Ladder program elements to deal with active high and/or active low input devices
This presentation is partially animated. Only use the control panel at the bottom of screen to review what you have seen. When using your mouse, make sure you click only when it is within the light blue frame that surrounds each slide.
Integrating the field devices with a programmable controller and then creating the program that operates the field devices is a critical task.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Simple Programmable Controller that has two input modules and two output modules
Note the different voltage rating for the modules. Other modules with different voltage rating are available.
Input Modules Output Modules
Motor
Starter
To FCE motor
120 volts
N.O.
Simple Programmable Controller that has two input modules and two output modules
Note the different voltage rating for the modules. Other modules with different voltage rating are available.
Input devices
Output device
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
N.O.
Input devices
If this were a Temperature Sense High alarm device would it have an active high or active low output?
The challenge is not in attaching the wires to an assigned address (terminal) at the appropriate module.
24 volts
N.O.
TSH
(active low)
The important thing is to know if the devices are wired to be active high or active low so you can pick the proper programming element for your ladder program.
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
Motor
Starter
To FCE motor
120 volts
Output device
The challenge is not in attaching the wires to an assigned address (terminal) at the appropriate module.
120 volts
What about this Start push button?
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
If this were a Temperature Sense High alarm device would it have an active high or active low output?
24 volts
N.O.
TSH
(active low)
Motor
Starter
To FCE motor
120 volts
Output device
The challenge is not in attaching the wires to an assigned address (terminal) at the appropriate module.
120 volts
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
24 volts
N.O.
TSH
(active low)
(active low)
Motor
Starter
To FCE motor
120 volts
Output device
Start P.B.
The challenge is not in attaching the wires to an assigned address (terminal) at the appropriate module.
Motor
Starter
To FCE motor
120 volts
Output device
120 volts
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
24 volts
N.O.
TSH
(active low)
(active low)
Start P.B.
Now lets attach the output device
The challenge is not in attaching the wires to an assigned address (terminal) at the appropriate module.
Motor
Starter
To FCE motor
120 volts
Output device
120 volts
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
24 volts
N.O.
TSH
(active low)
(active low)
Start P.B.
Now lets attach the output device
Ladder Program
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
Motor
Starter
To FCE motor
120 volts
Output device
120 volts
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
24 volts
N.O.
TSH
(active low)
(active low)
Start P.B.
Rule of Thumb for programmable logic controllers“When the computer inside a programmable logic controller senses that an input address is at “logic 1” the computer changes the symbol you put into your program and then executes the ladder program rung.”
Next, we write a ladder program to control this motor.
Ladder Program
Motor
Starter
To FCE motor
120 volts
Output device
120 volts
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
24 volts
N.O.
TSH
(active low)
(active low)
Start P.B.
“When the computer inside a programmable logic controller senses that an input address is at “logic 1” the computer changes the symbol you put into your program and then executes the ladder program rung.”
If the input device attached at input address I-0,0 is passive,
(a) Will the programmable control change the symbol that is associated with input address I-0,0 ?
YES !
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
Ladder Program
Motor
Starter
To FCE motor
120 volts
Output device
120 volts
N.O.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
Input Modules Output Modules
24 volts
N.O.
TSH
(active low)
(active low)
Start P.B.
“When the computer inside a programmable logic controller senses that an input address is at “logic 1” the computer changes the symbol you put into your program and then executes the ladder program rung.”
If the input device attached at input address I-1,3 is passive,
(a) Will the programmable control change the symbol that is associated with input address I-1,3 ?
YES !
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
“We-build-them” Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts 120 volts
120 volts
48 volts
24 volts
TSH
N.O.
motor
Starter
To motor and FCE
120 volts
120 volts
N.O.
(active high)
(active low)
Notice how this wiring of the temperature alarm input device is different than the previous example.
Start P.B.
“We-build-them” Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts 120 volts
120 volts
48 volts
TSH
N.O.
motor
Starter
To motor and FCE
120 volts
120 volts
N.O.
(active high)
(active low)
Notice how the program symbol for the TSH is also different as well.
Program for previous active low wired temperature sense high alarm device.
Start P.B.
OldNew
You put this symbol into your program so the computer can change it to the other symbol when the terminal I-0,0 changes from logic “0” to logic “1”.
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
24 volts
TSH
“We-build-them”
Programmable Controllers
O-0,3
WBT-4
I-1,3 O-1,3
120 volts 120 volts
48 volts
motorStarter
To motor and FCE
I-0,3
24 volts
24 volts
TSH
N.O.
120 volts
N.O.
(active high)
(active low)
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts 120 volts
120 volts
48 volts
motor
Starter
To motor and FCE
Start P.B.
24 volts
TSHN.O.
120 volts
N.O.
(active low)
(active low)
Notice how the wiring of the TSH input devices are different.
Notice how the program elements are different as well. Start
P.B.
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
O-0,1
O-0,1
Ladder Program
I-0,0I-1,3
TSHStart P.B.
O-0,1
O-0,1
Ladder Program
I-0,0I-1,3
TSHStart P.B.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
motor
Starter
To motor and FCE
120 volts
24 volts
TSH
N.O.
120 volts
N.C.
(active high)
(active high)
Study this example and write the program before you go on.
Start P.B.
Ladder Program
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
motor
Starter
To motor and FCE
120 volts
TSH
N.O.
(active high)
Now try this one.
24 volts
120 volts
N.C.
(active low)
Start P.B.
O-0,1
O-0,1I-0,0I-1,3
TSHStart P.B.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
motorStarter
To motor and FCE
24 volts
TSH
N.O.
120 volts
Start P.B.
N.C.
(active high)
(active low)
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
motorStarter
To motor and FCE
24 volts
TSH
N.O.
120 volts
Start P.B.
N.C.
(active high)
(active high)
Notice the difference.
O-0,1
O-0,1
Ladder Program
I-0,0I-1,3
TSHStart P.B.
Notice the difference.
24 volts
TSH
N.O.
120 volts
Start P.B.
N.C.
(active high)
(active high)
24 volts
TSH
N.O.
120 volts
Start P.B.
N.C.
(active high)
(active low)O-0,1
O-0,1
Ladder Program
I-0,0I-1,3
TSHStart P.B.
“We-build-them”
Programmable Controllers
I-0,3 O-0,3
WBT-4
I-1,3 O-1,3
24 volts
120 volts
120 volts
48 volts
24 volts
TSH
N.C.
motor
Starter
To motor and FCE
120 volts
120 volts
Start P.B.
N.C.
O-0,1
O-0,1
Ladder Program
I-0,0I-1,3
TSHStart P.B.
(active high)
(active Low)
Self assessment tool
Write the program for this input device configuration.
Check your answer, if it doesn’t agree run this presentation again.