Kidde ADS - ttlcompany.comttlcompany.com/documentation/download.php?fname=./1.KIDDE_FE… · Kidde...

10
A UTC Fire & Security Company Effective: April 2007 K-90-120 Kidde ADS 3-Way Directional Ball Valve P/Ns: 90-118325-00X and 90-118327-00X FEATURES For Use with Kidde ADS Systems Cost-Effective Option for Protecting Multiple Hazards Pneumatic Operation Using Nitrogen Pilot Cylinder 3-Way Valve Comes Pre-Assembled with Pneumatic Actuator and Solenoid Stainless Steel Low Loss Three Port Design FM Approved DESCRIPTION The Kidde ADS Series System offers the use of direc- tional valves for protection of multiple hazards from one central storage bank of agent and nitrogen driver cylin- ders. When the same set of cylinders are used to protect different hazards, 3-Way Directional Ball Valves may be included in the system. Since only one system (i.e., distri- bution piping and nozzles) can be entered and calculated at one time, it is necessary to create separate projects (.flc files) for each configuration. With respect to the directional valves, separate objects are used for a given valve size depending on the orientation of the valve. An “open” valve is used to allow agent to flow through the side (branch) outlet of the valve, and a “closed” valve would be used to allow agent to flow through the run out- let of the valve. When working with multiple files, the user should ensure that the type, diameter and length of any pipes common to more than one project file are identical. The pipe locking feature is useful here. In addition, the agent quantity per cylinder and area of the nitrogen restrictor orifice should be identical. Note: Per NFPA 2001–In sections where a valve arrangement introduces sections of closed pip- ing, such sections shall be equipped with pres- sure relief devices, or the valves shall be designed to prevent entrapment of liquid. For pressure relief of manifold arrangements using directional valves, use a safety outlet (P/N 844346). Figure 1. T Flow Ball Position Figure 2. L Flow Ball Position TOP VIEW PIPING TO HAZARD AGENT SOURCE PIPING TO HAZARD TOP VIEW AGENT SOURCE

Transcript of Kidde ADS - ttlcompany.comttlcompany.com/documentation/download.php?fname=./1.KIDDE_FE… · Kidde...

A UTC Fire & Security Company

Effective: April 2007K-90-120

Kidde ADS3-Way Directional Ball ValveP/Ns: 90-118325-00X and 90-118327-00X

FEATURES• For Use with Kidde ADS Systems• Cost-Effective Option for Protecting

Multiple Hazards• Pneumatic Operation Using Nitrogen

Pilot Cylinder

• 3-Way Valve Comes Pre-Assembled with Pneumatic Actuator and Solenoid

• Stainless Steel• Low Loss Three Port Design• FM Approved

DESCRIPTIONThe Kidde ADS Series System offers the use of direc-tional valves for protection of multiple hazards from onecentral storage bank of agent and nitrogen driver cylin-ders. When the same set of cylinders are used to protectdifferent hazards, 3-Way Directional Ball Valves may beincluded in the system. Since only one system (i.e., distri-bution piping and nozzles) can be entered and calculatedat one time, it is necessary to create separate projects(.flc files) for each configuration. With respect to thedirectional valves, separate objects are used for a givenvalve size depending on the orientation of the valve. An“open” valve is used to allow agent to flow through theside (branch) outlet of the valve, and a “closed” valvewould be used to allow agent to flow through the run out-let of the valve. When working with multiple files, the usershould ensure that the type, diameter and length of anypipes common to more than one project file are identical.The pipe locking feature is useful here. In addition, theagent quantity per cylinder and area of the nitrogenrestrictor orifice should be identical.

Note: Per NFPA 2001–In sections where a valvearrangement introduces sections of closed pip-ing, such sections shall be equipped with pres-sure relief devices, or the valves shall bedesigned to prevent entrapment of liquid. Forpressure relief of manifold arrangements usingdirectional valves, use a safety outlet (P/N844346).

Figure 1. T Flow Ball Position Figure 2. L Flow Ball PositionTOP VIEW

PIPING TO HAZARD

AGENTSOURCE

PIPING TO HAZARD

TOP VIEW

AGENTSOURCE

3-W

ay

Ba

llV

alv

e

Sw

ing

Ch

ec

ko

rC

he

ck

Va

lve

Ele

ctr

icC

on

tro

lH

ea

dE

EE

E

Dis

ch

arg

eM

an

ifo

ld

CY

L.1

-3

3-W

ay

Ba

llV

ALV

E1

3-W

ay

Ba

llV

ALV

E2

PIP

ING

TO

HA

ZA

RD

BH

AZ

AR

DA

CY

L2

-3

PIP

ING

TO

#3

N2

FM

-200

Tan

k

#2

N2

FM

-200

Tan

k

#1

N2

FM

-200

Tan

k

Sw

ing

Ch

ec

ko

rC

he

ck

Va

vle

Fle

xH

os

eo

rH

ard

Pip

e

Ele

ctr

icC

on

tro

l

1/4

inc

hS

ch

40

pip

eo

r

Sta

inle

ss

ste

el

tub

ing

5/1

6O

.D.

X0

.03

5"

wa

ll

He

ad

He

ad

Ele

ctr

icC

on

tro

lN

itro

ge

nP

ilo

t

Nit

rog

en

Pil

ot

Pan

el

E

•N

itro

gen

pilo

tlin

eco

nn

ecte

dto

each

3-w

ay

ball

valv

e.

•E

lectr

icco

ntr

olh

ead

so

neach

nit

rog

en

pilo

tcylin

der

toco

ntr

ol

the

dir

ecti

on

alvalv

es.

•E

ach

pilo

tcylin

der

co

uld

als

ob

em

an

ually

actu

ate

d.

Ch

an

ne

lsN

ee

de

d=

#o

fD

ire

cti

on

al

Va

lve

s

EE

Pla

inN

ut–

Dis

ch

arg

eH

ead

(Typ

.),P

/N872450

Pla

inN

ut–

Dis

ch

arg

eH

ead

(Typ

.),P

/N872450

1"

Tra

ns

fer

Ho

se

(Ty

p.)

P/N

06

-11

82

07

-00

3

Ele

ctr

icC

on

tro

lH

ead

Actu

ati

on

Assem

bly

Kit

for

225

an

d395

lb.S

yste

ms,

P/N

06-1

29882-0

01

for

675

an

d1010

lb.S

yste

ms,

P/N

06-1

29985-0

01

So

l.S

ol.

SID

EV

IEW

TO

PV

IEW

Op

tio

na

l

No

te:

Tw

o3-w

ay

ball

valv

es

are

sh

ow

nfo

rre

fere

nce.

Gen

era

lu

sag

eis

no

tlim

ited

totw

o3-w

ay

valv

es.

Pre

ss

ure

Re

gu

lato

r(P

/N0

6-1

18

33

4-0

01

)F

ac

tory

Se

tto

11

6P

SI

(8b

ar)

•A

llcylin

ders

mu

st

be

of

the

sam

esiz

ean

dfi

lld

en

sit

y.

•A

lln

itro

gen

dri

vers

mu

st

be

of

the

sam

esiz

ean

dp

ressu

re(1

800

PS

IG).

No

te:

Th

earr

an

gem

en

tssh

ow

nab

ove

use

the

larg

er

cylin

ders

(675

an

d1010

lb.)

for

the

pu

rpo

se

of

cla

rity

.T

his

co

ncep

tcan

als

ob

each

ieved

usin

gth

e225

an

d395

lb.cylin

ders

.

SO

LE

lec

tric

So

len

oid

(P/N

06

-11

83

29

-00

1)

S/O

Sa

fety

Ou

tle

t(P

/N8

44

34

6)

S/O

Figu

re 3

. A

rran

gem

ent 1

: 3-W

ay B

all V

alve

with

Pne

umat

ic A

ctua

tor D

edic

ated

for E

ach

Dire

ctio

nal V

alve

- 2 -

3-W

ay

Ball

Va

lve

Sw

ing

Ch

eck

or

Ch

eck

Va

lve

Ele

ctr

icC

on

tro

lH

ead

E

EE

E

Dis

ch

arg

eM

an

ifo

ld

CY

L.1

-3

3-W

ay

Ba

llV

ALV

E1

3-W

ay

Ba

llV

ALV

E2

PIP

ING

TO

HA

ZA

RD

BH

AZ

AR

DA

CY

L2

-3

PIP

ING

TO

#3

N2

FM

-200

Tan

k

#2

N2

#1

N2

Sw

ing

Ch

ec

ko

rC

he

ck

Va

lve

Fle

xH

os

eo

rH

ard

Pip

e

Ele

ctr

icC

on

tro

lH

ead

1/4

"S

ch

40

Pip

eo

r

Sta

inle

ss

ste

el

tub

ing

5/1

6O

.D.

X0

.03

5"

wa

llN

itro

gen

Pilo

t

Pan

el

•N

itro

ge

np

ilo

tli

ne

co

nn

ec

ted

toe

ac

h3

-wa

yb

all

va

lve

.

•E

lec

tric

co

ntr

ol

he

ad

an

do

ne

pil

ot

cy

lin

de

rfe

ed

sa

llth

eb

all

va

lve

s.

•E

ac

h3

-wa

yb

all

va

lve

isw

ith

as

ole

no

idp

ne

um

ati

ca

ctu

ato

r(r

ota

tes

90

°).

So

l.S

ol.

Ch

an

nels

Need

ed

=#

of

Dir

ecti

on

alV

alv

es

+1

1"

Tra

ns

fer

Ho

se

(Ty

p.)

,P

/N0

6-1

18

20

7-0

03

E

Ele

ctr

icC

on

tro

lH

ea

dP

lain

Nu

t–D

isc

ha

rge

He

ad

(Ty

p.)

P/N

87

24

50

Pla

inN

ut–

Dis

ch

arg

eH

ea

d(T

yp

.),

P/N

87

24

50

EE

SID

EV

IEW

TO

PV

IEW

FM

-200

Tan

kF

M-2

00

Tan

k

No

te:

Tw

o3

-wa

yb

all

va

lve

sa

res

ho

wn

for

refe

ren

ce

.G

en

era

lu

sa

ge

isn

ot

lim

ite

dto

two

3-w

ay

va

lve

s.

•A

llc

yli

nd

ers

mu

st

be

of

the

sa

me

siz

ea

nd

fill

de

ns

ity.

•A

lln

itro

ge

nd

riv

ers

mu

st

be

of

the

sa

me

siz

ea

nd

pre

ss

ure

(18

00

PS

IG).

Pre

ssu

reR

eg

ula

tor

(P/N

06-1

18334-0

01)

Facto

ryS

et

to116

PS

I(8

bar)

SO

LE

lectr

icS

ole

no

id(P

/N06-1

18329-0

01)

Ac

tua

tio

nA

ss

em

bly

Kit

for

22

5a

nd

39

5lb

.S

ys

tem

s,

P/N

06

-12

98

82

-00

1fo

r6

75

an

d1

01

0lb

.S

ys

tem

s,

P/N

06

-12

99

85

-00

1

No

te:

Th

ea

rra

ng

em

en

tss

ho

wn

ab

ov

eu

se

the

larg

er

cy

lin

de

rs(6

75

an

d1

01

0lb

.)fo

rth

ep

urp

os

eo

fc

lari

ty.

Th

isc

on

ce

pt

ca

na

lso

be

ac

hie

ve

du

sin

gth

e2

25

an

d3

95

lb.

cy

lin

de

rs.

S/O

Sa

fety

Ou

tle

t(P

/N8

44

34

6)

S/O

Figu

re 4

. A

rran

gem

ent 2

: 3-W

ay B

all V

alve

with

Pne

umat

ic A

ctua

tor C

ontro

lled

by a

24

Vdc

Sol

enoi

d

- 3 -

OPERATION

Figure 5. 3-Way Directional Ball Valves (See Table 2 for more information.)

FRONT VIEWSIDE VIEW

c

B

A

SPRINGRETURN ACTUATOR

BALL VALVE

Note: Figure 3 illustrates Arrangement 1 whichuses nitrogen pilot actuation for each 3-WayDirectional Ball Valve. Figure 4 illustratesArrangement 2 which uses a single nitrogenpilot cylinder to actuate only one of a seriesof 3-Way Directional Ball Valves

A nitrogen pilot line is connected to each 3-WayDirectional Ball Valve. An electric control head isinstalled on each nitrogen pilot cylinder to actuateand release the nitrogen, which, in turn, pneumati-cally opens the ball valve. The nitrogen pilot line mustbe installed with a pressure regulator. The nitrogenline is then installed into the pneumatic solenoid (P/N06-118329-001) that is attached to the pneumaticactuator. The pneumatic solenoid acts as a gatevalve; when the signal is received from the panel toopen the pneumatic solenoid, the pressure is thenallowed to pass through the pneumatic actuator,which thereby turns the valve to the 90° “Open” orien-tation.

Ball ValveSize

MaximumNumber from

One PilotCylinder

MaximumTubing 5/16" x0.035" Weight

Maximum1/4" Schedule

40 Pipe

4" 3 200 ft. 100 ft.

3" 3 200 ft. 100 ft.

2" 8 200 ft. 100 ft.

1½" 8 200 ft. 100 ft.

1¼" 8 200 ft. 100 ft.

1" 8 200 ft. 100 ft.

3/4" 8 200 ft. 100 ft.

1/2" 8 200 ft. 100 ft.

Table 1. 3-Way Directional Ball Valve

WARNING

The pneumatic actuator and pneumaticsolenoid are rated for a pressure of 100to150 PSI (6.89 to 10.34 bar gauge). Apressure regulator must be installed inline to reduce the nitrogen pressure thatis being released from the pilot cylinder.Pressure regulator P/N06-118334-001 isfactory set to 116 PSI (8 bar gauge).

- 4 -

Part Number Nominal Size Material Body Style Inlets PortT-Flow

EquivalentLength

L-FlowEquivalent

Length

90-118325-001 1/2" 316 SS Threaded NPT Full 0.42 ft. 3.67 ft.

90-118325-002 3/4" 316 SS Threaded NPT Full 0.50 ft. 5.42 ft.

90-118325-003 1" 316 SS Threaded NPT Full 0.94 ft. 7.38 ft.

90-118325-004 1¼" 316 SS Threaded NPT Full 1.07 ft. 11.18 ft.

90-118327-001 1½" 316 SS Bolted NPT Full 2.39 ft. 14.05 ft.

90-118327-002 2" 316 SS Bolted NPT Full 2.73 ft. 17.80 ft.

90-118327-003 3" 316 SS Bolted NPT Full 3.02 ft. 24.56 ft.

90-118327-004 4" 316 SS Bolted Flanged Full 4.54 ft. 25.62 ft.

Part Number Nominal SizeDimensions Valve Working

PressureBreakaway

TorqueA* B C*

90-118325-001 1/2" 6 in. 0.59 8 in. 500 PSIG 100 in.-lb.

90-118325-002 3/4" 6 in. 0.79 8 in. 500 PSIG 130 in.-lb.

90-118325-003 1" 7 in. 0.98 10 in. 500 PSIG 190 in.-lb.

90-118325-004 1¼" 7 in. 1.25 10 in. 500 PSIG 300 in.-lb.

90-118327-001 1½" 9 in. 1.50 12 in. 500 PSIG 576 in.-lb.

90-118327-002 2" 15 in. 1.97 14 in. 500 PSIG 877 in.-lb.

90-118327-003 3" 22 in. 2.93 23 in. 500 PSIG 2366 in.-lb.

90-118327-004 4" 23 in. 3.53 23 in. 500 PSIG 3300 in.-lb.

*Note: Dimensions are approximate for the entire assembly.

Part Number NominalSize

ActuatorMechanism Actuator Type Actuator

VolumeActuatorTorque

WorkingPressure

MaximumPressure

90-118325-001 1/2" Rack and Pinion Spring Return 14 cu. in. 180 in.-lb. 115 PSIG 145 PSIG

90-118325-002 3/4" Rack and Pinion Spring Return 14 cu. in. 180 in.-lb. 115 PSIG 145 PSIG

90-118325-003 1" Rack and Pinion Spring Return 21 cu. in. 266 in.-lb. 115 PSIG 145 PSIG

90-118325-004 1¼" Rack and Pinion Spring Return 40 cu. in. 429 in.-lb. 115 PSIG 145 PSIG

90-118327-001 1½" Rack and Pinion Spring Return 61 cu. in. 782 in.-lb. 115 PSIG 145 PSIG

90-118327-002 2" Rack and Pinion Spring Return 92 cu. in. 924 in.-lb. 115 PSIG 145 PSIG

90-118327-003 3" Rack and Pinion Spring Return 366 cu. in. 3539 in.-lb. 115 PSIG 145 PSIG

90-118327-004 4" Rack and Pinion Spring Return 366 cu. in. 3539 in.-lb. 115 PSIG 145 PSIG

Table 2. 3-Way Directional Ball Valve Specifications

Table 2. 3-Way Directional Ball Valve Specifications (cont.)

Table 3. Pneumatic Actuator Specifications

- 5 -

COMPONENTS3-WAY DIRECTIONAL BALL VALVES(P/NS 90-118325-00X AND 90-118327-00X)The stainless steel, 3-Way Directional Ball Valves areused for applications where a single bank of cylinders areused to protect multiple hazards (see ADS Design, Instal-lation, Operation and Maintenance Manual, P/N 90-FM200M-030, for more information). The directionalvalves have a factory installed pneumatic, spring loadedactuator and range in sizes from 1/2 inch to 4 inches. Thedirectional valves can be installed in the network, pro-vided that they are accounted for in the software calcula-tion. Refer to Figure 5, and Table 2 for more information.

Pneumatic Solenoid (P/N 06-118329-001)

The pneumatic solenoid is a cost-effective componentthat is used with the pneumatic actuators and 3-WayDirectional Ball Valves. With the solenoid, one nitrogenpilot cylinder can be used for multiple directional valves.The solenoid is factory set to normally closed. A signalfrom the panel opens the solenoid that is attached to theappropriate pneumatic actuator. Pressure is then allowedto pass through the solenoid and open the 3-Way Direc-tional Ball Valve.

Figure 6. Pneumatic SolenoidPressure Regulator (P/N 06-118334-001)

The pressure regulator is used up stream of the pneu-matic solenoid to regulate the nitrogen pressure to 116PSI (8 bar gauge) prior to operating the pneumatic actua-tor on the directional valve.

Figure 7. Pressure Regulator

COMPONENT SPECIFICATIONS

INSTALLATIONAll Kidde FM-200 equipment must be installed to facilitateproper inspection, testing, manual operation, rechargingand any other required maintenance as may be neces-sary. Equipment must not be subject to severe weatherconditions or mechanical, chemical, or other damage thatcould render the equipment inoperative. Equipment mustbe installed in accordance with NFPA Standard 2001,current edition.

0.95REF

5.22 REF

2.76 REF

1.63 REF 0.63 REF

0.16REF

1.26 REF

CYLINDER PORTS

2- 0.19 REF

MUFFLERS

6.66 in.(169 mm)

ASSEMBLY INLET,1/4 NPT

ASSEMBLY OUTLET,1/4 NPT

WARNING

The FM-200 cylinder/valve assembliesmust be handled, installed and servicedin accordance with the instructions con-tained in this Section and CompressedGas Association (CGA) pamphlets C-1,C-6 and P-1. CGA pamphlets may beobtained from: Compressed Gas Asso-ciation, 1235 Jefferson Davis Highway,Arlington, VA 22202. Failure to followthese instructions can cause FM-200cylinders to violently discharge, result-ing in severe injury, death and/or prop-erty destruction.

Description Measurement

Pressure Range 55 to 120 PSIG

Voltage Rating 24 Vdc

Power Consumption (DC) 3W

Power Consumption (AC) 4.5A

Coil 9AAG

Weight 0.72 lb.

Ports 1/4" NPT

Includes: Locking Manual Override Button

Part Number Description

06-118334-001 Pressure Regulator

Table 4. Pneumatic Solenoid Specifications

Table 5. Pressure Regulator Specifications

- 6 -

PRESSURE ACTUATION PIPEThe pressure actuation pipe must be 1/4-inch Schedule40 or 80 pipe or 5/16 in. O.D. x 0.035 in. wall stainlesssteel tubing. Actuation lines shall be protected againstcrimping and mechanical damage (per NFPA 2001, Sec-tion 2-3.4.2). The pipe or tubing must be routed in themost direct manner with a minimum number of fittings.Pipe and fittings must be in accordance with the require-ments listed in the ADS Design, Installation, Operationand Maintenance Manual (P/N 90-FM200M-030). Fittingscan be flared or compression type. The pressure-temper-ature ratings of the fitting manufacturer must not beexceeded.

DIRECTIONAL VALVES WITH PNEUMATICACTUATORS AND SOLENOIDS

Note: Flanged fittings are to be installed per ANSI B16.5.

1. Gather the required parts for the chosen directionalsystem based upon the number of 3-Way Direc-tional Ball Valves needed and the actuation schemedesired.

• Single pilot cylinder actuation requires one pilotcylinder, actuation hoses (number of hosesequals two times the number of directionalvalves), electric control head, the directionalvalves with solenoid pneumatic actuators and apressure regulator.

• Multiple pilot actuation requires pilot cylinders(number of pilot cylinders equals one times thenumber of directional valves), actuation hoses(number of hoses equals one times the numberof directional valves), electric control heads(number of control heads equals one times thenumber of directional valves), directional valveswith pneumatic actuators and a pressure regula-tor.

Note: The pressure regulator must be located within 12 in. of the solenoid and pneumatic actuator.

2. Ensure that all directional valves are in the “straightthrough” position before installation (the T-port in thevalve should be open on both ends with the sideport closed).

Figure 8. Straight Through OrientationThe directional valve must be installed so that the 90°turn of the actuator brings the T-port open on the sidebranch and the end of the valve that faces the FM-200source. The arrow on the valve must be pointed in thedirection of the flow.

Figure 9. 90° Orientation3. Connect the actuators on the directional valves to

the pneumatic source in one of two ways:For pilot cylinder actuation, all directional valvesmust have a 24 Vdc solenoid (P/N 06-118329-001)and a 24 Vdc connection from the control panel.

✶ Connect the pilot cylinder to the second pressur-ization port of the solenoid actuator using theactuation line.

✶ Connect each of the solenoids and the electriccontrol head to the control panel so that the elec-tric control head fires and the correct directionalvalve operates for the desired hazard.

✶ Test each hazard with the control panel by listen-ing for the solenoid click at each directionalvalve.

✶ Reconnect all electrical connections.✶ Attach an electric control head to the pilot cylin-

der (being sure it is set before installation).

VALVE 1

3-Way Ball

HAZARD APIPING TO

VALVE 2

3-Way Ball

PIPING TOHAZARD B

Straight through position;Closed to pipe network.

Nipple

Cap Endof Manifold

VALVE 1

3-Way Ball

HAZARD APIPING TO

VALVE 2

3-Way Ball

PIPING TOHAZARD B

90° counterclockwiseturn to Hazard B.

(In Alarm)

Nipple

Cap Endof Manifold

- 7 -

4. Set the control panel to provide a 5.5 second delaybetween the firing of the pilot cylinders for the direc-tional valves and the firing of the FM-200 system(see Table 6). This delay provides sufficient time forthe valves to fully open before the system is dis-charged.

Note: 5.5 seconds is the maximum time needed for the 4 in. ball valve to open under pressure.

SYSTEM RELEASECONTROL CONFIGURATIONIMPORTANT— The information in this paragraph refersto circuits and wiring employed on PEGAsys panels;specific ADS configurations and/or other programmablepanels may require different wiring and/or panel-to-panelconnections.A maximum of eight suppression hazards and a maxi-mum of eight electrically actuated nitrogen driver cylin-ders are allowed per system. Multiple panels may beemployed to control and release the system. The small-est ADS system configuration would require a minimumof four release circuits.

Figure 10. Typical Single Panel System Release Circuit Wiring (See Notes below.)

Figure 11. Typical Multiple Panel System Release Circuit Wiring (See Notes below.)

Notes:1. Must use Pneumatic Solenoid (P/N 06-118329-001).

Ratings: 24 Vdc, 4.8 W; 2.0 Vdc minimum dropout.2. Must use 24 Volt DC control head. The fire alarm

suppression panel release circuit must be capable of supplying a minimum of 24 Vdc @ 2.8 Amps for 30 milliseconds for control head P/N 890181, and a minimum of 24 Vdc @ 0.5 Amps continuous for con-trol head P/N 81-100000-001.

3. Release control relays are only required if the nitro-gen driver solenoids are released by a separate panel. Relays employed must be electrically com-patible with the release circuit output characteristics for both pull-in and dropout voltages.

WARNING

Regardless of configuration, the follow-ing sequence of activation must beadhered to:1. When a call for suppression is

received by the panel for a specificsuppression zone, the appropriateselector valve solenoid and nitrogenpilot control head must activate within0.5 seconds of each other.

2. Six to ten seconds after the selectorvalve solenoid and nitrogen pilot con-trol head actuates, the appropriatenitrogen driver control heads mustactivate. After any hazard activates,no other activation is allowed until thesystem is serviced. Failure to followthese sequence could result in sys-tem malfunction.

Part Number Description Time DelaysRequired to Open

90-118325-001 1/2" NPT 5.5 sec.

90-118325-002 3/4" NPT 5.5 sec.

90-118325-003 1" NPT 5.5 sec.

90-118325-004 1¼" NPT 5.5 sec.

90-118327-001 1½" NPT 5.5 sec.

90-118327-002 2" NPT 5.5 sec.

90-118327-003 3" NPT 5.5 sec.

90-118327-004 4" Flanged 5.5 sec.

PEGAsys or otherFM Approved/UL Listedfire alarm suppression

control panel

ReleaseCircuit

ReleaseCircuit

ReleaseCircuit

Selector ValveSolenoid (see note 1)

Nitrogen PilotControl Head (see note 2)

Nitrogen DriverControl Head (see note 2)

PEGAsys or otherprogrammable FM Approved(for FM insured installations)/UL Listed compatible fire alarmsuppression control panel

S

S

S

S Denotes Supervised Circuit

ReleaseCircuit

Selector ValveSolenoid (see note 1)

S

Nitrogen DriverControl Head (see note 2)

SRelease

Circuit

Circuit

PEGAsys or otherFM Approved/UL Listedfire alarm suppressioncontrol panel

ReleaseCircuit

ReleaseCircuit

ReleaseCircuit

Selector ValveSolenoid (see note 1)

Nitrogen PilotControl Head (see note 2)

ReleaseControl Relay (see note 3)

Circuit

PEGAsys or otherFM Approved/UL Listedfire alarm suppression

control panel

InitiatingCircuit

ReleaseCircuit

ReleaseCircuit

Nitrogen DriverControl Head (see Note 2)

Nitrogen DriverControl Head (see Note 2)

EOLR

+_

S Denotes Supervised Circuit

S

S

S

S

S

S

Panel 1

Panel 2

Selector ValveSolenoid (see note 1)

S

CircuitRelease

PEGAsys or otherprogrammable FM Approved

(for FM insured installations)/UL Listed compatible fire alarm

suppression control panel

PEGAsys or otherprogrammable FM Approved

(for FM insured installations)/UL Listed compatible fire alarm

suppression control panel

Table 6. Directional Valve Data

- 8 -

4. A means of manual release of the system shall be provided. Manual release shall be accomplished by a mechanical manual release, or by an electrical manual release, when the control equipment moni-tors the battery voltage level of the standby battery supply and will provide a low battery signal. The release shall cause simultaneous operation of auto-matically operated valves controlling agent release and distribution.

✶ Refer to the PEGAsys Installation, Operation and Maintenance Manual (P/N 76-200016-001) for com-plete details.

ORDERING INFORMATION

WARNING

The referenced control heads andsolenoids are compatible with PEGA-sys panels. The use of other panels tooperate these control heads and sole-noids has not been verified and couldresult in system malfunction.

- 9 -

Part Number Description

Valves

90-118325-001 3-Way Directional Valve, 1/2-inch

90-118325-002 3-Way Directional Valve, 3/4-inch

90-118325-003 3-Way Directional Valve, 1-inch

90-118325-004 3-Way Directional Valve, 1¼-inch

90-118327-001 3-Way Directional Valve, 1½-inch

90-118327-002 3-Way Directional Valve, 2-inch

90-118327-003 3-Way Directional Valve, 3-inch

90-118327-004 3-Way Directional Valve, 4-inch

Pneumatic Solenoid(Note: Part of Valve Assembly. Use below for spare parts only.)

06-118329-001 Pneumatic Solenoid, 24 Vdc

Pressure Regulator

06-118334-001 Pressure Regulator, 116 PSI (8 bar)

A UTC Fire & Security Company400 Main StreetAshland, MA 01721Ph: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or ques-tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.

K-90-120 Rev AB © 2007 Kidde-Fenwal Inc. Printed in USA