LCD Multifunction Power Analyzer with Data Logger

6
Shenzhen Huayansheng Electron Co.,Ltd Description MPM8000 is a powerful multifunction power meter with modular design, which can be applied for monitoring and controlling of the electrical system. MPM8000 can measure and analyze real time data, such as U, I, P, Q, S, COSΦ, F, kWh, kVAr, etc. MPM8000 has the following functions: RS-485 communication port, 2 energy pulse output (include active energy and reactive energy), Max/min data record, and SOE event record. MPM8000 can extend functions by choosing the external optional modules: harmonic analysis, 8 remote signals on/off mode, programmable 4 analog outputs (0~5V or 4~20mA optional), data storage, Profibus Com. protocol, Ethernet communication functions. The multi-tariff function allows the user to measure energy in any interval (the min. interval is 30min.), which can read the sum, sharp, peak, valley, flat energy data in 30 days, and measure 2nd to 63rd harmonics in statistics. All our instruments fulfill all important requirements and regulations concerning electromagnetic compatibility and safety isolation (IEC61000, IEC1010 standard and EN61010 standard). The devices have been developed, manufactured and tested in accordance with Quality Assurance System ISO 9001. Measured Scope Parameter setup The meter MPM8000 can be applied in single phase, 3-Ph 3Wire, 3-Ph 4Wire system. It can be applied vastly in the field of secondary measurement in high Voltage, low Voltage system, or transmission of measured data. The programmable parameters are: com. address, PT, CT, baud rte, clock, demand cycle, user password, multi-tariff rate, etc. The user can set up relay output, analog output on PC. The parameters setup on meter and PC: com. address, PT, CT, baud rate, time, demand statistics, no. of remote signal, user password, multi-tariff, IO module detection, Ethernet setup. Technical Data Input Current Input Current: 5A (Current value can be set up) Measurement scope: 0.5%~120% Overload capacity: 2 X rated continuously, 100A/1s non continuously Power consumption: 0.2VA per phase Voltage Input Input Voltage: 400VAC (L-N), 693VAC (L-L) (Voltage value can be set up) System frequency: 45~65Hz Measurement scope: 3%~120% Overload Capacity: 2 X rated continuous, 2500V/1s non continuous Power consumption: 0.5VA per phase Pulse output No. of outputs 2 channels (active/reactive energy each) Serial com. port NO. of outputs 1 RS-485 port Communication protocol Modbus-RTU protocol Baud rate 2400/4800/9600/1920 0/38400bps www.szhyes.com Email: [email protected] Tel: 86-755-33581652 Multifunction Power Meter MPM8000 www.szhyes.com

Transcript of LCD Multifunction Power Analyzer with Data Logger

Page 1: LCD Multifunction Power Analyzer with Data Logger

Shenzhen Huayansheng Electron Co.,Ltd

Description

MPM8000 is a powerful multifunction power meter withmodular design, which can be applied for monitoring andcontrolling of the electrical system. MPM8000 can measureand analyze real time data, such as U, I, P, Q, S, COSΦ, F,kWh, kVAr, etc. MPM8000 has the following functions:RS-485 communication port, 2 energy pulse output (includeactive energy and reactive energy), Max/min data record,and SOE event record. MPM8000 can extend functions bychoosing the external optional modules: harmonic analysis,8 remote signals on/off mode, programmable 4 analogoutputs (0~5V or 4~20mA optional), data storage, ProfibusCom. protocol, Ethernet communication functions. Themulti-tariff function allows the user to measure energy inany interval (the min. interval is 30min.), which can read thesum, sharp, peak, valley, flat energy data in 30 days, andmeasure 2nd to 63rd harmonics in statistics.

All our instruments fulfill all important requirementsand regulations concerning electromagnetic compatibilityand safety isolation (IEC61000, IEC1010 standard andEN61010 standard). The devices have been developed,manufactured and tested in accordance with QualityAssurance System ISO 9001.

Measured Scope

Parameter setup

The meter MPM8000 can be applied in single phase, 3-Ph3Wire, 3-Ph 4Wire system. It can be applied vastly in thefield of secondary measurement in high Voltage, lowVoltage system, or transmission of measured data.

The programmable parameters are: com. address, PT, CT,baud rte, clock, demand cycle, user password, multi-tariffrate, etc. The user can set up relay output, analog output onPC.The parameters setup on meter and PC: com. address, PT,CT, baud rate, time, demand statistics, no. of remote signal,user password, multi-tariff, IO module detection, Ethernetsetup.

Technical Data

Input CurrentInput Current: 5A (Current value can be set up)Measurement scope: 0.5%~120%Overload capacity: 2 X rated continuously, 100A/1s noncontinuouslyPower consumption: ≤0.2VA per phaseVoltage InputInput Voltage: 400VAC (L-N), 693VAC (L-L) (Voltagevalue can be set up)System frequency: 45~65HzMeasurement scope: 3%~120%Overload Capacity: 2 X rated continuous, 2500V/1s noncontinuousPower consumption: ≤0.5VA per phasePulse output

No. of outputs2 channels(active/reactive energyeach)

Serial com. portNO. of outputs 1 RS-485 portCommunication protocol Modbus-RTU protocol

Baud rate2400/4800/9600/19200/38400bps

www.szhyes.com Email: [email protected] Tel: 86-755-33581652

Multifunction Power Meter MPM8000

www.szhyes.com

Page 2: LCD Multifunction Power Analyzer with Data Logger

Shenzhen Huayansheng Electron Co.,Ltd

Technical Data

Other parametersAuxiliary Power 85~265VAC/DC

Display moduleLCD Display76mmx66mm

Storage Capacity 2GBTemp. drifting factor <100PPM/℃Withstand Voltage 2500V/1 minTotal power consumption <8VAOperation temperature -20℃~60℃Storage temperature -40℃~85℃Operation humidity 5~95% RHPollution Class Class 2

Material of HousingFlammability acc. toUL94V0

Size 96x99x78mm

Parameters Display AccuracyVoltage 0~9999.9kV Class 0.2

scope:5%~100%V

Current 0~9999.9kA

Class 0.2scope: 5%~100%AZero sequencecurrent Class 0.5

Power factor -1~+1 Class 1Frequency 45~65Hz ±0.01HzActive Power -9999~9999MW Class 0.5Reactive Power -9999~9999MVAr Class 0.5Apparent Power 0~9999MVA Class 0.5Active Demand -9999~9999MW Class 1.0Reactive Demand -9999~9999MVAr Class 1.0Active Energy 0~9999999.99Mwh Class 1.0Reactive Energy 0~9999999.99MVArh Class 2.0Phase Angle 0.0°~359.9° Class 2.0Currenttotal harmonic %

0~100% Class 2.0

Voltage totalharmonic %

0~100% Class 2.0

Technical Data

EMC and Safety Standard

IEC61000-4-2 (GB/T17626.2)IEC61000-4-8 (GB/T17626.8)IEC61000-4-4 (GB/T17626.4)IEC61010-1 (GB/T4793.1)

Terminal Chart

Terminal 1, 2, 3, 4 are Voltage In, marked as L1, L2,L3, N.Terminal 5, 6 , 7, 8, 9, 10are Current In, marked asI1*,I1, I2*, I2, I3*, I3.Terminal 11, 12, 13 as auxiliary power input, 12 as Lend, 11 as N end, 13 as ground line. It isrecommended to connect the ground line.Terminal 15, 16 are RS 485 com. 15 as A+, 16 as B-.Terminal 17, 18,19 are a pair of active and reactiveenergy pulse output, 17 as active positive end, 18 asreactive positive end, and 12 as COM negative end.Terminal 14,20, 21,22,23,24 are standby ends.

www.szhyes.com Email: [email protected] Tel: 86-755-33581652

Multifunction Power Meter MPM8000

www.szhyes.com

Page 3: LCD Multifunction Power Analyzer with Data Logger

Shenzhen Huayansheng Electron Co.,Ltd

Function Description

Mainunit

Real time measurementPhase Voltage Phase Voltage, average phase Voltage

Line Voltage Line Voltage, average line Voltage

CurrentPhase Current, average phase Current, zero sequenceCurrent

Active Power Phase active power, 3 phase active total power

Reactive Power Phase reactive power, 3 phase reactive total power

Apparent Power Phase apparent power, 3 phase apparent total power

Power 4 quadrant Power 4 quadrant

Frequency System frequency

Power Factor Phase power factor, 3 phase total power factor

Demand statistic Demand3 phase active/reactive demand power, demand apparentpower

Energy Reading Active energyImported, exported and net active energy, 1 channel activeenergy pulse output

Reactive energyImported, exported and net reactive energy, 1 channelreactive energy pulse output

Multi tariff billing Multi tariff setup

Time display Real time display Year/month/day/hour/minute/second

Data communicationRS-485communication

1 Modbus-RTU protocol

1. Exterior size: 91 mm×91 mm×72mm2. Installation size: 91 mm×91mm

During the installation, please insert the meter in the hole of the cabinet, then push and buckle up the meter with theinstallation accessories. It is strongly recommended there should be 20mm space around the surface of the meter forventilation purpose.

Hole

Supporting comp.

Buckle up position.

Installation

www.szhyes.com Email: [email protected] Tel: 86-755-33581652

Multifunction Power Meter MPM8000

www.szhyes.com

Page 4: LCD Multifunction Power Analyzer with Data Logger

Shenzhen Huayansheng Electron Co.,LtdShenzhen Huayansheng Electron Co.,LtdShenzhen Huayansheng Electron Co.,Ltd

www.szhyes.com Email: [email protected] Tel: 86-755-33581652

Page 5: LCD Multifunction Power Analyzer with Data Logger

Shenzhen Huayansheng Electron Co.,Ltd

Auxiliary module's function and usage

8 remote signals input module: This module has 8sourcefree remote signals input channels, each channel canbe setted up separately to check the outside on-off status.Detail setup can be finished through the key on the meterand upper computer. The function of upper readSOE(Sequence of events) by connecting the SOE interfacewhich record accurately the status and detail time of events.

Programmable 4 relay outputs module: This module has 4separate electric relay output channels, which can be setted upseparately to corresponding different electricity parameter’sautomatic model and manual model which can be operated byupper computer. Associated automatic alarm function can triggerevent to record the present power system status; without alarm,the 4 electric relay will normally keep open.

Programmable 4 analog outputs module: This modulehas 4 analog output, voltage or current model optional.Output adopts 4 channels same negative terminal format,each channel corresponding separately to differentelectricity parameter. Current is: (4--20) mA output, voltageis: (0--5) V output.

SD card data storage module: Adopted advanced high-capacityinternal storage SD card to store electrical measurementparameter at real time; and store the data for a given period oftime. The data can be educed and analysed by upper computer,internal storage of SD card is optional.

Harmonic analysis module: It can display each measuredinformation of the harmonic, and feedback the electricharmonic parameter, including (2~63 times) harmoniccontent; phase angle etc. measured information.

Data storage and harmonic analysis module: This modulecombined SD card data storage and harmonic analysis function,which can store electrical measurement data and harmonicmeasurement data, including analysis and display (2~63times)harmonic content; phase angle etc. measured information.

Ethernet communication module: It can connect toEthernet by RJ45, and read electrical measurement byremote access. Adopted 10M and 100M self-adaptionmodel. (Default IP address is:192.168.0.250; Local port27011)

Profibus communication module: The meter can Networkthrough Profibus communication Protocol terminal, fullycomplied with Profibus-DP Communication Protocol.

Note: A max. of 4 modules can be applied to 1 main unit, and the same type of modules can’t be selected together. C and Vcan’t be selected at the same time; B can’t be selected with M or H.

www.szhyes.com Email: [email protected] Tel: 86-755-33581652

Multifunction Power Meter MPM8000

www.szhyes.com

Page 6: LCD Multifunction Power Analyzer with Data Logger

Shenzhen Huayansheng Electron Co.,Ltd

Typical Wiring Diagram

www.szhyes.com Email: [email protected] Tel: 86-755-33581652

Multifunction Power Meter MPM8000

www.szhyes.com