LED Driver Compact dimming Driver LCAI 35W 350mA–900mA ECO C flat ECO … · 2020. 12. 15. ·...

8
www.tridonic.com 1 Subject to change without notice. Information provided without guarantee. Data sheet 04/21-LC094-23 LED Driver Compact dimming Product description • Dimmable built-in LED Driver for LED • Constant current LED Driver • Dimming range 1 ... 100 % • Output current adjustable between 350 – 900 mA • Max. output power 35 W • Nominal lifetime up to 100,000 h • 5 years guarantee (conditions at www.tridonic.com) Housing properties • Compact low-profile dimensions • Casing: polycarbonate, white • Type of protection IP20 Interfaces • DALI DEVICE Type 6 • DSI • switchDIM (with memory function) • corridorFUNCTION Functions • Adjustable output current in 1-mA-steps (I-SELECT resistor or DALI) • Power-up fading at AC • Intelligent Temperature Guard (overtemperature protection) • Short-circuit proof • Overload protection • Constant Light Output function • Intelligent Voltage Guard (overvoltage and undervoltage monitoring) • Suitable for emergency escape lighting systems acc. to EN50172 È Standards, page 5 Driver LCAI 35W 350mA–900mA ECO C flat ECO series 15 100 140 50 130 90 50 5 5 4.2 tc Ordering data Type Article number Packaging carton Packaging pallet Weight per pc. LCAI 35W 350mA-900mA ECO C flat 28000336 20 pc(s). 1,000 pc(s). 0.170 kg

Transcript of LED Driver Compact dimming Driver LCAI 35W 350mA–900mA ECO C flat ECO … · 2020. 12. 15. ·...

  • www.tridonic.com 1Subject to change without notice. Information provided without guarantee.Data sheet 04/21-LC094-23

    LED Driver

    Compact dimming

    Product description

    • Dimmable built-in LED Driver for LED

    • Constant current LED Driver

    • Dimming range 1 ... 100 %

    • Output current adjustable between 350 – 900 mA

    • Max. output power 35 W

    • Nominal lifetime up to 100,000 h

    • 5 years guarantee (conditions at www.tridonic.com)

    Housing properties

    • Compact low-profile dimensions

    • Casing: polycarbonate, white

    • Type of protection IP20

    Interfaces

    • DALI DEVICE Type 6

    • DSI

    • switchDIM (with memory function)

    • corridorFUNCTION

    Functions

    • Adjustable output current in 1-mA-steps (I-SELECT resistor or

    DALI)

    • Power-up fading at AC

    • Intelligent Temperature Guard (overtemperature protection)

    • Short-circuit proof

    • Overload protection

    • Constant Light Output function

    • Intelligent Voltage Guard (overvoltage and undervoltage

    monitoring)

    • Suitable for emergency escape lighting systems acc. to EN50172

    ÈStandards, page 5

    Driver LCAI 35W 350mA–900mA ECO C flat

    ECO series

    15

    100

    140

    50130

    9050

    5

    5 4.2

    tc

    Ordering data

    TypeArticle number

    Packaging carton

    Packaging pallet

    Weight per pc.

    LCAI 35W 350mA-900mA ECO C flat 28000336 20 pc(s). 1,000 pc(s). 0.170 kg

  • www.tridonic.com 2Subject to change without notice. Information provided without guarantee.Data sheet 04/21-LC094-23

    LED Driver

    Compact dimming

    Technical dataRated supply voltage 220 – 240 V

    AC voltage range 198 – 264 V

    DC voltage range 170 – 280 V

    Mains frequency 0 / 50 / 60 Hz

    Overvoltage protection 320 V AC, 48 h

    Typ. current (at 230 V, 50 Hz, full load)1 2 153 – 185 mA

    Typ. current (220 V, 0 Hz, full load, 15 % dimming

    level)232 – 35 mA

    Leakage current (PE) < 0.22 mA

    Max. input power 42.5 W

    Typ. efficiency (at 230 V / 50 Hz / full load)2 86 – 89 %

    λ (at 230 V, 50 Hz, full load)1 ≥ 0.98

    Typ. power input on stand-by3 75 – 100 mW

    THD (at 230 V, 50 Hz, full load) < 4.4 %

    Starting time (at 230 V, 50 Hz, full load, acc. to DALI) < 0.6 s

    Starting time (DC mode ) < 0.2 s

    Switchover time (AC/DC)8 < 0.2 s

    Turn off time (at 230 V, 50 Hz, full load) < 20 ms

    Hold on time (at 230 V, 50 Hz, full load)4 < 14 ms

    Output current tolerance1 7 ± 5 %

    Output LF current ripple (< 120 Hz) < 2 %

    Max. peak output current ≤ output current + 20 %

    PWM frequency5 500 Hz

    Dimming range 1 – 100 %

    Output PstLM (at full load) ≤ 1

    Output SVM (at full load) ≤ 0.4

    Max. output voltage 120 V

    Burst / surge peaks output side against PE 1.2 kV

    Type of protection IP20

    Lifetime up to 100,000 h

    Guarantee (conditions at www.tridonic.com) 5 years

    Dimensions L x W x H 140 x 100 x 15 mm

  • www.tridonic.com 3Subject to change without notice. Information provided without guarantee.Data sheet 04/21-LC094-23

    LED Driver

    Compact dimming

    Specific technical dataType Output cur-

    rent7Min. forward

    voltageMax. forward

    voltage6Max. output

    power6Typ. power consumption

    (at 230 V, 50 Hz, full load)

    Typ. current consumption (at 230 V, 50 Hz, full

    load)

    Max. casing temperature tc

    Ambient temperature ta max.

    I-SELECT resistor value

    LCAI 35W 350mA-900mA ECO C flat

    350 mA 40 V 90 V 31.5 W 34.7 W 153 mA 80 °C -25 ... +60 °C open

    375 mA 40 V 90 V 33.8 W 37.4 W 165 mA 80 °C -25 ... +60 °C 71.50 kΩ

    400 mA 39 V 88 V 35.2 W 39.5 W 174 mA 80 °C -25 ... +60 °C 66.50 kΩ

    425 mA 37 V 83 V 35.3 W 40.0 W 176 mA 80 °C -25 ... +60 °C 61.90 kΩ

    450 mA 35 V 79 V 35.6 W 40.4 W 177 mA 80 °C -25 ... +60 °C 57.60 kΩ

    475 mA 33 V 75 V 35.6 W 40.4 W 178 mA 80 °C -25 ... +60 °C 53.60 kΩ

    500 mA 31 V 71 V 35.5 W 40.5 W 178 mA 80 °C -25 ... +60 °C 49.90 kΩ

    525 mA 30 V 68 V 35.7 W 40.6 W 178 mA 85 °C -25 ... +60 °C 45.30 kΩ

    550 mA 28 V 65 V 35.8 W 40.8 W 179 mA 85 °C -25 ... +60 °C 42.20 kΩ

    575 mA 27 V 62 V 35.7 W 40.8 W 179 mA 85 °C -25 ... +60 °C 38.30 kΩ

    600 mA 26 V 59 V 35.4 W 40.6 W 178 mA 85 °C -25 ... +60 °C 35.70 kΩ

    625 mA 25 V 57 V 35.6 W 40.9 W 180 mA 85 °C -25 ... +60 °C 32.40 kΩ

    650 mA 24 V 55 V 35.8 W 41.0 W 180 mA 85 °C -25 ... +60 °C 28.70 kΩ

    675 mA 23 V 53 V 35.8 W 41.2 W 181 mA 90 °C -25 ... +55 °C 26.10 kΩ

    700 mA 22 V 51 V 35.7 W 41.4 W 182 mA 90 °C -25 ... +55 °C 22.00 kΩ

    725 mA 21 V 49 V 35.5 W 41.1 W 181 mA 90 °C -25 ... +55 °C 17.40 kΩ

    750 mA 21 V 47 V 35.3 W 40.9 W 180 mA 90 °C -25 ... +55 °C 15.00 kΩ

    775 mA 20 V 46 V 35.7 W 41.5 W 182 mA 90 °C -25 ... +55 °C 12.40 kΩ

    800 mA 19 V 44 V 35.2 W 41.3 W 181 mA 90 °C -25 ... +55 °C 10.00 kΩ

    825 mA 19 V 43 V 35.5 W 41.5 W 182 mA 90 °C -25 ... +55 °C 7.68 kΩ

    850 mA 18 V 42 V 35.7 W 41.8 W 184 mA 90 °C -25 ... +55 °C 5.36 kΩ

    875 mA 17 V 41 V 35.9 W 42.1 W 185 mA 90 °C -25 ... +55 °C 3.16 kΩ

    900 mA 17 V 39 V 35.1 W 41.3 W 182 mA 90 °C -25 ... +55 °C short circuit (0 Ω)

    1 Valid at 100 % dimming level.

    2 Depending on the selected output current.

    3 Depending on the DALI traffic at the interface.

    4 At power failure.

    5 ± 20 %.

    6 At full load.

    7 Output current is mean value.

    8 Valid for immediate change of power supply type otherwise the starting time is valid.

  • www.tridonic.com 4Subject to change without notice. Information provided without guarantee.Data sheet 04/21-LC094-23

    LED Driver

    Compact dimming

    Product description

    • Ready-for-use resistor to set output current value

    • Compatible with LED Driver series TOP and ECO

    • Resistor is base insulated

    • Resistor power 0.25 W

    • Resistor value tolerance ± 1 %

    I-SELECT PLUG TOP / ECO

    ACC

    ES-

    SOR

    IES

    3,5

    xxxx

    5,5 3,5

    613

    ,5

    9

    Ordering data

    TypeArticle number

    Colour MarkingResistor value

    Packaging bag

    Weight per pc.

    I-SELECT PLUG 400mA GN 28000451 Green 0400 66.50 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 450mA GN 28000452 Green 0450 57.60 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 500mA GN 28000277 Green 0500 49.90 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 550mA GN 28000453 Green 0550 42.20 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 600mA GN 28000454 Green 0600 35.70 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 650mA GN 28000455 Green 0650 28.70 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 700mA GN 28000278 Green 0700 22.00 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 750mA GN 28000456 Green 0750 15.00 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 800mA GN 28000457 Green 0800 10.00 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG 850mA GN 28000458 Green 0850 5.36 kΩ 10 pc(s). 0.001 kg

    I-SELECT PLUG MAX GR 28000274 Grey MAX 0 Ω 10 pc(s). 0.001 kg

  • www.tridonic.com 5Subject to change without notice.Data sheet 04/21-LC094-23

    LED-Treiber

    Kompakt Dimming

    StandardsEN 55015EN 61000-3-2EN 61000-3-3EN 61347-1 EN 61347-2-13 EN 62384EN 61547EN 62386-101 (according to DALI standard V1)EN 62386-102EN 62386-207According to EN 50172 for use in central battery systemsAccording to EN 60598-2-22 suitable for emergency lighting installations

    Maximum loading of automatic circuit breakers in relation to inrush current

    Automatic circuit breaker type C10 C13 C16 C20 B10 B13 B16 B20 Inrush current

    Installation Ø 1.5 mm2 1.5 mm2 2.5 mm2 4 mm2 1.5 mm2 1.5 mm2 2.5 mm2 4 mm2 Imax

    time

    LCAI 35W 350mA-900mA ECO C flat 32 50 56 66 16 25 28 33 3.4 A 358 μs

    Harmonic distortion in the mains supply (at 230 V / 50 Hz and full load) in %

    THD 3. 5. 7. 9. 11.

    LCAI 35W 350mA-900mA ECO C flat < 4.4 4.4 < 1 < 1 < 1 < 1

    Conditions of use and storage

    Humidity: 5 % up to max. 85 %, not condensed (max. 56 days/year at 85 %)

    Storage temperature: -40 °C up to max. +80 °C

    The devices have to be within the specified temperature range (ta) before they can be operated.

    Overload protectionIf the maximum load is exceeded by a defined internal limit, the LED Driver turns off the LED output. After restart of the LED Driver the output will be activated again. The restart can either be done via mains reset or via interface (DALI, DSI, switchDIM).

    Overtemperature protectionThe LED Driver is protected against temporary thermal overheating. If the temperature limit is exceeded the output current of the LED module(s) is reduced. The temperature protection is activated above tc max. The activation temperature differs depending on the LED load. On DC operation this function is deactivated to fulfill emergency requirements.

    Short-circuit behaviourIn case of a short circuit at the LED output the LED output is switched off. After restart of the LED Driver the output will be activated again. The restart can either be done via mains reset or via interface (DALI, DSI, switchDIM).

    No-load operationThe LED Driver will not be damaged in the no-load operation. The output will be deactivated and therefore free of voltage. If a LED load is connected the device has to be restarted before the output will be activated again.

    Glow wire testaccording to EN 61347-1 with increased temperature of 850 °C passed.

    Expected lifetimeType Output current ta 40 °C 45 °C 50 °C 55 °C 60 °C

    LCAI 35W 350mA-900mA ECO C flat

    350 mAtc 65 °C 70 °C 75 °C 80 °C 80 °C

    Lifetime > 100,000 h > 100,000 h > 100,000 h > 100,000 h 80,000 h

    ≤ 650 mAtc 65 °C 70 °C 75 °C 80 °C 85 °C

    Lifetime > 100,000 h > 100,000 h > 100,000 h 95,000 h 70,000 h

    ≤ 900 mAtc 75 °C 80 °C 85 °C 90 °C 90 °C

    Lifetime > 100,000 h > 100,000 h 80,000 h 55,000 h –

    Hot plug-inHot plug-in is not recommend within 5 s after shutdown due to output voltage of > 0 V. If a LED load is connected the device has to be restarted before the output will be activated again. This can be done with mains reset, DALI, DSI or switchDIM.

    The LED Driver is designed for a lifetime stated above under reference conditions and with a failure probability of less than 10 %.

    Housing fulfils requirements for reinforced insulation according EN 60598-1.

    This are max. values calculated out of inrush current! Please consider not to exceed the maximum rated continuous current of the circuit breaker. Calculation uses typical values from ABB series S200 as a reference.Actual values may differ due to used circuit breaker types and installation environment.

  • www.tridonic.com 6Subject to change without notice.Data sheet 04/21-LC094-23

    LED-Treiber

    Kompakt Dimming

    Control input (DA/N, DA/L)Digital DALI signal or switchDIM can be wired on the same terminals (DA/N and DA/L).

    Digital signal DALI/DSIThe control input is non-polar for digital control signals (DALI, DSI). The control signal is not SELV. Control cable has to be installed in accordance to the requirements of low voltage installations. Different functions depending on each module.

    switchDIMIntegrated switchDIM function allows a direct connection of a push to make switch for dimming and switching.Brief push (< 0.6 s) switches LED Driver ON and OFF. The LED Drivers switch-ON at light level set at switch-OFF.When the push to make switch is held, LED modules are dimmed. After repush the LED modules are dimmed in the opposite direction.In installations with LED Drivers with different dimming levels or opposite dimming directions (e.g. after a system extension), all LED Drivers can be synchronized to 50 % dimming level by a 10 s push.Use of push to make switch with indicator lamp is not permitted.

    corridorFUNCTIONThe corridorFUNCTION can be programmed in two different ways.To program the corridorFUNCTION by means of software a DALI-USB interface is needed in combination with a DALI PS. The software can be the masterCONFIGURATOR.To activate the corridorFUNCTION without using software a voltage of 230 V simply has to be applied for five minutes at the switchDIM connection. The unit will then switch automatically to the corridorFUNCTION.

    Note:If the corridorFUNCTION is wrongly activated in a switchDIM system (for example a switch is used instead of pushbutton), there is the option of installing a pushbutton and deactivating the corridorFUNCTION mode by five short pushes of the button within three seconds.

    switchDIM and corridorFUNCTION are very simple tools for controlling ballasts with conventional momentary-action switches or motion sensors.To ensure correct operation a sinusoidal mains voltage with a frequency of 50 Hz or 60 Hz is required at the control input.Special attention must be paid to achieving clear zero crossings. Serious mains faults may impair the operation of switchDIM and corridorFUNCTION.

    225

    255

    DALI200

    175

    150

    125

    100

    75

    50

    25

    0

    1009080706050403020100

    Dimming characteristics

    Digital dimming value

    Relative lighting level %

    DSI

    Dimming characteristics as seen by the human eye

    DimmingDimming range 1 % to 100 %Digital control with:• DSI signal: 8 bit Manchester Code

    Speed 1 % to 100 % in 1.4 s• DALI signal: 16 bit Manchester Code Speed 1 % to 100 % in 0.2 s Programmable parameter:

    Minimum dimming level Maximum dimming level

    Default minimum = 1 % Programmable range 1 % ≤ MIN ≤ 100 % Default maximum = 100 % Programmable range 100 % ≥ MAX ≥ 1 %

    Dimming curve is adapted to the eye sensitiveness.Dimming is realized by a combination of analog amplitude dimming and PWM dimming.35 ... 100 %: amplitude dimming1 ... 34 %: PWM dimming

    Function: adjustable current (I-SELECT)The output current of the LED Driver can be selected between 350 and 900 mA via DALI.

    Adjustment can be done by masterCONFIGURATOR (see masterCONFIGURATOR documentation).

    Constant light output (CLO)The luminous flux of an LED decreases constantly over the lifetime. The CLO function ensures that the emitted luminous flux remains stable. For that pur-pose the LED current will increas continously over the LED lifetime. In masterCONFIGURATOR it is possible to select a start value (in percent) and an expected lifetime. The LED Driver adjusts the current afterwards automatically.

    DC emergency operationThe LED Driver is designed for operation on DC voltage and pulsed DC voltage.

    Light output level in DC operation: programmable 1 – 100 % (EOFi = 0.13).Programming by extended DSI or DALI signal (16 bit).Default value is 15 %In DC operation dimming mode can be activated.

    The voltage-dependent input current of Driver incl. LED module is depending on the used load.

    The voltage-dependent no-load current of Driver (without or defect LED module) is for:AC: 20.5 mADC: 5.5 mA

    Intelligent Voltage GuardIntelligent Voltage Guard is the name of the electronic monitoring of the mains voltage. It immediately shows if the mains voltage rises above certain thresholds. Measures can then be taken quickly to prevent damage to the LED Driver.

    • If the mains voltage rises above approx. 280 Vrms (voltage depends on the LED Driver type), the LED light starts flashing on and off.

    • To avoid a damage of the LED Driver the mains supply has to be switched off at this signal.

  • www.tridonic.com 7Subject to change without notice.Data sheet 04/21-LC094-23

    LED-Treiber

    Kompakt Dimming

    Power-up fadingThe power-up fading function offers the opportunity to realise a soft start.The soft start will be applied at turning on the mains and at starts by switchDIM.The function is programmed as a DALI fade time in the range from 0.7 to 16 seconds and dimms in the selected time from 0 % to the power-on level.By factory default power-up fading is not active (0 seconds).

    ProgrammingWith appropriate software and a USB interface different functions can be activated and various parameters can be configured in the LED Driver. All that is needed is a DALI-USB and the software (masterCONFIGURATOR).

    masterCONFIGURATORAt version 2.8: For programming functions (CLO, I-SET, ITM, power-up fading, corridorFUNCTION) and device settings (fade time, ePowerOnLevel, DC level, etc.). For further information see masterCONFIGURATOR manual.

    Circuit diagram

    Wiring guidelines• Run the secondary lines separately from the mains connections and lines

    to achieve good EMC performance.• The max. secondary cable length is 2 m (4 m circuit), this applies for LED output as well as for I-SELECT 2.• For good EMC performance, keep the LED wiring as short as possible.• Secondary switching is not permitted.• The LED Driver has no inverse-polarity protection on the secondary side. Wrong polarity can damage LED modules with no inverse-polarity protection.• To avoid the damage of the Driver, the wiring must be protected against short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.).

    Installation noteMax. torque at the clamping screw: 0.5 Nm / M4

    Earth connectionThe earth connection is conducted as protection earth (PE). If the LED Driver will be earthed, protection earth (PE) has to be used. There is no earth connection required for the functionality of the LED Driver.Earth connection is recommended to improve following behaviour.

    • Electromagnetic interferences (EMI)• LED glowing at stand-by• Transmission of mains transients to the LED output

    In general it is recommended to earth the LED Driver if the LED module is mounted on earthed luminaire parts respectively heat sinks and thereby representing a high capacity against earth.

    Electrical connections

    Wiring

    LED Driver / supply

    8 – 9 mm

    wire preparation:0.5 – 1.5 mm²

    Wiring type and cross sectionSolid wire with a cross section of 0.5 – 1.5 mm². Strip 8 – 9 mm of insulationfrom the cables to ensure perfect operation of terminals.

    Loosen wire through twisting and pulling or using a Ø 1 mm release tool

    Wiring type and cross sectionThe wiring can be solid or flexible cable with a cross section of 0.2 to 0.75 mm². For the push-wire connection you have to strip the insulation (6–7 mm).Loosen wire through twisting and pulling.

    6 – 7 mm

    wire preparation:0.2 – 0.75 mm²

    Release of the wiringPress down the “push button” and remove the cable from front.

    LED Driver / LED module

    Udriver LCAI 35W 350mA–900mA ECO C flat

    SEC

    PRI

    220–240 V

    LN

    0/50/60 Hz

    + LED– LED

    ��

    ��

    DALI/DSI DA/NDA/L

    ~~

    I sel 1I sel 2

    R

    Udriver LCAI 35W 350mA–900mA ECO C flat

    SEC

    PRI

    220–240 V

    LN

    0/50/60 Hz

    DA/NDA/L

    + LED– LED ��

    switchDIM220–240 V50/60 Hz

    NL

    ~~

    ��

    I sel 1I sel 2

    R

  • www.tridonic.com 8Subject to change without notice.Data sheet 04/21-LC094-23

    LED-Treiber

    Kompakt Dimming

    THD vs load

    0

    5

    10

    45 75 80 85 90 9565 7050 55 60 100

    Load [%]

    THD

    [%]

    Efficiency vs load

    50

    55

    60

    65

    70

    75

    80

    85

    45 65 70 75 80 85 90 9550 55 60 100

    90

    Load [%]

    E�ci

    ency

    [%]

    Power factor vs load

    Diagrams LCAI 35W 350mA-900mA ECO C flat

    0,900,910,920,930,940,950,960,970,980,991,00

    45 65 70 75 80 85 90 9550 55 60 100Load [%]

    Pow

    er fa

    ctor

    350 mA500 mA700 mA900 mA

    100 % load correspond to the max. output power (full load) according to the table on page 2.

    Insulation and electric strength testing of luminairesElectronic devices can be damaged by high voltage. This has to be considered during the routine testing of the luminaires in production.

    According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, each luminaire should be submitted to an insulation test with 500 V DC for 1 second. This test voltage should be connected between the interconnected phase and neutral terminals and the earth terminal. The insulation resistance must be at least 2 MΩ.

    As an alternative, IEC 60598-1 Annex Q describes a test of the electrical strength with 1500 V AC (or 1.414 x 1500 V DC). To avoid damage to the electronic devices this test must not be conducted.

    Additional information

    Additional technical information at www.tridonic.com → Technical Data

    Lifetime declarations are informative and represent no warranty claim.No warranty if device was opened.

    Maximum number of switching cycles

    All LED Driver are tested with 50,000 switching cycles.The actually achieved number of switching cycles is significantly higher.

    Conditions of use

    The LED Driver is declared as inbuilt LED controlgear, meaning it is intended to be used within a luminaire enclosure.If the product is used outside a luminaire, the installation must provide suitable protection for people and environment (e.g. in illuminated ceilings).

    Disposal of equipment

    Return old devices in accordance with the WEEE directive to suitable recycling facilities.