LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number:...

15
R Job Name: Job Number: Model Numbers: Page SPECIFICATION SUBMITTAL lcp230240-1 01.22.07 Power Equipment LCP128 Dimming & Switching Systems System Overview LCP128 is a combination dimming and switching system that provides a complete lighting control solution. The system consists of panels and control station devices. An integrated astronomical time clock provides system automation capability. System Features • 32 global lighting scenes and off. • Connect up to 8 power panels for up to 128 dimmed/switched outputs. • Connect up to 32 wallstations or control devices for multiple points of control. • Entire system is programmed using the LCD controller mounted in the panel. • Astronomical time clock provides automated selection of lighting scenes. • Works directly with incandescent, magnetic low voltage, reverse-phase electronic low voltage, neon, Lutron Tu-WireTM and switched load types. • Works with DSI, DALI, and 0-10 V dimming ballasts using Ten Volt Modules in the panel. • Motor modules are also available. • Panel may be surface or recess mounted. • Feed-through or branch circuit breaker panels are available. • Panel is pre-wired and pre-tested. LCP128 Dimming & Switching System LCP128 Panel

Transcript of LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number:...

Page 1: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-1 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

System Overview

LCP128 is a combination dimming and switching

system that provides a complete lighting control

solution. The system consists of panels and control

station devices. An integrated astronomical time

clock provides system automation capability.

System Features

• 32 global lighting scenes and off.

• Connect up to 8 power panels for up to 128

dimmed/switched outputs.

• Connect up to 32 wallstations or control devices for

multiple points of control.

• Entire system is programmed using the LCD

controller mounted in the panel.

• Astronomical time clock provides automated selection

of lighting scenes.

• Works directly with incandescent, magnetic low

voltage, reverse-phase electronic low voltage, neon,

Lutron Tu-WireTM and switched load types.

• Works with DSI, DALI, and 0-10 V dimming ballasts

using Ten Volt Modules in the panel.

• Motor modules are also available.

• Panel may be surface or recess mounted.

• Feed-through or branch circuit breaker panels are

available.

• Panel is pre-wired and pre-tested.

LCP128 Dimming & Switching System

LCP128 Panel

Page 2: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-2 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Overview

Lighting control may be automated by using the

astronomical time clock integrated into the LCP128

controller. The controller has an LCD screen for easy

programming.

Features

• Controller LCD screens may be displayed in English,

Spanish, German, French, Portuguese, Dutch, and

Italian.

• LCD interface simplifies scene, time clock event, and

control station programming.

• Time clock events automatically recall presets at a

specific time of day or at an offset from sunrise or

sunset.

• Up to 500 total events are programmable within 7

daily schedules and 40 holiday schedules.

• Holiday schedules are programmable to run once or

repeat up to ninety days in a row.

• Two integrated Contact Closure Inputs provide an

interface with occupancy sensors or Building

Management Systems.

• Select system location from a built-in city database or

by entering latitude and longitude.

• Time clock is battery backed; time and event settings

are remembered even after power failures.

LCP128 Controller

LCP128 Controller

LCP128

Page 3: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-3 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Standards

• CE

Power

• Input power: 230 V (CE),

220-240 V (non-CE). All voltages

50/60 Hz, phase-to-neutral.

• Branch Circuit Breakers (if

applicable): IEC-rated thermal

magnetic.

AIC rating:

230 V (CE) — 6,000 A

220-240 V (non-CE) — 6,000 A

• Lightning strike protection: meets

ANSI/IEEE standard 62.41-1980.

Can withstand surges of up to

6000 V and up to 3000 A.

• 10-year power failure memory:

automatically restores lighting to

scene selected prior to power

interruption.

• RTISSTM filter circuit technology

compensates for incoming line

voltage variations: no visible flicker

with +/-2% change in RMS

voltage/cycle and +/-2% Hz

change in frequency/second.

• SoftswitchTM arcless relay

technology featured in every 16 A

switched circuit.

Dimming Modules

4-Output Dimming Modules:

• Each Dimming Module can

control a fully loaded electrical

circuit (16 A max.), with four

dimming outputs per Module.

Switching Modules

• 4 Switched circuits (relays) per

Module.

• Softswitch relay is rated for 16 A

continuous use.

• Patented Softswitch circuit

eliminates arcing at mechanical

contacts when loads are

switched. Extends relay life to an

average of 1,000,000 cycles

(on/off) for resistive, capacitive or

inductive sources.

• Relay is mechanically held.

Specifications

Lighting Sources/Load Types

• Incandescent (Tungsten)/Halogen

• Magnetic Low Voltage Transformer

• Lutron Tu-WireTM

• Neon

• HID (full-conduction non-dim basis

only)

• Switched

• DSI, DALI, and 0-10V dimming

ballasts using Ten Volt Modules in

the panel.

• Motor

• Electronic Low Voltage

Transformer

Physical Design

• Enclosure: NEMA-Type 1, IP-20

protection; #16 U.S. Gauge Steel.

Indoors only.

• Weight: 80 lb. (37 kg).

Mounting

Surface mount or recess mount

between 16 in. (40 cm) studs.

Environment

32-104 °F (0-40 °C). Relative

humidity less than 90%

non-condensing.

Wiring

• Internal: prewired by Lutron.

• System communications: Low-

voltage Class 2 (PELV) wiring

connects dimming panels to

wallstations.

• Line (mains) voltage: Feed and

load wiring only. No other wiring or

assembly required.

Page 4: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-4 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

LCP128 Controller

• Configures entire LCP128 System.

• Two low-voltage (15-24 VDC)

contact closure inputs, momentary

or maintained, pull-up or pull-down.

• Emergency sensing.

• Astronomical Time Clock.

• Digital Control Link.

• Mounted inside LCP128 panel.

Astronomical Time Clock

• Capable of up to 500 events.

• 7 daily schedules and 40 holiday

schedules are available.

• 25 events per day.

• Holiday events are programmable

one year in advance.

• Holiday schedules are

programmable to run for up to 90

days.

• ATC location programmable by

built-in city database or by entering

latitude and longitude, plus a

sunrise or sunset offset to adjust

for local geography.

Specifications (continued)

Control Station Devices

• One to seven button seeTouchTM

wallstations.

• EOMX wallstations.

• Buttons are programmable to

select scenes or patterns, toggle

circuits, or activate delay-to-off.

• Buttons are programmed at the

LCP128 controller.

• Key Switch control is also

available.

• Controls are powered by and

communicate via the LCP128

low-voltage communication link.

• OMX-CCO-8 integrates third

party motorized window

treatments or A/V equipment.

• OMX-AV interfaces with occupant

or photo sensors.

• OMX-RS232 interfaces the

LCP128 system to a PC,

touchscreen, or building

management system.

• See specific product specification

sheets for further details.

Page 5: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-5 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Off

seeTouch Wallstation

(SO-4SN-WH-EGN)

Description

• Each seeTouch Wallstation features engraved, backlit

buttons allowing quick and easy recall of lighting

presets, even in low light conditions.

• Button functionality is fully programmable.

Specifications

• Low-voltage type Class 2 (PELV)

Operating voltage: 24 V.

• Meets IEC 801-2. Tested to withstand 15 kV

electrostatic discharge without damage or memory

loss.

• Faceplate snaps on with no visible means of

attachment.

• Terminals accept up to two #18 AWG (1.0 mm2)

wires typical.

• Environment: 32-104 °F (0-40 °C). Relative humidity

less than 90% non-condensing.

seeTouch Models

• Models available with one to seven buttons, with or

without raise/lower.

• Use SO series model numbers.

• Available with all standard colors and engraving.

Button Programming

• Each button may be programmed for scene

selection, toggle, delay-to-off, raise, or lower

functionality.

• Button programming can be used to provide

specialized manual control of multiple areas.

Button Engraving

Custom engraving is available using button/wallplate

replacement kits.

To order, contact Lutron Customer Service at

1-888-LUTRON1 (1-888-588-7661).

Typical wallbox dimensions: 3.74” (95 mm) high,

2.17 in. (55 mm) wide, 2.75 in. (70 mm) deep.

seeTouchTM Wallstations

Page 6: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-6 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Module Types and

Quantity in Panel

Example:

2U3E = Two 4U modules

and Three 4E modules

Prefix

C C P - _ X _ U _ E _ A _ M _ T- 2 3 0 4 I S - C E - L C P

Module Types

XP = Four-Circuit Switching (Relay) Module

4U = Four-Output Dimming Module

4E = Four-Output Electronic Low Voltage Dimming Module

4A = Four-Output Adaptive Dimming Module

4M = Four-Output Motor Module

TVM = 0-10 V Ballast Control Module

Voltage:

230 for 230 V (CE)

240 for 220-240 V (non-CE)

Feed:

FT = Feed-Through Panel (circuit breakers not included)

4IS = 3 Phase 4 Wire Feed with Isolation Switch

Suffix:

CE for 230 V (CE)

AU for 220-240 V (non-CE)

How to Build a LCP128 Panel Model Number

Voltage

Suffix

Feed

4U 4E 4MXP TVM

Note: The following information is given for general use only. Consult Lutron for available module

combinations and assistance with specifying appropriate model numbers.

4A

Page 7: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-7 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Number

of

Modules

Feed

Type

Feed

Size (A)

LCP128 Combo Panels with Branch Circuit Breakers, No XP Switching Modules(Standard panels only)

2

3

4

5

6

7

8

1Ø, 2 W

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

16 A

16 A

125 A

125 A

125 A

125 A

125 A

Model Numbers – 230 V (CE), 220-240 V (non-CE)

Number

of

Modules

Feed

Type

Feed

Size (A)

LCP128 Combo Panels with Branch Circuit Breakers, With XP Switching Modules(Standard panels only)

2

3

4

5

6

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

3Ø, 4 W

125 A

125 A

125 A

125 A

125 A

Mini

Mini

Standard

Standard

Standard

Standard

Standard

Panel Size

Standard

Standard

Standard

Standard

Standard

Panel Size

Number

of

Modules

Feed

Type

Feed

Size (A)

Feed-Through LCP128 Combo Panels(Without branch circuit breakers)

2

3

4

5

6

7

8

1Ø, 2 W

1Ø, 2 W

1Ø, 2 W

1Ø, 2 W

1Ø, 2 W

1Ø, 2 W

1Ø, 2 W

16 A

16 A

16 A

16 A

16 A

16 A

16 A

Mini

Mini

Standard

Standard

Standard

Standard

Standard

Panel Size

Page 8: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-8 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

2.21(56)

1.34(34)

2.21(56)

4.09(104)

15.13(384)

14.38 (365)

0.15(4)

54.15(105)

24.00(610)

10.75(273)

21.50(546)

8.00(203)

15.875(403)

24.50(622)

Mini Panel Dimensions

Top View

Left Side View Right Side View

Bottom View

All dimensions in inches (mm).

Front View

Cover

Page 9: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-9 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

4.15 (105)

41.75 (1060)

2.69 (68)

2.43 (62)

15.875

(403)

8.00

(203)

14.375

(365)

59.50 (1511)

2.43 (62)11.00

(279)

15.125

(394)

59.00

(1498)

4.21

(107)

0.150

(4)

Standard-Size Panel Dimensions

Top View

Left Side View Right Side View

Bottom ViewAll dimensions in inches (mm).

Front View

Cover

Page 10: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-10 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

• Surface or recess mount indoors.

• Panel generates heat – mount only where ambient

temperature is 32-104 °F (0-40 °C).

• This equipment is air-cooled. Do not block vents or

the warranty will be void. Leave 12 in. (31cm)

clearances in front of panel.

• Reinforce wall structure for weight and local codes.

• Mount panels where audible noise is acceptable.

(Panels hum slightly and internal relays click).

• Mount panels so line (mains) voltage wiring (including

load wiring) is at least 6 ft. (1.8 m) from sound or

electronic equipment and wiring.

• Mount panel within 7° of true vertical.

Surface Mounting

• Surface mounting keyholes accept 1/4 in. (6 mm)

max. mounting bolts. This size is recommended.

Recess Mounting

• Mount panel flush to 1/8 in. (3 mm) below finished

wall surface.

• Front cover overlaps wall 3/4 in. (18 mm) on each

side.

12

45

67

3

89

12

45

67

3

89

Feed and Load Wiring

Feed

and

Load

Wiring

Class 2

(PELV)

Wiring

Isolation Switch

Do not block

vents! Leave

12 in. (31 cm)

minimum

clearance

Front View Side View Front View Side View

Terminal

Blocks

for Load

Wiring

2 170 35 lbs (16 kg)

3 250 37 lbs (17 kg)

4 330 55 lbs (25 kg)

5 410 57 lbs (26 kg)

6 490 59 lbs (27 kg)

7 570 61 lbs (28 kg)

8 650 63 lbs (29 kg)

Dimming

Modules

Maximum

BTUs/hour

Weight without

packaging

Panel Power Dissipation and Weight

Class 2

(PELV)

Wiring

Isolation Switch

Do not block

vents! Leave

12 in. (31 cm)

minimum

clearance

Terminal

Blocks

for Load

Wiring

Panel Mounting

Feed

and

Load

Wiring

Feed and Load Wiring

Page 11: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-11 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Wiring Details – Isolation Switch with Breakers Panel230 V (CE), 220-240 V (non-CE)

Dimming Module

LCP128

Controller

Class 2 (PELV)

wire entry

NNeeuuttrraallPower (Hot/Live)

Feed Wiring

Switching Module1

Wire Sizes for Power Feed,Panels without XP Switching Modules

• Power Feed:#14 AWG (2.0mm2) to #2 AWG (35mm2)

• Neutral Feed:#14 AWG (2.0mm2) to #2 AWG (35mm2)

Wire Sizes for Power Feed,Panels with XP Switching Modules

• Power (Hot/Live):#14 AWG (2.0mm2) to #2 AWG (35mm2)

• Neutral:#14 AWG (2.0mm2) to #2 AWG (35mm2)

Wire Sizes for Load Wiring,All Models

• Dimmed/Switched Hot (Live):#14 AWG (2.0mm2) to #10 AWG (4.0mm2)

• Load Neutral:#14 AWG (2.0mm2) to #10 AWG (4.0mm2)

Terminal Blocks

for Load Wiring.

See Load Wiring

to Terminal Blocks

page for details

Note: See Load Wiring to Terminal Blocks

page for load wiring details.

Note: Actual number and type of modules in panel may vary from example shown.

1Switching modules shown for identification purposes only. Breaker panels with switching modules

require 4 breakers per module (not shown). Limitations on number of modules in panel may also apply.

Page 12: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-12 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

N

N

N

L L

N N

DL

DLL

G G

Wiring Details – Feed-Through Panel – 230 V (CE), 220-240 V (non-CE)

Feed

Breaker

230 VAC,

13A Feed

Control FeedAn additional feed (230V on a dedicated

breaker) is required for feed-through panels

to power the low voltage control transformer.

Load

Hot/Live

Neutral

Dimmed Hot

#14 AWG (2.0 mm2) to

#10 AWG (4.0 mm2)

#14 AWG (2.0 mm2) to

#10 AWG (4.0 mm2)

Neutral

Wire Sizes for Power Feed,To Each Circuit

• Power Feed:#14 AWG (2.0mm2) to #10 AWG (4.0mm2)

• Neutral Feed:#14 AWG (2.0mm2) to #10 AWG (4.0mm2)

Wire Sizes for Load Wiring,From Each Output

• Dimmed/Switched Hot (Live):#14 AWG (2.0mm2) to #10 AWG (4.0mm2)

• Load Neutral:#14 AWG (2.0mm2) to #10 AWG (4.0mm2)

Note: See Load Wiring to Terminal Blocks

page for load wiring details.

Typical Dimming/Switching Leg

Dimming Module

LCP128

Controller

Class 2 (PELV)

wire entry

Switching Module

Note: Actual number and type of modules in panel may vary from example shown.

Breaker

Ground

Page 13: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-13 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

N

N

N

DL

DL

L

DL

DL

N

N

N

L

SL

L

SL

L

SL

L

SL

L

N

R

L

L1

L

R

L

R

L

R

N

N

N

N

Load Wiring to Terminal Blocks – 230 V (CE), 220-240 V (non-CE)

Note: Do not remove bypass jumpers until after

load wiring has been verified.

Typical Dimming/Switching Leg Shown

Neutral

Load

Switched Live

Dimmed Live

Neutral

Load

Raise

Lower

Neutral

4-Output Dimming Module (4U)4-Output ELV Dimming Module (4E)

4-Output Switching Module (XP)

4-Output Motor Module (4M) 0-10 V Ballast Control Module (TVM)

+ 1 –

+ 2 –DLDLDLDLL

NNNNN

L

N

+

TVM

Ballast

Bypass Jumper

Bypass Jumper

Page 14: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-14 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Class 2 (PELV) Wiring

The LCP128 system communicates to control stations using a Class 2 (PELV) low voltage link. Control

stations include wallstations, contact closure input and output devices, and RS232 interfaces.

Wire the Class 2 (PELV) link according to the following guidelines:

• Link must be daisy chained.

• Must run in separate trough from line (mains) voltage.

• Link must be less than 2000 ft. (600 m) long.

• Make wire connections inside the wallbox and LCP128 panel.

• Install Link Terminators (LT-1) at the start and end of the Class 2 (PELV) daisy-chained link.

• The order of controls on the control link is not important.

• Use Lutron GRX-CBL-46L cable or equivalent.

Maximum total length of the control link is 2,000 ft.

This distance is based on proper shielding of the

twisted/shielded pair, proper wire size, and the use of

link terminators (LT-1) at each end of the link. If

unapproved cable or smaller wire is used, control link

length must be de-rated according to the following

chart:

LT-1 LT-1

2000 ft. (600 m) maximum

Terminal 1 & 2

Wire Sizes

#12 AWG#14 AWG#16 AWG#18 AWG

2.5 mm2

1.0 mm2

Max. Control

Link Length

2000 ft. (600 m)1400 ft. (425 m)900 ft. (275 m)600 ft. (180 m)

450 m (1500 ft.)

200 m (650 ft.)

Note: Link Terminators (LT-1) are

required at the start and end of the

LCP128 Class 2/PELV Link.

Notice! If Link Terminators (LT-1) are not

used or improper wiring topology is

employed, the system will not

communicate properly.

LCP128 Panels

Control Stations:

Wallstations, contact closure input,

contact closure output, and RS232

devices

Page 15: LCP128 Dimming & Switching System - Lutron Electronics · 2018-04-05 · R Job Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page lcp230240-6 01.22.07 Dimming & Switching

R

Job Name:

Job Number:

Model Numbers:

PageSPECIF ICATION SUBMITTAL

lcp230240-15 01.22.07

Power EquipmentLCP128Dimming & Switching Systems

Wiring Notes:

• Use a wire connector to attach

one #18 AWG wire for Common

(terminal 1) and one #18 AWG

wire for 24 V (terminal 2) from

the Class 2 (PELV) link to the

control. Two #12 AWG wires

cannot both be terminated on

the control station. Maximum

wire length from link to control is

8 ft. (2.5 m).

• Only connect the Drain/Shield

wire (bare copper) to terminal ‘D’

in LCP128 panels. Maintain the

shield throughout the link but do

not allow it to touch ground

(earth) or wallstation circuitry.

1

2

3,4,D

1 2 3 4 D 5

CC

I1C

OM

CC

I2C

OM

1 2 3 4 D 5

1

2

3,4,D

5

CC

I1C

OM

CC

I2C

OM

To LCP128

control stations

Control Power:

(2) #12 AWG (2.5 mm2)

1: Common

2: 24 V

Control Data:

(1) twisted shielded pair

#22 AWG (.625 mm2)

3: MUX

4: MUX

D: Drain/Shield

To additional

LCP128 panels

Emergency Sense

(1) #18 AWG (1.0 mm2)

5: Sense Line

4321

1 2 3 4 D 5

LCP128 Controller LCP128 Controller

Control station

terminal

Drain wire

Class 2 (PELV) WiringPanel to Panel and Panel to Control Stations