26: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water
Page 27: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Domestic Water System

Upgrades

• Hand-over-hand pipe

investigation

• Mapped the entire

domestic hot and cold

water systems: 450,000 sf

• Identified dead legs and

abandoned piping

• Designed remedies

• Legionella management

program

Renovation Case Study

VA Medical Center Clarksburg, WV

Page 28: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Field Investigation

• HEPA Containment Cart

• Infection Control Risk Assessment (ICRA)

• Work with Infection Control Staff

Page 29: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Piping Details

Page 30: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Building Automation System

Domestic hot water supply and return systems

• Graphic displays

• Temperature sensors

• Trending

• Alarm

Page 31: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Water Balancing

• Plumbing professionals need to craft a detailed water balancing specification similar to the HVAC colleagues

• Contractor needs to have credentials and provide a report at the end of the balancing exercise

• This will ensure that hot water is circulating properly throughout the facility

Page 32: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Commissioning

• Water heating equipment: 140 Deg F or above

• ASSE 1017 Master Mixing Valve

• Point-of-use ASSE 1070 mixing valves at lavatories

• Shower temperature limit stops

• Recirculation systems:

– System temps above 124 deg F

Page 33: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Energy Codes

• 120 deg F storage temperature

• Cycling of circulation pumps and heat trace based on occupancy schedule or demand

• Don’t have to comply if it affects health/safety

• International Energy Conservation Code

– Maximum allowable pipe length method

– Maximum allowable pipe volume method

• Veterans Administration has adopted similar pipe volume restrictions

Page 34: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

International Energy Conservation Code

Maximum allowable pipe length method

• 2 foot maximum runout to a public lavatory faucet with 1/2” HW (from the nearest source of heated water)

Maximum allowable pipe volume method

• Volume from the nearest source of heated water to a public lavatory faucet is 2 ounces. A 3/8” pipe has 0.75 ounces/ft.

Page 35: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

2015 IECC Complaint

Page 36: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Take Aways

There is going to come a day when people and organizations will be held to a higher level of accountability for:

• Designing

• Constructing

• Operating

• Maintaining

Domestic hot water systems

Page 37: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Take Away for Critical Facilities

• DHW distribution: 130 deg F minimum

• Generation and storage: 140 deg F minimum

• DHW return: 124 deg F minimum

• Use of TMVs throughout

• Extend return lines DEEP into system

• Minimize dead legs & stagnant area

Page 38: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Other Considerations

• Create schematics of water systems

• Include temperature and chlorine monitoring

• Access to water hammer arrestors, trap primers

• Building Automation System

• Water balancing

• Commissioning

Page 39: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Other Approaches

• Copper-Silver Ionization

– Optimal concentration of ions is not know (ASHRAE Guideline 12-2000)

– Was used at Pittsburgh VAMC where 6 died of LD

• Chlorine Dioxide

– Used by municipal water providers

– Secondary treatment in buildings requires EPA approval

– Has been used in UK and continental Europe

Page 40: Legionella Control in Building Systems - ASPE · Legionella Basics • Bacterium that causes respiratory diseases such as Legionellosis and Pontiac Fever • Present widely in water

Questions?

January 9, 2017

[email protected]

[email protected]