TIA-1005 (Proposed by TR-42.9)Industrial Cabling Standard
Pete LockhartAnixter
Manufacturing IT ForumCleveland, OhioMay 20-21, 2008
![Page 2: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/2.jpg)
Key Points to be Covered
• Definition of Structured Cabling for Commercial Networks• Definition of Structured Cabling for Industrial Networks• The proposed TIA-1005 Draft Standard Structure• Industrial Area Concepts• Recognized cables• Recognized connectivity• The Automation Outlet• 2-Pair Cabling• Multi-connector Ethernet Channels• M.I.C.E.
![Page 3: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/3.jpg)
Structured Cabling 1st Defined in TIA/EIA-568
![Page 4: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/4.jpg)
ANSI/TIA-PN-3-4822-G 12-12-2007
• Ballot proposal from TIA-TR-42.9 working group• Will become ANSI/TIA-1005 Industrial Cabling
Standard on approval• Based closely on the ANSI/TIA/EIA 568-B,
TIA-569-B, ANSI-J-STD-607-A, ANSI/TIA/EIA-606-A, and ISO/IEC 11801Standards
• Also related to ISO/IEC 24702 Information Technology-Industrial Premises
• Environmental references: IEC60721-x, IEC60654-x
Telecommunications Infrastructure Standard for Industrial Premises
![Page 5: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/5.jpg)
Purpose of Standard
• To enable the planning and installation of telecommunications cabling infrastructure within and between industrial buildings
• The potential exposure to hostile environments in the industrial space is the central concept of the standard in contrast to that of TIA/EIA 568, which addresses commercial buildings
• The special cabling system requirements of industrial operations is also a prime design principle of the document
![Page 6: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/6.jpg)
New Terms, not in TIA/EIA-568B
•Automation island– Area in proximity to the industrial machines
•Automation outlet– Where the generic telecommunications cabling ends and the automation-specific
cabling begins
•Device area– Where system I/O interacts with control equipment
•Industrial segment– A point-to-point connection between two active industrial communications devices
•M.I.C.E.– For Mechanical, Ingress, Climate/Chemical, Electromechanical
![Page 7: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/7.jpg)
Horizontal Topology Same as TIA/EIA-568B
![Page 8: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/8.jpg)
Industrial Area Concept
•Control/equipment/telecomm room•Factory floor•Work area•Automation island
![Page 9: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/9.jpg)
Industrial Horizontal Star Channel Topology
TO = Telecommunications OutletAO = Automation Outlet
![Page 10: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/10.jpg)
Horizontal Allowable Distances for Copper Links
• In many cases industrial cabling can be made almost entirely of work area cabling, which must be accounted for when combined with equipment and patch cabling in the limited 100 m (328 ft.) channel.
• The following formula must be used to calculate the maximum cord and link lengths:
![Page 11: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/11.jpg)
Recognized Horizontal Cables
• Twisted-pair copper– 4-pair, 100 ohm balanced (unshielded or shielded)– 2-pair, 100 ohm balanced (unshielded or shielded)
• Optical fiber– Optical (glass) fiber, single-mode and multimode cable
(ANSI/TIA/EIA-568-B.3)
• Plastic Optical Fiber: Removed from the issue of the Standard and referred to a Working Group for later addition as an Addendum– Plastic polymer optical fiber (ISO/IEC 24702)– Plastic polymer clad silica optical fiber (ISO/IEC 24702)
![Page 12: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/12.jpg)
AO
Must be 4-pair
Can be 2-pair
Horizontal Cabling Beyond the Automation Outlet
• The Automation Outlet demarks the point at which non-generic horizontal cabling components maybe used.
• The 2-pair, 100 ohm balanced cabling may not be used prior to the Automation Outlet.
![Page 13: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/13.jpg)
Recognized Backbone Cables
• Copper– 4-pair, 100 ohm balanced (unshielded or shielded)
• Optical fiber– Optical (glass) fiber, single-mode and multimode cable
(ANSI/TIA/EIA-568-B.3)
• Plastic Optical Fiber: Removed from the issue of the Standard and referred to a Working Group for later addition as an Addendum.– Plastic polymer optical fiber (ISO/IEC 24702)– Plastic polymer clad silica optical fiber (ISO/IEC 24702)
![Page 14: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/14.jpg)
Grounding and Bonding Considerations
• Use ANSI-J-STD-607-A for grounding requirements– Use single point grounds– Grounding and bonding should
be configured to provide an equal potential grounding system to prevent ground loops
– The use of star grounding in communications coverage areas can be used to mitigate ground loops
![Page 15: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/15.jpg)
Industrial Cabling Performance
• Industrial cabling performance– Requires a combination of environmental
and enhanced transmission performance to support the intended applications
• The standard states– That for the above reasons and because
Channels with more than four connections are allowed – Category 6, or better, cabling SHOULD be used
![Page 16: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/16.jpg)
Industrial Cabling Performance Requirements
• Twisted-pair copper
• The installed channels and permanent links shall meet the requirements for cabling as specified for– Category 5e per ANSI/TIA/EIA-568-B.1, clause11.2– Category 6 per ANSI/TIA/EIA-568-B.2, clause 7
![Page 17: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/17.jpg)
Industrial Cabling Performance Requirements
• Standard optical fiber cables– Optical fiber (glass) cabling shall meet
the performance requirements of ANSI/TIA/EIA-568-B.1. Depending on the environmental conditions additional enhancements or separation/isolation may be required.
![Page 18: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/18.jpg)
Connecting Hardware – Copper
• Telecommunications outlet/connector– 8-position modular: (100 ohm balanced twisted pair) per
ANSI/TIA/EIA-568-B.1 using T568A 0r B wiring method
– Non-Sealed: 4-pair terminated, must meet the performance requirements of ANSI/TIA/EIa-568-B.2
– Sealed: may be housed (encapsulated) within a protective housing, must meet the performance requirements of ANSI/TIA/EIa-568-B.2, when subject to the applicable environmental conditions – defined by MICE Table
![Page 19: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/19.jpg)
Connecting Hardware – Copper
• Automation outlet/connector– Serves as the interface between generic
cabling and the automation island
– 8-position modular: (100 ohm balanced twisted pair) per ANSI/TIA/EIA-568-B.2 required to meet Category 6 or better
– Non-sealed: each 100-ohm 4-pair cable shall terminate on an 8-position connector
– Sealed: shall use connector encapsulation variant 1 from IEC 61076-3-106
![Page 20: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/20.jpg)
M12-4 ‘D’ Plug M12-4 ‘D’ Jack
Connecting Hardware – Copper
• Automation outlet/connector– A 2-pair sealed connector. Where a full set of applications is not
required (100BASE-T max), the M12-4 D-coding connector as defined in IEC 61076-2-100 may be used. It should be a minimum of Category 5e for four connections or less and Category 6 for more than four connections.
![Page 21: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/21.jpg)
Connecting Hardware – Fiber Optic
• Telecommunications outlet connector– LC connector family, as specified in ANSI/TIA/EIA-604-10A and
shall perform to ANSI/TIA/EIA-568-B.3
– Sealed optical fiber connectors, may be protected by encapsulation, isolation or separation. Variant 1 of IEC 61076-3-106 methods should be used, but any suitable encapsulation may be used, as long as a single method is used throughout the facility.
![Page 22: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/22.jpg)
Connecting Hardware – Fiber Optic
• Optical fiber automation outlet/connector– Non-sealed: LC connector family, as specified in ANSI/TIA/EIA-
604-10A and shall perform to ANSI/TIA/EIA-568-B.3
– Sealed: the sealed outlet connector housing shall be Variant 1 of IEC 61076-3-106, incorporating the duplex LC connector of ANSI/TIA/EIA-604-10A
![Page 23: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/23.jpg)
L < 10cm L > 10cm
Adapters
• Balanced twisted pair– Back-to-back jack is recommended for use on enclosures for
bulkhead quick connections.– Mated adapters shall conform to the transmission requirements
of the appropriate media type and category
– When two connections are used in very close proximity, they should be of the next higher performance category. If the space is less then 10 cm, it can count as a single connection.
![Page 24: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/24.jpg)
Consolidation Point
• Interconnection point within the horizontal cabling using ANSI/TIA/EIA-568-B.2 or -B.3 compliant connecting hardware in accordance with the requirements of Clause 0
• Differs from a MUTOA as it requires an additional connection point
• No more than a single consolidation point or transition point shall be used in the same horizontal run
• Each cable extending to the work area from a consolidation point shall be terminated to a compliant TO, AO or MUTOA
![Page 25: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/25.jpg)
Consolidation Point Examples
![Page 26: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/26.jpg)
Annex A: Requirements for 2-pair Cabling
• All unused conductors of a 4-pair cable shall be common mode terminated
• When connecting a complete 2-pair cabling system into equipment designed for 4-pair cabling (e.g., 100BASE-T), ensure the correct pair assignment is used
• Network switches designed for use with 2-pair cabling should not be connected with 4-pair cabling
• If mixing 2-pair and 4-pair cabling systems, ensure that the resulting cabling channel meets the requirements of the application.
![Page 27: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/27.jpg)
MICE Concept – Now in TIA-568-C0
• There are three basic types of industrial areas:– Factory floor (MICE 1 or 2)– Work area (MICE 2 or 3)– Automation island (MICE 3)
• The areas have mixed environments and are given classifications (subscripts 1, 2 and 3) based on the MICE limits assigned to that level of hazard
![Page 28: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/28.jpg)
“MICE Definitions
![Page 29: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/29.jpg)
MICE Table for Mx & Ix
![Page 30: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/30.jpg)
Example of Environmental Change Along Cable Channel
![Page 31: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/31.jpg)
MICE Environmental Boundaries
• Environmental boundaries may occur at the connector locations, enclosures, walls or along any portion of the cabling run
Five connection channel with MICE boundaries.
![Page 32: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/32.jpg)
Summary
• Standard Allows for 2-pair Cabling Systems• Standard Defines an “Automation Island”• Standard Defines “Automation” Outlets & Cables• Standard States that Category 6 or Better Cabling shall be
used for the Automation Islands.• Defines Environmental Concerns in concrete terms with
M.I.C.E. Tables (referenced in TIA-568-C0)• POF-Plastic Optical Fiber has been removed for further
technical review for later addition to Standard.• The Draft “SP” Ballot is expected to be issued in April for final
review in June 2008, possible release of Standard in 2009.
![Page 33: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/33.jpg)
Questions and Discussion
![Page 34: Key Points to be Covered](https://reader035.fdocuments.net/reader035/viewer/2022062300/568134d5550346895d9bfdf4/html5/thumbnails/34.jpg)
Related Resources
Phone: (919) 549-8411 E-mail Address: [email protected]
• TIA-TR-42.9 Industrial Cabling Working Group• ANSI/TIA-1005 Industrial Cabling Standard-Proposed• ANSI/TIA/EIA 568-B Commercial Building Telecommunications
Cabling Standard• ANSI/TIA-569-B Commercial Building Standard for Pathways &
Spaces• ANSI-J-STD-607-A Commercial Building Grounding and Bonding
Requirements for Telecommunications• ANSI/TIA/EIA-606-A Administration Standard for Commercial
Telecommunications Infrastructure• ISO/IEC 11801Generic Cabling for Customer Premises• ISO/IEC 24702 Information Technology-Industrial Premises• Environmental references: IEC60721-x, IEC60654-x