LCD Electronic Thermostat CFU-D series · LCD Electronic Thermostat CFU-D series Mounting Method...

2
Installation manual 1 V1.1 02.2011 Subject to modification. 1. open the left clip with screw driver 3. Open the front cover 4. Mounting the housing LCD Electronic Thermostat CFU-D series Mounting Method Wiring Diagram 2. open the right clip with screw driver 5. Wiring 6. Close the front cover 1 2 2-wire actuator connection CFU-D422 CFU-D221 / D222 CFU-D221-SS L VO VC N I S1 S2 S3 2 3 1 L N Occupancy contact Ext. Sensor 6A fuse Actuator FAN L VO VC N S1 S2 S3 2 3 1 L N Occupancy contact Ext. Sensor 6A fuse Actuator FAN Lo Mid Hi II I III L CO N S1 S2 S3 2 3 1 L N Occupancy contact Ext. Sensor 6A fuse Actuator for cooling FAN Lo Mid Hi II I III 2 3 1 Actuator for heating CC HO HC 3-wire actuator connection

Transcript of LCD Electronic Thermostat CFU-D series · LCD Electronic Thermostat CFU-D series Mounting Method...

Page 1: LCD Electronic Thermostat CFU-D series · LCD Electronic Thermostat CFU-D series Mounting Method Wiring Diagram 2. open the right clip with screw driver 5. Wiring 6. Close the front

Installation manual

1

V1.1

02.

2011

Sub

ject

to m

odific

atio

n.

1. open the left clip with screw driver

3. Open the front cover

4. Mounting the housing

LCD Electronic Thermostat CFU-D series

Mounting Method

Wiring Diagram

2. open the right clip with screw driver

5. Wiring 6. Close the front cover

1

2

2-wire

3-wire

CFU-D422CFU-D221 / D222 CFU-D221-SS

L

VO VCN I

S1 S2 S3

2 3

1

L

N

Occupancycontact

Ext.Sensor

6A fuse

Actuator

FAN

L

VO VCN

S1 S2 S3

2 3

1

L

N

Occupancycontact

Ext.Sensor

6A fuse

ActuatorFAN

Lo Mid Hi

II I III

L

2

1

VO VCN

S1 S2 S3

L

N

Occupancycontact

Ext.Sensor

6A fuse

ActuatorFAN

Lo Mid Hi

II I III

L

L

2

1

VO VCN I

N

S1 S2 S3

Occupancycontact

Ext.Sensor

6A fuse

Actuator

FAN

L

2

1

N

S1 S2 S3

L

N

Occupancycontact

Ext.Sensor

6A fuse

Actuator forcooling

FAN

Lo Mid Hi

II I III

L

CON

S1 S2 S3

2 3

1

L

N

Occupancycontact

Ext.Sensor

6A fuse

Actuator forcooling

FAN

Lo Mid Hi

II I III

2

1

Actuator forheating

2 3

1

Actuator forheating

CC HO HC

CO CC HO HC

2-wire actuator connection

CFU-D422CFU-D221 / D222 CFU-D221-SS

L

VO VCN I

S1 S2 S3

2 3

1

L

N

Occupancycontact

Ext.Sensor

6A fuse

ActuatorFAN

L

VO VCN

S1 S2 S3

2 3

1

L

N

Occupancycontact

Ext.Sensor

6A fuse

Actuator

FAN

Lo Mid Hi

II I III

L

CON

S1 S2 S3

2 3

1

L

N

Occupancycontact

Ext.Sensor

6A fuse

Actuator forcooling

FAN

Lo Mid Hi

II I III

2 3

1

Actuator forheating

CC HO HC

3-wire actuator connection

Page 2: LCD Electronic Thermostat CFU-D series · LCD Electronic Thermostat CFU-D series Mounting Method Wiring Diagram 2. open the right clip with screw driver 5. Wiring 6. Close the front

V1.

1 0

2.20

11 S

ubje

ct to

mod

ifica

tion.

2

Basic Operation

Modes

Fan speed

On/Off , Cooling / Heating

Backlight The backlight will light up 120 seconds when any button pressed.

Valve The icon “ ” displays when valve open.

3 speed ( Low , Middle , High ) / Auto ( > > )

Memory All last saved parameters will be kept after power failure or switch off.

Occupancy contact Contacts close > economy mode ; Contact open > normal mode

Fan output is synchronised with valve output (economy mode).Display selection In parameter setting, select display ambient temperature or set point.

Temperature offset In parameter setting, adjust measured temperature to +3, +2, +1, 0, -1, -2, -3.

Low temperature protection(Defrost)

When unit is off and measured temperature < 5°C , unit start in heating mode automatically until tempaerature reached 7°C.

External sensor In parameter setting, select external sensor or built-in sensor.

Press button “ ” to switch on or off. To switch off, press and hold the button 2 seconds.Press button “ M ” to select cooling or heating mode.*CFU-D422, auto change mode for cooling and heating.

Auto speed: difference between set point and ambient temperature; 1 K - Low ; 2 K - Middle ; 3 K - High .Fan will keep running when power on (except economy mode).

LCD Segment & Dimensions [mm]

HeatingCooling

Valve outputEconomy

Defrost

Key lockSet pointAmbient temp.

Auto speed

ErrorP-setting mode

LowMid High

Parameter Setting

Key lock To lock or unlock the buttons, press & simultaneously and hold 5 seconds.When key lock is activated, buttons will no action when press it.

When the unit in “ OFF ” status, press and hold for 5 seconds to enter “ p-setting mode ”. Press to change over from dISP > OSEt > dEfr > USP > LSP > SEn* > COOL* > HEAt* . Use , button to change setting. If button is not pressed over 10 seconds, the changed setting will be saved and exit automatically.

dISP Display selection : ambient temperature “rt” / set point “SP” [ factory setting rt ]OSEt Temperature offset : -3,-2,-1, 0, 1, 2, 3 [ factory setting 0 ]dEfr Defrost - low temperature protection : On / OFF [ factory setting OFF ] USP Upper set point limit : 10 ... 35 °C [ factory setting 35°C ]LSP Lower set point limit : 5 ... 30 °C [ factory setting 5°C ]SEn Sensor selection : external “Et” / internal “Int” [ factory setting Int ]COOL Economy set point range for cooling : 25 ... 30 °C [ factory setting 28°C ]HEAt* Economy set point range for heating : 15 ... 20 °C [ factory setting 15°C ]

*available on corresponding models

CFU-D221-SS CFU-D221/CFU-D422

On / Off

Down

Up

Mode

M

Fan speed

CFU-D222

Error code E1 : Internal sensor short circuit. E2 : Internal sensor open circuit.E3 : External sensor short circuit. E4 : External sensor open circuit.

M

84

110

28

60

83.5

LCD Electronic Thermostat CFU-D series